You are on page 1of 42

BS EN 62386-204:2009

BSI Standards Publication

Digital addressable lighting


interface —
Part 204: Particular requirements for control gear —
Low voltage halogen lamps (device type 3)
BS EN 62386-204:2009 BRITISH STANDARD

National foreword
This British Standard is the UK implementation of EN 62386-204:2009. It is
identical to IEC 62386-204:2009.
The UK participation in its preparation was entrusted by Technical Committee
CPL/34, Lamps and related equipment, to Subcommittee CPL/34/3, Auxiliaries
for lamps.
A list of organizations represented on this committee can be obtained on
request to its secretary.
This publication does not purport to include all the necessary provisions of a
contract. Users are responsible for its correct application.
© BSI 2009
ISBN 978 0 580 57539 6
ICS 29.130.99; 29.140.50; 29.140.99

Compliance with a British Standard cannot confer immunity from


legal obligations.

This British Standard was published under the authority of the Standards
Policy and Strategy Committee on 31 October 2009

Amendments issued since publication

Amd. No. Date Text affected


BS EN 62386-204:2009
EUROPEAN STANDARD EN 62386-204
NORME EUROPÉENNE
EUROPÄISCHE NORM August 2009

ICS 29.140.50; 29.140.99

English version

Digital addressable lighting interface -


Part 204: Particular requirements for control gear -
Low voltage halogen lamps (device type 3)
(IEC 62386-204:2009)

Interface d'éclairage Digital adressierbare Schnittstelle


adressable numérique - für die Beleuchtung -
Partie 204: Exigences particulières Teil 204: Besondere Anforderungen
pour les appareillages de commande - an Betriebsgeräte -
Lampes à halogène à basse tension Niedervolt-Halogenlampen (Gerätetyp 3)
(dispositif de type 3) (IEC 62386-204:2009)
(CEI 62386-204:2009)

This European Standard was approved by CENELEC on 2009-07-01. CENELEC members are bound to comply
with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard
the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.

This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and notified
to the Central Secretariat has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Cyprus, the
Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain,
Sweden, Switzerland and the United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Central Secretariat: Avenue Marnix 17, B - 1000 Brussels

© 2009 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.

Ref. No. EN 62386-204:2009 E


BS EN 62386-204:2009
EN 62386-204:2009 -2-

Foreword
The text of document 34C/876/FDIS, future edition 1 of IEC 62386-204, prepared by SC 34C, Auxiliaries
for lamps, of IEC TC 34, Lamps and related equipment, was submitted to the IEC-CENELEC parallel vote
and was approved by CENELEC as EN 62386-204 on 2009-07-01.

This Part 204 is intended to be used in conjunction with EN 62386-101 and EN 62386-102, which contain
general requirements for the relevant product type (control gear or control devices).

The following dates were fixed:

– latest date by which the EN has to be implemented


at national level by publication of an identical
national standard or by endorsement (dop) 2010-04-01

– latest date by which the national standards conflicting


with the EN have to be withdrawn (dow) 2012-07-01

Annex ZA has been added by CENELEC.

__________

Endorsement notice
The text of the International Standard IEC 62386-204:2009 was approved by CENELEC as a European
Standard without any modification.

In the official version, for Bibliography, the following notes have to be added for the standards indicated:
IEC 60598-1 NOTE Harmonized as EN 60598-1:2008 (modified).

IEC 60669-2-1 NOTE Harmonized as EN 60669-2-1:2004 (modified).

IEC 60921 NOTE Harmonized as EN 60921:2004 (not modified).

IEC 60923 NOTE Harmonized as EN 60923:2005 (not modified).

IEC 60925 NOTE Harmonized as EN 60925:1991 (not modified).

IEC 60929 NOTE Harmonized as EN 60929:2006 (not modified).

IEC 61347-1 NOTE Harmonized as EN 61347-1:2008 (modified).

IEC 61347-2-3 NOTE Harmonized as EN 61347-2-3:2001 (not modified).

IEC 61547 NOTE Harmonized as EN 61547:2009 (not modified).

CISPR 15 NOTE Harmonized as EN 55015:2006 (not modified).

__________
BS EN 62386-204:2009
-3- EN 62386-204:2009

Annex ZA
(normative)

Normative references to international publications


with their corresponding European publications
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.

NOTE When an international publication has been modified by common modifications, indicated by (mod), the relevant EN/HD
applies.

Publication Year Title EN/HD Year


IEC 62386-101 2009 Digital addressable lighting interface - EN 62386-101 2009
Part 101: General requirements - System
IEC 62386-102 2009 Digital addressable lighting interface - EN 62386-102 2009
Part 102: General requirements - Control gear
BS EN 62386-204:2009
–2– 62386-204  IEC:2009

CONTENTS
FOREWORD...........................................................................................................................3
INTRODUCTION.....................................................................................................................5
1 Scope ...............................................................................................................................6
2 Normative references .......................................................................................................6
3 Terms and definitions .......................................................................................................6
4 General ............................................................................................................................7
5 Electrical specifications ....................................................................................................7
6 Interface power supply .....................................................................................................7
7 Transmission protocol structure ........................................................................................7
8 Timing ..............................................................................................................................7
9 Method of operation .........................................................................................................7
10 Declaration of variables ....................................................................................................8
11 Definition of commands ....................................................................................................9
12 Test procedures ............................................................................................................. 14
Annex A (informative) Examples of algorithms ..................................................................... 35
Bibliography.......................................................................................................................... 36

Figure 1 – Application extended configuration command sequence example ......................... 10


Figure 2 – Test sequence 'QUERY FEATURES' .................................................................... 15
Figure 3 – Test sequence 'QUERY SHORT CIRCUIT' ........................................................... 16
Figure 4 – Test sequence 'QUERY OPEN CIRCUIT' ............................................................. 17
Figure 5 – Test sequence 'QUERY LOAD DECREASE' ......................................................... 18
Figure 6 – Test sequence 'QUERY LOAD INCREASE' .......................................................... 19
Figure 7 – 'QUERY CURRENT PROTECTOR ACTIVE: Underload' ....................................... 20
Figure 8 – 'QUERY CURRENT PROTECTOR ACTIVE: Overload' ......................................... 21
Figure 9 – 'QUERY THERMAL SHUT DOWN' ....................................................................... 22
Figure 10 – 'QUERY THERMAL OVERLOAD'........................................................................ 23
Figure 11 – 'REFERENCE SYSTEM POWER' ....................................................................... 24
Figure 12 – 'REFERENCE SYSTEM POWER: 100 ms-timeout' ............................................. 25
Figure 13 – 'REFERENCE SYSTEM POWER: Command in-between' ................................... 27
Figure 14 – 'REFERENCE SYSTEM POWER: 15 minutes timer' ........................................... 27
Figure 15 – 'REFERENCE SYSTEM POWER: failed'............................................................. 28
Figure 16 – 'ENABLE / DISABLE CURRENT PROTECTOR' .................................................. 29
Figure 17 – 'ENABLE DEVICE TYPE: Application extended commands'................................ 30
Figure 18 – 'ENABLE DEVICE TYPE: Application extended configuration commands 1'........ 32
Figure 19 – 'ENABLE DEVICE TYPE: Application extended configuration commands 2'........ 32
Figure 20 – 'QUERY EXTENDED VERSION NUMBER' ......................................................... 33
Figure 21 – 'RESERVED APPLICATION EXTENDED COMMANDS' ...................................... 34

Table 1 – Declaration of variables ...........................................................................................9


Table 2 – Summary of the application extended command set .............................................. 14
BS EN 62386-204:2009
62386-204  IEC:2009 –3–

INTERNATIONAL ELECTROTECHNICAL COMMISSION


____________

DIGITAL ADDRESSABLE LIGHTING INTERFACE –

Part 204: Particular requirements for control gear –


Low voltage halogen lamps (device type 3)

FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with an IEC Publication.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.

International Standard IEC 62386-204 has been prepared by subcommittee 34C: Auxiliaries
for lamps, of IEC technical committee 34: Lamps and related equipment.

The text of this standard is based on the following documents:

FDIS Report on voting


34C/876/FDIS 34C/885/RVD

Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.

This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.

This part 204 is intended to be used in conjunction with IEC 62386-101 and IEC 62386-102,
which contain general requirements for the relevant product type (control gear or control
devices).
BS EN 62386-204:2009
–4– 62386-204  IEC:2009

A list of all parts of IEC 62386 series, under the general title Digital addressable lighting
interface, can be found on the IEC website.

The committee has decided that the contents of this publication will remain unchanged until
the maintenance result date indicated on the IEC web site under "http://webstore.iec.ch" in
the data related to the specific publication. At this date, the publication will be

• reconfirmed;
• withdrawn;
• replaced by a revised edition; or
• amended.
BS EN 62386-204:2009
62386-204  IEC:2009 –5–

INTRODUCTION

This first edition of IEC 62386-204 is published in conjunction with IEC 62386-101 and
IEC 62386-102. The division of IEC 62386 into separately published parts provides for ease
of future amendments and revisions. Additional requirements will be added as and when a
need for them is recognised.

This International Standard, and the other parts that make up IEC 62386-200 series, in
referring to any of the clauses of IEC 62386-101 or IEC 62386-102, specifies the extent to
which such a clause is applicable and the order in which the tests are to be performed. The
parts also include additional requirements, as necessary. All parts that make up the
IEC 62386-200 series are self-contained and therefore do not include references to each
other.

Where the requirements of any of the clauses of IEC 62386-101 or IEC 62386-102 are
referred to in this International Standard by the sentence " The requirements of IEC 62386-
1XX, clause ’n’ apply”, this sentence is to be interpreted as meaning that all requirements of
the clause in question of Part 101 or Part 102 apply, except any which are inapplicable to the
specific type of lamp control gear covered by Part 204.

All numbers used in this International Standard are decimal numbers unless otherwise noted.
Hexadecimal numbers are given in the format 0xVV, where VV is the value. Binary numbers
are given in the format XXXXXXXXb or in the format XXXX XXXX, where X is 0 or 1; "x" in
binary numbers means "don't care".
BS EN 62386-204:2009
–6– 62386-204  IEC:2009

DIGITAL ADDRESSABLE LIGHTING INTERFACE –

Part 204: Particular requirements for control gear –


Low voltage halogen lamps (device type 3)

1 Scope

This International Standard specifies a protocol and methods of test for the control by digital
signals of electronic control gear for use on a.c. or d.c. supplies, associated with low voltage
halogen lamps.

NOTE Tests in this standard are type tests. Requirements for testing individual control gear during production are
not included.

