The Flatpack2 2000 41,7A/48V is a modern switch


mode power supply designed for battery charging
and supplying high quality DC power to telecom
equipment and similar applications.
Flatpack2 delivers an industry leading power
density of 22W/in3 a perfect match to build flexible
and expandable DC power solutions

DESCRIPTION

HIGH PERFORMANCES, HIGH POWER DENSITY & FEATURES RICH

• Introducing digital controllers for excellent monitoring and regulation characteristics


• Front to back air flow with built in advanced fan speed control
• Front LED indicators gives easy on site information regarding rectifier status.
• Full power from - 40°C (-40°F) up to + 45°C (113°F) ambient temperature
• Wide input voltage range, 85 VAC to 300 VAC. Power limitations will be activated below 185
VAC.
• 275 VAC – 300 VAC, full power is available but with reduced power factor.
• Automatic shutdown at input voltages above 300 VAC.
• Protection against surges, caused by lightning or switching transients
• High efficiency, above 92%
• Temperature monitoring with automatic power limitation and shutdown at high temperatures
• Constant power charging during battery recharge
• True hot plug-in

COMPLIANT TO INTERNATIONAL STANDARDS

Electrical safety: IEC 60950-1, UL 60950

EMC: EN 300 386 V.1.3.3 (telecommunication network)


EN 61000-6-3 (emission, light industry)
EN 61000-6-2 (immunity, industry)

Environment: ETSI EN 300 019-2


ETSI EN 300 132-2
RoHS compliant from July 06

Specifications within this document are subject to change without notice. If deviations between information in this datasheet and
Eltek original (doc number 241115.100.DS3) Eltek original holds the valid information.

CAH 01 13.01.2006 Flatpack2 2000W 48V


Mobile
Networks
Division
ELTEK 241115.100 ALCATEL 1/3
ENVIRONMENTAL CHARACTERISTICS

TEMPERATURE RANGE
Operation: - 40°C to + 45°C (-40°F to 113°F) – No temperature de-rating. Max. output
power = 2000W;
+ 45°C to + 75°C (113°F to 167°F) – Output will be de-rated (min output power
1400W) and rectifier will finally stop in auto-protect mode

Storage: - 40°C to + 85°C (-40°F to 185°F)

HUMIDITY
Storage: 0–99 % RH non-condensing (recommended: 10-30 % RH)

Operation: 5–95 % RH non-condensing

OPERATING ALTITUDE
Up to 4000m, for altitudes between 2500m and 4000m, output power may derate at lower
ambient temperatures.

COOLING
2 speed controlled fans (front to back airflow), brushless with magnetic bearing; In case of fan failure
on one fan Power derating will start at 25°C rectifier shutdown at 75°C. In case of fan failure on both
fans rectifier will shutdown immediately

MECHANICAL CHARACTERISTICS

Dimensions: 109 x 327 x 41,5mm (wxdxh) (4.25 x 1.69 x 13”), Weight: 1.9kg (4,19lbs)

ELECTRICAL CHARACTERISTICS

INPUT OUTPUT
Input voltage / 85 VAC / 840W Output power
840 W – 2000W (depending on
maximum 85-185 VAC / linear up to 2000W
mains input , see input
output power: 185-275 VAC / 2000 W
voltage/max output power)
275-300 VAC /Full output power
reduced power factor
High voltage The rectifier will disconnect itself from Maximum 41,7 Amps at 48 VDC and
the mains input > 300 VAC. current nominal AC input (185-275 VAC)
Automatically restart when the input
voltage is within a safe level
Low voltage The rectifier will shut down at mains Current share ±3% from true average current
voltages < 85 VAC between modules
Frequency 45 to 66Hz Static voltage
regulation ±0.5% from 0 to full load
Harmonics According to EN 61000-3-2 Dynamic
voltage ±4.0% for 10-90% or 90-10%
regulation load variation, regulation time <
50ms
Maximum 12,5 Arms maximum at 185 VAC and Hold up time > 20ms
Current 2000 W output
Power factor > 0.99 at 50% load or more Voltage 48 VDC (range: 43,5-57,6 VDC)
Total Ripple and < 100 mV peak to peak,
harmonic Noise 30 MHz bandwidth
< 5%
distortion < 0.96mV rms psophometric
(THD)

CAH 01 13.01.2006 Flatpack2 2000W 48V


Mobile
Networks
Division
ELTEK 241115.100 ALCATEL 2/3
PROTECTIONS

INPUT/OUTPUT

Input Soft start Output Blocking diode


protection Surge protection (varistors) protection High voltage shutdown
Internal fuses (L & N) Temp derating/shutdown
Automatic disconnect at 300 VAC , and Non destructive short
shutdown < 85VAC circuit operation

SIGNALLING

The Flatpack 2000 has the following LED indications:

• Power (green) indicates that the power supply is ON/OFF and communication with controller
• Warning (yellow) indicates an abnormal situation
• Alarm (red) indicates an alarm situation

LED Status Description


Power
ON Rectifier is powered
(green)
Flashing Smartpack controller accessing information from the rectifier
OFF Mains are unavailable
Warning Rectifier is in Derating Mode (reduced output power) due to
(yellow) high internal temperature (+45 to 75 °C) or
low input voltage (lower than 185VAC) or
fan failure
ON
The remote Battery Current Limit is activated
AC input voltage is out of range
Rectifier in stand-alone mode (or loss of communication with the
Smartpack controller
Flashing Rectifier is in Over-voltage Protection Mode (AC input)
OFF No abnormal situation is present
Alarm Rectifier is in Shut-down Mode due to
(red) low mains (0 – 85VAC) or
high internal temperature (+75 °C or higher) or
high output voltage (higher than 59.5 VDC)
ON
Internal rectifier failure (malfunction)
Fan failure (single or double fan malfunction)
Low output voltage (0 to 43.5VDC)
CAN bus failure
OFF No alarm situation is present

SUPPLIER NAME
ELTEK ENERGY
DESIGNATION SUPPLIER’S CODE ALCATEL’S CODE
Flatpack2 2000W 48V 241115.100

CAH 01 13.01.2006 Flatpack2 2000W 48V


Mobile