Notes: 1. Expected Life = Standard Life x Operating Condition Rating (Operating Condition Rating defaults as 1).
2. Shaded items were historically ACA Elements but are no longer.

SAP Class Type / Use Material Size Standard Initial Suggested Current Required
Life Assessment Subsequent Condition Condition
Assigned for Interval as Assessment Profile Profile
ACA % Expected Interval
Life* (Years)
ACA_RETIC_TOWN/SUB 100 100 5 N/A N/A
AMMONIATOR 15 66 2 CP – 002 CP – 001
ANALYSER Chlorine 8 63 2 CP – 006 CP – 001
Conductivity 8 63 2 CP – 006 CP – 001
Dissolved Oxygen 8 63 2 CP – 006 CP – 001
Fluoride 8 63 2 CP – 006 CP – 001
PH 8 63 2 CP – 006 CP – 001
Turbidity 8 63 2 CP – 006 CP – 001
Oxygen Reduction Potential 8 63 2 CP – 006 CP – 001
Ammonia 8 63 2 CP – 006 CP – 001
Hydrogen Sulphide 8 63 2 CP – 006 CP – 001
Hardness 8 63 2 CP – 006 CP – 001
UV Absorbents 8 63 2 CP – 006 CP – 001
B/WASH_FILTER_UNIT 20 75 5 CP – 002 CP – 001
BLOWER 25 60 5 CP – 002 CP – 001
BORE_AND_CASE ABS 35 71 5 CP – 107 CP – 001
Mild steel 30 50 5 CP – 108 CP – 001
Mild steel cement grout 35 71 5 CP – 108 CP – 001
PVC 35 71 5 CP – 107 CP – 001
Stainless steel 40 75 5 CP – 105 CP – 001
GRP 35 71 5 CP – 106 CP – 001
BORE_COLUMN Wellmaster 20 25 5 CP – 109 CP – 001
Galvanised steel 10 50 5 CP – 110 CP – 001
Mild steel 8 63 3 CP – 111 CP – 001
Epoxy lined steel 8 63 3 CP – 112 CP – 001
PVC 15 33 5 CP – 113 CP – 001
ABS 15 33 5 CP – 113 CP – 001
GRP 15 33 5 CP – 114 CP – 001
BUILDING Asbestos 50 20 5 CP – 006 CP – 001
Concrete 80 12 5 CP – 006 CP – 001
Masonry 80 12 5 CP – 006 CP – 001
Steel 50 20 5 CP – 006 CP – 001
Timber 50 20 5 CP – 006 CP – 001
Seatainer 25 40 5 CP – 006 CP – 001
BUND_AREA 50 10 5 CP – 002 CP – 001
Asset Condition Assessment Standard Lives and Inspection Intervals Page 1 of 15
 Copyright 2001 Water Corporation of Western Australia 31 October 2011
ACA – Business Information Sheet

ACA/BIS 02 ACA Standard Lives and Inspection Intervals


SAP Class Type / Use Material Size Standard Initial Suggested Current Required
Life Assessment Subsequent Condition Condition
Assigned for Interval as Assessment Profile Profile
ACA % Expected Interval
Life* (Years)
CATCHMENT_SILT_PIT 80 25 10 CP – 002 CP – 001
CATCHMENT_SURFACE Bitumen 50 10 5 CP – 002 CP – 001
Natural 150 3 5 CP – 002 CP – 001
Roaded 50 10 5 CP – 002 CP – 001
Rock 150 1 2 CP – 002 CP – 001
CENTRIFUGE 25 60 5 CP – 002 CP – 001
CHLORINATION_UNIT 15 66 2 CP - 002 CP – 001
CHLORINATOR 15 66 2 CP – 002 CP – 001
COMMON_SITE_INFRST 30 17 5 CP – 014 CP – 001
COMPRESSOR 20 50 10 CP – 002 CP – 001
COMMUNIC_TOWR/MAST 35 29 5 CP – 002 CP – 001
CONVEYOR 25 20 5 CP – 002 CP – 001
CRANE 40 100 5 CP – 002 CP – 001
D_BRIDGE Dumped Rock 60 8 5 CP – 002 CP – 001
Mass Concrete 60 8 5 CP – 002 CP – 001
Reinforced Concrete 80 6 5 CP – 406 CP – 001
Steel 50 10 5 CP – 406 CP – 001
Wood 40 12 5 CP – 406 CP – 001
Concrete Top / Steel Piles 50 10 5 CP – 406 CP – 001
D_CULVERT Monier Concrete 110 36 20 CP – 451 CP – 001
HEL-COR Aluminium 40 50 20 CP – 002 CP – 001
HEL-COR Galv Mild Steel 40 50 20 CP – 002 CP – 001
Mass Concrete 110 36 20 CP – 451 CP – 001
Reinforced Concrete 110 36 20 CP – 451 CP – 001
Rein Conc Box Culvert 110 36 20 CP – 451 CP – 001
Asbestos 110 36 20 CP – 451 CP – 001
D_GATE Floodgate Cast Iron 40 50 10 CP – 002 CP – 001
Stainless Steel 100 25 10 CP – 002 CP – 001
GRP 30 66 10 CP – 002 CP – 001
Aluminium 30 66 10 CP – 002 CP – 001
Floodgate/outlet pipe Cast Iron 40 50 10 CP – 002 CP – 001
Stainless Steel 100 25 10 CP – 002 CP – 001
GRP 30 66 10 CP – 002 CP – 001
Aluminium 30 66 10 CP – 002 CP – 001
D_GRAVITY_PIPE Asbestos 80 50 20 CP – 002 CP – 001
Brick 100 40 20 CP – 002 CP – 001
Cast Iron 110 36 20 CP – 002 CP – 001
Monier Concrete 110 36 20 CP – 451 CP – 001
Concrete Tunnel 110 36 20 CP – 451 CP – 001
Asset Condition Assessment Standard Lives and Inspection Intervals Page 2 of 15
 Copyright 2001 Water Corporation of Western Australia 31 October 2011
ACA – Business Information Sheet

