Integration Guide

BACnet™ and Modbus™ RTU Communication


Interfaces for Trane® Rotary Chiller
Model RTHD

SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-
conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment 
by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and
on the tags, stickers, and labels that are attached to the equipment.

August 2015 BAS-SVP023C-EN


Overview
The integration guide provides the following information for Model RTHD Chiller with the
Tracer® UC800 controller:
• BACnet Protocol
• Tracer UC800 Controller Rotary Switches
• BACnet Data Points and Configuration Property Definitions
• Modbus RTU Data Points and Configuration Property Definitions
• Diagnostics: Inputs with Alarming Capabilities

Copyright
© 2015 Trane. All rights reserved.
This document and the information in it are the property of Trane and may not be used o

Trademarks
Trane and its logo are trademarks of Trane in the United States and other countries. All
trademarks referenced in this document are the trademarks of their respective owners.

Revision Summary
BAS-SVP023C-EN
• Removed BI 14 and MI 11, Compressor Running Diagnostic. Not supported.
• Added BI 520, Comm Loss: Master Oil Line SV

© 2015 Trane. All rights reserved. BAS-SVP023C-EN


Table of Contents
BACnet Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Tracer UC800 Controller Rotary Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Communication Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Rotary Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
LED Description and Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
BACnet/Modbus Equivalent Data Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
BACnet Data Points and Configuration Property Definitions . . . . . . . . . . . . . . . 8
BACnet Protocol Implementation Conformance Statement (PICS) . . . . . . . 8
Standardized Device Profile (Annex L) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Interoperability Building Blocks (Annex K) . . . . . . . . . . . . . . . . . . . . . . . . . 8
Segmentation Capability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Object Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Baud Rate, Device ID, and Supported Character Sets . . . . . . . . . . . . . . . . . 11
Baud Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Device ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Measurements/Units/Conversion Factors . . . . . . . . . . . . . . . . . . . . . . . . . 11
BACnet Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Data Link Layer Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Device Address Binding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Networking Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Character Sets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Notification Class Objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Object Data Points and Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Device Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Notification Class Objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Read/Write Values (Sorted by Object Type and Instance) . . . . . . . . . . . . 13
Read-Only Values (Sorted by Object Type and Instance) . . . . . . . . . . . . 13

Diagnostic Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Modbus RTU Data Points and Configuration Property Definitions . . . . . . . . . 20
Holding Registers—Read/Write (Sorted by Register) . . . . . . . . . . . . . . . . . . 20
Input Registers—Read Only (Sorted by Register) . . . . . . . . . . . . . . . . . . . . 20
Determining Input Register Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3DC (Hex) and 3DC (Dec) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

BAS-SVP023C-EN 3
BACnet Protocol
The Building Automation and Control Network (BACnet and ANSI/ASHRAE Standard 135-2008)
protocol is a standard that allows building automation systems or components from different
manufacturers to share information and control functions. BACnet provides building owners the
capability to connect various types of building control systems or subsystems together for a variety
of reasons. In addition, multiple vendors can use this protocol to share information for monitoring
and supervisory control between systems and devices in a multi-vendor interconnected system.
The BACnet protocol identifies standard objects (data points) called BACnet objects. Each object
has a defined list of properties that provide information about that object. BACnet also defines a
number of standard application services that are used to access data and manipulate these objects
and provides a client/server communication between devices. For more details, refer to the BTL
web site a www.bacnetinternational.org.

Tracer UC800 Controller Rotary Switches


This section provides information about the Tracer™ UC800 controller rotary switches and LED
displays.

Communication Interfaces
The UC800 supports the communication interfaces listed below. There is one set of terminations
(link) for BACnet and Modbus. LonTalk and Comm4 communication interfaces connect to the IPC3
bus which is the MBUS connection.
• BACnet MS/TP
• Modbus Slave
• LonTalk® using LCI-C (from the IPC3 bus)
• Comm4 using TCI (from the IPC3 bus)

Rotary Switches
There are three rotary switches on the front of the UC800 as shown in Figure 1, p. 5. Use these
switches to define a three-digit address when the UC800 is installed in a BACnet or Modbus RTU
system (for example, 107, 127, and so on).
Note: Valid MAC addresses are 001 to 127 for BACnet and 001 to 247 for Modbus RTU.

4 BAS-SVP023C-EN
Tracer UC800 Controller Rotary Switches

LED Description and Operation


There are 10 LEDs on the front of the UC800. Figure 1 shows the locations of each LED and a
description of its behavior in specific instances.

Figure 1. LED locations


Marquee LED
• Shows solid green when the UC800 is
powered and operating normally
IMC +24
VDC
IMC
Marquee LED
LINK MBUS
• Shows solid red when the UC800 is
powered, but represents low power or a
1 malfunction
• Blinks red when an alarm exists.
LINK, MBUS, IMC
UC800
LINK MBUS IMC
LINK MBUS IMC • The TX LED blinks green at the data transfer
TX TX rate when the UC800 transfers data to other
RX
LINK RX devices on the link
SERVICE
ACT
SERVICE TOOL
LINK • The RX LED blinks yellow at the data
ADDRESS
SERVICE transfer rate when the UC800 receives data
901 901 901 ACT from other devices on the link
2 3

2 3

2 3
7 8

7 8

7 8

Ethernet Link
456 456 456

x100 x10 x1

• The LINK LED shows solid green if the


Ethernet link is connected and
communicating
• The ACT LED blinks yellow at the data
USB
transfer rate when data flow is active on the
link
SERVICE
• Shows solid green when pressed. For more
details, refer to the document, CVHE, CVHF,
and CVHG Water-cooled CenTraVac Chillers
with Tracer AdaptiView™ Control
Installation, Operation, and Maintenance
Guide (CVHE-SVX02).

