Professional Documents
Culture Documents
INSTALLATION
OPERATION AND SERVICE MANUAL
PDW(H) SERIES
VW – 2 pipe
PW – 4 pipe (Optional 1 row coil)
2010 V.2.5
2
HYDRONIC DUCTED FAN COIL
INDEX
PDW (H) SERIES
HYDRONIC FAN COIL DUCTED
PAGE
A. PDW DUCTED FAN COILS MODEL ASSIGNMENTS 1
B. GENERAL DESCRIPTION 2
C. STANDARD SPECIFICATION 3-5
2-Pipe System Unit (VW) Standard Specification 3
4-Pipe System Unit (PW) Standard Specification 4
Coil Data 5
D. PERFORMANCE TABLES 6-19
Performance Data (Cooling Capacity, 3 rows) - 2 pipe & 4 pipe 6-10
ETHYLENE GLYCOL SOLUTIONS 10
Performance Data (Heating Capacity, 3 rows) - 2 pipe 11-15
Performance Data (Heating Capacity, 1 row) - 4 pipe 15-19
E. SAMPLE SIZING PERFORMANCE CALCULATIONS 20-22
F. PARTS DESCRIPTION 23
G. INSTALLATION 24-31
Location & Unit Installation 24
Unit Dimensions 25-26
Pipe connections 27
How to interchange Left / Right hand connection 28-30
Valve installation 31
H. ELECTRIC WIRING DIAGRAMS 32-38
I. MAINTENANCE 39-41
J. OPTIONS 42-71
3-speed & LCD Wall Pad Thermostat 42-43
Electronic PCB with wired wall pad and remote control and 44-66
control specification
Motorized Valve 67-68
Air Purifier 69
Modules 70-71
Intake (Discharge) Plenum 70
Auxiliary 1 row heating coil module & electrical heater 71
K. TROUBLE SHOOTING 72
L. APPENDIX 73-83
1
HYDRONIC DUCTED FAN COIL
PDW(H)–12-VW
SERIES
VW 2 PIPES
PW 4 PIPES
STRUCTURE
The structure of the unit is made from galvanized steel paneling, and includes couplings for
the connection of ducting, a gravity drain condensate pan, and internal self-extinguishing
closed cell expanded polyethylene as thermal and acoustic insulation. The removable and
regenerative filter is made of self-extinguishing acrylic (class EU2).
FAN
The centrifugal fan features three speed regulation, statically and dynamically balanced
impellers and high external static pressure.
ELECTRICAL SWITCHBOARD
The electrical switchboard is constructed in accordance with IEC 204-1/EN60204-1, and
comes complete with regulator and terminal board for connection to power supply and
auxiliary controls.
NOTE: for a complete unit, a valve must be installed for each water coil used. If valves are
not installed, JP01 must be shorted, as shown in the electrical connection diagram.
3
HYDRONIC DUCTED FAN COIL
STANDARD SPECIFICATION
PDW (H) – VS SERIES 3-SPEED SPECIFICATIONS
Model PDW(H)-12 PDW(H)-15 PDW(H)-18 PDW(H)-24 PDW(H)-30 PDW(H)-40 PDW(H)-44 PDW(H)-50 PDW(H)-66
Total Airflow M m3/hr 635 750 870 1110 1390 1700 1900 2400 2900
Electric Heater
Kw 2.0 2.0 2.5 3.0 4.0 4.5 5.0 6.0 6.0
Capacity (optional)
Noise Level @ 1 M
dB(A) 46/43/41 47/44/42 49/46/44 54/50/47 56/52/49 58/54/52 62/58/55 66/62/59 70/66/62
(H/M/L)
Fan Motor Power W 84 100 133 334 385 534 550 697 750
Water Flow Rate L/h 618 760 840 1237 1550 1750 1960 2560 3000
Water Pressure Drop KPa 35.0 25.0 29.0 23.4 37.0 33.0 40.0 42.7 24.2
Water Content L 0.74 1.06 1.06 1.76 1.76 2.16 2.16 3.38 4.61
Cond. Drain
mm(in) 19.05(3/4)
Connection I.D.
Dimensions W mm 460 460 460 510 510 580 580 710 710
Gross Weight kg 30 31 32 51 52 66 67 85 93
In mm(in) 19.05(3/4)
Water
Connection
Out mm(in) 19.05(3/4)
*Cooling: 27qC db/19qC wb entering air temperature, 7qC entering water and 12qC leaving water temperature.
**Heating: 20qC db entering air temperature, 50qC entering water temperature with water flow rates same as for the cooling test.
4
HYDRONIC DUCTED FAN COIL
Model PDW(H)-12 PDW(H)-15 PDW(H)-18 PDW(H)-24 PDW(H)-30 PDW(H)-40 PDW(H)-44 PDW(H)-50 PDW(H)-66
Total Airflow M m3/hr 635 750 870 1110 1390 1700 1900 2400 2900
Electric Heater
Kw - - - - - - - - -
Capacity (optional)
Noise Level @ 1 M
dB(A) 46/43/41 47/44/42 49/46/44 54/50/47 56/52/49 58/54/52 62/58/55 66/62/59 70/66/62
(H/M/L)
Fan Motor Power W 84 100 133 334 385 534 550 697 750
Cond. Drain
mm(in) 19.05(3/4)
Connection I.D.
Dimensions W mm 460 460 460 510 510 580 580 710 710
Gross Weight kg 33 34 35 52 53 73 74 94 99
In mm(in) 19.05(3/4)
Water
Connection
Out mm(in) 19.05(3/4)
*Cooling: 27qC db/19qC wb entering air temperature, 7qC entering water and 12qC leaving water temperature.
**Heating: 20qC db entering air temperature, 70qC entering water temperature and 60qC leaving water temperature.
5
HYDRONIC DUCTED FAN COIL
COIL DATA (2 PIPE SYSTEM)
Fin height Fin Length Fins per No. of Fin width No. of Tube Ø
Model
(mm) (mm) Inch Rows (mm) Circuits (mm)
PDW(H)-12 225 655 15 2 44 2 9.52
PDW(H)-15 225 655 15 3 66 3 9.52
PDW(H)-18 225 655 15 3 66 3 9.52
PDW(H)-24 275 880 15 3 66 6 9.52
PDW(H)-30 275 880 15 3 66 6 9.52
PDW(H)-40 275 1080 15 3 66 6 9.52
PDW(H)-44 275 1080 15 3 66 6 9.52
PDW(H)-50 375 1230 15 3 66 12 9.52
PDW(H)-66 375 1230 15 4 88 12 9.52
PDW(H)-12-VW/PW
TAI DB25ć-WB17.8ć TAI DB27ć-WB19ć TAI DB27ć-WB19.5ć TAI DB29ć-WB21.1ć
Twi Qw dpw Qa Pf Pfs Tad Taw Pf Pfs Tad Taw Pf Pfs Tad Taw Pf Pfs Tad Taw
θćιθ1/hιθkPaι θm3/h θkWιθkWιθćι θćιθkWιθkWι θćι θćιθkWι θkWιθćι θćιθkWιθkWι θćι θćι
925 42 680 4.41 2.49 14.3 10.7 4.93 2.78 15 11.3 5.13 2.68 15.4 11.6 5.86 2.9 16.4 12.5
5,0 705 30 510 3.35 2.03 13.4 10.6 3.75 2.27 14 11.2 3.91 2.27 14 11.5 4.5 2.36 15.4 12.3
490 15.6 340 2.3 1.64 11 10.4 2.58 1.74 12.2 11 2.71 1.75 12.1 11.2 3.13 1.85 13.4 13.1