ACA/BIS 02 ACA Standard Lives and Inspection Intervals


SAP Class Type / Use Material Size Standard Initial Suggested Current Required
Life Assessment Subsequent Condition Condition
Assigned for Interval as Assessment Profile Profile
ACA % Expected Interval
Life* (Years)
Enclosed Concrete Channel 110 36 20 CP – 451 CP – 001
Fibre Rein Conc 60 33 20 CP – 002 CP – 001
Mass Concrete 110 36 20 CP – 451 CP – 001
Reinforced Concrete 110 36 20 CP – 451 CP – 001
Rein Conc Box Culvert 110 36 20 CP – 451 CP – 001
Steel 110 36 20 CP – 002 CP – 001
HEL-COR Aluminium 40 50 20 CP – 002 CP – 001
HEL-COR Galv Mild Steel 40 50 20 CP – 002 CP – 001
Vitrified Clay 110 36 20 CP – 002 CP – 001
PVC 80 50 20 CP – 002 CP – 001
D_MANHOLE 100 40 20 CP – 401 CP – 001
D_OPEN_CHANNEL Landscaped 150 14 20 CP – 441 CP – 001
Normal Open Earth Channel 150 14 20 CP – 441 CP – 001
Open Drain with Flood Levee 150 4 5 CP – 441 CP – 001
Half Pipe 100 20 20 CP – 441 CP – 001
Lined Channel 100 20 20 CP – 441 CP – 001
Swale / Shallow Depression 150 14 20 CP – 441 CP – 001
Natural Water Course 150 14 20 CP – 441 CP – 001
D_PENSTOCK Cast Iron 40 50 10 CP – 002 CP – 001
Stainless steel 100 25 10 CP – 002 CP – 001
Steel 40 66 10 CP – 002 CP – 001
D_PRES_FITTING Air Valve 30 66 10 CP – 003 CP – 001
Manhole (pressure type) 40 75 10 CP – 003 CP – 001
Scour 40 75 10 CP – 003 CP – 001
D_PRESS_PIPE/VALVE Asbestos (A & AC) 50 80 10 CP – 072 CP – 001
Steel 80 50 20 CP – 070 CP – 001
Plastic 80 50 20 CP – 071 CP – 001
Reinforced Concrete 80 50 20 CP – 075 CP – 001
D_PRESSURE_PIPE Asbestos (A & AC) 80 50 20 CP – 043 CP – 001
Steel 110 36 20 CP – 046 CP – 001
Plastic 80 50 20 CP – 047 CP – 001
Reinforced Concrete 110 36 20 CP – 045 CP – 001
D_PUMP 35 57 5 CP – 251 CP – 001
D_PUMP_UNIT < 55 kW 15 67 5 CP – 250 CP – 001
> 55 kW 15 33 5 CP – 250 CP – 001
D_STRUCTURE Inlet Asbestos 40 25 10 CP – 421 CP – 001
Brick 80 25 10 CP – 421 CP – 001
Concrete block 80 25 10 CP – 421 CP – 001
Concrete revetment mattress 80 25 10 CP – 421 CP – 001
Asset Condition Assessment Standard Lives and Inspection Intervals Page 3 of 15
 Copyright 2001 Water Corporation of Western Australia 31 October 2011
ACA – Business Information Sheet

ACA/BIS 02 ACA Standard Lives and Inspection Intervals


SAP Class Type / Use Material Size Standard Initial Suggested Current Required
Life Assessment Subsequent Condition Condition
Assigned for Interval as Assessment Profile Profile
ACA % Expected Interval
Life* (Years)
Limestone 50 40 10 CP – 421 CP – 001
Metal 40 25 10 CP – 421 CP – 001
Reinforced Concrete 80 25 10 CP – 421 CP – 001
Sand bag 40 25 10 CP – 421 CP – 001
Spray concrete 80 25 10 CP – 421 CP – 001
Stone masonry 50 40 10 CP – 421 CP – 001
Stone 50 40 10 CP – 421 CP – 001
Timber 40 25 10 CP – 421 CP – 001
Outlet Asbestos 40 25 10 CP – 421 CP – 001
Brick 80 25 10 CP – 421 CP – 001
Concrete block 80 25 10 CP – 421 CP – 001
Concrete revetment mattress 80 25 10 CP – 421 CP – 001
Limestone 50 40 10 CP – 421 CP – 001
Metal 40 25 10 CP – 421 CP – 001
Reinforced concrete 80 25 10 CP – 421 CP – 001
Sand bag 40 25 10 CP – 421 CP – 001
Spray concrete 80 25 10 CP – 421 CP – 001
Stone masonry 50 40 10 CP – 421 CP – 001
Stone 50 40 10 CP – 421 CP – 001
Timber 40 25 10 CP – 421 CP – 001
Inlet / Outlet Brick 80 25 10 CP – 421 CP – 001
Reinforced concrete 80 25 10 CP – 421 CP – 001
Control / Check Brick 80 25 10 CP – 421 CP – 001
Reinforced concrete 80 25 10 CP – 421 CP – 001
Stone masonry 50 40 10 CP – 421 CP – 001
Timber 40 25 10 CP – 421 CP – 001
Chute Reinforced concrete 80 25 10 CP – 421 CP – 001
Stone masonry 50 40 10 CP – 421 CP – 001
Drop Brick 80 25 10 CP – 421 CP – 001
Concrete block 80 25 10 CP – 421 CP – 001
Concrete revetment mattress 80 25 10 CP – 421 CP – 001
Limestone 50 40 10 CP – 421 CP – 001
Metal 40 25 10 CP – 421 CP – 001
Reinforced concrete 80 25 10 CP – 421 CP – 001
Stone masonry 50 40 10 CP – 421 CP – 001
Stone 50 40 10 CP – 421 CP – 001
Timber 40 25 10 CP – 421 CP – 001
Pit Access Reinforced concrete 80 25 10 CP – 421 CP – 001
Brick 80 25 10 CP – 421 CP – 001

Asset Condition Assessment Standard Lives and Inspection Intervals Page 4 of 15


 Copyright 2001 Water Corporation of Western Australia 31 October 2011
ACA – Business Information Sheet