2 Normative references

The following referenced documents are indispensable for the application of this document.
For dated references, only the edition cited applies. For undated references, the latest edition
of the referenced document (including any amendments) applies.

IEC 62386-101:2009, Digital addressable lighting interface – Part 101: General requirements
– System

IEC 62386-102:2009, Digital addressable lighting interface – Part 102: General requirements
– Control gear

3 Terms and definitions

For the purposes of this document, the terms and definitions given in Clause 3 of IEC 62386-
101:2009 and Clause 3 of IEC 62386-102:2009 apply, with the following additions.

3.1
reference measurement
process during which gear determines the actual lamp load with internal procedures and
measurements, not specified by this standard

NOTE The details of this process are a matter of detailed design of gear and are outside the scope of this
standard.

3.2
detection of load decrease
recognition that the actual lamp load is significantly below the load measured during a
successful ‘reference measurement’

NOTE The criteria for regarding a load increase or decrease as significant can only be decided by the
manufacturer and these criteria should be described in the manual.

3.3
detection of load increase
recognition that the actual lamp load is significantly above the load measured during a
successful ‘reference measurement’

NOTE The criteria for regarding a load increase or decrease as significant can only be decided by the
manufacturer, and these criteria should be described in the manual.
BS EN 62386-204:2009
62386-204  IEC:2009 –7–

3.4
current protector
protective device switching off the output if the actual lamp load differs by more than ΔP from
the load detected during the reference measurement.

NOTE The value ΔP can only be specified by the manufacturer of the control gear and this value should be stated
in the manual.

3.5
thermal overload
scenario where the maximum permissible gear temperature is exceeded

3.6
thermal shut down
scenario where gear switches off the lamp because of a persistent thermal overload

3.7
light level reduction due to thermal overload
reduction of light level with the objective of decreasing gear temperature

4 General

The requirements of Clause 4 of IEC 62386-101:2009 and Clause 4 of IEC 62386-102:2009


apply.

5 Electrical specifications

The requirements of Clause 5 of IEC 62386-101:2009 and Clause 5 of IEC 62386-102:2009


apply.

6 Interface power supply

The requirements of Clause 6 of IEC 62386-101:2009 and Clause 6 of IEC 62386-102:2009


apply, if a power supply is integrated with the control gear.

7 Transmission protocol structure

The requirements of Clause 7 of IEC 62386-101:2009 and Clause 7 of IEC 62386-102:2009


apply.

8 Timing

The requirements of Clause 8 of IEC 62386-101:2009 and Clause 8 of IEC 62386-102:2009


apply.

9 Method of operation

The requirements of Clause 9 of IEC 62386-101:2009 and Clause 9 of IEC 62386-102:2009


apply, except as follows:

Addition to Clause 9 of IEC 62386-102:2009:


BS EN 62386-204:2009
–8– 62386-204  IEC:2009

9.9 Detection of load decrease

If the actual lamp load is significantly below the load measured during a successful ‘reference
measurement’, the gear may switch off the lamp if this is necessary for its safe operation. The
flag bit ‘load decrease’ is to be set in such circumstances.

9.10 Detection of load increase

If the actual lamp load is significantly above the load measured during a successful ‘reference
measurement’, the gear may switch off the lamp if this is necessary for its safe operation. The
flag bit ‘load increase’ is to be set in such circumstances.

9.11 Current protector

If the actual lamp load of the control gear differs by more than a defined amount ΔP from the
load detected during the reference measurement, the current protector becomes active and
switches off the lamp.

The current protector shall not become active until there has been a successful reference
measurement.

There are two possible situations in which the current protector becomes active:

– Overload: The actual lamp load is higher than the load detected during the reference
measurement by at least ΔP.
– Underload: The actual lamp load is lower than the load detected during the reference
measurement by at least ΔP.

The current protector shall become inactive either on mains voltage interruption or on receipt
of a command which causes the arc power level to be 0. If after switching on again the
situation causing the current protector to become active still pertains, the current protector
shall become active again.

The current protector can be enabled and disabled by the commands 225 'ENABLE
CURRENT PROTECTOR' and 226 'DISABLE CURRENT PROTECTOR'.

An active current protector shall become inactive on reception of command 226 ‘DISABLE
CURRENT PROTECTOR’.

If the current protector is active command 224 ‘REFERENCE SYSTEM POWER’ shall be
ignored.

9.12 Lamp replacement on gear with load increase/decrease or current protector


feature

If a lamp is replaced with one of a different wattage without a new ‘REFERENCE SYSTEM
POWER’ measurement being performed, the gear shall detect a load increase or a load
decrease as appropriate.

NOTE If a lamp is replaced with one of the same wattage, the user should initiate a new ‘REFERENCE SYSTEM
POWER’ measurement only if this is recommended by the manufacturer.

10 Declaration of variables

The requirements of Clause 10 of IEC 62386-101:2009 and Clause 10 of IEC 62386-102:2009


apply, with the following additional variables for this device type, as indicated in Table 1.
BS EN 62386-204:2009
62386-204  IEC:2009 –9–

Power levels stored in persistent memory due to command 224 ‘REFERENCE SYSTEM
POWER’ shall not be changed due to command ‘RESET’.

Additional variables for this device type are as indicated in Table 1.

Table 1 – Declaration of variables


a
Variable Default value Reset value Range of Memory
validity
(control gear leaves
the factory)
b c
“FAILURE STATUS” ???? ???? no change 0 – 255 1 byte RAM
“FEATURE BYTE” factory burn-in no change 0 – 255 1 byte ROM
“EXTENDED 1 no change 0 – 255 1 byte ROM
VERSION NUMBER”
“DEVICE TYPE” 3 no change 0 – 254, 1 byte ROM
255 (mask)
? = undefined.
a
Persistent memory (storage time indefinite) if not stated otherwise.
b
Power up value.
c
Bit 7 of this byte shall be stored in the persistent memory.

11 Definition of commands

The requirements of Clause 11 of IEC 62386-101:2009 and Clause 11 of IEC 62386-102:2009


apply, except as follows:

Amendment of Clause 11 of IEC 62386-102:2009:

11.3.1 Queries related to status information

Amendment:

Command 146: YAAA AAA1 1001 0010 'QUERY LAMP FAILURE'

Asks if there is a lamp problem at the given address. Answer shall be ‘Yes’ or ‘No’.

‘Yes’ means either open circuit or short circuit or load increase or load decrease or current
protector active. ‘No’ does not necessarily imply that no lamps have failed.

Command 153: YAAA AAA1 1001 1001 'QUERY DEVICE TYPE'

Answer shall be 3.

11.3.4 Application extended commands

Replacement:

11.3.4.1 Application extended configuration commands

Every configuration command (224 – 226) shall be received a second time within 100 ms
(nominal) before it is executed in order to reduce the probability of incorrect reception. No
other commands addressing the same control gear shall be sent between these two
commands, otherwise the first such command shall be ignored and the respective control or
configuration sequence shall be aborted.
BS EN 62386-204:2009
– 10 – 62386-204  IEC:2009

Command 272 shall be received before the two instances of the application extended
configuration command, but not between them (see Figure 1).

Application extended Application extended


Command 272 configuration command configuration command

max. 100 ms

IEC 639/09

Figure 1 – Application extended configuration command sequence example

All values of DTR shall be checked against the values mentioned in Clause 10, Range of
validity, i.e. the value shall be set to the upper / lower limit if it is above / below the valid
range defined in Table 1.

Command 224: YAAA AAA1 1110 0000 ‘REFERENCE SYSTEM POWER’

Reference measurement is an optional feature, the presence of which is indicated in bits 2, 3


and 4 of the ‘FEATURES’ byte (see command 240). If all these bits are zero, then reference
measurement is not supported, and this command shall be ignored. Otherwise, on receipt of
this command, the control gear shall proceed as follows.

The control gear shall measure and store system power levels in order to detect load increase
or load decrease. It is up to the manufacturer to decide upon the number of system power
levels each type of gear should measure.

The measured power level shall be stored in the persistent memory. Commands received
during the measuring period shall be ignored except query commands and command 256.

After 15 min at most, the control gear shall finish the measurement process and shall go back
to normal operation. The measurement process shall be aborted if command 256
‘TERMINATE’ is received.

When there has been no successful reference measurement or the most recent reference
measurement was unsuccessful, bit 7, reference measurement failed, in the answer to
command 240 ‘QUERY FAILURE STATUS’ shall be set and command 249 ‘QUERY
REFERENCE MEASUREMENT FAILED’ shall be answered with ‘Yes’.

If the current protector is active this command shall be ignored. In this case bit 7, reference
measurement failed, in the answer to command 240 ‘QUERY FAILURE STATUS’ shall be set
and command 249 ‘QUERY REFERENCE MEASUREMENT FAILED’ shall be answered with
‘Yes’.

Command 225: YAAA AAA1 1110 0001 'ENABLE CURRENT PROTECTOR'

Enables the current protector of the control gear. The current protector can become active
after a successful reference measurement started by command 224.

The default configuration of the gear is 'CURRENT PROTECTOR ENABLED'. The status of
the current protector (enabled / disabled) shall be stored in the persistent memory of the
control gear.

The current protector is an optional feature. Control gear without this feature shall not react
(see command 240).
BS EN 62386-204:2009
62386-204  IEC:2009 – 11 –

Command 226: YAAA AAA1 1110 0010 'DISABLE CURRENT PROTECTOR'

Disables the current protector of the control gear.

The current protector is an optional feature. Control gear without this feature shall not react in
any way.
(see command 240).

Commands 227: YAAA AAA1 1110 0011

Reserved for future needs. The control gear shall not react in any way.

Commands 228-231: YAAA AAA1 1110 01XX

Reserved for future needs. The control gear shall not react in any way.

Commands 232-239: YAAA AAA1 1110 1XXX

Reserved for future needs. The control gear shall not react in any way.

11.3.4.2 Application extended query commands

Command 240: YAAA AAA1 1111 0000 ‘QUERY FEATURES’

The answer from the control gear shall be the following information about which optional
features and query commands are implemented.

bit 0 ‘1’ = short circuit detection can be queried


bit 1 ‘1’ = open circuit detection can be queried
bit 2 ‘1’ = detection of load decrease can be queried
bit 3 ‘1’ = detection of load increase can be queried
bit 4 ‘1’ = current protector is implemented and can be queried
bit 5 ‘1’ = thermal shut down can be queried
bit 6 ‘1’ = light level reduction due to thermal overload can be queried
bit 7 ‘1’ = physical selection supported
Bits 2, 3, 4. If any of these features is available, command 224 ‘REFERENCE SYSTEM
POWER’, command 249 ‘QUERY REFERENCE RUNNING’ and command 250 'QUERY
REFERENCE MEASUREMENT FAILED' are mandatory.