BAS-SVP023C-EN 5
BACnet/Modbus Equivalent Data Points
The following table provides a quick reference to equivalent data point object names when using
either BACnet or Modbus RTU communications. This table is sorted alphabetically by data point
names.
Table 1. Equivalent Data Point Listing

Data Point BACnet Object Modbus Register


Active Base Loading Command BI7 30026
Active Base Loading Setpoint AI3 30005
Active Cool/Heat Setpoint Temperature AI1 30007
Active Current Limit Setpoint AI2 30004
Actual Running Capacity AI4 30006
AFD Output Power AI33 30047
Alarm Present BI12 30019
Approx Cond Water Flow AI36 30061
Approx Evap Water Flow AI34 30059
Approximate Chiller Capacity- Evap N/A 30057
Approximate Chiller Capacity- Cond N/A 30058
BAS Communication Status MI3 30018
Chiller Design Capacity AI31 30051
Chiller Mode Command MI2 30017
Chiller Running BI4 30003
Chiller Running Status MI1 30016
Compressor Oil Pressure AI16 30035
Compressor Running Status BI8 30030
Compressor Running Time AI11 30063/30064
Compressor Starts AI10 30033/30034
Cond Differential Wtr Press AI37 30062
Condenser Entering Water Temperature AI14 30010
Condenser Leaving Water Temperature AI15 30011
Condenser Refrigerant Pressure AI7 30030
Condenser Saturated Rfgt Temp AI8 30032
Condenser Water Flow Status BI5 30015
Condenser Water Pump Command BI10 30014
Cooling Type MI35 30054
Discharge Temperature AI17 30036
Evap Differential Wtr Press AI35 30060
Evaporator Entering Water Temperature AI12 30008
Evaporator Leaving Water Temperature AI13 30009
Evaporator Refrigerant Pressure AI5 30029
Evaporator Saturated Rfgt Temp AI6 30031
Evaporator Water Flow Status BI11 30013
Evaporator Water Pump Command BI9 30012
EXV Position Percent AI38 30065
Frequency Command AI32 30046
Head Pressure Control Command AI18 30025
Head Relief Request Relay BI6 30024
Limit Mode Relay Status BI3 30023

6 BAS-SVP023C-EN
BACnet/Modbus Equivalent Data Points

Table 1. Equivalent Data Point Listing

Data Point BACnet Object Modbus Register


Local Atmospheric Pressure AI9 30028
Local Setpoint Control BI2 30022
Manufacturing Location MI7 30055
Model Information MI34 30053
Number of Circuits AI28 30048
Number of Compressors for Circuit1 AI29 30049
Number of Compressors for Circuit2 AI30 30050
Refrigerant Type MI4 30052
Run Enable BI1 30021
Shutdown Alarm Present BI13 30020
Software Revision N/A 30002
Software Type N/A 30001
Starter Input Voltage AB AI19 30037
Starter Input Voltage BC AI20 30038
Starter Input Voltage CA AI21 30039
Starter Motor Current L1 AI22 30040
Starter Motor Current L1 % RLA AI25 30043
Starter Motor Current L2 AI23 30041
Starter Motor Current L2 % RLA AI26 30044
Starter Motor Current L3 AI24 30042
Starter Motor Current L3 % RLA AI27 30045

BAS-SVP023C-EN 7
BACnet Data Points and Configuration Property
Definitions
This section includes information about:
• “BACnet Protocol Implementation Conformance Statement (PICS)”
• “Object Types,” p. 9
• “BACnet Protocol,” p. 12
• “Object Data Points and Configurations,” p. 13

BACnet Protocol Implementation Conformance Statement (PICS)


Standardized Device Profile (Annex L)
BACnet Operator Workstation (B-OWS) 
BACnet Building Controller (B-BC) 
BACnet Advanced Application Controller (B-AAC) 
BACnet Application Specific Controller (B-ASC) 
BACnet Smart Sensor (B-SS) 
BACnet Smart Actuator (B-SA) 

Interoperability Building Blocks (Annex K)


Data Sharing Supported
ReadProperty-B (DS-RP-B) 
ReadPropertyMultiple-B (DS-RPM-B) 
WriteProperty-B (DS-WP-B) 
WritePropertyMultiple-B (DS-WPM-B) 
Alarm and Event Management Supported
Notification Internal-B (AE-N-I-B) 
Information-B (AE-INFO-B) 
Device Management Description Supported
Dynamic Device Binding-A (DM-DDB-A) 
Dynamic Device Binding-B (DM-DDB-B) 
Dynamic Object Binding-B (DM-DOB-B) 
Device Communication Control-B (DM-DCC-B) 
TimeSynchronization-B (DM-TS-B) 
UTCTimeSynchronization-B (DM-UTC-B) 

Segmentation Capability
Segmentation Supported
Segmented Requests/ Window Size: 1 
Segmented Responses/ Window Size: 1 

8 BAS-SVP023C-EN
BACnet Data Points and Configuration Property Definitions

Object Types
Note: For objects that contain the Present_Value and Reliability properties, these properties are
only writable when the Out_Of_Service property is True.

