Chlorine Volume Calculation

Pipe Type
Dia. (mm) SDR ID (mm) SDR = "Standard Dimension Ratio
HPPE 180 17 158.823529 SDR is a ratio of pipe diameter to wa
SDR 11 means that "D" outside diam

Watermain Volume

Length (m) ID (m) Vol (m3)


Watermain 944 0.15882353 18.702
Connections 0 0.000
18.702 m3
Chlorine dose at 50 mg/l 0.00093511 m3
Chlorine requirement 0.93510755 litres
2
1.87021511
R = "Standard Dimension Ratio" is used by many PE pipe manufacturers as a method of rating pressure piping.
R is a ratio of pipe diameter to wall thickness and can be expressed as SDR = D/s.
R 11 means that "D" outside diameter of the pipe is eleven times the thickness "s" of the wall.
ressure piping.