Bit 5; bit 6. A ‘thermal shut down’ or a ‘light level reduction due to thermal overload’ are not
interpreted as lamp failure; nevertheless the control gear shall answer ‘MASK’ to a ‘QUERY
ACTUAL LEVEL’.

NOTE The fact that a thermal overload protection is implemented, the actual status of which can be queried, does
not relieve the user from the obligation to comply with any safety-relevant information for installation given by the
manufacturer. A note to this effect should be included in the manual.

Command 241: YAAA AAA1 1111 0001 ‘QUERY FAILURE STATUS’

Answer is the following ‘FAILURE STATUS’ byte:

bit 0 short circuit ‘0’ = No


bit 1 open circuit ‘0’ = No
bit 2 load decrease ‘0’ = No
bit 3 load increase ‘0’ = No
bit 4 current protector active ‘0’ = No
bit 5 thermal shut down ‘0’ = No
bit 6 thermal overload with light level reduction ‘0’ = No
bit 7 reference measurement failed ‘0’ = No
BS EN 62386-204:2009
– 12 – 62386-204  IEC:2009

Bit 0, short circuit, means either a severe short circuit or a physical control gear overload
(> 100 % of nominal load).

If any of the bits 0 to 4 are set, the answer to command 146 'QUERY LAMP FAILURE' shall
be 'Yes' and bit 1 in the answer to command 144 'QUERY STATUS' shall be set.

If any of the back-channel bits 0, 1, 5 or 6 are set, the answer to command 160 'QUERY
ACTUAL LEVEL' shall be 'MASK'.

Bit 7 shall be set if the reference measurement of the system power failed for any reason, or if
there has been no reference measurement at all. It shall be stored in the persistent memory.
If the reference measurement is not supported, this bit shall always be ‘0’.

The ‘FAILURE STATUS’ byte shall be available in the RAM of the control gear and shall be
updated regularly by the control gear according to the actual situation. The bits shall not be
changed if the relevant situation cannot be checked.

Command 242: YAAA AAA1 1111 0010 ‘QUERY SHORT CIRCUIT’

Asks if there is a short circuit detected at the given address. Answer shall be ‘Yes’ or ‘No’.

If this query is answered with 'Yes' the answer to command 146 'QUERY LAMP FAILURE'
shall be 'Yes' and bit 1 in the answer to command 144 'QUERY STATUS' shall be set.

Control gear without this feature shall not react (see command 240).

Command 243: YAAA AAA1 1111 0011 ‘QUERY OPEN CIRCUIT’

Asks if there is an open circuit detected at the given address. Answer shall be ‘Yes’ or ‘No’.

If this query is answered with 'Yes' the answer to command 146 'QUERY LAMP FAILURE'
shall be 'Yes' and bit 1 in the answer to command 144 'QUERY STATUS' shall be set.

Control gear without this feature shall not react (see command 240).

Command 244: YAAA AAA1 1111 0100 ‘QUERY LOAD DECREASE’

Asks if there is a significant load decrease (compared to the system reference power)
detected at the given address.

If this query is answered with 'Yes' the answer to command 146 'QUERY LAMP FAILURE'
shall be 'Yes' and bit 1 in the answer to command 144 'QUERY STATUS' shall be set.

Answer shall be ‘Yes’ or ‘No’. Control gear without this feature shall not react (see command
240).

Command 245: YAAA AAA1 1111 0101 ‘QUERY LOAD INCREASE’

Asks if there is a significant load increase (compared to the system reference power) detected
at the given address.

If this query is answered with 'Yes' the answer to command 146 'QUERY LAMP FAILURE'
shall be 'Yes' and bit 1 in the answer to command 144 'QUERY STATUS' shall be set.

Answer shall be ‘Yes’ or ‘No’. Control gear without this feature shall not react (see command
240).
BS EN 62386-204:2009
62386-204  IEC:2009 – 13 –

Command 246: YAAA AAA1 1111 0110 ‘QUERY CURRENT PROTECTOR


ACTIVE’

Asks if the current protector is active at the given address. Answer shall be ‘Yes’ or ‘No’.

If this query is answered with 'Yes' the answer to command 146 'QUERY LAMP FAILURE'
shall be 'Yes' and bit 1 in the answer to command 144 'QUERY STATUS' shall be set.

Control gear without this feature shall not react (see command 240).

Command 247: YAAA AAA1 1111 0111 ‘QUERY THERMAL SHUT DOWN’

Asks if there is a thermal shut down detected at the given address. Answer shall be ‘Yes’ or
‘No’.
Control gear without this feature shall not react (see command 240).

Command 248: YAAA AAA1 1111 1000 ‘QUERY THERMAL OVERLOAD’

Asks if there is a thermal overload with light level reduction detected at the given address.
Answer shall be ‘Yes’ or ‘No’. Control gear without this feature shall not react (see command
240).

Command 249: YAAA AAA1 1111 1001 ‘QUERY REFERENCE RUNNING’

Asks if there is the ‘REFERENCE SYSTEM POWER’ measurement running at the given
address.

Answer shall be ‘Yes’ or ‘No’.

Control gear without this feature shall not react (see command 240).

Command 250: YAAA AAA1 1111 1010 ‘QUERY REFERENCE MEASUREMENT


FAILED’

Asks if the reference measurement started by command 224 'REFERENCE SYSTEM POWER'
failed at the given address. Answer shall be ‘Yes’ or ‘No’.

Control gears without this feature shall not react (see command 240).

Command 251: YAAA AAA1 1111 1011 'QUERY CURRENT PROTECTOR


ENABLED'

Asks if the current protector is enabled. Answer shall be ‘Yes’ or ‘No’.

The current protector is an optional feature. Control gear without this feature shall not react in
any way (see command 240).

Commands 252-253: YAAA AAA1 1111 110X

Reserved for future needs. The control gear shall not react in any way.

Command 254: YAAA AAA1 1111 1110

Reserved for future needs. The control gear shall not react in any way.

Command 255: YAAA AAA1 1111 1111 ‘QUERY EXTENDED VERSION


NUMBER’
BS EN 62386-204:2009
– 14 – 62386-204  IEC:2009

The answer shall be 1.

11.4.4 Extended special commands

Amendment:

Command 272: 1100 0001 0000 0011 ‘ENABLE DEVICE TYPE 3’

The device type for control gear for low voltage halogen lamps is 3.

11.5 Summary of the command set

The commands listed in subclause 11.5 of IEC 62386-102:2009 apply with the following
additional commands for device type 3 listed in Table 2.

Table 2 – Summary of the application extended command set

Command Number Command Code Command Name


224 YAAA AAA1 1110 0000 REFERENCE SYSTEM POWER
225 YAAA AAA1 1110 0001 ENABLE CURRENT PROTECTOR
226 YAAA AAA1 1110 0010 DISABLE CURRENT PROTECTOR
a
227 YAAA AAA1 1110 0011
a
228 – 231 YAAA AAA1 1110 01XX
a
232 – 239 YAAA AAA1 1110 1XXX
240 YAAA AAA1 1111 0000 QUERY FEATURES
241 YAAA AAA1 1111 0001 QUERY FAILURE STATUS
242 YAAA AAA1 1111 0010 QUERY SHORT CIRCUIT
243 YAAA AAA1 1111 0011 QUERY OPEN CIRCUIT
244 YAAA AAA1 1111 0100 QUERY LOAD DECREASE
245 YAAA AAA1 1111 0101 QUERY LOAD INCREASE
246 YAAA AAA1 1111 0110 QUERY CURRENT PROTECTOR ACTIVE
247 YAAA AAA1 1111 0111 QUERY THERMAL SHUT DOWN
248 YAAA AAA1 1111 1000 QUERY THERMAL OVERLOAD
249 YAAA AAA1 1111 1001 QUERY REFERENCE RUNNING
250 YAAA AAA1 1111 1010 QUERY REFERENCE MEASUREMENT FAILED
251 YAAA AAA1 1111 1011 QUERY CURRENT PROTECTOR ENABLED
a
252 – 253 YAAA AAA1 1111 110X
a
254 YAAA AAA1 1111 1101
255 YAAA AAA1 1111 1111 QUERY EXTENDED VERSION NUMBER
272 1100 0001 0000 0011 ENABLE DEVICE TYPE 3
a
Reserved for future needs. The control gear shall not react in any way.

12 Test procedures

The requirements of Clause 12 of IEC 62386-102:2009 apply, except as follows.

12.4 Test sequence 'Physical address allocation'

Addition:
BS EN 62386-204:2009
62386-204  IEC:2009 – 15 –

This test sequence is only mandatory for control gears supporting this feature.

Additional subclause:

12.7 Test sequences 'APPLICATION EXTENDED COMMANDS FOR DEVICE TYPE 3'

12.7.1 Test sequence 'APPLICATION EXTENDED QUERY COMMANDS'

12.7.1.1 Test sequence 'QUERY FEATURES'

Command 240 'QUERY FEATURES' as well as command 272 'ENABLE DEVICE TYPE 3' are
tested. The test sequence 'QUERY FEATURES' is shown in Figure 2.

Test
QUERY FEATURES

SEND TWICE
BROADCAST Reset DUT
RESET

wait
(300 ms + Response time)

SEND TO DEVICE TYPE


Test command using
3 BROADCAST
broadcast address
QUERY FEATURES

Error 7111
"QUERY FEATURES
any reply ? No
not answered for
device type 3"

Yes

Test
done
IEC 640/09

Figure 2 – Test sequence 'QUERY FEATURES'


BS EN 62386-204:2009
– 16 – 62386-204  IEC:2009

12.7.1.2 Test sequence 'QUERY SHORT CIRCUIT'

Command 242 'QUERY SHORT CIRCUIT', bit 0 of the answer of command 241 'QUERY
FAILURE STATUS', bit 1 and bit 2 of the answer of command 144 'QUERY STATUS' and the
correct function of the commands 146 'QUERY LAMP FAILURE', 147 'QUERY LAMP POWER
ON' and 160 'QUERY ACTUAL LEVEL' during short circuit conditions are tested. The test
sequence 'QUERY SHORT CIRCUIT' is shown in Figure 3.