ACA/BIS 02 ACA Standard Lives and Inspection Intervals


SAP Class Type / Use Material Size Standard Initial Suggested Current Required
Life Assessment Subsequent Condition Condition
Assigned for Interval as Assessment Profile Profile
ACA % Expected Interval
Life* (Years)
Weir Reinforced concrete 80 25 10 CP – 421 CP – 001
Timber 40 25 10 CP – 421 CP – 001
Gully 100 40 20 CP – 401 CP – 001
Flume Reinforced concrete 80 25 10 CP – 421 CP – 001
Spillway Reinforced concrete 80 25 10 CP – 421 CP – 001
Stone masonry 50 40 10 CP – 421 CP – 001
Stone 50 40 10 CP – 421 CP – 001
Transition Reinforced concrete 80 25 10 CP – 421 CP – 001
Shaft 100 40 20 CP – 401 CP – 001
Vent 100 40 20 CP – 401 CP – 001
Levee Bank Flood Fuse Earth 150 14 20 CP – 002 CP – 001
D_VALVE Butterfly valve < 300mm 40 75 10 CP – 080 CP – 001
> 300mm 40 75 10 CP – 080 CP – 001
Reflux valve < 300mm 40 75 10 CP – 080 CP – 001
> 300mm 40 75 10 CP – 080 CP – 001
Sluice valve < 300mm 40 75 10 CP – 080 CP – 001
> 300mm 40 75 10 CP – 080 CP – 001
D_WELL_STRUCTURE 80 25 10 CP – 460 CP – 001
DAM_INTAKE_STRUCT Tower 70 7 5 CP – 002 CP – 001
Submerged 70 7 5 CP – 002 CP – 001
DAM_WALL_STRUCTURE Earth 120 4 5 CP – 002 CP – 001
Earth/Rock 120 4 5 CP – 002 CP – 001
Reinforced Concrete 120 4 5 CP – 002 CP – 001
ELECT_INSTALLATION 25 40 10 CP – 273 CP – 001
ELECTRIC_MOTOR Borehole Cannister < 55 kW 10 100 2 CP – 224 CP – 001
> 55 kW 10 50 5 CP – 224 CP – 001
Borehole Wet Type < 55 kW 10 100 2 CP – 224 CP – 001
> 55 kW 10 50 5 CP – 224 CP – 001
Squirrel Cage < 55 kW 30 100 3 CP – 224 CP – 001
> 55 kW 30 33 10 CP – 224 CP – 001
Wound Rotor < 55 kW 30 100 3 CP – 224 CP – 001
> 55 kW 30 33 10 CP – 224 CP – 001
EMBANKMENT Compensating Basin 150 14 20 CP – 414 CP – 001
Reservoir 150 3 5 CP – 002 CP – 001
Sump 150 7 5 CP – 002 CP – 001
WW Treatment Pond 120 4 5 CP - 002 CP - 001
ENGINE 5 100 1 CP – 002 CP – 001
FENCING Standard security 30 17 5 CP – 002 CP – 001
Electric 30 17 5 CP – 002 CP – 001
Asset Condition Assessment Standard Lives and Inspection Intervals Page 5 of 15
 Copyright 2001 Water Corporation of Western Australia 31 October 2011
ACA – Business Information Sheet

ACA/BIS 02 ACA Standard Lives and Inspection Intervals


SAP Class Type / Use Material Size Standard Initial Suggested Current Required
Life Assessment Subsequent Condition Condition
Assigned for Interval as Assessment Profile Profile
ACA % Expected Interval
Life* (Years)
Colourbond 30 17 5 CP – 002 CP – 001
FUEL TANK 40 12 5 CP – 002 CP – 001
GENERATING_SET 25 40 10 CP – 002 CP – 001
HV_SWITCHGEAR 30 17 5 CP – 002 CP – 001
INSTRUMENTATION 10 70 3 CP – 026 CP – 001
LADDR/LANDING/RAIL 30 50 5 CP – 028 CP – 001
MECHANICAL_EQUIPMT Shredder 25 60 5 CP – 002 CP – 001
Scraper 25 60 5 CP – 002 CP – 001
Distribution Arm 25 60 5 CP – 002 CP – 001
Filter Belt Press 25 60 5 CP – 002 CP – 001
Aerator Paddle 25 60 5 CP – 002 CP – 001
Gate Winch 25 60 5 CP – 002 CP – 001
Vibrator 25 60 5 CP – 002 CP – 001
Powder Feeder 25 60 5 CP – 002 CP – 001
Mixer 25 60 5 CP – 002 CP – 001
MEMBRANE/LINER 15 20 3 CP – 034 CP – 001
MOTOR_CONTROL 25 40 10 CP – 218 CP – 001
MOTOR_STARTER 25 40 10 CP – 219 CP – 001
PIPE_SUPPORT Bolsters Reinforced concrete 80 25 10 CP – 050 CP – 001
Beams Steel 50 20 10 CP – 050 CP – 001
Timber 40 25 10 CP – 050 CP – 001
Trestles Steel 50 20 10 CP – 050 CP – 001
Timber 40 25 10 CP – 050 CP – 001
Overhead hangers Steel 50 10 5 CP – 050 CP – 001
Stainless steel 50 10 5 CP – 050 CP – 001
PIPES/VALVES/FITTS 50 50 10 CP – 052 CP – 001
PIT 100 100 10 CP – 053 CP – 001
POWER_DISTRIBUTION HV Aerial 30 33 10 CP – 215 CP – 001
HV Underground 40 25 10 CP – 216 CP – 001
LV 30 33 10 CP – 217 CP – 001
PRESSURE_VESSEL 40 100 5 CP – 002 CP – 001
PROG_LOGIC_CONTR 10 66 3 CP – 026 CP – 001
PUMP_MISC Chemical dosing 25 100 5 CP – 002 CP – 001
Other 25 100 5 CP – 002 CP – 001
PUMP_UNIT_MISC Sump 15 100 3 CP – 002 CP – 001
Chemical dosing 15 100 3 CP – 002 CP – 001
Other 15 100 3 CP – 002 CP – 001
ROAD 30 17 5 CP – 002 CP – 001
RO_TREATMENT_UNIT 25 40 5 CP – 002 CP – 001
Asset Condition Assessment Standard Lives and Inspection Intervals Page 6 of 15
 Copyright 2001 Water Corporation of Western Australia 31 October 2011
ACA – Business Information Sheet