822 38 681 3.95 2.39 14.7 11.5 4.42 2.64 15.6 12.2 4.56 2.57 15.9 12.6 5.3 2.73 17.2 13.5
6,0 635 25 511 3.06 2.01 13.5 11.3 3.41 2.18 14.5 12 3.52 2.14 14.7 12.4 4.05 2.24 16.1 13.3
436 12.8 341 2.1 1.53 11.9 11.1 2.34 1.69 12.6 11.8 2.42 1.59 13.4 12.2 2.8 1.72 14.2 13
650 24 683 3.1 2.28 15.2 13.0 3.58 2.54 16.0 13.6 3.6 2.5 16.2 14.2 4.45 2.48 18.2 14.8
7,0 560 18 510 2.5 1.92 14 12.6 2.87 2.08 15 13.2 3.1 2.07 15.2 13.4 3.58 2.07 17 14.3
380 9.5 341 1.73 1.4 13 12.4 1.99 1.55 13.7 13 2.1 1.5 14.2 13.3 2.5 1.62 15.2 14.1
636 20 683 2.9 2.13 15.8 13.3 3.35 2.38 16.7 14 3.53 2.28 17.1 14.3 4.13 2.43 18.4 15.3
8,0 496 16.2 513 2.28 1.75 15 13.1 2.6 1.94 15.8 13.8 2.75 1.9 16.1 14.1 3.2 2.0 17.4 15.1
342 8.3 342 1.59 1.34 13.6 12.9 1.8 1.45 14.5 13.6 1.9 1.47 14.4 13.9 2.2 1.5 16 14.9
532 18 684 2.48 1.99 16.4 14 2.77 2.26 17.2 14.9 2.95 2.11 17.8 15.2 3.55 2.27 19.1 16.2
9,0 418 11.9 513 1.9 1.67 15.4 13.9 2.23 1.86 16.3 14.6 2.32 1.79 16.7 15 2.75 1.89 18 16
300 6.4 343 1.35 1.27 14.2 13.7 1.55 1.39 15 14.4 1.65 1.39 15.1 14.7 1.96 1.47 16.4 15.7
Pf: total cooling capacity Tal: in flow air temperature dpw: pressure drop standard coil
Twi: inflow fluid temperature Qw: fluid flow rate in heat exchanger Qa: air flow
Pfs: sensible cooling capacity Tad: discharge air dry temperature Taw: discharge air wet temperature
PDW(H)-15-VW/PW
TAI DB25ć-WB17.8ć TAI DB27ć-WB19ć TAI DB27ć-WB19.5ć TAI DB29ć-WB21.1ć
Twi Qw dpw Qa Pf Pfs Tad Taw Pf Pfs Tad Taw Pf Pfs Tad Taw Pf Pfs Tad Taw
θćι θ1/hιθkPaι θm3/h θkWιθkWιθćι θćιθkWιθkWι θćι θćιθkWι θkWιθćι θćιθkWιθkWι θćι θćι
1081 14.6 850 5.1 3.32 13.6 11.3 5.75 3.78 14 11.9 6.0 3.65 14.4 12.2 6.75 3.75 16 13.3
5,0 815 8.8 623 3.9 2.76 12.3 11.1 4.31 3.0 12.9 11.7 4.52 2.99 13 12 5.18 3.14 14.4 13
560 4.5 421 2.73 2.08 11 10.9 3.01 2.25 11.5 11.5 3.1 2.19 11.9 11.9 3.58 2.34 12.9 12.8
946 11.5 850 4.53 3.2 14 12.1 5.09 3.54 14.8 12.8 5.25 3.41 15.2 13.2 6.04 3.62 16.4 14.2
6,0 726 7.15 632 3.46 2.64 12.8 11.9 3.89 2.91 13.5 12.6 4.03 2.78 14.1 13 4.6 2.91 15.4 14.0
505 3.71 426 2.43 1.96 11.7 11.7 2.71 2.14 12.4 12.4 2.8 2.06 12.9 12.8 3.2 2.2 13.9 13.8
838 9.3 852 3.86 2.96 14.8 13 4.4 3.32 15.5 13.7 4.65 3.3 15.6 14 5.41 3.45 17 15
7,0 642 5.7 630 2.97 2.41 13.8 12.8 3.38 2.68 14.5 13.5 3.56 2.66 14.6 13.8 4.13 2.82 15.8 14.8
442 2.9 426 2.1 1.83 12.6 12.6 2.39 2.02 13.3 13.3 2.45 1.94 13.7 13.7 2.91 2.11 14.6 14.6
708 6.84 850 3.25 2.75 15.5 13.8 3.78 3.14 16.1 14.5 3.93 3.02 16.5 14.9 4.6 3.22 17.8 16
8,0 543 4.23 625 2.52 2.28 14.4 13.6 2.92 2.57 15 14.3 3.01 2.48 15.3 14.7 3.52 2.59 16.8 15.8
384 2.27 426 1.8 1.71 13.4 13.4 2.05 1.87 14.1 14.1 2.13 1.81 14.5 14.5 2.5 1.96 15.6 15.6
593 4.97 854 2.54 2.48 16.4 14.7 3.14 2.97 16.7 15.3 3.29 2.85 15.7 15.7 3.85 3.08 18.3 16.9
9,0 461 3.2 632 2.0 1.95 15.9 14.5 2.45 2.42 15.7 15.1 2.56 2.33 15.5 15.5 2.96 2.44 17.5 16.7
325 1.68 434 1.46 1.42 15.4 14.3 1.76 1.72 15.3 14.9 1.8 1.71 15.4 15.4 2.15 1.85 16.5 16.5
Pf: total cooling capacity Tal: in flow air temperature dpw: pressure drop standard coil
Twi: inflow fluid temperature Qw: fluid flow rate in heat exchanger Qa: air flow
Pfs: sensible cooling capacity Tad: discharge air dry temperature Taw: discharge air wet temperature
7
HYDRONIC DUCTED FAN COIL
PDW(H)-18-VW/PW
TAI DB25ć-WB17.8ć TAI DB27ć-WB19ć TAI DB27ć-WB19.5ć TAI DB29ć-WB21.1ć
Twi Qw dpw Qa Pf Pfs Tad Taw Pf Pfs Tad Taw Pf Pfs Tad Taw Pf Pfs Tad Taw
θćι θ1/hιθkPaιθm3/hι θkWιθkWιθćι θćιθkWιθkWι θćι θćιθkWιθkWιθćι θćιθkWιθkWι θćι θćι
1265 19.4 1020 6.02 3.84 14 11.4 6.73 4.25 14.8 12.1 7.02 4.1 15.2 12.4 8.0 4.36 16.4 13.4
5,0 973 12.1 764 4.63 3.21 12.7 11.2 5.15 3.44 13.8 11.9 5.4 3.39 14 12.2 6.1 3.51 15.4 13.2
670 6.1 510 3.2 2.34 11.7 11 3.55 2.52 12.6 11.7 3.71 2.52 12.6 12.0 4.2 2.58 14.2 13
1103 15.2 1021 5.25 3.66 14.5 12.3 5.92 3.96 15.6 13 6.12 3.77 16.1 13.4 7.06 4.1 17.1 14.4
6,0 853 9.54 765 4.05 3.0 13.5 12.1 4.56 3.25 14.5 12.8 4.73 3.12 15 13.2 5.43 3.36 16 14.2
588 4.88 511 2.85 2.26 12.1 11.8 3.06 2.32 13.5 12.7 3.26 2.31 13.8 13 3.75 2.44 15 14
988 12.4 1022 4.53 3.3 15.5 13.1 5.2 3.75 16.2 13.8 5.48 3.63 16.5 14.1 6.31 3.86 17.8 15.2
7,0 753 7.64 765 3.52 2.81 14.2 12.9 4.01 3.11 15 13.6 4.18 3.02 15.4 14 4.86 3.23 16.5 15
521 3.9 511 2.46 2.07 13.2 12.7 2.8 2.31 13.8 13.4 2.89 2.21 14.3 13.8 3.35 2.36 15.4 14.8
838 9.3 1028 3.89 3.22 15.7 13.8 4.44 3.56 16.7 14.6 4.65 3.44 17.1 15 5.42 3.65 18.4 16.1
8,0 650 5.8 764 3.04 2.67 14.7 13.6 3.45 2.94 15.6 14.4 3.6 2.84 16 14.8 4.18 2.98 17.4 15.9
452 3.1 511 2.14 2.0 13.6 13.4 2.42 2.2 14.4 14.2 2.51 2.1 14.9 14.6 2.91 2.21 16.2 15.7
676 6.3 1025 2.95 2.87 16.7 14.8 3.57 3.38 17.2 15.5 3.75 3.21 17.7 15.9 4.8 3.54 18.7 16.7
9,0 532 4.1 765 2.35 2.3 16.1 14.6 2.81 2.76 16.3 15.3 2.95 2.64 16.8 15.7 3.75 2.89 17.8 16.5
375 2.2 513 1.67 1.63 15.6 14.4 2.0 2.05 15.3 15.1 2.08 1.98 15.6 15.5 2.6 2.06 17 16.3
Pf: total cooling capacity Tal: in flow air temperature dpw: pressure drop standard coil
Twi: inflow fluid temperature Qw: fluid flow rate in heat exchanger Qa: air flow
Pfs: sensible cooling capacity Tad: discharge air dry temperature Taw: discharge air wet temperature
PDW(H)-24-VW/PW
TAI DB25ć-WB17.8ć TAI DB27ć-WB19ć TAI DB27ć-WB19.5ć TAI DB29ć-WB21.1ć