Test
QUERY SHORT
CIRCUIT

Error 7123
SEND TWICE
answer "QUERY STATUS
BROADCAST Reset DUT No
= XXXXX01Xb ? answered wrong with
RESET
short circuit"

Yes
wait
(300 ms + Response time)

SEND
SEND TO DEVICE TYPE BROADCAST Lamp Failure detected?
3 BROADCAST QUERY LAMP FAILURE
QUERY FEATURES
Error 7124
"QUERY LAMP
answer Feature supported any reply ? No FAILURE not
No answered with
= XXXXXXX1b ? by DUT?
short circuit applied"
Yes
Yes

SEND TO DEVICE TYPE


3 BROADCAST FAILURE STATUS correct? SEND
Lamp Power has to be
QUERY FAILURE STATUS BROADCAST
switched off
QUERY LAMP POWER ON
Error 7121
"QUERY FAILURE Error 7125
answer "QUERY LAMP
No STATUS answered
= XXXXXXX0b ? any reply ? Yes POWER ON
wrong without
short circuit" answered wrong with
short circuit applied"
Yes
No

Apply
Short Circuit to output SEND
Query must be answered with
BROADCAST
MASK
QUERY ACTUAL LEVEL
wait 5 s Time to detect failure
Error 7126
"QUERY ACTUAL
answer = '255'
No LEVEL answered
SEND TO DEVICE TYPE (MASK) ?
wrong with
3 BROADCAST FAILURE STATUS correct?
short circuit applied"
QUERY FAILURE STATUS
Yes
Error 7122
"QUERY FAILURE
answer
No STATUS answered
= XXXXXXX1b ? SEND TO DEVICE TYPE
wrong with Test command using
3 BROADCAST
short circuit" broadcast address
QUERY SHORT CIRCUIT FAILURE
Yes

Error 7127
"QUERY SHORT
any reply ? No
SEND CIRCUIT FAILURE
STATUS correct when short
BROADCAST not answered"
circuit applied?
QUERY STATUS
Yes

Remove
Short Circuit at output
Report:
"QUERY SHORT
CIRCUIT FAILURE
not supported
by DUT "

Test
done

IEC 641/09

Figure 3 – Test sequence 'QUERY SHORT CIRCUIT'


BS EN 62386-204:2009
62386-204  IEC:2009 – 17 –

12.7.1.3 Test sequence 'QUERY OPEN CIRCUIT'

Command 243 'QUERY OPEN CIRCUIT' as well as bit 1 of the answer of command 241
'QUERY FAILURE STATUS' and the correct answer of command 160 'QUERY ACTUAL
LEVEL' is tested. The test sequence 'QUERY OPEN CIRCUIT' is shown in Figure 4.

Test
QUERY OPEN
CIRCUIT

Error 7133
SEND TWICE
answer "QUERY STATUS
BROADCAST Reset DUT No
= XXXXX01Xb ? answered wrong with
RESET
open circuit"

Yes
wait
(300 ms + Response time)

SEND
SEND TO DEVICE TYPE BROADCAST Lamp Failure detected?
3 BROADCAST QUERY LAMP FAILURE
QUERY FEATURES
Error 7134
"QUERY LAMP
answer Feature supported any reply ? No FAILURE not
No answered with
= XXXXXX1Xb ? by DUT?
open circuit applied"
Yes
Yes

SEND TO DEVICE TYPE


3 BROADCAST FAILURE STATUS correct? SEND
Lamp Power has to be
QUERY FAILURE STATUS BROADCAST
switched off
QUERY LAMP POWER ON
Error 7131
"QUERY FAILURE Error 7135
answer "QUERY LAMP
No STATUS answered
= XXXXXX0Xb ? any reply ? Yes POWER ON
wrong without
open circuit" answered wrong with
open circuit applied"
Yes
No

Disconnect
Lamp(s) SEND
Query must be answered with
BROADCAST
MASK
QUERY ACTUAL LEVEL
wait 5 s Time to detect failure
Error 7136
"QUERY ACTUAL
answer = '255'
No LEVEL answered
SEND TO DEVICE TYPE (MASK) ?
wrong with
3 BROADCAST FAILURE STATUS correct?
open circuit applied"
QUERY FAILURE STATUS
Yes
Error 7132
"QUERY FAILURE
answer
No STATUS answered
= XXXXXX1Xb ? SEND TO DEVICE TYPE
wrong with Test command using
3 BROADCAST
open circuit" broadcast address
QUERY OPEN CIRCUIT FAILURE
Yes

Error 7137
"QUERY OPEN
any reply ? No
SEND CIRCUIT FAILURE
STATUS correct when open
BROADCAST not answered"
circuit applied?
QUERY STATUS
Yes

Reconnect
Lamp(s)
Report:
"QUERY OPEN
CIRCUIT FAILURE
not supported
by DUT "

Test
done

IEC 642/09

Figure 4 – Test sequence 'QUERY OPEN CIRCUIT'


BS EN 62386-204:2009
– 18 – 62386-204  IEC:2009

12.7.1.4 Test sequence 'QUERY LOAD DECREASE'

Command 244 'QUERY LOAD DECREASE' as well as bit 2 of the answer of command 241
'QUERY FAILURE STATUS' are tested. The correct function of the command 224
'REFERENCE SYSTEM POWER' and command 241 'QUERY FAILURE STATUS' has to be
ensured using the test sequence 7.2.1. The test sequence 'QUERY LOAD DECREASE' is
shown in Figure 5.

Test
QUERY LOAD
DECREASE

SEND TWICE SEND TO DEVICE TYPE


BROADCAST Reset DUT 3 BROADCAST FAILURE STATUS correct?
RESET QUERY FAILURE STATUS

wait Error 7143


(300 ms + Response time) "QUERY FAILURE
answer
No STATUS answered
= XXXXX0XXb ?
wrong without
SEND TO DEVICE TYPE load decrease"
Feature supported
3 BROADCAST Yes
by DUT?
QUERY FEATURES

Disconnect
answer part of the load according Simulate Failure
No
= XXXXX1XXb ? to manufacturer

Yes SEND
BROADCAST STATUS correct?
SEND TWICE TO DEVICE TYPE QUERY STATUS
3 BROADCAST Start reference measurement
REFERENCE SYSTEM POWER
Error 7144
answer "QUERY STATUS
No
= XXXXX01Xb ? answered wrong at
time := 0 load decrease"

Yes

SEND TO DEVICE TYPE


3 BROADCAST Measurement finnished? SEND
QUERY REFERENCE RUNNING BROADCAST Lamp Failure detected?
Yes QUERY LAMP FAILURE

Error 7145
answer "QUERY LAMP
No any reply ? No FAILURE not
= YES ?
answered at load
decrease"
Yes Yes

time < 17 min. Timeout? SEND TO DEVICE TYPE


3 BROADCAST Test command
QUERY FAILURE STATUS
No
Error 7146
"QUERY FAILURE
answer
No STATUS answered
= XXXXX1XXb ?
wrong at load
decrease"
SEND TO DEVICE TYPE
3 BROADCAST Test command Yes
QUERY LOAD DECREASE FAILURE

Error 7142 SEND TO DEVICE TYPE


"QUERY LOAD 3 BROADCAST Test command
any reply ? Yes DECREASE FAILURE QUERY LOAD DECREASE FAILURE
answered without
load decrease"
Error 7147
"QUERY LOAD
No any reply ? No
DECREASE FAILURE
not answered"

Error 7141
Yes
Timeout

Reconnect
complete load
Report:
"QUERY LOAD
DECREASE FAILURE
not supported by DUT"

Test
done

IEC 643/09

Figure 5 – Test sequence 'QUERY LOAD DECREASE'


BS EN 62386-204:2009
62386-204  IEC:2009 – 19 –

12.7.1.5 Test sequence 'QUERY LOAD INCREASE'

Command 245 'QUERY LOAD INCREASE' as well as bit 3 of the answer of command 241
'QUERY FAILURE STATUS' are tested. The correct function of the command 224
'REFERENCE SYSTEM POWER' and command 241 'QUERY FAILURE STATUS' has to be
ensured using the test sequence 7.2.1. The test sequence 'QUERY LOAD INCREASE' is
shown in Figure 6.

Test
QUERY LOAD
INCREASE

SEND TWICE SEND TO DEVICE TYPE


BROADCAST Reset DUT 3 BROADCAST FAILURE STATUS correct?
RESET QUERY FAILURE STATUS

wait Error 7153


(300 ms + Response time) "QUERY FAILURE
answer
No STATUS answered
= XXXX0XXXb ?
wrong without
SEND TO DEVICE TYPE load increase"
Feature supported
3 BROADCAST Yes
by DUT?
QUERY FEATURES

Connect
answer additional load according Simulate Failure
No
= XXXX1XXXb ? to manufacturer

Yes SEND
BROADCAST STATUS correct?
SEND TWICE TO DEVICE TYPE QUERY STATUS
3 BROADCAST Start reference measurement
REFERENCE SYSTEM POWER
Error 7154
answer "QUERY STATUS
No
= XXXXX01Xb ? answered wrong at
time := 0 load increase"

Yes

SEND TO DEVICE TYPE


3 BROADCAST Measurement finnished? SEND
QUERY REFERENCE RUNNING BROADCAST Lamp Failure detected?
Yes QUERY LAMP FAILURE

Error 7155
answer "QUERY LAMP
No any reply ? No FAILURE not
= YES ?
answered at load
increase"
Yes Yes

time < 17 min. Timeout? SEND TO DEVICE TYPE


3 BROADCAST Test command
QUERY FAILURE STATUS
No
Error 7156
"QUERY FAILURE
answer
No STATUS answered
= XXXX1XXXb ?
wrong at load
increase"
SEND TO DEVICE TYPE
3 BROADCAST Test command Yes
QUERY LOAD INCREASE FAILURE

Error 7152 SEND TO DEVICE TYPE


"QUERY LOAD 3 BROADCAST Test command
any reply ? Yes INCREASE FAILURE QUERY LOAD INCREASE FAILURE
answered without
load increase"
Error 7157
"QUERY LOAD
No any reply ? No
INCREASE FAILURE
not answered"

Error 7151
Yes
Timeout

Disconnect
additional load
Report:
"QUERY LOAD
INCREASE FAILURE
not supported by DUT"

Test
done

IEC 644/09

Figure 6 – Test sequence 'QUERY LOAD INCREASE'


BS EN 62386-204:2009
– 20 – 62386-204  IEC:2009

12.7.1.6 Test sequence 'QUERY CURRENT PROTECTOR ACTIVE: Underload'

Command 246 'QUERY CURRENT PROTECTOR ACTIVE' as well as bit 4 of the answer of
command 241 'QUERY FAILURE STATUS' are tested in case of underload condition. The
correct function of the command 224 'REFERENCE SYSTEM POWER' and command 241
'QUERY FAILURE STATUS' has to be ensured using the test sequence 7.2.1. The test
sequence 'QUERY CURRENT PROTECTOR ACTIVE: Underload' is shown in Figure 7.
Test
QUERY CURRENT PROTECTOR
ACTIVE: Underload

Error 7163
SEND TWICE "QUERY FAILURE
BROADCAST Reset DUT answer
No STATUS answered
RESET = XXX0XXXXb ?
wrong with nominal
load"
wait Yes
(300 ms + Response time)

SEND TO DEVICE TYPE Disconnect


Feature supported
3 BROADCAST part of the load according Simulate Failure
by DUT?
QUERY FEATURES to manufacturer

SEND
answer BROADCAST STATUS correct?
No
= XXX1XXXXb ? QUERY STATUS

Yes Error 7164


answer "QUERY STATUS
No
= XXXXX01Xb ? answered wrong with
SEND TWICE TO DEVICE TYPE underload"
3 BROADCAST Start reference measurement
REFERENCE SYSTEM POWER Yes

time := 0
SEND
BROADCAST Lamp Failure detected?
QUERY LAMP FAILURE

SEND TO DEVICE TYPE Error 7165


3 BROADCAST Measurement finnished? "QUERY LAMP
QUERY REFERENCE RUNNING any reply ? No FAILURE not
Yes answered with
underload"
Yes
answer
= YES ?

