You are on page 1of 1

Customer: Peroni Pompe

Ref.: PTO190

Date: 27-gen-2010

VFD ELECTRICAL EQUIPMENT DATA SHEET


Ambient Conditions Operating temperature 0°C to +40°C up to +50°C with derating
Storage and transport temperature -20°C to +70°C
Relative humidity (non-condensing) 5% to 95%
Altitude max. 1000m without derate up to 3000m with derating

Compliance with standards Standards EN 60204-1; EN 60146-1; EN 61800-3; EN 50178; EN 60529


CE marking According to EMC directive no. 89/336/EC and low voltage directive No. 73/23/EC
Electromagnetic compatibility Radio interference suppression filter according to EN 55 011 A
RI suppression According to EMC product standard for VFD EN 61800-3 (restricted distribution)

General data Drive type SVGT 780KE


Configuration 6 pulse at network side
Operation 2 quadrants - without braking
Control type Digital PWM - Microprocessor Plus
Rated current 520 A @ 40°C
Rated power 622 KVA @ 690V
Overload capacity 150% the rated current for 60 seconds every 10 min
Output voltage 0 to 690V
Output frequency 0 to 50Hz
Efficiency Greater than 98% (at 50Hz and rated load)
Local speed set point and human interface Keypad with LCD display
Communication card Not Present

Mechanical data Degree of protection IP44 with closed doors


Installation Indoor; Safe Area
Overall dimensions 2800x2392x800 mm (W x H x D)
Inside and outside colour RAL 7035
Approx. Weight 1200 kg
Type of cooling Forced air cooling
Power loss 8800W
Sound pressure level <75 dB(A) at 1m
Cooling air requirement 5500 m³/h
Cable input/output from bottom/bottom

Electrical data Input ratings


Voltage 690V +/-10%
Frequency 47 to 63Hz
Power factor Greater than 0,98
Current 444A @ VFD rated current Include 20A for auxiliaries
Control circuit voltage 24Vdc Feed from internal auxiliary supply
Auxiliary circuit supply (lights, heaters) 230Vac - 1Ph - 50Hz Feed from internal auxiliary transformer
Auxiliary circuit supply (fans, ac motors) 400Vac - 3Ph - 50Hz Feed from internal auxiliary supply

Power composition Three pole automatic main switch with minimun voltage coil
Three phase input reactor
Three phase output reactor
Control panel transformer
AC motor fan feeder
Motor space heater circuit Feed from external source
Panel space heater circuit Feed from external source
Internal lighting circuit Feed from external source
Mounted in door Keypad with LCD display
Emergency stop push-button - category 0 - uncontrolled stop with safety relay
Ready for running, run and fault pilot lights
PT100 control box (8 inputs) Temperature control for main motor windings and bearings
PT100 control box (4 inputs) Temperature control for HV/LV transformer windings

Nameplate and tags service language English

Interface control Input signals Ready to start contact (n.o.)


Start/Stop contact (n.o.)
Emercengy contact (n.c.)
4-20mA / 0-10Vdc analog signal control speed
Output signals VFD fault (generic protection intervention - n.o.)
VFD ready to run (n.o.)
VFD start (n.o.)
Motor running (speed > 0 rpm) (n.o.)
Motor Thermal protection activated (Pt100) (n.c.)
Transformer Thermal protection activate (Pt100) (n.c.)
Emergency mushroom push-button contact (n.c.)
4-20mA / 0-10Vdc analog motor speed
4-20mA / 0-10Vdc analog motor current

Test of the equipment Routine tests dimensional check


construction check
feedings check
interlock check
electronic regulation check
instruments of measure check
protections check
verification of the sequences
control of the continuity of the protection circuit
test of applied tension
measure of the resistance of isolation

27/01/2010 1/1