Twi Qw dpw Qa Pf Pfs Tad Taw Pf Pfs Tad Taw Pf Pfs Tad Taw Pf Pfs Tad Taw
θćι θ1/hιθkPaιθm3/hι θkWιθkWιθćι θćιθkWιθkWι θćι θćιθkWιθkWιθćι θćιθkWιθkWι θćι θćι
1729 37.3 1361 8.25 4.93 14.4 11.2 9.17 5.37 15.4 11.9 9.59 5.27 15.6 12.2 11 5.57 16.9 13.1
5,0 1334 23.4 1023 6.36 4.05 13.4 11.0 7.1 4.41 14.4 11.7 7.4 4.36 14.5 12 8.45 4.57 15.8 12.9
912 11.8 682 4.37 3.07 11.9 10.8 4.85 3.27 13 11.5 5.06 3.22 13.2 11.8 5.8 3.45 14.2 12.7
1512 29.3 1361 7.22 4.64 15 12.1 8.12 5.03 16.1 12.8 8.39 4.93 16.3 13.2 9.78 5.24 17.6 14.1
6,0 1172 18.5 1022 5.6 3.84 14 11.9 6.28 4.17 15 12.6 6.5 4.1 15.2 13 7.45 4.32 16.5 14
815 9.6 681 3.85 2.85 12.8 11.7 4.32 3.15 13.5 12.4 4.52 3.12 13.6 12.7 5.25 3.3 14.8 13.6
1314 22.8 1362 6.28 4.35 15.6 12.9 7.04 4.75 16.7 13.7 7.29 4.69 16.8 14.1 8.52 4.95 18.2 15.1
7,0 1024 14.5 1024 4.9 3.63 14.6 12.7 5.46 3.91 15.7 13.5 5.68 3.82 16 13.9 6.58 4.06 17.2 14.9
717 7.6 682 3.4 2.7 13.4 12.5 3.84 2.98 14.2 13.2 3.98 2.88 14.6 13.6 4.68 3.11 15.6 14.5
1132 17.4 1361 5.31 4.16 16 13.7 6.05 4.52 17.2 14.5 6.28 4.36 17.5 14.9 7.33 4.62 18.9 16
8,0 885 11.2 1022 4.16 3.4 15.2 13.5 4.72 3.74 16.2 14.3 4.91 3.63 16.5 14.7 5.7 3.78 18 15.8
616 5.8 684 2.91 2.56 14 13.3 3.3 2.8 15 14.1 3.42 2.74 15.2 14.5 4.01 2.88 16.5 15.5
944 12.6 1361 4.32 3.83 16.7 14.5 5.02 4.32 17.6 15.3 5.24 4.12 18 15.7 6.12 4.38 19.4 16.9
9,0 746 8.2 1023 3.43 3.23 15.7 14.3 3.96 3.56 16.7 15.1 4.14 3.42 17.1 15.5 4.9 3.64 18.4 16.6
521 4.3 681 2.42 2.35 14.9 14.1 2.78 2.64 15.6 14.9 2.89 2.56 15.9 15.3 3.48 2.79 16.9 16.3
Pf: total cooling capacity Tal: in flow air temperature dpw: pressure drop standard coil
Twi: inflow fluid temperature Qw: fluid flow rate in heat exchanger Qa: air flow
Pfs: sensible cooling capacity Tad: discharge air dry temperature Taw: discharge air wet temperature
8
HYDRONIC DUCTED FAN COIL
PDW(H)-30-VW/PW
TAI DB25ć-WB17.8ć TAI DB27ć-WB19ć TAI DB27ć-WB19.5ć TAI DB29ć-WB21.1ć
Twi Qw dpw Qa Pf Pfs Tad Taw Pf Pfs Tad Taw Pf Pfs Tad Taw Pf Pfs Tad Taw
θćι θ1/hιθkPaιθm3/hιθkWι θkWιθćι θćι θkWιθkWι θćι θćι θkWι θkWιθćι θćι θkWι θkWι θćι θćι
2105 34.2 1700 10.18 6.16 14.4 11.3 11.32 6.65 15.5 12 11.68 6.41 15.9 12.4 13.3 6.67 17.4 13.4
5,0 1622 21.4 1276 7.82 5.05 13.4 11.1 8.72 5.52 14.3 11.8 9.0 5.26 14.9 12.2 10.3 5.61 16 13.1
1110 10.8 850 5.4 3.87 11.8 10.9 6.0 4.16 12.8 11.6 6.16 3.93 13.5 12 7.1 4.28 14.3 12.9
1865 27.5 1703 8.89 5.8 15 12.2 10.0 6.35 16 12.9 10.35 6.05 16.5 13.3 11.9 6.36 17.9 14.3
6,0 1442 17.3 1276 6.86 4.82 13.9 12 7.73 5.21 15 12.7 8.0 4.99 15.5 13.1 9.16 5.25 16.8 14.1
991 8.82 851 4.75 3.6 12.7 11.8 5.32 3.9 13.6 12.5 5.5 3.75 14.1 12.9 6.4 4.04 15.1 13.8
1644 21.9 1703 7.7 5.44 15.6 13 8.8 6.0 16.6 13.7 9.12 5.75 17 14.1 10.65 6.19 18.2 15.1
7,0 1272 13.8 1273 5.99 4.51 14.6 12.8 6.8 4.96 15.5 13.5 7.06 4.75 16 13.9 8.2 5.06 17.2 14.9
883 7.2 854 4.16 3.41 13.3 12.6 4.72 3.78 14 13.3 4.9 3.57 14.7 13.7 5.68 3.82 15.8 14.7
1388 16.2 1703 6.48 5.13 16.1 13.8 7.4 5.7 17.1 14.6 7.7 5.46 17.5 15 9.16 5.83 18.8 16
8,0 1083 10.3 1275 5.08 4.24 15.2 13.6 5.77 4.7 16.1 14.4 6.01 4.48 16.6 14.8 7.11 4.8 17.8 15.8
757 5.43 856 3.56 3.23 13.9 13.4 4.02 3.47 15 14.2 4.2 3.43 15.2 14.6 4.94 3.64 16.4 15.6
1153 11.6 1705 5.24 4.9 16.5 14.6 6.1 5.27 17.8 15.4 6.4 5.1 18.1 15.8 7.63 5.47 19.4 16.9
9,0 908 7.53 1276 4.15 4.06 15.6 14.4 4.81 4.39 16.8 15.2 5.04 4.22 17.2 15.6 5.98 4.54 18.4 16.7
638 3.99 854 2.95 2.88 15.1 14.2 3.4 3.31 15.6 15 3.54 3.15 16.1 15.4 4.18 3.4 17.2 16.5
Pf: total cooling capacity Tal: in flow air temperature dpw: pressure drop standard coil
Twi: inflow fluid temperature Qw: fluid flow rate in heat exchanger Qa: air flow
Pfs: sensible cooling capacity Tad: discharge air dry temperature Taw: discharge air wet temperature
PDW(H)-40-VW/PW
TAI DB25ć-WB17.8ć TAI DB27ć-WB19ć TAI DB27ć-WB19.5ć TAI DB29ć-WB21.1ć
Twi Qw dpw Qa Pf Pfs Tad Taw Pf Pfs Tad Taw Pf Pfs Tad Taw Pf Pfs Tad Taw
θćι θ1/hιθkPaιθm3/hιθkWι θkWιθćι θćι θkWιθkWι θćι θćι θkWι θkWιθćι θćιθkWιθkWι θćι θćι
2748 47.5 2039 13.22 8.04 13.5 10.7 14.65 8.78 14.4 11.4 15.25 8.55 14.7 11.7 17.6 9 16 12.5
5,0 2114 29.6 1530 10.19 6.63 12.4 10.5 11.4 7.24 13.2 11.1 11.73 7.07 13.5 11.5 12.5 7.51 14.6 12.3
1460 15.2 1020 7.0 5.02 10.8 10.3 7.84 5.18 11.5 10.9 8.1 5.33 11.8 11.2 9.31 5.74 12.6 12
2498 39.9 2042 11.7 7.6 14.1 11.6 13.25 8.34 15 12.2 13.86 8.05 15.4 12.5 16 8.58 16.6 13.4
6,0 1925 25 1530 9.05 6.25 13.1 11.4 10.22 6.85 13.9 12.0 10.68 6.68 14.2 12.3 12.3 7.14 15.3 13.2
1321 12.7 1022 6.22 4.68 11.7 11.2 7.01 5.19 12.2 11.8 7.33 5.05 12.6 12.1 8.5 5.4 13.5 12.9
2172 31 2041 10.3 7.16 14.7 12.4 11.65 7.83 15.7 13.1 12.05 7.61 16 13.5 14.1 8.13 17.2 14.4
7,0 1683 19.7 1532 8.0 5.91 13.7 12.2 9.03 6.47 14.6 12.9 9.34 6.31 14.9 13.3 10.9 6.75 16 14.2
1173 10.2 1020 5.53 4.42 12.4 12.0 6.21 4.9 13 12.7 6.51 4.75 13.4 13.0 7.6 5.1 14.4 13.9
1903 24.5 2040 8.9 6.75 15.3 13.2 10 7.47 16.2 14 10.56 7.18 16.6 14.3 12.4 7.64 17.9 15.3
8,0 1481 15.6 1531 6.94 5.54 14.4 13 7.8 6.1 15.3 13.8 8.22 5.92 15.6 14.1 9.59 6.36 16.7 15.1
1024 8.03 1021 4.72 4.16 13.1 12.9 5.4 4.58 13.9 13.6 5.68 4.46 14.2 13.9 6.7 4.82 15.1 14.8
1595 17.7 2043 7.23 6.38 15.8 14.1 8.48 6.96 16.9 14.8 8.85 6.75 17.2 15.2 10.4 7.21 18.5 16.3