SEND TO DEVICE TYPE


Yes 3 BROADCAST Test command
QUERY FAILURE STATUS

time < 17 min. Timeout? No Error 7166


answer "QUERY FAILURE
No
= XXX1XXXXb ? STATUS answered
wrong with underload"

Yes

SEND TO DEVICE TYPE


SEND TO DEVICE TYPE 3 BROADCAST Test command
3 BROADCAST Test command QUERY CURRENT PROTECTOR FAILURE
QUERY CURRENT PROTECTOR FAILURE

Error 7167
No Error 7162 "QUERY CURRENT
"QUERY CURRENT any reply ? No PROTECTOR
any reply ? Yes PROTECTOR FAILURE not
FAILURE answered answered"
with nominal load"
Yes
No

SEND
SEND TO DEVICE TYPE Query must be answered with
BROADCAST
3 BROADCAST FAILURE STATUS correct? MASK
QUERY ACTUAL LEVEL
QUERY FAILURE STATUS

Error 7168
answer = '255' "QUERY ACTUAL
No
(MASK) ? LEVEL answered
wrong with underload"

Error 7161 Yes


Timeout

Reconnect
complete load
Report:
"QUERY CURRENT
PROTECTOR FAILURE
not supported by DUT"

Test
done

IEC 645/09

Figure 7 – 'QUERY CURRENT PROTECTOR ACTIVE: Underload'


BS EN 62386-204:2009
62386-204  IEC:2009 – 21 –

12.7.1.7 Test sequence 'QUERY CURRENT PROTECTOR ACTIVE: Overload'

Command 246 'QUERY CURRENT PROTECTOR ACTIVE' as well as bit 4 of the answer of
command 241 'QUERY FAILURE STATUS' are tested in case of overload condition. The
correct function of the command 224 'REFERENCE SYSTEM POWER' and command 241
'QUERY FAILURE STATUS' has to be ensured using the test sequence 7.2.1. The test
sequence 'QUERY CURRENT PROTECTOR ACTIVE: Overload' is shown in Figure 8.
Test
QUERY CURRENT PROTECTOR
ACTIVE: Overload

Error 7173
SEND TWICE "QUERY FAILURE
BROADCAST Reset DUT answer
No STATUS answered
RESET = XXX0XXXXb ?
wrong with nominal
load"
wait Yes
(300 ms + Response time)

SEND TO DEVICE TYPE Connect


Feature supported
3 BROADCAST additional load according Simulate Failure
by DUT?
QUERY FEATURES to manufacturer

SEND
answer BROADCAST STATUS correct?
No
= XXX1XXXXb ? QUERY STATUS

Yes Error 7174


answer "QUERY STATUS
No
= XXXXX01Xb ? answered wrong with
SEND TWICE TO DEVICE TYPE overload"
3 BROADCAST Start reference measurement
REFERENCE SYSTEM POWER Yes

time := 0
SEND
BROADCAST Lamp Failure detected?
QUERY LAMP FAILURE

SEND TO DEVICE TYPE Error 7175


3 BROADCAST Measurement finnished? "QUERY LAMP
QUERY REFERENCE RUNNING any reply ? No FAILURE not
Yes answered with
overload"
Yes
answer
= YES ?

SEND TO DEVICE TYPE


Yes 3 BROADCAST Test command
QUERY FAILURE STATUS

time < 17 min. Timeout? No Error 7176


answer "QUERY FAILURE
No
= XXX1XXXXb ? STATUS answered
wrong with overload"

Yes

SEND TO DEVICE TYPE


SEND TO DEVICE TYPE 3 BROADCAST Test command
3 BROADCAST Test command QUERY CURRENT PROTECTOR FAILURE
QUERY CURRENT PROTECTOR FAILURE

Error 7177
No Error 7172 "QUERY CURRENT
"QUERY CURRENT any reply ? No PROTECTOR
any reply ? Yes PROTECTOR FAILURE not
FAILURE answered answered"
with nominal load"
Yes
No

SEND
SEND TO DEVICE TYPE Query must be answered with
BROADCAST
3 BROADCAST FAILURE STATUS correct? MASK
QUERY ACTUAL LEVEL
QUERY FAILURE STATUS

Error 7178
answer = '255' "QUERY ACTUAL
No
(MASK) ? LEVEL answered
wrong with overload"

Error 7171 Yes


Timeout

Disconnect
additional load
Report:
"QUERY CURRENT
PROTECTOR FAILURE
not supported by DUT"

Test
done
IEC 646/09

Figure 8 – 'QUERY CURRENT PROTECTOR ACTIVE: Overload'


BS EN 62386-204:2009
– 22 – 62386-204  IEC:2009

12.7.1.8 Test sequence 'QUERY THERMAL SHUT DOWN'

Command 247 'QUERY THERMAL SHUT DOWN' as well as bit 5 of the answer of
command 241 'QUERY FAILURE STATUS' are tested. The correct answer to the commands
144 'QUERY STATUS', 146 'QUERY LAMP FAILURE', 147 'QUERY LAMP POWER ON' and
160 'QUERY ACTUAL LEVEL' is checked. The test sequence 'QUERY THERMAL SHUT
DOWN' is shown in Figure 9.
Test
QUERY THERMAL
SHUT DOWN

SEND TWICE
BROADCAST Reset DUT
RESET

wait
(300 ms + Response time)

SEND TO DEVICE TYPE


Feature supported
3 BROADCAST
by DUT?
QUERY FEATURES
Error 7184
answer "QUERY STATUS
No
= XXXXX00Xb ? answered wrong at
answer thermal shut down"
No
= XX1XXXXXb ?
Yes

Yes
SEND
SEND TO DEVICE TYPE BROADCAST Lamp Failure detected?
3 BROADCAST Test command QUERY LAMP FAILURE
QUERY THERMAL SHUT DOWN FAILURE

Error 7185
Error 7181 "QUERY LAMP
"QUERY THERMAL any reply? Yes
FAILURE answered at
any reply ? Yes SHUT DOWN FAILURE thermal shut down"
answered without
thermal shut down" No
No

SEND
Lamp Power has to be
BROADCAST
SEND TO DEVICE TYPE switched off
QUERY LAMP POWER ON
3 BROADCAST Test command
QUERY FAILURE STATUS
Error 7186
"QUERY LAMP
Error 7182 any reply? Yes POWER ON
"QUERY FAILURE answered wrong at
answer
No STATUS answered thermal shut down"
= XX0XXXXXb ?
wrong without thermal
No
shut down"
Yes
SEND
Query must be answered with
BROADCAST
MASK
Heat up QUERY ACTUAL LEVEL
DUT according to Simulate Failure
manufacturer Error 7187
"QUERY ACTUAL
answer = '255'
No LEVEL answered
(MASK) ?
SEND TO DEVICE TYPE wrong at thermal shut
3 BROADCAST FAILURE STATUS correct? down"
QUERY FAILURE STATUS Yes

Error 7183
"QUERY FAILURE SEND TO DEVICE TYPE
answer
No STATUS answered 3 BROADCAST Test command
= XX1XXXXXb ?
wrong at thermal shut QUERY THERMAL SHUT DOWN FAILURE
down"
Yes Error 7188
"QUERY THERMAL
any reply ? No SHUT DOWN
FAILURE not
SEND
answered"
BROADCAST STATUS correct?
QUERY STATUS Yes

Cool down
DUT to normal operating
temperature
Report:
"QUERY THERMAL SHUT
DOWN FAILURE not
supported by DUT"

Test
done

IEC 647/09

Figure 9 – 'QUERY THERMAL SHUT DOWN'


BS EN 62386-204:2009
62386-204  IEC:2009 – 23 –

12.7.1.9 Test sequence 'QUERY THERMAL OVERLOAD'

Command 248 'QUERY THERMAL OVERLOAD' as well as bit 6 of the answer of


command 241 'QUERY FAILURE STATUS' are tested. Due to reduction of the light level
command 160 'QUERY ACTUAL LEVEL' has to be answered with 'MASK'. The test sequence
'QUERY THERMAL OVERLOAD' is shown in Figure 10.

Test
QUERY THERMAL
OVERLOAD

SEND TWICE Error 7192


BROADCAST Reset DUT "QUERY FAILURE
RESET answer
No STATUS answered
= X0XXXXXXb ?
wrong at normal
temperature"
wait
(300 ms + Response time) Yes

SEND TO DEVICE TYPE


Feature supported Heat up
3 BROADCAST
by DUT? DUT according to Simulate Failure
QUERY FEATURES
manufacturer

answer SEND TO DEVICE TYPE


No 3 BROADCAST FAILURE STATUS correct?
= X1XXXXXXb ?
QUERY FAILURE STATUS

Yes Error 7193


"QUERY FAILURE
answer
SEND TO DEVICE TYPE No STATUS answered
= X1XXXXXXb ?
3 BROADCAST Test command wrong at over
QUERY THERMAL OVERLOAD FAILURE temperature"
Yes
Error 7191
"QUERY THERMAL
any reply ? Yes OVERLOAD FAILURE
answered without over SEND
temperature" BROADCAST Lamp Power reduced?
QUERY ACTUAL LEVEL
No
Error 7194
"QUERY ACTUAL
answer = '255'
No LEVEL answered
SEND TO DEVICE TYPE (MASK) ?
wrong at over
3 BROADCAST Test command
temperature"
QUERY FAILURE STATUS
Yes

SEND TO DEVICE TYPE


3 BROADCAST Test command
QUERY THERMAL OVERLOAD FAILURE

Error 7195,i
"QUERY THERMAL
any reply ? No
OVERLOAD FAILURE
not answered"

Yes

Cool down
DUT to normal operating
temperature
Report:
"QUERY THERMAL
OVERLOAD FAILURE not
supported by DUT"

Test
done

IEC 648/09

Figure 10 – 'QUERY THERMAL OVERLOAD'


BS EN 62386-204:2009
– 24 – 62386-204  IEC:2009

12.7.2 Test sequence 'APPLICATION EXTENDED CONFIGURATION COMMANDS'

12.7.2.1 Test sequence 'REFERENCE SYSTEM POWER'

Command 224 'REFERENCE SYSTEM POWER' as well as command 249


'QUERY REFERENCE RUNNING' are tested using different device types. The test sequence
'REFERENCE SYSTEM POWER' is shown in Figure 11.