Table 2. Descriptions and Configurations


Ability Ability
Optional Properties to to
Object Type Writable Properties Required Properties Supported Create Delete
Analog Input • Object_Name • Object_Identifier • Reliability None None
• Out_Of_Service • Object_Name
• Present_Value • Object_Type
• Reliability • Present_Value
• Status_Flags
• Event_State
• Out_Of_Service
• Units
Analog Value • Object_Name • Object_Identifier • Priority_Array None None
• Out_Of_Service • Object_Name • Relinquish_Default
• Present_Value • Object_Type • Reliability
• Reliability • Present_Value
• Relinquish_Default • Status_Flags
• Event_State
• Out_Of_Service
• Units
Binary Input • Object_Name • Object_Identifier • Inactive_Text None None
• Out_Of_Service • Object_Name • Active_Text
• Inactive_Text • Object_Type • Time_Delay
• Active_Text • Present_Value • Notification_Class
• Present_Value • Status_Flags • Alarm_Value
• Reliability • Event_State • Event_Enable
• Out_Of_Service • Acked_Transitions
• Polarity • Notify_Type
• Event_Time_Stamps
• Reliability
Binary Value • Object_Name • Object_Identifier • Inactive_Text None None
• Out_Of_Service • Object_Name • Active_Text
• Inactive_Text • Object_Type • Priority_Array
• Active_Text • Present_Value • Relinquish_Default
• Present_Value • Status_Flags • Reliability
• Reliability • Event_State
• Relinquish_Default • Out_Of_Service
Device • Object_Name • Object_Identifier • Max_Segments_Accepted None None
• UTC Offset • Object_Name • APDU_Segment_Timeout
• Object_Type • Max_Master
• System_Status • Max_Info_Frames
• Vendor_Name • Local_Time
• Vendor_Identifier • Local_Date
• Model_Name • UTC_Offset
• Firmware_Revision • Daylight_Savings_Status
• Application_Software_Version
• Protocol_Version
• Protocol_Revision
• Protocol_Services_Supported
• Protocol_Object_Types_Supported
• Object_List
• Max_APDU_Length_Accepted
• Segmentation_Supported
• APDU_Timeout
• Number_Of_APDU_Retries
• Device_Address_Binding
• Database_Revision
Multistate • Object_Name • Object_Identifier • State_Text None None
Input • State_Text • Object_Name • Reliability
• Out_Of_Service • Object_Type
• Present_Value • Present_Value
• Reliability • Status_Flags
• Event_State
• Out_Of_Service
• Number_Of_States

BAS-SVP023C-EN 9
BACnet Data Points and Configuration Property Definitions

Table 2. Descriptions and Configurations (continued)


Ability Ability
Optional Properties to to
Object Type Writable Properties Required Properties Supported Create Delete
Multistate • Object_Name • Object_Identifier • State_Text None None
Value • State_Text • Object_Name • Priority_Array
• Out_Of_Service • Object_Type • Reliability
• Present_Value • Present_Value • Relinquish_Default
• Reliability • Status_Flags
• Relinquish_Default • Event_State
• Out_Of_Service
• Number_Of_States
Notification • Object_Name • Object_Identifier • None None None
Class • Recipient_List • Object_Name
• Object_Type
• Notification_Class
• Priority
• Ack_Required
• Recipient_List

10 BAS-SVP023C-EN
BACnet Data Points and Configuration Property Definitions

Baud Rate, Device ID, and Supported Character Sets

Baud Rate
MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400 (default), 76800, and 115200

Device ID
The Device ID is used to uniquely identify each BACnet device and it can be in the range of 0 to
4194302. There cannot be more than one device using the same Device ID. Each of the sample
applications operates as a device and requires its own Device ID which defaults to the rotary dial
settings.
• Current Device ID—The default Device ID is set to the Tracer UC800 MAC address set on the
rotary dials. The device ID can also be soft set using the Tracer™ TU service tool.
• Soft Set Device ID—If the BACnet protocol is being used, you can enter a soft set device ID using
the Tracer TU software.
Note: This is required if a device ID larger than 127 is needed.

Measurements/Units/Conversion Factors
The UC800 communicates all units in System International (SI). The table below shows units by
data type and conversion factors.

Measurement UC800 Units Conversion Factor


Concentration PPM NA
Current Amps NA
Flow, Air Liters/Second cfm = value x 2.12
Flow, Water Liters/Minute gpm = value x 0.264
Frequency Hz NA
Power, Electrical kW NA
Power, Cooling kW Tons = value x 0.284
Pressure kPa psi = value x 0.145
Temperature °C °F = (value x 1.8) + 32
Time Seconds NA
Voltage V NA

BAS-SVP023C-EN 11
BACnet Data Points and Configuration Property Definitions

BACnet Protocol
Data Link Layer Options
Data Link Layer Options
BACnet IP, (Annex J) 
BACnet IP, (Annex J), Foreign Device 
ISO 8802-3, Ethernet (Clause 7) (10Base2, 10Base5, 10BaseT, Fiber) 
ANSI/ATA 878.1, 2.5 Mb ARCNET (Clause 8) 
ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), Baud Rate(s) 
MS/TP Master (Clause 9), Baud Rate(s): 9600, 19200, 38400, 76800, 115,200 @1.5% nominal baud rate 
MS/TP Slave (Clause 9), Baud Rate(s) 
Point-to-Point, EIA 232 (Clause 10), Baud Rate(s): 9600, 19200, 38400 
Point-to-Point, Modem (Clause 10), Baud Rate(s): 9600, 19200, 38400 
LonTalk, (Clause 11), Medium 
Other 

Device Address Binding


Is static device binding supported?  Yes  No

Networking Options
Router 
Annex H, BACnet Tunneling 
BACnet/IP Broadcast Management Device (BBMD) 
Does the BBMD Support Registrations by Foreign Devices? 

Character Sets
Indicating support for multiple characters sets does not imply that all character sets are supported simultaneously.
Maximum supported string length is 64 bytes (any character set).