ACA/BIS 02 ACA Standard Lives and Inspection Intervals


SAP Class Type / Use Material Size Standard Initial Suggested Current Required
Life Assessment Subsequent Condition Condition
Assigned for Interval as Assessment Profile Profile
ACA % Expected Interval
Life* (Years)
S_AERATION_UNIT 25 60 5 CP – 002 CP – 001
S_BRIDGE Reinforced concrete 80 25 5 CP – 002 CP – 001
Steel 50 40 5 CP – 002 CP – 001
Wood 40 36 5 CP – 002 CP – 001
S_CHANNEL_STRUCTUR 100 20 15 CP – 002 CP – 001
S_GATE GRP 30 17 5 CP – 002 CP – 001
Steel 30 17 5 CP – 002 CP – 001
Timber 30 17 5 CP – 002 CP – 001
S_GRAVITY_PIPE Asbestos Cement > 200mm 75 27 10 CP – 002 CP – 001
Brick > 200mm CP – 001
Cast iron > 200mm 90 28 20 CP – 002 CP – 001
Ductile iron > 200mm 80 31 20 CP – 002 CP – 001
GRP > 200mm 110 23 20 CP – 002 CP – 001
HDPE / MDPE > 200mm 110 23 20 CP – 002 CP – 001
Steel > 200mm 60 9 5 CP – 002 CP – 001
Steel - Polyethylene Lined > 200mm 80 9 5 CP – 002 CP – 001
PVC > 200mm 110 23 20 CP – 002 CP – 001
Resin aggregate > 200mm 75 27 10 CP – 237 CP – 001
RC unlined > 200mm 75 27 10 CP – 237 CP – 001
RC lined > 200mm 110 27 20 CP – 237 CP – 001
Vitreous clay unlined > 200mm 100 20 10 CP – 238 CP – 001
Vitreous clay lined > 200mm 110 23 20 CP – 002 CP – 001
HCAL > 200mm 50 40 10 CP – 002 CP – 001
S_MANHOLE Discharge Brick 50 10 10 CP – 201 CP – 001
Cerelox brickwork 50 10 10 CP – 201 CP – 001
RC plastic lined 110 5 20 CP – 201 CP – 001
RC unlined 50 10 10 CP – 201 CP – 001
PVC 110 23 20 CP – 201 CP – 001
Overflow Brick 50 40 10 CP – 201 CP – 001
Cerelox brickwork 50 40 10 CP – 201 CP – 001
RC plastic lined 110 23 20 CP – 201 CP – 001
Gate Brick 50 40 10 CP – 201 CP – 001
RC plastic lined 110 23 20 CP – 201 CP – 001
RC unlined 50 40 10 CP – 201 CP – 001
Maintenance shaft PVC 110 23 20 CP – 002 CP – 001
RC plastic lined 110 23 20 CP – 201 CP – 001
Inspection shaft RC unlined 50 40 10 CP – 201 CP – 001
Sealed RC unlined 50 40 10 CP – 201 CP – 001
Standard Brick 50 40 10 CP – 201 CP – 001
Asset Condition Assessment Standard Lives and Inspection Intervals Page 7 of 15
 Copyright 2001 Water Corporation of Western Australia 31 October 2011
ACA – Business Information Sheet

ACA/BIS 02 ACA Standard Lives and Inspection Intervals


SAP Class Type / Use Material Size Standard Initial Suggested Current Required
Life Assessment Subsequent Condition Condition
Assigned for Interval as Assessment Profile Profile
ACA % Expected Interval
Life* (Years)
Cerelox brickwork 50 40 10 CP – 201 CP – 001
RC plastic lined 110 23 20 CP – 201 CP – 001
RC unlined 50 40 10 CP – 201 CP – 001
Oversize Brick 50 40 10 CP – 201 CP – 001
RC plastic lined 110 23 20 CP – 201 CP – 001
RC unlined 50 40 10 CP – 201 CP – 001
Pit access Brick 50 40 10 CP – 201 CP – 001
RC unlined 50 40 10 CP – 201 CP – 001
Sandtrap RC unlined 50 40 10 CP – 201 CP – 001
Brick 50 40 10 CP – 201 CP – 001
RC unlined 50 40 10 CP – 201 CP – 001
Drop Cerelox brickwork 50 40 10 CP – 201 CP – 001
Brick 50 40 10 CP – 201 CP – 001
Cerelox brickwork 50 40 10 CP – 201 CP – 001
RC plastic lined 110 23 20 CP – 201 CP – 001
Vortex Drop RC unlined 50 40 10 CP – 201 CP – 001
RC plastic lined 80 25 10 CP – 201 CP – 001
Vacuum RC unlined 40 25 10 CP – 201 CP – 001
RC unlined 110 100 10 CP – 201 CP – 001
Chase RC plastic lined 110 100 10 CP – 201 CP – 001
RC unlined 50 40 10 CP – 201 CP – 001
S_MH_M/PART_COVER 20 25 5 CP – 002 CP – 001
S_OCEAN_O/LET_PIPE Outlet 100 20 5 CP – 002 CP – 001
Diffuser Pipe 100 20 5 CP – 002 CP – 001
S_OVERFLOW_STORAGE Tank 75 26 10 CP – 002 CP – 001
Pipe 75 26 10 CP – 002 CP – 001
Sump Lined 75 26 10 CP – 002 CP – 001
Unlined 150 13 10 CP – 002 CP – 001
S_PENSTOCK Cast Iron 40 50 5 CP – 002 CP – 001
Stainless steel 100 25 10 CP – 002 CP – 001
PVC/Stainless steel 100 25 10 CP – 002 CP – 001
Mild Steel 40 50 5 CP – 002 CP – 001
S_PRES_FITTING Air valve 30 17 5 CP – 003 CP – 001
Pressure main manhole 40 25 10 CP – 003 CP – 001
Scour 40 25 10 CP – 003 CP – 001
Expansion joint 40 25 10 CP – 002 CP – 001
Balancing pipes 20 25 2 CP – 002 CP – 001
S_PRESS_PIPE/VALVES Asbestos cement < 300mm 50 40 10 CP – 072 CP – 001
Cast iron < 300mm 90 22 10 CP – 073 CP – 001
Asset Condition Assessment Standard Lives and Inspection Intervals Page 8 of 15
 Copyright 2001 Water Corporation of Western Australia 31 October 2011
ACA – Business Information Sheet