9,0 1250 11.5 1531 5.7 5.21 15 13.9 6.52 5.77 15.9 14.7 6.93 5.54 16.3 15 8.1 5.93 17.5 16.1
872 6.02 1024 4.0 3.84 14 13.7 4.56 4.26 14.8 14.5 4.84 4.14 15.1 14.8 5.72 4.5 16 15.8
Pf: total cooling capacity Tal: in flow air temperature dpw: pressure drop standard coil
Twi: inflow fluid temperature Qw: fluid flow rate in heat exchanger Qa: air flow
Pfs: sensible cooling capacity Tad: discharge air dry temperature Taw: discharge air wet temperature
9
HYDRONIC DUCTED FAN COIL
PDW(H)-44-VW/PW
TAI DB25ć-WB17.8ć TAI DB27ć-WB19ć TAI DB27ć-WB19.5ć TAI DB29ć-WB21.1ć
Twi Qw dpw Qa Pf Pfs Tad Taw Pf Pfs Tad Taw Pf Pfs Tad Taw Pf Pfs Tad Taw
θćι θ1/hιθkPaιθm3/hιθkWι θkWιθćι θćιθkWιθkWι θćι θćι θkWι θkWιθćι θćι θkWι θkWι θćι θćι
2984 36.3 2380 14.42 8.53 14.5 11.2 16.05 9.39 15.4 11.9 16.56 9.14 15.7 12.3 18.75 9.66 17 13.2
5,0 2292 22.6 1780 11.11 7.14 13.3 11.0 12.35 7.79 14.2 11.7 12.72 7.59 14.5 12.1 14.58 8.07 15.7 13.0
1595 11.8 1191 7.65 5.46 11.7 10.8 8.59 5.94 12.5 11.4 8.85 5.8 12.8 11.8 10.1 6.2 13.8 12.6
2650 29.3 2383 12.63 8.11 15 12.1 14.2 8.89 16 12.8 14.7 8.64 16.3 13.2 16.85 9.17 17.6 14.1
6,0 2044 18.4 1784 9.78 6.71 14 11.9 10.97 7.35 14.9 12.6 11.34 7.16 15.2 13.0 12.93 7.66 16.3 13.9
1426 9.6 1191 6.75 5.15 12.4 11.7 7.55 5.5 13.5 12.4 7.91 5.46 13.6 12.7 9.0 5.88 14.5 13.6
2343 23.5 2387 11.0 7.62 15.6 12.9 12.3 8.47 16.5 13.7 13.0 8.15 16.9 14 14.82 8.65 18.2 15
7,0 1811 14.8 1783 8.55 6.33 14.6 12.7 9.56 6.98 15.5 13.5 10.05 6.77 15.8 13.8 11.48 7.24 17 14.8
1254 7.6 1193 5.94 4.82 13.2 12.5 6.71 5.28 14 13.2 6.96 5.16 14.3 13.6 8.03 5.47 15.5 14.5
1986 17.5 2389 9.28 7.2 16.1 13.7 10.56 7.88 17.2 14.5 11.02 7.57 17.6 14.9 12.78 8.16 18.8 15.9
8,0 1546 11.1 1785 7.13 5.95 15.2 13.6 8.25 6.53 16.2 14.3 8.58 6.28 16.6 14.7 9.93 6.86 17.6 15.7
1076 5.8 1193 5.1 4.49 14 13.3 5.74 4.95 14.8 18.1 5.97 4.83 15.1 14.5 6.99 5.21 16.1 15.4
1654 12.6 2384 7.56 6.78 16.6 14.5 8.77 7.55 17.6 15.3 9.18 7.14 18.1 15.7 10.65 7.74 19.3 16.8
9,0 1303 8.2 1787 6.0 5.58 15.8 14.3 6.91 6.21 16.7 15.1 7.23 5.97 17.1 15.5 8.35 6.42 18.3 16.6
912 4.3 1193 4.22 4.14 14.8 14.1 4.85 4.7 15.4 14.9 5.06 4.44 16 15.3 5.94 4.91 16.8 16.3
Pf: total cooling capacity Tal: in flow air temperature dpw: pressure drop standard coil
Twi: inflow fluid temperature Qw: fluid flow rate in heat exchanger Qa: air flow
Pfs: sensible cooling capacity Tad: discharge air dry temperature Taw: discharge air wet temperature
PDW(H)-50-VW/PW
TAI DB25ć-WB17.8ć TAI DB27ć-WB19ć TAI DB27ć-WB19.5ć TAI DB29ć-WB21.1ć
Twi Qw dpw Qa Pf Pfs Tad Taw Pf Pfs Tad Taw Pf Pfs Tad Taw Pf Pfs Tad Taw
θćι θ1/hιθkPaιθm3/hι θkWιθkWιθćι θćι θkWιθkWι θćι θćιθkWι θkWι θćι θćιθkWιθkWι θćι θćι
3352 45.8 3008 15.9 11.7 13.6 12.1 17.9 12.6 14.6 12.8 18.6 12.3 15 13.2 22.2 12.8 16.4 13.9
5,0 2865 34.6 2500 13.7 10.3 13 11.9 15.6 11.1 14 12.5 15.9 10.9 14.2 13 19.2 11.3 15.7 13.6
2450 26.1 2070 11.8 9.01 12.4 11.7 13.3 9.77 13.2 12.3 13.6 9.65 13.4 12.8 16.6 10 14.9 13.3
3050 38.6 3000 14.1 11.0 14.2 12.8 16.4 12 15.3 13.4 16.9 11.6 15.6 13.8 20.2 12.2 17 14.6
6,0 2631 29.8 2505 12.5 9.71 13.7 12.5 14.3 10.4 14.8 13.1 14.6 10.3 14.9 13.6 17.6 10.8 16.3 14.3
2250 22.4 2078 10.9 8.4 13.2 12.2 12.4 9.2 14 12.8 12.5 9.07 14.2 13.4 15.2 9.47 15.6 14
2700 31.3 3003 13 10.2 15 13.2 14.7 11.2 16 14 15 10.98 16.2 14.5 18.2 11.3 17.8 15.3
7,0 2350 24.1 2507 11.4 9.0 14.5 13.0 12.7 9.93 15.3 13.8 13 9.7 15.6 14.3 15.9 10.1 17.1 15.0
2020 18.3 2080 9.8 7.9 13.9 12.8 11.2 8.6 14.9 13.5 11.2 8.5 15 14.1 13.8 8.85 16.4 14.7
2310 23.3 3020 10.9 9.6 15.6 14 12.5 10.6 16.6 14.8 12.8 13 16.9 15.3 16.2 10.5 18.6 16
8,0 2000 18.2 2504 9.55 8.43 15.1 13.8 10.9 9.26 16.1 14.6 11.1 9.16 16.2 15.1 14.2 9.3 18 15.7
1750 14.3 2090 8.5 7.37 14.6 13.5 9.4 8.24 15.3 14.4 9.7 8.11 15.6 14.9 12.4 8.2 17.3 15.4
1980 18.0 3007 9.0 8.8 16.4 14.7 10.8 9.85 17.3 15.4 11 9.73 17.4 15.9 14.4 9.7 19.4 16.6
9,0 1750 14.3 2516 8.0 7.8 15.9 14.5 9.5 8.84 16.6 15.2 9.7 8.6 16.9 15.7 12.8 8.52 18.9 16.3
1515 11.1 2074 7.0 6.87 15.3 14.3 8.3 7.64 16.2 15 8.4 7.51 16.3 15.5 11.2 7.5 18.3 16
Pf: total cooling capacity Tal: in flow air temperature dpw: pressure drop standard coil
Twi: inflow fluid temperature Qw: fluid flow rate in heat exchanger Qa: air flow
Pfs: sensible cooling capacity Tad: discharge air dry temperature Taw: discharge air wet temperature
10
HYDRONIC DUCTED FAN COIL
PDW(H)-66-VW/PW
TAI DB25ć-WB17.8ć TAI DB27ć-WB19ć TAI DB27ć-WB19.5ć TAI DB29ć-WB21.1ć
Twi Qw dpw Qa Pf Pfs Tad Taw Pf Pfs Tad Taw Pf Pfs Tad Taw Pf Pfs Tad Taw
θćι θ1/hιθkPaιθm3/hι θkWιθkWιθćι θćιθkWιθkWι θćι θćιθkWι θkWι θćι θćιθkWιθkWι θćι θćι
4578 16.1 4000 22 14.7 14.3 11.9 24.6 15.9 15.3 12.6 25.4 15.3 15.7 13 29.5 16.3 17.1 14
5,0 3910 12.1 3320 18.9 13.0 13.6 11.7 21 14.2 14.5 12.4 21.7 13.8 14.8 12.8 24.9 14.7 16 13.8
3334 9.1 2753 16.2 11.3 13.1 11.5 17.9 12.4 13.8 12.2 18.5 12.0 14.2 12.6 21.3 12.7 15.5 13.6
4073 13.1 4011 19.6 13.8 14.9 12.6 21.8 15.1 15.9 13.4 22.6 14.5 16.3 13.8 26 15.5 17.6 14.9
6,0 3425 9.5 3315 16.3 12.3 14.2 12.6 18.3 13.4 15.1 13.3 19 12.9 15.5 13.7 22.1 13.7 16.8 14.7
2956 7.3 2772 14.1 10.8 13.7 12.4 15.9 11.7 14.6 13.1 16.4 11.3 15 13.5 19 12.1 16.2 14.5
3478 10 4017 16.5 13.1 15.5 13.5 18.5 14.4 16.4 14.3 19.3 13.7 16.9 14.7 22.4 14.6 18.2 15.8