ANSI X3.4 (UTF-8) 


IBM/Microsoft DBCS 
JIS C 6226 
ISO 10646 (UCS-4) 
ISO 10646 (UCS2) 
ISO 8859-1 

Notification Class Objects

Object Name Instance Property Values


Warning 1 NA
Normal Shutdown 2 NA
Immediate ShutDown 3 NA

12 BAS-SVP023C-EN
BACnet Data Points and Configuration Property Definitions

Object Data Points and Configurations

Device Object

Object Name Instance Property Values


UC800 (Dev Instance) Configurable NA

Notification Class Objects

Object Name Instance Property Values


Warning 1 NA
Normal Shutdown 2 NA
Immediate Shutdown 3 NA

Read/Write Values (Sorted by Object Type and Instance)

Table 3. Read/Write Values


Object Relinquish
Object Name Type Instance Property Values Default Valid Range Desc.
-17.78° to 18.32°C/
BAS Chilled Water Setpoint AV 1 Real 6.7°C/44°F 0°F to 65°F (depending Temp
on installed options)
BAS Current Limit Setpoint AV 2 Real 100% 0% to 100% Percent
26.66°C to 48.89°C/
BAS Hot Water Setpoint AV 3 Real 48.88°C/120°F Temp
80°F to 120°F
BAS Base Loading Setpoint AV 4 Real 50% 40% to 100% Percent
0=auto
0=auto
BAS Base Loading Command BV 1 1=true (can 0 or 1
1=on
reset)
0=false (no reset); 0=false; 1=true
BAS Reset Diagnostic BV 2 0 or 1
1=true (can reset) (can reset)
1=stop
BAS Chiller Auto Stop Command MV 1 0 = false 1 or 2
2=auto
1=cool
BAS Chiller Mode Command MV 2 2=heat 1 = cool 1 to 3
3=ice;

Read-Only Values (Sorted by Object Type and Instance)


Inputs- Analog, Binary, Multi-state

Table 4. Read-Only Values

Data Point Object Type Instance Property Value


Active Cool/Heat Setpoint Temperature AI 1 Real
Active Current Limit Setpoint AI 2 Real
Active Base Loading Setpoint AI 3 Real
Actual Running Capacity AI 4 Real
Evaporator Refrigerant Pressure AI 5 Real
Evaporator Saturated Rfgt Temp AI 6 Real
Condenser Refrigerant Pressure AI 7 Real
Condenser Saturated Rfgt Temp AI 8 Real

BAS-SVP023C-EN 13
BACnet Data Points and Configuration Property Definitions

Table 4. Read-Only Values

Data Point Object Type Instance Property Value


Local Atmospheric Pressure AI 9 Real
Compressor Starts AI 10 Real
Compressor Running Time AI 11 Real
Evaporator Entering Water Temperature AI 12 Real
Evaporator Leaving Water Temperature AI 13 Real
Condenser Entering Water Temperature AI 14 Real
Condenser Leaving Water Temperature AI 15 Real
Compressor Oil Pressure AI 16 Real
Discharge Temperature AI 17 Real
Head Pressure Control Command AI 18 Real
Starter Input Voltage AB AI 19 Real
Starter Input Voltage BC AI 20 Real
Starter Input Voltage CA AI 21 Real
Starter Motor Current L1 AI 22 Real
Starter Motor Current L2 AI 23 Real
Starter Motor Current L3 AI 24 Real
Starter Motor Current L1 % RLA AI 25 Real
Starter Motor Current L2 % RLA AI 26 Real
Starter Motor Current L3 % RLA AI 27 Real
Number of Circuits AI 28 Real
Number of Compressors for Circuit1 AI 29 Real
Number of Compressors for Circuit2 AI 30 Real
Chiller Design Capacity AI 31 Real
Frequency Command AI 32 Real
AFD Output Power AI 33 Real
Approx Evap Water Flow AI 34 Real
Evap Differential Wtr Press AI 35 Real
Approx Cond Water Flow AI 36 Real
Cond Differential Wtr Press AI 37 Real
EXV Position Percent AI 38 Real
0=stop
Run Enable BI 1
1=auto
0=no
Local Setpoint Control BI 2
1=yes
0=inactive
Limit Mode Relay Status BI 3
1=active
0=off
Chiller Running BI 4
1=on
0=no flow
Condenser Water Flow Status BI 5
1=flow
0=off
Head Relief Request Relay BI 6
1=on
0=auto
Active Base Loading Command BI 7
1= on
0=off
Compressor Running Status BI 8
1=running
0=off
Evaporator Water Pump Command BI 9
1=on

14 BAS-SVP023C-EN
BACnet Data Points and Configuration Property Definitions

Table 4. Read-Only Values

Data Point Object Type Instance Property Value


0=off
Condenser Water Pump Command BI 10
1=on
0=no flow
Evaporator Water Flow Status BI 11
1=flow
0=no
Alarm Present BI 12
1=yes
0=no
Shutdown Alarm Present BI 13
1=yes
1=not running;
2=starting;
3=running;
Chiller Running Status MI 1
4=stopping
5= Chiller in service
mode
1=cool
2=heat
Chiller Mode Command MI 2
3=ice
4=not used
1=established
2=lost
BAS Communication Status MI 3
3=never established
4=starting
Refrigerant Type MI 4 5=R-134A
3=Pueblo, CO, USA;
Manufacturing Location MI 7 4=Charmes, France;
15=Taicang, China
Model Information MI 34 6=RTH
Cooling Type MI 35 1=water cooled