ACA/BIS 02 ACA Standard Lives and Inspection Intervals


SAP Class Type / Use Material Size Standard Initial Suggested Current Required
Life Assessment Subsequent Condition Condition
Assigned for Interval as Assessment Profile Profile
ACA % Expected Interval
Life* (Years)
Ductile iron < 300mm 80 25 10 CP – 073 CP – 001
HDPE / MDPE < 300mm 80 25 10 CP – 071 CP – 001
Steel < 300mm 80 13 5 CP – 070 CP – 001
PVC < 300mm 80 25 10 CP – 071 CP – 001
RC unlined < 300mm 80 19 10 CP – 075 CP – 001
RC lined < 300mm 80 25 10 CP – 075 CP – 001
S_PRESSURE_PIPE Asbestos cement < 300mm 50 40 10 CP – 043 CP – 001
300 – 600mm 80 25 10 CP – 043 CP – 001
Cast iron < 300mm 90 22 10 CP – 049 CP – 001
300 – 600mm 90 22 10 CP – 049 CP – 001
Ductile iron < 300mm 80 25 10 CP – 049 CP – 001
300 – 600mm 80 25 10 CP – 049 CP – 001
GRP 300 – 600mm 80 25 10 CP – 002 CP – 001
HDPE / MDPE < 300mm 80 25 10 CP – 047 CP – 001
300 – 600mm 80 25 10 CP – 047 CP – 001
Steel < 300mm 80 13 5 CP – 046 CP – 001
300 – 600mm 80 13 5 CP – 046 CP – 001
> 600mm 110 9 5 CP – 046 CP – 001
Steel - polyethylene lined 300 – 600mm 80 13 5 CP – 046 CP – 001
> 600mm 110 9 5 CP – 046 CP – 001
PVC < 300mm 80 25 10 CP – 047 CP – 001
300 – 600mm 80 25 10 CP – 047 CP – 001
RC unlined < 300mm 80 19 10 CP – 045 CP – 001
300 – 600mm 80 19 10 CP – 045 CP – 001
> 600mm 110 14 10 CP – 045 CP – 001
RC lined 300 – 600mm 80 25 10 CP – 045 CP – 001
> 600mm 110 18 10 CP – 045 CP – 001
S_PUMP 35 57 5 CP – 251 CP – 001
S_PUMP_UNIT < 55 kW 15 67 5 CP – 250 CP – 001
> 55 kW 15 33 5 CP – 250 CP – 001
S_STRUCTURE Inlet Reinforced Concrete 30 66 5 CP – 002 CP – 001
Brick 30 66 5 CP – 002 CP – 001
Steel 30 66 5 CP – 002 CP – 001
Overflow Reinforced Concrete 30 66 5 CP – 002 CP – 001
Steel 30 66 5 Cp – 002 Cp – 001
Service Access Pit Reinforced Concrete 80 37 10 CP – 053 CP – 001
Flume Reinforced Concrete 50 20 10 CP – 002 CP – 001
Brick 30 66 5 CP – 002 CP – 001
Steel 30 17 5 CP – 002 CP – 001
Asset Condition Assessment Standard Lives and Inspection Intervals Page 9 of 15
 Copyright 2001 Water Corporation of Western Australia 31 October 2011
ACA – Business Information Sheet

ACA/BIS 02 ACA Standard Lives and Inspection Intervals


SAP Class Type / Use Material Size Standard Initial Suggested Current Required
Life Assessment Subsequent Condition Condition
Assigned for Interval as Assessment Profile Profile
ACA % Expected Interval
Life* (Years)
Retaining Wall Reinforced Concrete 50 30 10 CP – 002 CP – 001
Structure Stand Steel 30 33 5 CP – 002 CP – 001
S_TANK_COVER GRP 30 33 5 CP – 002 CP – 001
Aluminium 30 33 5 CP – 002 CP – 001
Steel 20 50 5 CP – 002 CP – 001
S_TANK_ROOF GRP sheet / ss structure 30 16 5 CP – 002 CP – 001
GRP sheet / steel structure 15 33 5 CP – 002 CP – 001
Reinforced Concrete 30 16 5 CP – 002 CP – 001
Steel sheet/timber structure 30 16 5 CP – 002 CP – 001
S/alum sheet/alum and or RC str 30 16 5 CP – 002 CP – 001
S_TANK_STRUCTURE Pre-primary Reinforced Concrete 30 17 5 CP – 002 CP – 001
Steel 30 17 5 CP – 002 CP – 001
Primary Sedimentation Reinforced Concrete 30 17 5 CP – 002 CP – 001
Secondary Sedimentation Reinforced Concrete 30 17 5 CP – 002 CP – 001
Steel 30 17 5 CP – 002 CP – 001
Aeration Reinforced Concrete 30 17 5 CP – 002 CP – 001
Steel 30 17 5 CP – 002 CP – 001
Clarifier Reinforced Concrete 30 17 5 CP – 002 CP – 001
Imhoff Reinforced Concrete 30 17 5 CP – 002 CP – 001
Treated WW Storage Reinforced Concrete 30 17 5 CP – 002 CP – 001
Trickle Filter Reinforced Concrete 30 17 5 CP – 002 CP – 001
Thickener Reinforced Concrete 30 17 5 CP – 002 CP – 001
Steel 30 17 5 CP – 002 CP – 001
Overflow Storage Reinforced Concrete 30 17 5 CP – 002 CP – 001
GRP 30 17 5 CP – 002 CP – 001
Effluent Storage Reinforced Concrete 30 17 5 CP – 002 CP – 001
Daft Reinforced Concrete 30 17 5 CP – 002 CP – 001
S_VACUUM_PUMP 15 33 5 CP – 002 CP – 001
S_VALVE Mobile pumping branch 50 20 10 CP – 080 CP – 001
Reflux valve < 300mm 50 20 10 CP – 080 CP – 001
> 300mm 50 20 10 CP – 080 CP – 001
Sluice valve < 300mm 50 20 10 CP – 080 CP – 001
> 300mm 50 20 10 CP – 080 CP – 001
Knife < 300mm 50 20 10 CP – 080 CP – 001
> 300mm 50 20 10 CP – 080 CP – 001
Butterfly < 300mm 50 20 10 CP – 080 CP – 001
> 300mm 50 20 10 CP – 080 CP – 001
S_WELL_STRUCTURE Rein Conc plastic lined 110 18 15 CP – 259 CP – 001
Rein Conc unlined 80 12 10 CP – 259 CP – 001
Asset Condition Assessment Standard Lives and Inspection Intervals Page 10 of 15
 Copyright 2001 Water Corporation of Western Australia 31 October 2011
ACA – Business Information Sheet