7,0 3010 7.5 3340 14.2 11.6 14.8 13.3 16 12.8 15.7 14.1 16.7 12.2 16.2 14.5 19.3 13.1 17.4 15.6
2595 5.8 2780 12.1 10.1 14.3 13.2 13.6 11.1 15.2 14 14.4 10.6 15.7 14.3 16.6 11.4 16.8 15.4
2920 7.2 4004 13.6 12.4 16 14.3 15.5 13.5 17 15.1 16.2 12.9 17.4 15.5 18.8 13.9 18.7 16.7
8,0 2560 5.6 3350 11.8 11.0 15.3 14.1 13.6 12 16.4 14.9 14.2 11.54 16.8 15.3 16.3 12.4 17.9 16.5
2235 4.5 2798 10.4 9.5 15 13.9 11.8 10.4 15.9 14.7 12.4 10.1 16.3 15.1 14.2 10.9 17.4 16.3
2306 4.7 4042 10.9 10.6 17.2 15 12.2 11.9 18.3 16 12.8 12.2 18 16.4 15.5 12.7 19.5 17.5
9,0 2018 3.7 3330 9.7 9.4 16.7 14.8 10.7 10.5 17.7 15.8 11.2 10.8 17.4 16.2 14 11.1 19.1 17.2
1785 2.9 2780 8.6 8.33 16.2 14.6 9.5 9.3 17.2 15.6 9.9 9.4 17 16 12.2 9.7 18.6 17.0
Pf: total cooling capacity Tal: in flow air temperature dpw: pressure drop standard coil
Twi: inflow fluid temperature Qw: fluid flow rate in heat exchanger Qa: air flow
Pfs: sensible cooling capacity Tad: discharge air dry temperature Taw: discharge air wet temperature
PDW(H)-12-VW
TAI 18ć TAI 20ć TAI 22ć TAI 24ć
PDW(H)-15-VW
TAI 18ć TAI 20ć TAI 22ć TAI 24ć
PDW(H)-18-VW
TAI 18ć TAI 20ć TAI 22ć TAI 24ć
PDW(H)-24-VW
TAI 18ć TAI 20ć TAI 22ć TAI 24ć
PDW(H)-30-VW
TAI 18ć TAI 20ć TAI 22ć TAI 24ć
PDW(H)-40-VW
TAI 18ć TAI 20ć TAI 22ć TAI 24ć
PDW(H)-44-VW
TAI 18ć TAI 20ć TAI 22ć TAI 24ć
PDW(H)-50-VW
TAI 18ć TAI 20ć TAI 22ć TAI 24ć
PDW(H)-66-VW
TAI 18ć TAI 20ć TAI 22ć TAI 24ć
PDW(H)-12-PW
TAI 18ć TAI 20ć TAI 22ć TAI 24ć
PDW(H)-15-PW
TAI 18ć TAI 20ć TAI 22ć TAI 24ć
PDW(H)-18-PW
TAI 18ć TAI 20ć TAI 22ć TAI 24ć
PDW(H)-24-PW
TAI 18ć TAI 20ć TAI 22ć TAI 24ć
PDW(H)-30-PW
TAI 18ć TAI 20ć TAI 22ć TAI 24ć
F PDW(H)-40-PW
TAI 18ć TAI 20ć TAI 22ć TAI 24ć
PDW(H)-44-PW
TAI 18ć TAI 20ć TAI 22ć TAI 24ć
PDW(H)-50-PW
TAI 18ć TAI 20ć TAI 22ć TAI 24ć
PDW(H)-66-PW
TAI 18ć TAI 20ć TAI 22ć TAI 24ć
PDW(H)-18-VW/PW
TAI DB25к-WB17.8к TAI DB27к-WB19к
By applying the correction factors as multipliers to the Cooling/Heating load, the loads can be
adjusted to reveal the equivalent 100% water/sea level capacity. These adjusted capacities are
used with the tables to determine unit size, entering water temperature (if not fixed) and the
required flow rate.
With the previous example information given, the calculation would look as follows:
On the sample table of Performance Data (cooling capacity) with 27qC DB / 50% R.H., locate the
capacities within the 7qC entering water that meet or exceed the corrected capacities. By
following the row to the left, we find a flow rate of 0.70 m3/min (based on high fan speed). This is
the required flow rate.
22
HYDRONIC DUCTED FAN COIL
With the flow rate now specified at 0.70 m3/min, we can find the pressure drop through the coil to
assist in pump sizing. The pressure drop can be found on the same table. The model PDW-18
with 0.70 m3/min shows us a pressure drop of 22.9 KPa. This is adjusted for the propylene glycol
solution by using the correction factor as a multiplier. The formula would look as follows:
UNIT PERFORMANCE
By applying the correction factors as divisors to the capacities in the tables, the performance of
existing equipment can be determined.
Entering air and water conditions along with elevation and percentage/type of glycol solution is
still required. The basic formula for total and sensible capacity usage appears below.
ADDITIONAL NOTES
The tables are arranged in some of the more common DB / RH combinations found in
specifications. Interpolation between columns is allowed.
The sensible capacities and leaving dry bulb temperatures are based upon the entering dry bulb.
Total capacities and leaving wet bulb temperatures are based upon entering wet bulb. It is
acceptable to mix entering DB / RH columns as long as entering values are constant.
ALTITUDE CORRECTION
Elevation TH SH
300 m 1.010 1.042
600 m 1.020 1.075
900 m 1.031 1.111
1200 m 1.042 1.163
1500 m 1.064 1.205
1800 m 1.087 1.250
Case
Coil
Filter
Drain pan
Control box
1) LOCATION
Before installation and running the unit, please check the following:
i. There must be enough space for the unit installation and maintenance. Please
refer to Figure 1 for the unit's outlines and dimensions and Figure 2 for the minimum
distance between the unit and the obstacle.
ii. Please ensure enough space for piping connection and electrical wiring.
iii. Check whether the hanging rods can support weight of the unit (see specification
table for weight of the unit).
iv. The unit must be installed horizontally to ensure proper operation and condensate
draining.
v. The external static pressure of the ducting must be within the design static pressure
range.
vi. Confirm that the unit has been switched OFF before installing or servicing the unit.
2) UNIT INSTALLATION
i. The unit is designed to be installed in a concealed ceiling. Installation and
maintenance should be performed by qualified persons who are familiar with local
codes and regulations, and experienced with this type of appliance.
ii. Please refer to picture below illustrates the installation procedure.
Caution:
Make sure the top of the unit is level after installation. The drain pan is designed with a
little gradient to facilitate drainage.
