Introduction Input
Smart Power Ⅱ 48/3000 HE is a digital rectifier with Voltage 85~300VAC(Norminal 220VAC)
outstanding reliability, efficiency and power
Frequency 45Hz~66Hz
density. It is specially designed for telecom,
<15Arms at 220VAC input
network access and data center applications. Input Current <19Arms at 176VAC input
Power Factor >0.99
THDi <5%
Features
High efficiency and high power density Output
96.2% efficiency and 33.43W/in3 power density.
Voltage 42~58V DC (Nominal 53.5V DC)
Digital control
Digital primary and secondary control, realize Power 3000W
excellent monitoring and regulation. Maximum 62.5A at 48VDC
Current
High reliability design
One fan front-to-back air flow with latest thermal Static Voltage <0.5%
Regulation
solution and experienced design.
Dynamic
Disconnect mains when hazardous input <5% for 10%~90% load,
Voltage
regulation time < 50ms
Smart Power Ⅱ 48/3000HE disconnect mains to Regulation
protect itself when it can not sustain the input
Ripple <150mV peak to peak
voltage.
Psophometric <2mv
Excellent EMC performance
Lower interference and excellent susceptibility give Current <5%
module better compatibility. Sharing
Efficiency 96.2%
Altitude 4000m
IP level IP 20
42
Weight 2.2Kg
20
Applicable Standards 0 35 51 8 56 1 62 5
. . .
I o(A)
Safety IEC60950-1 UL60950-1 EN60950-1 Fig3 output voltage vs. output current
EN55022 ClassB(emission)
IEC61000-3-2 97
IEC61000-3-3 96
IEC61000-4-2(electrostatic discharge)
95
IEC61000-4-3(radiated immunity)
Efficien cy ( % )
EMC 94
IEC61000-4-4(EFT)
93
IEC61000-4-5(surge immunity)
92
IEC61000-4-6(conducted immunity)
91
IEC61000-4-8
IEC61000-4-11 90
89
ETSI EN 300 019-2(-1,-2,-3) 88
ETSI EN 300 132-2 0 20 40 60 80
Environment Telcordia NEBS GR63 CORE Zone 4 L OAD (%)
RoHS compliant Fig4 efficiency vs. load (at 220VAC input)