ACA/BIS 02 ACA Standard Lives and Inspection Intervals


SAP Class Type / Use Material Size Standard Initial Suggested Current Required
Life Assessment Subsequent Condition Condition
Assigned for Interval as Assessment Profile Profile
ACA % Expected Interval
Life* (Years)
GRP 30 17 5 CP – 002 CP – 001
Steel 30 17 5 CP – 002 CP – 001
SCREEN 25 20 5 CP – 002 CP – 001
SITE_DRAINAGE Toe drain 100 20 10 CP – 002 CP – 001
Roof drainage 30 66 5 CP – 002 CP – 001
General site drainage 100 20 10 CP – 002 CP – 001

SITE_SCADA 15 66 3 CP – 272 CP – 001


SITE_SECURITY Site Business Cont Cat – A 30 7 2 CP – 015 CP – 015
Site Business Cont Cat – B 30 13 4 CP – 015 CP – 015
Site Business Cont Cat – C 30 13 4 CP – 015 CP – 015
Site Business Cont Cat – D 30 20 6 CP – 015 CP – 015
Site Business Cont Cat – E 30 20 6 CP – 015 CP – 015
SPILLWAY Rock 70 7 5 CP – 002 CP – 001
Reinforced Concrete 70 7 5 CP – 002 CP – 001
STORAGE_UNIT Chemical storage tank Reinforced concrete 30 17 5 CP – 002 CP – 001
Steel 30 17 5 CP – 002 CP – 001
GRP 30 17 5 CP – 002 CP – 001
Poly 10 50 5 CP – 002 CP – 001
Process Water Storage SS 30 17 5 CP – 002 CP - 001
Reinforced Concrete 30 17 5 CP – 002 CP – 001
Steel 30 17 5 CP – 002 CP – 001
Mixing Tank GRP 30 17 5 CP – 002 CP – 001
GRP 30 17 5 CP – 002 CP – 001
Poly 10 50 5 CP – 002 CP – 001
Steel 30 17 5 CP – 002 CP – 001
Stainless Steel 50 20 5 CP – 002 CP – 001
Vacuum Vessel Reinforced Concrete 30 17 5 CP – 002 CP – 001
Steel 30 17 5 CP – 002 CP – 001
Sludge Storage Stainless Steel 30 17 5 CP – 002 CP – 001
Steel 30 17 5 CP – 002 CP – 001
Effluent Storage Stainless Steel 30 17 5 CP – 002 CP – 001
Steel 30 17 5 CP – 002 CP – 001
Vacuum Seal Water Stainless Steel 30 17 5 CP – 002 CP – 001
Process Water Storage Steel 30 17 5 CP – 002 CP – 001
POLY 10 50 5 CP – 002 CP – 001
SWITCHBOARD_MISC 25 40 10 CP – 002 CP – 001
TRANSFORMER 40 50 10 CP – 278 CP – 001
TRANSITION_TOWER 50 20 10 CP – 002 CP – 001
Asset Condition Assessment Standard Lives and Inspection Intervals Page 11 of 15
 Copyright 2001 Water Corporation of Western Australia 31 October 2011
ACA – Business Information Sheet