BAS-SVP023C-EN 15
Diagnostic Inputs

Table 5. Diagnostics: Inputs with Alarming Capabilities (Sorted by Instance)

Object Name Object Type Instance


Comm Loss: Ext Base Loading Command Chiller BI 501

Comm Loss: Ext Base Loading Setpoint Chiller BI 502

External Base Loading Setpoint Chiller BI 503

Comm Loss: Evap Entering Water Temp Chiller BI 504

Comm Loss: Evap Leaving Water Temp Chiller BI 505

Comm Loss: Outdoor Air Temperature Chiller BI 506

Comm Loss: Excessive Loss of Communication Chiller BI 507

Outdoor Air Temperature Sensor Chiller BI 508

BAS Communication Loss BI 510

BAS Failed to Establish Communication BI 511

Comm Loss: Local BAS Interface BI 512

LCI-C Software Mismatch: Use BAS Tool BI 516

Comm Loss: Oil Loss Level Sensor Input Chiller BI 517

Comm Loss: Cprsr Discharge Rfgt Temp Chiller BI 518

Comm Loss: High Pressure Cutout Switch Chiller BI 519

Comm Loss: Master Oil Line SV BI 520

Comm Loss: Oil Pressure Chiller BI 521

Comm Loss: Oil Return Gas Pump Drain Chiller BI 522

Comm Loss: Oil Return Gas Pump Fill Chiller BI 523

Compressor Discharge Temperature Sensor Chiller BI 524

High Cprsr Rfgt Discharge Temperature Chiller BI 525

High Differential Refrigerant Pressure Chiller BI 526

High Pressure Cutout Chiller BI 527

High Refrigerant Pressure Ratio Chiller BI 528

Loss of Oil at Compressor (Running) Chiller BI 529

Loss of Oil at Compressor (Stopped) Chiller BI 530

Low Differential Refrigerant Pressure Chiller BI 531

Low Discharge Superheat Chiller BI 532

Low Oil Flow Chiller BI 533

No Differential Refrigerant Pressure Chiller BI 534

Oil Flow Protection Fault Chiller BI 535

Oil Pressure Transducer Chiller BI 536

Comm Loss: Slide Valve Load Chiller BI 537

Comm Loss: Slide Valve Unload Chiller BI 538

Restart Inhibit Chiller BI 539

Comm Loss: Condenser Rfgt Pressure Chiller BI 540

Evaporator Rfgt Pressure Transducer Chiller BI 541

Comm Loss: Condenser Water Flow Switch BI 542

16 BAS-SVP023C-EN
Diagnostic Inputs

Table 5. Diagnostics: Inputs with Alarming Capabilities (Sorted by Instance) (continued)


Comm Loss: Condenser Water Pump Relay Chiller BI 543

Condenser Water Flow Lost Chiller BI 544

Condenser Water Flow Overdue Chiller BI 545

Comm Loss: Condenser Entering Water Temp Chiller BI 546

Comm Loss: Condenser Leaving Water Temp Chiller BI 547

Condenser Entering Water Temp Sensor Chiller BI 548

Condenser Leaving Water Temp Sensor Chiller BI 549

Comm Loss: Evaporator Rfgt Liquid Level Chiller BI 550

Evaporator Liquid Level Sensor Chiller BI 551

High Evaporator Liquid Level Chiller BI 552

Low Evaporator Liquid Level Chiller BI 553

Low Evaporator Refrigerant Pressure Chiller BI 554

Low Evaporator Refrigerant Temperature Chiller BI 555

Low Evaporator Temp: Unit Off Chiller BI 556

Comm Loss: Evaporator Water Flow Switch Chiller BI 557

Comm Loss: Evaporator Water Pump Relay Chiller BI 558

Evaporator Water Flow Lost Chiller BI 559

Evaporator Water Flow Overdue Chiller BI 560

High Evaporator Refrigerant Pressure Chiller BI 561

High Evaporator Water Temperature Chiller BI 562

Evap Water Flow (Entering Water Temp) Chiller BI 563

Evaporator Entering Water Temp Sensor Chiller BI 564

Evaporator Leaving Water Temp Sensor Chiller BI 565

Low Evaporator Water Temp (Unit On) Chiller BI 566

Low Evaporator Water Temp (Unit Off) Chiller BI 567

Comm Loss: Electronic Expansion Valve 1 Chiller BI 568

Comm Loss: Electronic Expansion Valve 2 Chiller BI 569

Comm Loss: Evaporator Rfgt Pressure Chiller BI 570

Evaporator Rfgt Pressure Transducer Chiller BI 571

Comm Loss: Compressor % RLA Output Chiller BI 572

Comm Loss: Cond Rfgt Pressure Output BI 573

Comm Loss: Cond Head Press Cntrl Output Chiller BI 574

Comm Loss: Emergency Stop Chiller BI 575

Comm Loss: Ext Chilled/Hot Water Setpoint Chiller BI 576

Comm Loss: Ext Current Limit Setpoint Chiller BI 577

Comm Loss: External Auto/Stop Chiller BI 578

Comm Loss: External Hot Water Command Chiller BI 579

Comm Loss: Op Status Programmable Relays Chiller BI 580

Comm Loss: Refrigerant Monitor Input Chiller BI 581

Emergency Stop Chiller BI 582

External Chilled/Hot Water Setpoint Chiller BI 583

BAS-SVP023C-EN 17
Diagnostic Inputs

Table 5. Diagnostics: Inputs with Alarming Capabilities (Sorted by Instance) (continued)