Test
REFERENCE SYSTEM
POWER

Error 7211
SEND TWICE "QUERY REFERENCE
BROADCAST Reset DUT any reply ? Yes RUNNING answered
RESET when no measurement
started"
wait No
(300 ms + Response time)

SEND SEND TWICE TO DEVICE TYPE


Terminate all special
SPECIAL COMMAND 3 BROADCAST Test configuration command
processes of DUT
TERMINATE REFERENCE SYSTEM POWER

SEND TO DEVICE TYPE SEND TO DEVICE TYPE


Feature supported
3 BROADCAST 3 BROADCAST Test query command
by DUT?
QUERY FEATURES QUERY REFERENCE RUNNING

Error 7212
bit 2, 3 or 4 "REFERENCE
No any reply ? No
of answer set? SYSTEM POWER
not started"

Yes Yes

SEND TO DEVICE TYPE


3 BROADCAST Test command SEND
Terminate all special
QUERY REFERENCE RUNNING SPECIAL COMMAND
processes of DUT
TERMINATE

Report:
"REFERENCE
SYSTEM POWER not
supported by DUT"

Test
done

IEC 649/09

Figure 11 – 'REFERENCE SYSTEM POWER'


BS EN 62386-204:2009
62386-204  IEC:2009 – 25 –

12.7.2.2 Test sequence 'REFERENCE SYSTEM POWER: 100 ms-timeout'

In this sequence the reference measurement is tried to be started with the configuration
command 224 'REFERENCE SYSTEM POWER' sent twice with a timeout of 150 ms. It is also
checked if command 256 'TERMINATE' stops the reference measurement. The test sequence
'REFERENCE SYSTEM POWER: 100 ms-timeout' is shown in Figure 12.

Test
REFERENCE SYSTEM
POWER: 100ms timeout

SEND TWICE SEND


BROADCAST Reset DUT BROADCAST Send command second time
RESET REFERENCE SYSTEM POWER

wait
wait 150 ms Wait for timeout
(300 ms + Response time)

SEND SEND TO DEVICE TYPE


Terminate all special
SPECIAL COMMAND 3 BROADCAST Measurement running?
processes of DUT
TERMINATE QUERY REFERENCE RUNNING

SEND TO DEVICE TYPE Error 7221


Feature supported
3 BROADCAST any reply ? Yes "Command executed
by DUT?
QUERY FEATURES with timeout"

No
bit 2, 3 or 4
of answer set?

SEND TWICE TO DEVICE TYPE


Yes 3 BROADCAST Start measurement
REFERENCE SYSTEM POWER

SEND TO DEVICE TYPE


3 BROADCAST Send command first time
SEND
REFERENCE SYSTEM POWER Terminate measurement
SPECIAL COMMAND
process
TERMINATE

wait 150 ms Wait for timeout


No
SEND TO DEVICE TYPE
3 BROADCAST measurement running?
QUERY REFERENCE RUNNING

Error 7222
"TERMINATE does
any reply ? Yes
not stop reference
measurement"

Report: No
"REFERENCE
SYSTEM POWER
not supported by DUT"

Test
done

IEC 650/09

Figure 12 – 'REFERENCE SYSTEM POWER: 100 ms-timeout'


BS EN 62386-204:2009
– 26 – 62386-204  IEC:2009

12.7.2.3 Test sequence 'REFERENCE SYSTEM POWER: Command in-between'

In this sequence the reference measurement is tried to be started with commands in-between
the two commands 224 'REFERENCE SYSTEM POWER'. The two commands 224 and the
command in-between are to be sent within 100 ms. The test sequence 'REFERENCE
SYSTEM POWER: Command in-between' is shown in Figure 13.
Test
REFERENCE SYSTEM POWER:
Command in-between

SEND TO DEVICE TYPE


SEND TWICE Send command
3 BROADCAST
BROADCAST Reset DUT first time
REFERENCE SYSTEM POWER
RESET

SEND
wait Send command
<address 1>
(300 ms + Response time) in-between
OFF

SEND TWICE SEND


Send command
BROADCAST BROADCAST
second time
ADD TO GROUP 1 REFERENCE SYSTEM POWER

SEND wait
Add Converter to
SPECIAL COMMAND 150 ms
GROUP 1
DTR (3)

SEND TO DEVICE TYPE


SEND TWICE Reference measurement
Program 3 BROADCAST
BROADCAST started?
SHORT ADDRESS 1 QUERY REFERENCE RUNNING
STORE DTR AS SHORT ADDR

Error 7231,i
SEND
Terminate all special answer "Command 'REFERENCE
SPECIAL COMMAND No
processes of DUT = <answer> ? SYSTEM POWER'
TERMINATE
<error text>"

SEND TO DEVICE TYPE Yes


Feature supported
3 BROADCAST
by DUT?
QUERY FEATURES

SEND
Command in-between
BROADCAST
executed?
bit 2, 3 or 4 QUERY ACTUAL LEVEL
No
of answer set ?

Error 7232,i
answer
Yes No "Command in-between
= <level> ?
executed"
i := 0; iMAX := 4
Yes

SEND
Terminate reference
SPECIAL COMMAND
measurement
TERMINATE

SEND
BROADCAST
RECALL MAX LEVEL

wait
(Switch-On Time + Response time)

i := i + 1

No i > iMAX ?

Report: Yes
"REFERENCE
SYSTEM POWER not
supported by DUT "
SEND TWICE
BROADCAST Remove DUT from group
REMOVE FROM GROUP 1

SEND
SPECIAL COMMAND
DTR (255)

SEND TWICE
BROADCAST Delete short address
STORE DTR AS SHORT ADDR

Test
done

IEC 651/09
BS EN 62386-204:2009
62386-204  IEC:2009 – 27 –

i <address 1> <answer> <level> <error text>

0 Short Address 1 'No' 254 executed


1 GROUP 1 'No' 254 executed
2 BROADCAST 'No' 254 executed
3 Short Address 2 'Yes' ≠ 0 not executed
4 GROUP 2 'Yes' ≠ 0 not executed

Figure 13 – 'REFERENCE SYSTEM POWER: Command in-between'

12.7.2.4 Test sequence 'REFERENCE SYSTEM POWER: 15 minutes timer'

Not later than 15 min after receiving command 224 'REFERENCE SYSTEM POWER' the
measurement has to be finished and the converter has to return to normal operation. The test
sequence 'REFERENCE SYSTEM POWER: 15 minutes timer' is shown in Figure 14.

Test
REFERENCE SYSTEM POWER:
15 minutes timer

SEND TWICE SEND TWICE TO DEVICE TYPE


BROADCAST Reset DUT 3 BROADCAST Start measurement
RESET REFERENCE SYSTEM POWER

wait
(300 ms + Response time)
SEND TO DEVICE TYPE
3 BROADCAST Measurement running?
SEND QUERY REFERENCE RUNNING
Terminate all special
SPECIAL COMMAND
processes of DUT
TERMINATE

answer
No
SEND TO DEVICE TYPE = YES ?
Feature supported
3 BROADCAST
by DUT?
QUERY FEATURES
Yes

bit 2, 3 or 4
Yes time := 0 No time > 17 min.
of answer set?

No Yes

Report: Error 7241:


Report:
"REFERENCE "Measurement not
"Measurement
SYSTEM POWER finished after
finished after <time>"
not supported by DUT" 15 min + 10%"

SEND
Terminate all special
SPECIAL COMMAND
processes of DUT
TERMINATE

Test
done

IEC 652/09

Figure 14 – 'REFERENCE SYSTEM POWER: 15 minutes timer'


BS EN 62386-204:2009
– 28 – 62386-204  IEC:2009

12.7.2.5 Test sequence 'REFERENCE SYSTEM POWER: failed'

Bit 7 in the answer of command 241 'QUERY FAILURE STATUS' and command 250 'QUERY
REFERENCE MEASUREMENT FAILED' is checked.

The reference measurement is caused to fail by e.g. under voltage. The way how to cause the
measurement to fail shall be stated by the manufacturer of the device under test (DUT). The
test sequence 'REFERENCE SYSTEM POWER: failed' is shown in Figure 15.

Test
REFERENCE SYSTEM
POWER: failed

SEND TWICE
BROADCAST Reset DUT
RESET

wait
(300 ms + Response time)

SEND
Terminate all special
SPECIAL COMMAND
processes of DUT
TERMINATE

SEND TO DEVICE TYPE


Feature supported
3 BROADCAST
by DUT?
QUERY FEATURES

Report:
bit 2, 3 or 4 "REFERENCE
No
of answer set ? SYSTEM POWER not
supported by DUT "

Yes
Test
done

SEND TWICE TO DEVICE TYPE


Set DUT
3 BROADCAST Start measurement
to normal operation
REFERENCE SYSTEM POWER

SEND TWICE TO DEVICE TYPE


3 BROADCAST Start measurement
Disturb
Cause reference REFERENCE SYSTEM POWER
measurement according
measurement to fail
to manufacturer

Yes
SEND TO DEVICE TYPE SEND TO DEVICE TYPE
3 BROADCAST 3 BROADCAST
QUERY REFERENCE RUNNING Yes QUERY REFERENCE RUNNING

answer answer
Measurement running? Measurement running?
= YES ? = YES ?