ACA/BIS 02 ACA Standard Lives and Inspection Intervals


SAP Class Type / Use Material Size Standard Initial Suggested Current Required
Life Assessment Subsequent Condition Condition
Assigned for Interval as Assessment Profile Profile
ACA % Expected Interval
Life* (Years)
W_AERATOR_TRAYS Reinforced Concrete 30 17 5 CP – 002 CP – 001
Stainless Steel 30 17 5 CP – 002 CP – 001
Steel/Timber 25 20 5 CP – 002 CP – 001
Glass Reinforced Plastic 30 17 5 CP – 002 CP - 001
W_BORE_PUMP 15 33 5 CP – 251 CP – 001
W_BORE_PUMP_UNIT < 55 kW 15 67 5 CP – 250 CP – 001
> 55 kW 15 33 5 CP – 250 CP – 001
W_BRIDGE Reinforced concrete 80 6 5 CP – 002 CP – 001
Steel 50 10 5 CP – 002 CP – 001
Wood 40 12 5 CP – 002 CP – 001
W_CATCHMENT_DRAIN Collector Drain Bitumen 50 10 5 CP – 002 CP – 001
Concrete 50 10 5 CP – 441 CP – 001
Unlined 50 10 5 CP – 441 CP – 001
Rock 50 10 5 CP – 002 CP – 001
Perimeter Drain 50 10 5 CP – 441 CP – 001
Collector Wall 50 10 5 CP – 002 CP – 001
W_CHANNEL_STRUCTUR 100 20 15 CP – 441 CP – 001
W_FITTING Air valve 30 33 10 CP – 003 CP – 001
Manhole 60 66 20 CP – 003 CP – 001
Offtake 40 25 10 CP – 003 CP – 001
Pigstation 60 66 20 CP – 003 CP – 001
Scour 40 25 10 CP – 003 CP – 001
Stand pipe 40 25 10 CP – 003 CP – 001
Riparian Release Point 40 25 10 CP – 003 CP – 001
W_GATE Radial 50 10 5 CP – 002 CP – 001
Emergency 50 10 5 CP – 002 CP – 001
Service 50 10 5 CP – 002 CP – 001
Stop Log 50 10 5 CP – 002 CP – 001
Floodgate 50 10 5 CP – 002 CP – 001
W_PENSTOCK Cast Iron 40 25 10 CP – 002 CP – 001
Steel 40 25 10 CP – 002 CP – 001
Stainless Steel 60 17 10 CP – 002 CP – 001
PVC/SS 60 17 10 CP – 002 CP – 001
W_PIPE Asbestos cement < 300mm 50 80 10 CP – 043 CP – 001
300 – 600mm 80 50 20 CP – 043 CP – 001
Cast iron < 300mm 90 44 20 CP – 049 CP – 001
300 – 600mm 90 44 20 CP – 049 CP – 001
> 600mm 90 44 20 CP – 049 CP – 001
Ductile iron < 300mm 80 50 20 CP – 049 CP – 001
Asset Condition Assessment Standard Lives and Inspection Intervals Page 12 of 15
 Copyright 2001 Water Corporation of Western Australia 31 October 2011
ACA – Business Information Sheet

ACA/BIS 02 ACA Standard Lives and Inspection Intervals


SAP Class Type / Use Material Size Standard Initial Suggested Current Required
Life Assessment Subsequent Condition Condition
Assigned for Interval as Assessment Profile Profile
ACA % Expected Interval
Life* (Years)
300 – 600mm 80 50 20 CP – 049 CP – 001
Galvanised steel, GWI, Vict < 300mm 30 100 5 CP – 074 CP – 001
Glass Reinforced Plastic 300-600mm 80 50 20 CP – 002 CP – 001
HDPE / MDPE < 300mm 80 50 20 CP – 047 CP – 001
300 – 600mm 80 50 20 CP – 047 CP – 001
> 600mm 80 50 20 CP – 047 CP – 001
PVC < 300mm 80 50 20 CP – 047 CP – 001
300 – 600mm 80 50 20 CP – 047 CP – 001
Reinforced concrete < 300mm 80 50 20 CP – 045 CP – 001
300 – 600mm 80 50 20 CP – 045 CP – 001
> 600mm 110 36 20 CP – 045 CP – 001
MSCL < 300mm 80 50 20 CP – 046 CP – 001
300 – 600mm 80 50 20 CP – 046 CP – 001
> 600mm 110 36 20 CP – 046 CP – 001
Black Iron <300mm 30 100 5 CP – 074 CP – 001
W_PIPELINE/VALVES Trunk Steel < 300mm 80 50 20 CP – 070 CP – 001
Reinforced concrete < 300mm 80 50 20 CP – 075 CP – 001
Asbestos Cement < 300mm 50 80 10 CP – 072 CP – 001
PVC < 300mm 80 50 20 CP – 071 CP – 001
MDPE < 300mm 80 50 20 CP – 071 CP – 001
Cast iron < 300mm 90 44 20 CP – 073 CP – 001
Ductile iron < 300mm 80 50 20 CP – 073 CP – 001
Distribution Steel < 300mm 80 50 20 CP – 070 CP – 001
Reinforced concrete < 300mm 80 50 20 CP – 075 CP – 001
Asbestos Cement < 300mm 50 80 10 CP – 072 CP – 001
PVC < 300mm 80 50 20 CP – 071 CP – 001
MDPE < 300mm 80 50 20 CP – 071 CP – 001
Cast iron < 300mm 90 44 20 CP – 073 CP – 001
Ductile iron < 300mm 80 50 20 CP – 073 CP – 001
Bore Steel < 300mm 80 50 20 CP – 070 CP – 001
Reinforced concrete < 300mm 80 50 20 CP – 075 CP – 001
Asbestos Cement < 300mm 50 80 10 CP – 072 CP – 001
PVC < 300mm 80 50 20 CP – 071 CP – 001
MDPE < 300mm 80 50 20 CP – 071 CP – 001
Cast iron < 300mm 90 44 20 CP – 073 CP – 001
Ductile iron < 300mm 80 50 20 CP – 073 CP – 001
Delivery Steel < 300mm 80 50 20 CP – 070 CP – 001
Reinforced concrete < 300mm 80 50 20 CP – 075 CP – 001
Asbestos Cement < 300mm 50 80 10 CP – 072 CP – 001
Asset Condition Assessment Standard Lives and Inspection Intervals Page 13 of 15
 Copyright 2001 Water Corporation of Western Australia 31 October 2011
ACA – Business Information Sheet

ACA/BIS 02 ACA Standard Lives and Inspection Intervals


SAP Class Type / Use Material Size Standard Initial Suggested Current Required
Life Assessment Subsequent Condition Condition
Assigned for Interval as Assessment Profile Profile
ACA % Expected Interval
Life* (Years)
PVC < 300mm 80 50 20 CP – 071 CP – 001
MDPE < 300mm 80 50 20 CP – 071 CP – 001
Cast iron < 300mm 90 44 20 CP – 073 CP – 001
Ductile iron < 300mm 80 50 20 CP – 073 CP – 001
W_PIPEWK/SUBMERGED Cast Iron 50 10 5 CP – 002 CP – 001
Ductile Iron 50 10 5 CP – 002 CP – 001
GRP 50 10 5 CP – 002 CP – 001
Galvanised Steel 25 20 5 CP – 002 CP – 001
Steel 50 10 5 CP – 002 CP – 001
W_PUMP 25 80 5 CP – 251 CP – 001
W_STORAGE_STRUCTUR Reservoir Reinforced concrete 70 7 5 CP – 085 CP – 001
Bitumen lined 120 4 5 CP – 002 CP – 001
Clay lined 120 4 5 CP – 002 CP – 001
Rock / concrete 120 4 5 CP – 002 CP – 001
Rock / clay 120 4 5 CP – 002 CP – 001
Tank Reinforced concrete 70 7 5 CP – 082 CP – 001
Steel plate 50 10 5 CP – 002 CP – 001
Steel sheet panel 30 10 3 CP – 002 CP – 001
Plastic 25 40 5 CP – 002 CP – 001
Glass reinforced plastic 30 33 5 CP – 002 CP – 001
Surge Tank Reinforced concrete 70 7 5 CP – 082 CP – 001
Steel plate 50 10 5 CP – 002 CP – 001