25
HYDRONIC DUCTED FAN COIL
3) DIMENSIONS (2-PIPE SYSTEM)
1. Ducted unit 2. Two ways intake plenum 3. Intake plenum 4. Air purification module
5. Activated carbon filter 6. Electric heater module 7. Auxiliary heating coil module
8. Discharge plenum 9. Discharge plenum for round ducting
Model A B, C D E, F H G I ӽ N
PDW(H)-12/15/18 825 675 460 180 260 230 725 130 3
PDW(H)-24/30 1050 900 510 240 315 290 950 190 3
PDW(H)-40/44 1250 1100 580 240 315 290 1150 190 4
PDW(H)-50/66 1400 1250 710 325 400 375 1300 200 4
27
HYDRONIC DUCTED FAN COIL
Filter
Return grille
Inspection Manhole
4) PIPE CONNECTIONS
Make sure the diameter of the water pipes is adequate for the actual length of the piping and in any case not less than the
diameter of the connection on the unit. When connecting the water pipes to the coil, take care not to damage the coil manifold.
During this operation, hold the coil connections firm with a spanner to avoid damaging them.
The fittings are located on the back of the unit looking at the air outlets.
IMPORTANT
Gravity drainage may be converted into forced drainage by fitting the condensate drain pump available as an accessory.
28
HYDRONIC DUCTED FAN COIL
5) How to interchange Left / Right hand connection:
1st step: Loosen the six screws on the bottom panel #1 which is underneath the fan assembly. Then take off
the bottom panel #1.
Bottom panel #1
2nd step: Loosen another six screws on the bottom panel #2 which is underneath the drain pan. Then take
off the bottom panel #2.
Bottom panel #1
Bottom panel #2
29
HYDRONIC DUCTED FAN COIL
3rd step: Loosen two screws on the external drain pan. Then take off the external drain pan
4th step: Loosen the 4 screws from the both side and 4 screws on the drain pan. Then take off the drain pan.
5th step: Loosen the 2 screws on coil’s back cover and take it off.
7th step: Interchange the coil direction to left piping connection and install it properly with 4 screws on both
sides.
8th step: Install the coil’s back cover, drain pan, bottom panels and external drain pan to the unit with
screws.
31
HYDRONIC DUCTED FAN COIL
6) Valve Installation
Piping for 2-Pipe System
Drain Pipe
Note:
Electrical heater and 4-pipe system cannot be applied at the same time.
Stepping motor is not applied to PDW(H).
Warning:
Switch shall be connected to the supply terminals and shall have a contact
separation of at least 3 mm in each pole.
Confirm that the unit has been switched OFF before installing or servicing the unit.
37
HYDRONIC DUCTED FAN COIL
MASTER SLAVE CONTROL WIRING DIAGRAM
38
HYDRONIC DUCTED FAN COIL
HOST COMPUTER CONTROL WIRING DIAGRAM
39
HYDRONIC DUCTED FAN COIL
MAINTENANCE
GENERAL
1. Installation and maintenance should be performed by qualified persons who are familiar with
local codes and regulations, and experienced with this type of appliance.
2. Confirm that the unit has been switched OFF before installing or servicing the unit.
3. A good general maintenance plan will avoid losses and unexpected shutting down of the
equipment.
4. Dirty filters reduce air flow as well as unit performance. Thus changing or cleaning the filters
is very important. Check the cleanliness of filter and replace or clean as required monthly.
5. Coils should be cleaned from dust, dirt or lint with compressed air or water. They can be
brushed with a soft brush and vacuum cleaner.
6. Water coil not used during winter season should be drained, or anti-freezing solution should
be added to the water circuit to avoid freezing.
7. Monthly:
a. Inspect and clean condensate drain pan to avoiding clogging of drainage by dirt, dust, etc.
Inspect drainage piping to ensure the proper condensate flow.
b. Check and clean the coil. Clean the coils with low pressure water jet or low pressure air.
c. Clean and tighten all the wiring connections.
d. Drain out the system water and check for build up of mineral deposits.
AIR PURGING
1. After connecting the water inlet and outlet pipes to the main supply lines, turn on the main
breaker and operate the unit.
2. Open the water inlet valve and flood the coil.
3. Check all connections for water leakage, if no leak is found open the air vent valve with an
open end wrench. Then purge the air trapped inside the coil. When performing this, take care
not to touch the electrical parts.
4. Close the air vent valve when no bubbles appear.
5. Open the water outlet valve.
Bottom Panel #1
Control Specification
" Start/Stop: Press ” ” one time to turn on the thermostat and press again to turn it off;
" Temperature Setting: Press ”” to decrease the set temperature while pressing ”” to increase it. Each
press means 1к changed;
" Cool Mode: Press “M” to change the current mode. Stop when “ ” flashes, system will confirm it automatically in
5 seconds;
" Heat Mode: Press “M” to change the current mode. Stop when “ ” flashes, system will confirm it automatically in 5
seconds;
" Ventilation Mode: Press “M” to change the current mode. Stop when “ ” flashes, system will confirm it
automatically in 5 seconds. Fan runs at set speed;
" Speed Mode: Press “ ” to select fan speed “ ΰHiα, ΰMidα, ΰLowα or ΰAutoα;
In Auto Mode, the fan will change its speed automatically, it runs at low speed when the room temperature and set
temperature difference are between 1к- 3к; it runs at high speed, when the temperature difference is higher than 3к; when
there is no temperature difference, DA model will close the motorized valve with fan running at low speed and DB model
will close the motorized valve and the fan as well.
" Sleep Setting: press “¥” to change different time mode, stop when “ ” flashes, press “” to confirm the setting or
press “” to disable it;
43
HYDRONIC DUCTED FAN COIL
" Clock setting: Press “¥” to change different time mode, stop when “hh:mm” displays with “hh” flashing, press “”
or “” to adjust Hour and press “¥” again so that “mm” in “hh:mm” flashes, press “” or “” to adjust Minute, and
finally press “¥” to confirm the setting;
" Timer–on Setting: Press “¥” to change different time mode, stop when “¥” and “TIMER ON” flash, together with
“hh” in “hh:mm” flashing, press “” or “” to adjust Timer-on Hours, press “¥” again so that “mm” in “hh:mm” flashes,
then press “” or “” to adjust Timer-off Minute, and finally press “¥” to confirm the setting;
" Timer-off Setting: Press “¥” to change different time mode, stop when “¥” and “TIMER OFF” flash, together with
“hh” inϘhh:mmϙ flashing, press “” or “” to adjust Timer-off Hour, press “¥” again so that “mm” in “hh:mm”
flashes, then press “” or “” to adjust Timer-off Minute, and finally press “¥” to confirm the setting;
" Cancellation of Timer-on: Press “¥” to change different time mode, stop when “¥” and “TIMER ONϙ flashes,
together with “hh” in “hh:mm” flashing, press “” or “” to adjust Timer-on Hour to “00”, press “¥” again so that “mm”
in “hh:mm” flashes, then press “” or “” to adjust Timer-on Minute to “00” , and finally press “¥” to confirm the setting;
" Cancellation of Timer-off: Press “¥” to change different time mode, stop when “¥” and “TIMER OFF” flashes,
together with “hh” in “hh:mm” flashing, press “” or “” to adjust Timer-off Hour to “00”, press “¥” again so that “mm”
in “hh:mm” flashes, press “” or “” to adjust Timer-off Minute to “00”, and finally press “¥” to confirm the setting.
***When unit with handset is master, settings are automatically sent to slaves;
***Auto Cool-Heat operation will be applicable in 4-pipe system only.
***Swing and Louver are not applicable to PDW(H)-VW/PW models.
HYDRONIC DUCTED FAN COIL 46
***Wall pad will recognize the main board model automatically whether it is 2 pipes or 4 pipes. Auto Cool-Heat operation will be applicable in 4 pipe
system only.
***When the wall pad is connected to the main board, air sensor inside the wall pad will be automatically set as primary source and the return air
sensor from the unit will be disabled
HYDRONIC DUCTED FAN COIL 47
WALL PAD OPERATION
Real time clock display area indicates internal time clock which can be set by or 7,0( button.
display area shows , otherwise the on timer setting will be shown. Press or 7,0(
&$1&(/
button to change the on timer setting. Press key to cancel the current on timer selected
' $<
and the timer display area will show . Press button to change the day the on timer
is to be programmed.
7,0(5
b) Press button again, and OFF symbol blinking indicates off timer programming
mode. The setting method is the same as on timer setting above.
7,0(5
c) Press button again, to exit timer on/off setting function.
d) Should there be any on or off timer being programmed, will light up. Should there be any
unexecuted on or off timer for the current day, its corresponding ON or OFF icon will light up.
&$1&(/
e) Hold down button for 3 seconds to cancel all timer settings.
slave unit under control. Press 7,0( or to select the desired slave unit. Units that are
off will be skipped automatically.
7,0(5 '$ <
2. Press button once to enter into on timer programming mode. Press button to
select the required day of the week. Master unit will then retrieve the setting from the
selected slave unit and timer display area will show “rEAd”. The on timer setting will be
7,0(
shown upon reading the data successfully. Press or 7,0( button to change the on timer
setting.
