Professional Documents
Culture Documents
FUNCTION
DESCRIPTION
Specifications within this document are subject to change without notice. If deviations between information in this datasheet and
Eltek original (doc number 241115.100.DS3) Eltek original holds the valid information.
TEMPERATURE RANGE
Operation: - 40°C to + 45°C (-40°F to 113°F) – No temperature de-rating. Max. output
power = 2000W;
+ 45°C to + 75°C (113°F to 167°F) – Output will be de-rated (min output power
1400W) and rectifier will finally stop in auto-protect mode
HUMIDITY
Storage: 0–99 % RH non-condensing (recommended: 10-30 % RH)
OPERATING ALTITUDE
Up to 4000m, for altitudes between 2500m and 4000m, output power may derate at lower
ambient temperatures.
COOLING
2 speed controlled fans (front to back airflow), brushless with magnetic bearing; In case of fan failure
on one fan Power derating will start at 25°C rectifier shutdown at 75°C. In case of fan failure on both
fans rectifier will shutdown immediately
MECHANICAL CHARACTERISTICS
Dimensions: 109 x 327 x 41,5mm (wxdxh) (4.25 x 1.69 x 13”), Weight: 1.9kg (4,19lbs)
ELECTRICAL CHARACTERISTICS
INPUT OUTPUT
Input voltage / 85 VAC / 840W Output power
840 W – 2000W (depending on
maximum 85-185 VAC / linear up to 2000W
mains input , see input
output power: 185-275 VAC / 2000 W
voltage/max output power)
275-300 VAC /Full output power
reduced power factor
High voltage The rectifier will disconnect itself from Maximum 41,7 Amps at 48 VDC and
the mains input > 300 VAC. current nominal AC input (185-275 VAC)
Automatically restart when the input
voltage is within a safe level
Low voltage The rectifier will shut down at mains Current share ±3% from true average current
voltages < 85 VAC between modules
Frequency 45 to 66Hz Static voltage
regulation ±0.5% from 0 to full load
Harmonics According to EN 61000-3-2 Dynamic
voltage ±4.0% for 10-90% or 90-10%
regulation load variation, regulation time <
50ms
Maximum 12,5 Arms maximum at 185 VAC and Hold up time > 20ms
Current 2000 W output
Power factor > 0.99 at 50% load or more Voltage 48 VDC (range: 43,5-57,6 VDC)
Total Ripple and < 100 mV peak to peak,
harmonic Noise 30 MHz bandwidth
< 5%
distortion < 0.96mV rms psophometric
(THD)
INPUT/OUTPUT
SIGNALLING
• Power (green) indicates that the power supply is ON/OFF and communication with controller
• Warning (yellow) indicates an abnormal situation
• Alarm (red) indicates an alarm situation
SUPPLIER NAME
ELTEK ENERGY
DESIGNATION SUPPLIER’S CODE ALCATEL’S CODE
Flatpack2 2000W 48V 241115.100