W_STRUCTURE Access ramp Reinforced concrete 70 7 5 CP – 002 CP – 001


Culvert 110 36 20 CP – 451 CP – 001
Control well 80 25 10 CP – 002 CP – 001
Inlet structure Brick 70 7 5 CP – 002 CP – 001
Reinforced concrete 70 7 5 CP – 002 CP – 001
Steel 50 10 5 CP – 002 CP – 001
Outlet structure Brick 70 7 5 CP – 002 CP – 001
Reinforced concrete 70 7 5 CP – 002 CP – 001
Steel 50 10 5 CP - 002 CP – 001
Scour Brick 70 7 5 CP – 002 CP – 001
Reinforced concrete 70 7 5 CP – 002 CP – 001
Stone / masonry 50 40 10 CP – 002 CP – 001
Steel 50 10 5 CP – 002 CP – 001
Service access pit Reinforced concrete 80 25 10 CP – 002 CP – 001
Tank stand Steel 70 7 5 CP – 002 CP – 001
Steel/Timber 50 20 10 CP – 002 CP – 001
Asset Condition Assessment Standard Lives and Inspection Intervals Page 14 of 15
 Copyright 2001 Water Corporation of Western Australia 31 October 2011
ACA – Business Information Sheet

ACA/BIS 02 ACA Standard Lives and Inspection Intervals


SAP Class Type / Use Material Size Standard Initial Suggested Current Required
Life Assessment Subsequent Condition Condition
Assigned for Interval as Assessment Profile Profile
ACA % Expected Interval
Life* (Years)
Floating 20 25 5 CP – 002 CP – 001
Boat ramp 50 20 10 CP – 002 CP – 001
Weir Box Reinforced Concrete 70 7 5 CP – 002 CP – 001
Retaining Reinforced Concrete 70 15 10 CP – 002 CP – 001
W_TANK/RES_ROOF Tank Fibro sheet / timber structure 30 16 5 CP – 060 CP – 001
Reinforced concrete 70 7 5 CP – 002 CP – 001
Steel plate 50 10 5 CP – 002 CP – 001
S/Alum sheet – Alum/RC struct 50 10 5 CP – 062 CP – 001
Steel sheet – S/RC structure 50 10 5 CP – 062 CP – 001
Steel sheet / timber structure 30 16 5 CP – 062 CP – 001
Reservoir Fibro sheet / timber structure 30 16 5 CP – 060 CP – 001
S/Alum sheet – Alum/RC struct 50 10 5 CP – 062 CP – 001
Steel sheet – S/RC structure 50 10 5 CP – 062 CP – 001
Steel sheet / timber structure 30 16 5 CP – 062 CP – 001
W_TREAT_TANK_STRUC Aeration GRP 30 17 5 CP – 002 CP – 001
Reinforced Concrete 30 17 5 CP – 002 CP – 001
Steel 30 17 5 CP – 002 CP – 001
Clarifier GRP 30 17 5 CP – 002 CP – 001
Reinforced Concrete 30 17 5 CP – 002 CP – 001
Steel 30 17 5 CP – 002 CP – 001
Filter GRP 30 17 5 CP – 002 CP – 001
Reinforced Concrete 30 17 5 CP – 002 CP – 001
Steel 30 17 5 CP – 002 CP – 001
Backwash Holding GRP 30 17 5 CP – 002 CP – 001
Reinforced Concrete 30 17 5 CP – 002 CP – 001
Steel 30 17 5 CP – 002 CP – 001
Thickener GRP 30 17 5 CP – 002 CP – 001
Reinforced Concrete 30 17 5 CP – 002 CP – 001
Steel 30 17 5 CP – 002 CP – 001
Clearwater Reinforced Concrete 50 10 5 CP – 002 CP – 001
Steel 50 10 5 CP – 002 CP - 001
W_VALVE PRV / PSV / ACV < 300mm 40 100 5 CP – 002 CP – 001
> 300mm 40 50 10 CP – 002 CP – 001
Butterfly < 300mm 40 25 10 CP – 080 CP – 001
> 300mm 40 25 10 CP – 080 CP – 001
Resilient SV < 300mm 50 20 10 CP – 080 CP – 001
> 300mm 50 20 10 CP – 080 CP – 001
Regulating < 300mm 30 16 5 CP – 080 CP – 001
> 300mm 30 16 5 CP – 080 CP – 001
Asset Condition Assessment Standard Lives and Inspection Intervals Page 15 of 15
 Copyright 2001 Water Corporation of Western Australia 31 October 2011
ACA – Business Information Sheet

ACA/BIS 02 ACA Standard Lives and Inspection Intervals


SAP Class Type / Use Material Size Standard Initial Suggested Current Required
Life Assessment Subsequent Condition Condition
Assigned for Interval as Assessment Profile Profile
ACA % Expected Interval
Life* (Years)
Reflux < 300mm 40 25 10 CP – 080 CP – 001
> 300mm 40 25 10 CP – 080 CP – 001
Sluice < 300mm 40 25 10 CP – 080 CP – 001
> 300mm 40 25 10 CP – 080 CP – 001
Float < 300mm 30 100 5 CP – 002 CP – 001

Asset Condition Assessment Standard Lives and Inspection Intervals Page 16 of 15


 Copyright 2001 Water Corporation of Western Australia 31 October 2011
Section ‘AP’ – Appendices
#161149008

END OF DOCUMENT