48
HYDRONIC DUCTED FAN COIL
7,0(5 ' $<
3. Press button again to enter into off timer programming mode. Press button to
select the required day of the week. Master unit will then retrieve the setting from the
selected slave unit and timer display area will show “rEAd”. The off timer setting will be
7,0(
shown upon reading the data successfully. Press or 7,0( button to change the off
timer setting.
7,0(5
4. Upon completion of changing timer settings for the selected day, press button again
to exit timer programming mode. The settings will then upload to the selected slave unit. The
next day of the week settings can be done only upon completion of sending data to the slave
units. (Repeat steps 1~4 if setting is required for the next day of the week).
1. Press and 7,0( buttons for 3 seconds to activate clock synchronization to all slave
units. Master wall pad will respond with a beeping sound.
4) Key lock
In order to prevent unauthorized access to the system setting, a key lock function is provided to
prevent mischief. Hold down and for 3 seconds to activate key lock, symbol lights
up. Repeat the same to exit key lock. Only button is applicable in key lock mode.
5) Swing
*
Press 6:,1 to activate or deactivate swing function.
6) Sleep
6/((3
Press button to activate or deactivate sleep setting. Sleep is valid in cool or heat modes only.
7) Temperature setting
Press or to enter into temperature setting mode, temperature display area blinks indicating
the current set temperature. Press the above buttons to adjust the set temperature.
8) Mode setting
02'(
Press button to change the operation mode.
under control. Press 7,0( or to select the desired slave unit; Units that are off will be bypassed
automatically. Parameters that can be controlled are on/off, timer weekly program, set temperature,
1(7
mode, fan speed, swing and sleep. Parameter operation methods are the same as above. Press
button again to exit networking control mode.
1* )5(6+
Hold down 6:, and buttons for 3 seconds to enter into global control mode, lights up.
Repeat the same to exit global control mode. In global control mode, the settings of the master unit
will be broadcast to all the slave units.
Wall pad display temperature area Wall pad display time area
C0 Return air temperature displayed
C1 Indoor coil temperature displayed
C2 DIP switch setting displayed
C3 Indoor coil 2 temperature
&$1&(/
Press button to exit.
For system without master-slave settings, wall pad will indicate unit error codes as above.
50
HYDRONIC DUCTED FAN COIL
CONTROL SPECIFICATIONS
HOT AND CHILLED WATER CASSETTE
WITH MASTER-SLAVE CONTROL OR
WITH HOST COMPUTER CONTROL
Ts = Setting temperature
Tr = Room air temperature
Ti1 = Indoor coil temperature, ID1
Ti2 = Indoor coil temperature, ID2
MTV1 = Cool Motorized valve
MTV2 = Heat Motorized valve
The control PCB can be set either as a master unit or slave unit.
a) The master unit sends data on its setting to the slave unit.
b) The master unit settings are Unit ON/OFF, Mode, Fan Speed, Set Temperature, Swing Function, and
Sleep Function for handset operation.
c) The master unit settings are Unit ON/OFF, Mode, Fan Speed, Set Temperature, Swing Function, Sleep
Function and Weekly Timer ON/OFF program for wall pad operation.
a) The slave unit receives data on its settings from the master unit.
b) The slave unit is allowed to change to a locally desired setting by local controller as long as there are no
subsequent changes to the settings of the master unit.
c) The slave units can be set individually for timer on and off function by handset or wall pad. The handset
51
HYDRONIC DUCTED FAN COIL
cannot override wall pad timer and clock setting.
With MTV: The master unit will beep 3 times, and the slave unit will beep once.
Without MTV: The master unit will beep 4 times, and the slave unit will beep twice
a) Connect all the units PCBs according to the wire color and type of connector.
b) Select the master unit by closing the SW6 DIP switch on the main PCB
c) Ensure the SW6 DIP switch in the PCB of the slave unit is opened.
d) Switch on the units by connecting the main power supply.
e) Using handset set the operation parameters for the Master unit which will automatically send the
settings to the slave unit.
f) Master unit will beep twice confirming receipt of commands while Slave unit will beep once.
a) Connect all the units PCBs according to the wire color and type of connector.
b) Select the master unit by closing the SW6 DIP switch on the main PCB
c) Ensure the SW6 DIP switch in the PCB of the slave unit is opened.
d) Provide each slave unit an addressable code by closing SW1 – SW5 DIP switch according to the DIP
switch chart.
e) Switch on the units by connecting the main power supply.
f) Using the wall pad set the operation parameters for the Master unit which will send the setting to the
slave units based on Global-control communication or Addressable communication methods. For detail
please see 2.A.6 MASTER-SLAVE COMMUNICATION METHOD & Wall pad operation item 11
Networking Master – Slave control on page 49.
g) Master unit will beep twice confirming receipt of commands while Slave unit will beep once.
Important note: Please use RJ-11-6P-4C cable for setting up the Master-Slave network. (Picture of cable
please refer to Appendix I type A)
Master unit: close SW6 [DIP switch] before power on. Master will beep twice to the LCD wireless
handset or LCD wall pad confirming receipt of commands. Each master can command up to 31 slave
units.
Slave unit: open SW6 [DIP switch] before power on. Slave unit will beep once to the LCD wireless
handset or LCD wall pad confirming receipt of commands.
Above control PCB can receive data from both wireless LCD handset and wired wall pad. Once wall pad
is connected to the PCB, receiver from the unit will stop receiving signal from wireless LCD handset.
LCD handset can only provide signal to Wall Pad receiver. When wall pad is disconnected from the PCB
for 5 seconds, it will revert to wireless LCD handset reception automatically.
Addressable communication
Master controller must be LCD wall pad. Slave unit parameters are set as usual. Upon receiving the
control commands from a master, the addressed slave unit settings will be replaced by the master settings.
A number of master units can be grouped together via data logger [router] to form a bigger network [1 up
to 64 data loggers]. The maximum network size is 64 data loggers x 32 fan coils = 2048 fan coils
connected to a computer based control system. Host computer can monitor and control every single unit;
on/off, mode, set temperature, swing, sleep and fan speed and 365 days timer on/off program.
a) Shunt jumper S7 on PCB for the last unit in network on RS485 bus. (Please refer to Appendix III).
b) Connect the power cable according to the wiring diagram on page 38.
c) Connect line A and B on CN2 of data logger to CN2 of the last fan coil PCB according to the wiring
diagram on page 38 by using a RJ-11-6P-4C cable (please refer to Appendix I type B). Ensure Line A and
B does not connect reversely. (For configuration of Data Logger please refer to Appendix II)
d) Each data logger contains a 3 way mini shunt jumper JP2. Short the position 2 & 3 as shown below and
connect Line A and B on CN3 to RS485 port on the computer.
e) If more than one data logger is used (system with more than 32 units fan coil have to be connected),
connect Line A and B on CN4 of Data logger no.1 to CN3 of Data logger no.2.
Important note: If the connection distance between Data Logger no.1 to the Last Data Logger e.g. Data
Logger no.64 excess 300 meters, short position 1 & 2 on JP2 of the last Data logger as show below:
f) Provide each data logger with an addressable code by closing S1 – S6 DIP switch according to the DIP
switch chart below.
Important note: Please do not close SW6 [DIP switch on PCB] under Host Computer Control System as
Master-Slave function is not applicable when using Computer Control System.
Data logger DIP switch address setting: 1 for ON, 0 for OFF.