No No

SEND TO DEVICE TYPE SEND TO DEVICE TYPE


3 BROADCAST Failure status correct? 3 BROADCAST Failure status correct?
QUERY FAILURE STATUS QUERY FAILURE STATUS

Error 7251 Error 7253


"QUERY FAILURE "QUERY FAILURE
answer answer
No STATUS answered No STATUS answered
= 1XXXXXXXb ? = 0XXXXXXXb ?
wrong with reference wrong with successful
measurement failed" measurement"
Yes Yes

SEND TO DEVICE TYPE SEND TO DEVICE TYPE


3 BROADCAST Test Query 3 BROADCAST Test Query
QUERY REFERENCE MEASUREMENT FAILED QUERY REFERENCE MEASUREMENT FAILED

Error 7254
Error 7252 "QUERY REFERENCE
"QUERY REFERENCE MEASUREMENT
any reply ? No any reply ? Yes
MEASUREMENT FAILED answered after
FAILED not answered" successful
measurement"
No
Yes

Test
done

IEC 653/09

Figure 15 – 'REFERENCE SYSTEM POWER: failed'


BS EN 62386-204:2009
62386-204  IEC:2009 – 29 –

12.7.2.6 Test sequence 'ENABLE / DISABLE CURRENT PROTECTOR'

Command 225 'ENABLE CURRENT PROTECTOR', command 226 'DISABLE CURRENT


PROTECTOR and command 251 'QUERY CURRENT PROTECTOR ENABLED' are tested.
The storage of the configuration in the persistent memory is also tested by this sequence.
After the reference measurement the current protector is caused to become active with
additional load. It has to be ensured that the total load is not exceeding the maximum output
load of the control gear. The test sequence 'ENABLE / DISABLE CURRENT PROTECTOR' is
shown in Figure 16.
Test
REFERENCE SYSTEM
POWER: failed

SEND TWICE SEND TO DEVICE TYPE


BROADCAST Reset DUT 3 BROADCAST Test query command
RESET QUERY CURRENT PROTECTOR ENABLED

Error 7262
wait "QUERY CURRENT
(300 ms + Response time) any reply ? Yes PROTECTOR
ENABLED answered
wrong when disabled"
SEND
Terminate all special No
SPECIAL COMMAND
processes of DUT
TERMINATE

Connect Try to activate current


SEND TO DEVICE TYPE additional load protector
Feature supported
3 BROADCAST
by DUT?
QUERY FEATURES

wait 5 seconds Wait for failure detection


Report:
bit 4
No "Current Protector not
of answer set ? SEND
supported by DUT "
BROADCAST Current protector active?
QUERY LAMP POWER ON

Yes Error 7263


Test
done "CURRENT
any reply ? No
PROTECTOR not
disabled"
SEND TWICE TO DEVICE TYPE
3 BROADCAST Start measurement Yes
REFERENCE SYSTEM POWER

time := 0 SEND TWICE TO DEVICE TYPE


3 BROADCAST Test enable command
ENABLE CURRENT PROTECTOR

SEND TO DEVICE TYPE Interrupt mains supply


3 BROADCAST Measurement running? Test persistent memory
for 5 seconds
QUERY REFERENCE RUNNING No

Wait for restart and failure


wait 5 seconds
detection
answer
Yes time > 17 min ?
= YES ?
SEND TO DEVICE TYPE
3 BROADCAST Test query command
Yes QUERY CURRENT PROTECTOR ENABLED

Error 7261 Error 7264


Reference "QUERY CURRENT
No measurement timeout any reply ? No PROTECTOR
ENABLED answered
wrong when enabled"

No

Test
done
SEND TWICE TO DEVICE TYPE wait 5 seconds Wait for failure detection
3 BROADCAST Test disable command
DISABLE CURRENT PROTECTOR

SEND
BROADCAST Current protector active?
Interrupt mains supply QUERY LAMP POWER ON
Test persistent memory
for 5 seconds

Error 7265
Wait for restart and failure "CURRENT
wait 5 seconds any reply ? Yes
detection PROTECTOR not
enabled"

No

Disconnect
additional load

Test
done

IEC 654/09

Figure 16 – 'ENABLE / DISABLE CURRENT PROTECTOR'


BS EN 62386-204:2009
– 30 – 62386-204  IEC:2009

12.7.3 Test sequences 'ENABLE DEVICE TYPE'

12.7.3.1 Test sequence 'ENABLE DEVICE TYPE: Application extended commands'

An application extended command shall be executed if command 272 'ENABLE DEVICE


TYPE 3' precedes. If there is a command in-between command 272 and the application
extended command, the application extended command has to be ignored except if the
command in-between is addressed to another control gear. The test sequence uses command
6 'RECALL MIN LEVEL' as command in-between and command 240 'QUERY FEATURES' as
application extended command. The test sequence 'ENABLE DEVICE TYPE: Application
extended commands' is shown in Figure 17.
Test
E N A B L E D E V IC E T Y P E :
A p p lic a tio n e x te n d e d c o m m a n d s
SEND
S P E C IA L C O M M A N D E n a b le d e v ic e ty p e
E N A B L E D E V IC E T Y P E 3
S E N D T W IC E
BROADCAST R eset D U T
RESET SEND
< a d d re s s > S e n d o th e r c o m m a n d
R E C A L L M IN L E V E L
w a it
(3 0 0 m s + R e s p o n s e tim e )
SEND
S e n d a p p lic a tio n
BROADCAST
e x te n d e d c o m m a n d
S E N D T W IC E Q UERY FEATURES
A d d C o n v e rte r to
BROADCAST
GROUP 1
A DD TO G RO UP 1
E rro r 7 3 1 1 ,i
answer " C o m m a n d 'Q U E R Y
No
SEND = < a n s w e r> ? FEA TURES'
S P E C IA L C O M M A N D < e rro r te x t 1 > "
D T R (3 )
Y es

S E N D T W IC E
P ro g ra m
BROADCAST
SHORT ADDRESS 1 w a it
STORE DTR AS SHO RT A DDR
R e s p o n s e tim e

SEND
T e rm in a te a ll s p e c ia l SEND
S P E C IA L C O M M A N D O th e r c o m m a n d
p ro c e s s e s o f D U T BROADCAST
T E R M IN A T E e x e c u te d ?
Q U ER Y AC TU AL LEVEL

SEND
BROADCAST
E rro r 7 3 1 2 ,i
QUERY PHM answer
No " O th e r c o m m a n d
= < le v e l> ?
< e rro r te x t 2 > "

i := 0 ;
Y es
i M A X := 4

SEND
BROADCAST
R EC ALL M AX LEV EL

w a it
R e s p o n s e tim e

i := i + 1 N e x t te s t

No i > iM A X ? L a s t te s t d o n e ?

Y es

S E N D T W IC E
BROADCAST R e m o v e D U T fro m g ro u p
REM O VE FRO M G RO UP 1

SEND
S P E C IA L C O M M A N D
D T R (2 5 5 )

S E N D T W IC E
BROADCAST D e le te s h o rt a d d re s s
STO RE DTR AS SHO RT ADDR

Test
done

IEC 655/09

i <address> <answer> <level> <error text 1> <error text 2>

0 BROADCAST 'No' PHM executed not executed


1 Short Address 1 'No' PHM executed not executed
2 Short Address 2 XXXXXXXXb 254 not executed executed
3 GROUP 1 'No' PHM executed not executed
4 GROUP 2 XXXXXXXXb 254 not executed executed

Figure 17 – 'ENABLE DEVICE TYPE: Application extended commands'


BS EN 62386-204:2009
62386-204  IEC:2009 – 31 –

12.7.3.2 Test sequence 'ENABLE DEVICE TYPE: Application extended configuration


commands 1'

An application extended configuration command shall be executed if command 272 'ENABLE


DEVICE TYPE 3' precedes and the application extended configuration command is received
twice within 100 ms. If there is a command in-between command 272 and the application
extended configuration command, the application extended configuration command has to be
ignored except if the command in-between is addressed to another control gear and a short
address is used. The test sequence uses command 6 'RECALL MIN LEVEL' as command in-
between and command 224 'REFERENCE SYSTEM POWER' as application extended
configuration command. The test sequence 'ENABLE DEVICE TYPE: Application extended
configuration commands 1' is shown in Figure 18.
Test
ENABLE DEVICE TYPE:
Application extended
configuration commands 1
SEND
SPECIAL CO MMAND Enable device type
ENABLE DEVICE TYPE 3
SEND TW ICE
BRO ADCAST Reset DUT
RESET SEND
<address> Send other comm and
OFF
wait
(300 m s + Response tim e)
SEND TW ICE
Send application extended
BRO ADCAST
configuration command
SEND TW ICE REFERENCE SYSTEM POW ER
Add Converter to
BRO ADCAST
GRO UP 1
ADD TO GRO UP 1
SEND TO DEVICE TYPE
3 BRO ADCAST Com mand executed?
SEND QUERY REFERENCE RUNNING
SPECIAL COMM AND
DTR (3)
Error 7321,i
answer "A pplication extended
No
SEND TW ICE = <answer> ? configuration com m and
Program <error text 1>"
BRO ADCA ST
SHORT ADDRESS 1
STORE DTR AS S HORT ADDR
Yes

SEND
Terminate all special
SPECIAL COMM AND
processes of DUT wait
TERMINATE
Response tim e

SEND TO DEVICE TYPE


3 BRO ADCA ST SEND
O ther command
QUE RY FEATURE S BROADCAST
executed?
QUERY ACTUAL LEVEL

bit 2, 3 or 4 Error 7322,i


No answer
of answer set ? No "O ther com m and
= <level> ?
<error text 2>"

Yes
Yes
Feature supported
i := 0; iM AX := 4
by DUT?
SEND
Terminate all special
SPECIAL CO MMAND
processes of DUT
TERM INATE

SEND
BROADCAST
RECALL M AX LEVE L

wait
(Switch-On Tim e + Response tim e)

i := i + 1 Next test

No i > iM AX ? Last test done?

Yes

SE ND TW ICE
BRO ADCAST Rem ove DUT from group
REM OVE FROM GROUP 1

SEND
SPECIAL CO MMAND
DTR (255)

SEND TW ICE
BRO ADCAST Delete short address
STORE DTR A S SHORT ADDR
Report:
"REFE RE NCE
SYSTEM PO W ER not
supported by DUT "

Test
done

IEC 656/09
BS EN 62386-204:2009
– 32 – 62386-204  IEC:2009

i <address> <answer> <level> <error text 1> <error text 2>

0 BROADCAST 'No' 0 executed not executed


1 Short Address 1 'No' 0 executed not executed
2 Short Address 2 'Yes' ≠ 0 not executed executed
3 GROUP 1 'No' 0 executed not executed
4 GROUP 2 'Yes' ≠ 0 not executed executed

Figure 18 – 'ENABLE DEVICE TYPE: Application extended configuration commands 1'

12.7.3.3 Test sequence 'ENABLE DEVICE TYPE: Application extended configuration


commands 2'

An application extended configuration command shall be executed if command 272 'ENABLE


DEVICE TYPE 3' precedes and the application extended configuration command is received
twice within 100 ms. The application extended configuration command has to be ignored if a
second command 272' ENABLE DEVICE TYPE' is received in-between the two application
extended configuration commands. The two application extended configuration commands are
to be sent within 100 ms. The test sequence 'ENABLE DEVICE TYPE: Application extended
configuration commands 2' is shown in Figure 19.

