5% for ventilation of everyday vehicle pollution and smoke with at least 50%
being provided between opposite faces of the building; the openings provided
must be sufficient to create a through draught.
ULATION
Computed by:
Checked by:
Approved by:
Select necessary duct size using Sizing tool slider, keep velocity through ducts to less than
7m/s for vibration reasons.
Locate supply and exhaust ducts on opposite sides of car park, place vents approximately 6
metres apart. Draw lines of direct air paths between supply and exhaust vents.
Car park exhaust must be vented at least 3 metres above ground level and 6 meters away
from walkway/adjacent properties.
Supply air intake and exhaust point must be a minimum of 6 meters apart for discharges of
over 1000 L/s.
y through ducts to less than