External Current Limit Setpoint Chiller BI 584

Refrigerant Monitor Input Chiller BI 585

Comm Loss: External Ice Building Command Ice Building BI 586

Comm Loss: Ice Building Status Relay Ice Building BI 587

Comm Loss: SSS/AFD Fault Chiller BI 588

Comm Loss: Starter Chiller BI 589

Solid State Starter Fault Chiller BI 590

Starter Failed to Arm/Start Chiller BI 591

Unexpected Starter Shutdown Chiller BI 592

At Speed Input Opened Chiller BI 593

At Speed Input Shorted Chiller BI 594

Compressor Did Not Accel: Transition Chiller BI 595

Compressor Did Not Accelerate Fully Chiller BI 596

Compressor Did Not Accelerate: Shutdown Chiller BI 597

Starter Contactor Interrupt Failure Chiller BI 598

Momentary Power Loss Chiller BI 599

Motor Current Overload Chiller BI 600

Over Voltage Chiller BI 601

Phase Loss Chiller BI 602

Phase Reversal Chiller BI 603

Power Loss Chiller BI 604

Severe Current Unbalance Chiller BI 605

Starter Comm Loss: Main Processor Chiller BI 606

Starter Did Not Transition BI 607

Starter Dry Run Test Chiller BI 608

Starter Fault Type I Chiller BI 609

Starter Fault Type II Chiller BI 610

Starter Fault Type III Chiller BI 611

Starter Module Memory Error Type 1 Chiller BI 612

Starter Module Memory Error Type 2 Chiller BI 613

Transition Complete Input Opened BI 614

Transition Complete Input Shorted BI 615

Under Voltage Chiller BI 616

Check Clock BI 617

MP: Invalid Configuration Platform BI 619

MP: Reset Has Occurred Platform BI 622

AFD Drive Fault Chiller BI 623

AFD Output Power Input Chiller BI 624

Comm Loss: AFD Speed Signal Output Chiller BI 625

Comm Loss: AFD Output Power Input Chiller BI 626

Software Error 1001: Call Trane Service Chiller BI 627

18 BAS-SVP023C-EN
Diagnostic Inputs

Table 5. Diagnostics: Inputs with Alarming Capabilities (Sorted by Instance) (continued)


Low Evaporator Water Flow BI 628

Comm Loss: Evap Diff Water Pressure BI 629

Comm Loss: Cond Diff Water Pressure BI 630

Evaporator Diff Water Pressure Xdcr(a) BI 631

Condenser Diff Water Pressure Xdcr(a) BI 632

(a) Xdcr = transducer

BAS-SVP023C-EN 19
Modbus RTU Data Points and Configuration Property
Definitions
The Tracer UC800 controller is an equipment unit controller which provides the equipment system
sequences and performs closed-loop control. In addition, the UC800 integrates with Modbus
systems and devices using Modbus RTU protocol.

Holding Registers—Read/Write (Sorted by Register)


This function code is used to read the contents of a contiguous block of holding registers in a
remote device.
Table 6. Holding Registers
Register
Register Object Name Register Register Type Value Valid Range
BAS Chiller Auto Stop Command 40001 Binary 0,1
• 0 = Cool
BAS Chiller Mode Command 40002 Enumeration • 1 = Heat 0 to 2
• 2 = Ice
-17.78° to 18.32°C/
BAS Chilled Water Setpoint 40003 Temperature
0°F to 65°F (depending on installed options)
BAS Current Limit Setpoint 40004 Percent(a) 0% to 100%
BAS Hot Water Setpoint 40005 Temperature 26.66°C to 48.89°C/80°F to 120°F
BAS Base Loading Setpoint 40006 Percent 40% to 100%
BAS Base Loading Command 40007 Binary 0,1
BAS Diagnostic Reset 40008 Binary 0,1
(a) Percent, s16, 1% (100 = 100%). Refer to “Determining Input Register Type,” p. 22

Input Registers—Read Only (Sorted by Register)


This function code is used to read from 1 to 125 contiguous input registers in a remote device.
Table 7. Input Registers
Register Object Name Register Register Type Register Value
Software Type 30001 NA 623=RTH
Software Revision 30002 NA
Chiller Running 30003 Binary 0=off; 1=on
Active Current Limit Setpoint 30004 Percent
Active Base Loading Setpoint 30005 Percent
Actual running Capacity 30006 Percent
Active Cool/Heat Setpoint Temperature 30007 Temperature
Evaporator Entering Water Temperature 30008 Temperature
Evaporator Leaving Water Temperature 30009 Temperature
Condenser Entering Water Temperature 30010 Temperature
Condenser Leaving Water Temperature 30011 Temperature
30012 Binary 0=off
Evaporator Water Pump Command
1=on
30013 Binary 0=no flow
Evaporator Water Flow Status
1=flow
30014 Binary 0=off
Condenser Water Pump Command
1=on
30015 Binary 0=no flow
Condenser Water flow Status
1=flow
0=not running
1=starting= 
Chiller Running Status 30016 Enumeration
2=running
3=stopping

20 BAS-SVP023C-EN
Modbus RTU Data Points and Configuration Property Definitions

Table 7. Input Registers (continued)