Test
ENABLE DEVICE TYPE:
Application extended
configuration commands 2
SEND
SPECIAL COMMAND Enable device type
ENABLE DEVICETYPE 3
SEND TWICE
BROADCAST Reset DUT
RESET SEND Send application extended
BROADCAST configuration command
REFERENCE SYSTEM POWER first time
wait
(300 ms + Response time)
SEND
SPECIAL COMMAND 'Enable' device type again
SEND ENABLE DEVICETYPE (i)
Terminate all special
SPECIAL COMMAND
processes of DUT
TERMINATE
SEND Send application extended
BROADCAST configuration command
i := 0; REFERENCE SYSTEM POWER second time
iMAX := 254

SEND TO DEVICE TYPE


3 BROADCAST Command executed?
QUERY REFERENCE RUNNING

Error 7331,i
"Application extended
any reply ? Yes
configuration command
executed"

No

SEND
Terminate all special
SPECIAL COMMAND
processes of DUT
TERMINATE

i := i + 1 Next device type

No i > iMAX ? Last test done?

Yes

Test
done
IEC 657/09

Figure 19 – 'ENABLE DEVICE TYPE: Application extended configuration commands 2'


BS EN 62386-204:2009
62386-204  IEC:2009 – 33 –

12.7.6 Test sequences for standard application extended commands

12.7.6.1 Test sequences 'QUERY EXTENDED VERSION NUMBER'

The command 255 'QUERY EXTENDED VERSION NUMBER' is tested for all possible values
of X in command 272 'ENABLE DEVICE TYPE X'. The test sequence 'QUERY EXTENDED
VERSION NUMBER' is shown in Figure 20.

NOTE A control gear belonging to more than one device type will also answer to the query for X not equal to 3.

Test
QUERY EXTENDED
V E R S IO N N U M B E R

S E N D T W IC E
BROADCAST Reset D U T
RESET

w a it
(3 0 0 m s + R e s p o n s e tim e )

i := 0 In itia lis e c o u n te r fo r
i M A X := 2 5 4 d e v ic e ty p e

S E N D T O D E V IC E T Y P E
T e s t c o m m a n d u s in g
i BROADCAST
b ro a d c a s t a d d re s s
Q U E R Y E X T E N D E D V E R S IO N N U M B E R

M essage:
"E X T E N D E D V E R S IO N
a n y re p ly ? Yes
N U M B E R is < a n s w e r> fo r
d e v ic e ty p e < i> "

No

E rro r 7 6 1 1
"N o a n s w e r to
i = 3 ? Yes
Q UE RY EXTENDED
V E R S IO N N U M B E R "

No

i := i + 1 N e x t d e v ic e ty p e

No i > iM A X ? L a s t d e v ic e ty p e

Yes

Test
done
IEC 658/09

Figure 20 – 'QUERY EXTENDED VERSION NUMBER'


BS EN 62386-204:2009
– 34 – 62386-204  IEC:2009

12.7.6.2 Test sequence 'RESERVED APPLICATION EXTENDED COMMANDS'

The following test sequence checks the reaction to reserved application extended commands.
The control gear shall not react in any way. The test sequence 'RESERVED APPLICATION
EXTENDED COMMANDS' is shown in Figure 21.

Test
UNUSEDAPPLICATION
EXTENDED COMMANDS

SEND TWICE <command> := (227 + k) Calculate Command Byte


BROADCAST Set the DUT in reset state
RESET
Send twice the application extended
SEND TWICE TO DEVICE TYPE
command <command> preceded by
3 BROADCAST
wait "enable device type 3" ;
<command>
(300 ms + Response time) DUT must not react to this command!

Error 7621,k
SEND "Answer after receiving
BROADCAST any reply ? Yes
APPLICATION EXTENDED
QUERY DEVICE TYPE COMMAND <command>"

No

k := 0
answer = 3 ? Yes
kmax := 27
SEND
Initialise counter for BROADCAST DUT still in reset state?
No commands QUERY RESET STATE

Error 7622,k
No answer = 255 ? "DUT not in reset state after
answer
No receiving APPLICATION
= 'Yes' ?
EXTENDED COMMAND
<command>"
Yes
Yes
SEND TO DEVICE TYPE SEND TWICE
3 BROADCAST BROADCAST
QUERY EXTENDED VERSIONNUMBER RESET
Yes

wait
any reply ? (300 ms + Response time
+ Preheat time)

No
Increase command
k := (k + 1)
counter

Continue with command 252?

k = 13 ? Yes k := 25

No

No k > kmax ? Last command ?

Message: Yes
"DEVICE TYPE is not 3! Test of
APPLICATION EXTENDED
COMMANDS not possible with this
test sequence!"
Test
done

IEC 659/09

Figure 21 – 'RESERVED APPLICATION EXTENDED COMMANDS'


BS EN 62386-204:2009
62386-204  IEC:2009 – 35 –

Annex A
(informative)

Examples of algorithms

The requirements of Annex A of IEC 62386-102:2009 apply except as follows:

A.3 Address allocation by physical selection

Addition:

Address allocation by physical selection should only be used if all control gears in the system
support this feature.

Additional clause:

A. 5 Reference system power measurement


a) The control device sends command 224 'REFERENCE SYSTEM POWER’ to start the
measurement.
b) The control gear now measures and stores system power levels using its internal
algorithms. (The measurement procedure does not take more than 15 min.)
c) Meanwhile the control device periodically sends command 249 ‘QUERY REFERENCE
RUNNING’.
d) When all the control gears shall have finished their measurements and are back in normal
operation, the control device no longer receives any replies.
e) The control device can then use command 250 'QUERY REFERENCE MEASUREMENT
FAILED' to check whether the measurement was successful.
BS EN 62386-204:2009
– 36 – 62386-204  IEC:2009

Bibliography

[1] IEC 60598-1, Luminaires – Part 1: General requirements and tests

[2] IEC 60669-2-1, Switches for household and similar fixed electrical installations –
Part 2-1, Particular requirements – Electronic switches

[3] IEC 60921, Ballasts for tubular fluorescent lamps – Performance requirements

[4] IEC 60923, Auxiliaries for lamps – Ballasts for discharge lamps (excluding tubular
fluorescent lamps – Performance requirements

[5] IEC 60925, DC-supplied electronic ballasts for tubular fluorescent lamps – Performance
requirements

[6] IEC 60929, AC-supplied electronic ballasts for tubular fluorescent lamps – Performance
requirements

[7] IEC 61347-1, Lamp controlgear – Part 1: General and safety requirements

[8] IEC 61347-2-3, Lamp controlgear – Part 2-3: Particular requirements for a.c. supplied
electronic ballasts for fluorescent lamps

[9] IEC 61547, Equipment for general lighting purposes – EMC immunity requirements

[10] IEC 62034: Automatic test systems for battery powered emergency escape lighting

[11] CISPR 15, Limits and methods of measurement of radio disturbance characteristics of
electrical lighting and similar equipment

[12] GS1, General Specification: Global Trade Item Number, Version 7.0, published by the
GS1, Avenue Louise 326; BE-1050 Brussels, Belgium; and GS1, 1009 Lenox Drive,
Suite 202, Lawrenceville, New Jersey, 08648 USA.

___________
This page deliberately left blank
NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAW

British Standards Institution (BSI)


BSI is the national body responsible for preparing British Standards and other
standards-related publications, information and services.
BSI is incorporated by Royal Charter. British Standards and other standardization
products are published by BSI Standards Limited.

About us Revisions
We bring together business, industry, government, consumers, innovators Our British Standards and other publications are updated by amendment or revision.
and others to shape their combined experience and expertise into standards We continually improve the quality of our products and services to benefit your
-based solutions. business. If you find an inaccuracy or ambiguity within a British Standard or other
The knowledge embodied in our standards has been carefully assembled in BSI publication please inform the Knowledge Centre.
a dependable format and refined through our open consultation process.
Organizations of all sizes and across all sectors choose standards to help Copyright
them achieve their goals. All the data, software and documentation set out in all British Standards and
other BSI publications are the property of and copyrighted by BSI, or some person
Information on standards or entity that owns copyright in the information used (such as the international
We can provide you with the knowledge that your organization needs standardization bodies) and has formally licensed such information to BSI for
to succeed. Find out more about British Standards by visiting our website at commercial publication and use. Except as permitted under the Copyright, Designs
bsigroup.com/standards or contacting our Customer Services team or and Patents Act 1988 no extract may be reproduced, stored in a retrieval system
Knowledge Centre. or transmitted in any form or by any means – electronic, photocopying, recording
or otherwise – without prior written permission from BSI. Details and advice can
Buying standards be obtained from the Copyright & Licensing Department.
You can buy and download PDF versions of BSI publications, including British
and adopted European and international standards, through our website at Useful Contacts:
bsigroup.com/shop, where hard copies can also be purchased. Customer Services
If you need international and foreign standards from other Standards Development Tel: +44 845 086 9001
Organizations, hard copies can be ordered from our Customer Services team. Email (orders): orders@bsigroup.com
Email (enquiries): cservices@bsigroup.com
Subscriptions
Subscriptions
Our range of subscription services are designed to make using standards
Tel: +44 845 086 9001
easier for you. For further information on our subscription products go to
Email: subscriptions@bsigroup.com
bsigroup.com/subscriptions.
With British Standards Online (BSOL) you’ll have instant access to over 55,000 Knowledge Centre
British and adopted European and international standards from your desktop. Tel: +44 20 8996 7004
It’s available 24/7 and is refreshed daily so you’ll always be up to date. Email: knowledgecentre@bsigroup.com
You can keep in touch with standards developments and receive substantial
Copyright & Licensing
discounts on the purchase price of standards, both in single copy and subscription
format, by becoming a BSI Subscribing Member. Tel: +44 20 8996 7070
Email: copyright@bsigroup.com
PLUS is an updating service exclusive to BSI Subscribing Members. You will
automatically receive the latest hard copy of your standards when they’re
revised or replaced.
To find out more about becoming a BSI Subscribing Member and the benefits
of membership, please visit bsigroup.com/shop.
With a Multi-User Network Licence (MUNL) you are able to host standards
publications on your intranet. Licences can cover as few or as many users as you
wish. With updates supplied as soon as they’re available, you can be sure your
documentation is current. For further information, email bsmusales@bsigroup.com.

BSI Group Headquarters


389 Chiswick High Road London W4 4AL UK

You might also like