Register Object Name Register Register Type Register Value
0=cool
1=heat
Chiller Mode Command 30017 Enumeration
2=ice
3=not used
0=established 
1= lost
BAS Communication Status 30018 Enumeration
2=never established 
3=starting
30019 Binary 0=no
Alarm Present
1=yes
30020 Binary 0=no
Shutdown Alarm Present
1=yes
30021 Binary 0=stop 
Run Enable
1=auto
30022 Binary 0=no
Local Setpoint Control
1=yes
30023 Binary 0=inactive
Limit Mode Relay Status
1=active
30024 Binary 0=off
Head Relief Request Relay
1=on
Head Pressure Control Command 30025 Voltage
30026 Binary 0=inactive
Active Base Loading Command
1=active
30027 Binary 0=off
Compressor Running Status
1=running
Local Atmosphere Pressure 30028 Pressure
Evaporator Refrigerant Pressure 30029 Pressure
Condenser Refrigerant Pressure 30030 Pressure
Evaporator Saturated Rfgt Temp 30031 Temperature
Condenser Saturated Rfgt Temp 30032 Temperature
30033/
Compressor Starts Count
30034
Compressor Oil Pressure 30035 Pressure
Discharge Temperature 30036 Temperature
Starter Input Voltage AB 30037 Voltage
Starter Input Voltage BC 30038 Voltage
Starter Input Voltage CA 30039 Voltage
Starter Motor Current L1 30040 Current
Starter Motor Current L2 30041 Current
Starter Motor Current L3 30042 Current
Starter Motor Current L1 % RLA 30043 Percent
Starter Motor Current L2 % RLA 30044 Percent
Starter Motor Current L3 % RLA 30045 Percent
Frequency Command 30046 Frequency
AFD Output Power 30047 Power
Number of Circuits 30048 Number
Number of Compressors- Ckt1 30049 Number
Number of Compressors- Ckt2 30050 Number
Chiller Design Capacity 30051 Number
Refrigerant Type 30052 Enumeration 4=R-134A
Model Information 30053 Enumeration 5=RTH
Cooling Type 30054 Enumeration 0=water cooled
2=Pueblo, CO
Manufacturing Location 30055 Enumeration 3=Charmes, France
14=Taicang, China
Approximate Chiller Capacity- Evap 30057 Number
Approximate Chiller Capacity- Cond 30058 Number

BAS-SVP023C-EN 21
Modbus RTU Data Points and Configuration Property Definitions

Table 7. Input Registers (continued)


Register Object Name Register Register Type Register Value
Approx Evap Water Flow 30059 Number
Evap Differential Water Pressure 30060 Pressure
Approx Cond Water Flow 30061 Number
Cond Differential Water Pressure 30062 Pressure
30063/
Compressor Running Time Temperature
30064
EXV Position Percent 30065 Percent

Determining Input Register Type

Table 8. Register Type

Register Type Data Format Units


Binary u16 0 = false/off/no/disabled/stop, 1 = true/on/yes/enabled/auto
Concentration u16 PPM
Current U16 Amps
Enumeration u16 NA
Flow, Air u16 Liters/Second (100 = 212 cfm)
Flow, Water u16 Liters/Minute (1,000 = 264 gpm)
Frequency u16 0.1 Hz (600 = 60 Hz)
Percent s16 0.005% (20,000 = 100%)
Percent_1(a) s16 1% (100 = 100%)
Power u16 kW (3517 = 1,000 tons)
Power Factor s16 0.005 (200 = 1)
Pressure u16 0.1 kPa absolute (1,000 = 14.5 psi)
Differential Pressure s16 0.1 kPa absolute (1,000 = 14.5 psi)

Register  1.8
Temperature s16 0.01 °C (100 = 1 °C) F = -------------------------------------------- + 32
100

Time Interval u32 Seconds


Voltage u16 Volts
None u16 NA
(a) Refer to “Holding Registers—Read/Write (Sorted by Register),” p. 20

22 BAS-SVP023C-EN
3DC (Hex) and 3DC (Dec)

Table 9. Diagnostics- Sorted by Name

3 DC (Hex) 3 DC (Dec) Diagnostics Name


Many of the codes in this listing are the same. Refer to the local display for more detail.
701 1793 AFD Drive Fault
702 1794 AFD Output Power Input
3D8 984 At Speed Input Opened
3D6 982 At Speed Input Shorted
398 920 BAS Communication Lost
390 912 BAS Failed to Establish Communication
2E6 742 Check Clock
704 1796 Comm Loss: AFD Output Power Input
703 1795 Comm Loss: AFD Speed Signal Output
6B6 1718 Comm Loss: Compressor % RLA Output
7A8 1960 Comm Loss: Cond Diff Water Pressure
6B6 1718 Comm Loss: Cond Head Press Cntrl Output
6B6 1718 Comm Loss: Cond Rfgt Pressure Output
6B6 1718 Comm Loss: Condenser Entering Water Temp
6B6 1718 Comm Loss: Condenser Leaving Water Temp
5F2 1522 Comm Loss: Condenser Rfgt Pressure
6B6 1718 Comm Loss: Condenser Water Flow Switch
6B6 1718 Comm Loss: Condenser Water Pump Relay
6B6 1718 Comm Loss: Cprsr Discharge Rfgt Temp
694 1684 Comm Loss: Electronic Expansion Valve 1
695 1685 Comm Loss: Electronic Expansion Valve 2
5DE 1502 Comm Loss: Emergency Stop
7B3 1971 Comm Loss: Evap Diff Water Pressure
5E4 1508 Comm Loss: Evap Entering Water Temp
5E3 1507 Comm Loss: Evap Leaving Water Temp
688 1672 Comm Loss: Evaporator Rfgt Liquid Level
5F0 1520 Comm Loss: Evaporator Rfgt Pressure
5EF 1519 Comm Loss: Evaporator Water Flow Switch
5F8 1528 Comm Loss: Evaporator Water Pump Relay
6B6 1718 Comm Loss: Ext Base Loading Command
6B6 1718 Comm Loss: Ext Base Loading Setpoint
5E9 1513 Comm Loss: Ext Chilled/Hot Water Setpoint
5EA 1514 Comm Loss: Ext Current Limit Setpoint
5DD 1501 Comm Loss: External Auto/Stop
6B7 1719 Comm Loss: External Hot Water Command
5E1 1505 Comm Loss: External Ice Building Command
5EB 1515 Comm Loss: High Pressure Cutout Switch
5FA 1530 Comm Loss: Ice Building Status Relay
69D 1693 Comm Loss: Local BAS Interface
6B6 1718 Comm Loss: Master Oil Line SV
6B6 1718 Comm Loss: Oil Loss Level Sensor Input
5F4 1524 Comm Loss: Oil Pressure

BAS-SVP023C-EN 23
3DC (Hex) and 3DC (Dec)

Table 9. Diagnostics- Sorted by Name (continued)

3 DC (Hex) 3 DC (Dec) Diagnostics Name


6B6 1718 Comm Loss: Oil Return Gas Pump Drain
6B6 1718 Comm Loss: Oil Return Gas Pump Fill
6A0 1696 Comm Loss: Op Status Programmable Relays
5E2 1506 Comm Loss: Outdoor Air Temperature
6B6 1718 Comm Loss: Refrigerant Monitor Input
5D2 1490 Comm Loss: Slide Valve Load
5D1 1489 Comm Loss: Slide Valve Unload
6B6 1718 Comm Loss: SSS/AFD Fault
690 1680 Comm Loss: Starter
1FA 506 Compressor Did Not Accel: Transition
1F5 501 Compressor Did Not Accelerate Fully
EE 238 Compressor Did Not Accelerate: Shutdown
284 644 Compressor Discharge Temperature Sensor
2EC 748 Condenser Diff Water Pressure Xdcr(a)
9A 154 Condenser Entering Water Temp Sensor
9B 155 Condenser Leaving Water Temp Sensor
F7 247 Condenser Water Flow Lost
DC 220 Condenser Water Flow Overdue
FD 253 Emergency Stop
8A 138 Evap Water Flow (Entering Water Temp)
2EB 747 Evaporator Diff Water Pressure Xdcr(a)
8E 142 Evaporator Entering Water Temp Sensor
AB 171 Evaporator Leaving Water Temp Sensor
27D 637 Evaporator Liquid Level Sensor
5B8 1464 Evaporator Rfgt Pressure Transducer
5BA 1466 Evaporator Rfgt Pressure Transducer
ED 237 Evaporator Water Flow Lost
384 900 Evaporator Water Flow Overdue
4C4 1220 External Base Loading Setpoint
87 135 External Chilled/Hot Water Setpoint
89 137 External Current Limit Setpoint
1C2 450 High Cprsr Rfgt Discharge Temperature
1C6 454 High Differential Refrigerant Pressure
584 1412 High Evaporator Liquid Level
6B8 1720 High Evaporator Refrigerant Pressure
6B6 1718 High Evaporator Water Temperature
F5 245 High Pressure Cutout
1C6 454 High Refrigerant Pressure Ratio
390 912 LCI-C Software Mismatch: Use BAS Tool
59C 1436 Loss of Oil at Compressor (Running)
59D 1437 Loss of Oil at Compressor (Stopped)
1AE 430 Low Differential Refrigerant Pressure
18E 398 Low Discharge Superheat
583 1411 Low Evaporator Liquid Level
B5 181 Low Evaporator Refrigerant Pressure

24 BAS-SVP023C-EN
3DC (Hex) and 3DC (Dec)

Table 9. Diagnostics- Sorted by Name (continued)

3 DC (Hex) 3 DC (Dec) Diagnostics Name


FB 251 Low Evaporator Refrigerant Temperature
6B3 1715 Low Evaporator Temp: Unit Off
2F4 756 Low Evaporator Water Flow
C5 197 Low Evaporator Water Temp (Unit Off)
C6 198 Low Evaporator Water Temp (Unit On)
198 408 Low Oil Flow
E2 226 Momentary Power Loss
EC 236 Motor Current Overload
5FF 1535 MP: Invalid Configuration
D9 217 MP: Reset Has Occurred
297 663 No Differential Refrigerant Pressure
1E1 481 Oil Flow Protection Fault
5BE 1470 Oil Pressure Transducer
A1 161 Outdoor Air Temperature Sensor
D7 215 Over Voltage
E4 228 Phase Loss
E5 229 Phase Reversal
1A0 416 Power Loss
2F2 754 Refrigerant Monitor Input
28C 652 Restart Inhibit
E3 227 Severe Current Unbalance
705 1797 Software Error 1001: Call Trane Service
189 393 Solid State Starter Fault
5CD 1485 Starter Comm Loss: Main Processor
CA 202 Starter Contactor Interrupt Failure
F0 240 Starter Did Not Transition
188 392 Starter Dry Run Test
6A3 1699 Starter Failed to Arm/Start
1E9 489 Starter Fault Type I
1ED 493 Starter Fault Type II
1F1 497 Starter Fault Type III
5C5 1477 Starter Module Memory Error Type 1
5C9 1481 Starter Module Memory Error Type 2
3D7 983 Transition Complete Input Opened
3D5 981 Transition Complete Input Shorted
D8 216 Under Voltage
6B5 1717 Unexpected Starter Shutdown
(a) Xdcr = Transducer

BAS-SVP023C-EN 25
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in
creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced
controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com.

Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.

© 2015 Trane. All rights reserved.


BAS-SVP023C-EN 20 Aug 2015 We are committed to using environmentally
Supersedes BAS-SVP023B-EN 29 May 2015 conscious print practices that reduce waste.