ID S1 S2 S3 S4 S5 S6
1 0 0 0 0 0 0
2 0 0 0 0 0 1
3 0 0 0 0 1 0
4 0 0 0 0 1 1
5 0 0 0 1 0 0
6 0 0 0 1 0 1
7 0 0 0 1 1 0
8 0 0 0 1 1 1
9 0 0 1 0 0 0
10 0 0 1 0 0 1
11 0 0 1 0 1 0
54
HYDRONIC DUCTED FAN COIL
12 0 0 1 0 1 1
13 0 0 1 1 0 0
14 0 0 1 1 0 1
15 0 0 1 1 1 0
16 0 0 1 1 1 1
17 0 1 0 0 0 0
18 0 1 0 0 0 1
19 0 1 0 0 1 0
20 0 1 0 0 1 1
21 0 1 0 1 0 0
22 0 1 0 1 0 1
23 0 1 0 1 1 0
24 0 1 0 1 1 1
25 0 1 1 0 0 0
26 0 1 1 0 0 1
27 0 1 1 0 1 0
28 0 1 1 0 1 1
29 0 1 1 1 0 0
30 0 1 1 1 0 1
31 0 1 1 1 1 0
32 0 1 1 1 1 1
33 1 0 0 0 0 0
34 1 0 0 0 0 1
35 1 0 0 0 1 0
36 1 0 0 0 1 1
37 1 0 0 1 0 0
38 1 0 0 1 0 1
39 1 0 0 1 1 0
40 1 0 0 1 1 1
41 1 0 1 0 0 0
42 1 0 1 0 0 1
43 1 0 1 0 1 0
44 1 0 1 0 1 1
45 1 0 1 1 0 0
46 1 0 1 1 0 1
47 1 0 1 1 1 0
48 1 0 1 1 1 1
49 1 1 0 0 0 0
50 1 1 0 0 0 1
51 1 1 0 0 1 0
52 1 1 0 0 1 1
53 1 1 0 1 0 0
54 1 1 0 1 0 1
55 1 1 0 1 1 0
56 1 1 0 1 1 1
57 1 1 1 0 0 0
58 1 1 1 0 0 1
59 1 1 1 0 1 0
60 1 1 1 0 1 1
61 1 1 1 1 0 0
62 1 1 1 1 0 1
63 1 1 1 1 1 0
64 1 1 1 1 1 1
55
HYDRONIC DUCTED FAN COIL
HOST COMPUTER NETWORK
56
HYDRONIC DUCTED FAN COIL
2.C HARDWARE CONFIGURATION
S6 Motorized valve[MTV]
Short With MTV
Open No MTV
An on board mini shunt jumper S3, S4, S5, S7 and DIP Switch are used for below configuration.
S3 Type
Short Louver setting for 2 way cassettes
Open Louver setting for 4/6 way cassettes
S4 Type
Open 2-Pipe
S5 Preheat temperature
Short 28ºC
Open 36ºC
S7 Type
Short Last unit on RS485 communication bus
Open Other than above
2. E. POWER ON SETTING
a) When the power on signal is received by the air conditioner, the Mode, Fan Speed, Setting
temperature and Swing setting will be the same as the handset setting before the last power off.
b) When the power on signal is received by the air conditioner, the Mode, Fan Speed, Setting
temperature, Swing setting and Timer ON/OFF weekly program will be the same as wall pad setting
before the last power off.
57
HYDRONIC DUCTED FAN COIL
2. F. WITH MOTORIZED VALVE
2.F.1 COOL MODE
a) MTV2 and heater always off.
b) If Tr >= Ts+1ºC, cool operation is activated, MTV1 is turned on. Indoor fan runs at set speed.
c) If Tr = Ts, cool operation is terminated, MTV1 is turned off. Indoor fan runs at set speed.
d) The range of Ts is 16-30 ºC
e) Indoor fan speed can be adjusted for low, medium, high and auto.
f) When turned on, MTV1 requires 30 seconds before it is fully open.
g) When turned off, MTV1 requires 120 seconds before it is fully closed.
h) When the unit is turned off, indoor fan will delay for 5 seconds before it is turned off.
a) If Ti1 ̰ 2 ºC for 2 minutes, MTV1 is turned off. If indoor fan is set for low speed, it will run at
medium speed. If it is set at medium or high speed, it will keep running at the same speed.
b) If Ti1 ̱ 5ºC for 2 minutes, MTV1 is turned on. Indoor fun runs at set speed.
a) Indoor fan runs at the set speed while heater, MTV1 and MTV2 are turned off.
b) Indoor fan speed can be adjusted for low, medium and high.
2.F.5 PRE-HEAT
a) If Ti1<36 ºC [or 28ºC depends on S5 setting], when MTV1 is on, indoor fan remains off.
b) If Ti1>=38 ºC [or 30ºC depends on S5 setting], when MTV1 is on, indoor fan runs at set speed.
c) If indoor coil temperature sensor is damaged, pre-heat time is set for 2 minutes and indoor fan runs at
set speed.
a) Indoor fan will turn on after the electrical heater is turned on for 10 seconds.
2.F.6. POST-HEAT
a). If Ti1̱38ºC, when MTV1 is off, indoor fan continues to run at set speed.
b). If Ti1<36ºC, when MTV1 is off. Indoor fan runs 30 seconds and stop 3 minutes repeatedly.
c) If indoor coil temperature sensor is damaged, post-heat time is set for 3 minutes with indoor fan running
at set speed.
a) Indoor fan will turn off after the unit has been off for 20 seconds.
a) If Ti1 >= 75 ºC, MTV1 is turned off, indoor fan remains on and runs at set speed.
b) If Ti1<70 ºC, MTV1 is turned on, indoor fan continues to operate at set speed.
c) If indoor coil temperature sensor is damaged, the protection mode will become obsolete and the unit
will work as the Pre-heat and Post-heat set times.
a) If Ti1 ̰ 2 ºC for 2 minutes, if indoor fan runs at low speed, it will run at medium speed. If indoor fan
runs at medium or high speed, it will run at set speed.
b) If Ti1 ̱ 5 ºC for 2 minutes, Indoor fan runs at set speed.
2.G.4. PRE-HEAT
2.G.5. POST-HEAT
a) Indoor fan will turn off after the unit is turned off for 20 seconds.
a) If Ti1 >=75 ºC, while unit is on, Indoor fan remains on and runs at high speed.
b) If Ti1< 70 ºC, while unit is on, indoor fan remains on and runs at set speed.
c) If indoor coil temperature sensor is damaged, the protection mode will become obsolete and the unit
will work according to the pre-heat set time.
Ts+2.0
Ts+1.0
Ts+0.5
Ts Hour
0.5 1.0 2.0
Sleep on Sleep off
In cool mode, the fan speed cannot change until it has run at this speed for more then 30 seconds. Fan
speed is regulated according to the profile below.
Tr
High
Ts+3C
Medium High
Ts+2C
Low Medium
Ts+1C
Low Low
Ts
61
HYDRONIC DUCTED FAN COIL
In heat mode, the fan speed cannot change until it has run at this speed for more then 30 seconds.
Tr
Ts
Low Low
Ts-1C
Low Medium
Ts-2C
Medium High
Ts-3C
High
2.J BUZZER
If a command is received by the air conditioner, the master unit will respond with 2 beeps for each setting,
and the slave unit will respond with 1 beep.
The system uses non-volatile memory to save the present operation parameters when system is turned off
or in case of system failure or cessation of power supply. Operation parameters when using handset are
mode, set temperature, swing, and the fan speed. When using wall pad parameters are mode, set
temperature, swing, and the fan speed when power supply resumes or the system is switched on again, the
same operations as previously set will function.
62
HYDRONIC DUCTED FAN COIL
3. B LED lights
Note: If the address of slave unit is not set (refer to page 52) LED lights and Wall pad of the master unit
will not show the status of the defective slave unit.
R25: 10K±1%
B25/85: 3977±1%
T Rmin Rnom Rmax T Rmin Rnom Rmax
(ć ) (K) (K) (K) (ć) (K) (K) (K)
-30 174 182.7 191.8 4 26.11 26.9 27.71
-29 163.4 171.5 179.9 5 24.85 25.59 26.34
-28 153.6 161.1 168.9 6 23.65 24.35 25.05
-27 144.4 151.3 158.5 7 22.52 23.17 23.83
-26 135.8 142.2 148.9 8 21.45 22.06 22.68
-25 127.8 133.8 140 9 20.44 21.01 21.59
-24 120.3 125.8 131.6 10 19.48 20.02 20.55
-23 113.3 118.4 123.8 11 18.58 19.7 19.58
-22 106.7 111.5 116.5 12 17.71 18.18 18.65
-21 100.6 105.1 109.7 13 16.9 17.33 17.77
-20 94.9 99.03 103.3 14 16.12 16.53 16.94
-19 89.51 93.39 97.41 15 15.39 15.77 16.16
-18 84.5 88.11 91.85 16 14.69 15.05 15.41
-17 79.8 83.17 86.64 17 14.03 14.37 14.7
-16 75.39 78.53 81.76 18 13.41 13.72 14.03
-15 71.26 74.18 77.19 19 12.81 13.1 13.4
-14 67.37 70.1 72.9 20 12.24 12.52 12.79
-13 63.73 66.26 68.88 21 11.7 11.96 12.22
-12 60.3 62.67 65.1 22 11.19 11.43 11.67
-11 57.08 59.28 61.55 23 10.71 10.93 11.15
-10 54.05 56.1 58.22 24 10.24 10.45 10.66
-9 51.19 53.12 55.08 25 9.80 10.00 10.20
-8 48.51 50.3 52.14 26 9.374 9.57 9.765
-7 45.98 47.66 49.37 27 8.969 9.16 9.351
-6 43.61 45.17 46.77 28 8.584 8.77 8.957
-5 41.36 42.82 44.31 29 8.218 8.40 8.582
-4 39.25 40.61 42 30 7.869 8.047 8.225
-3 37.26 38.53 39.83 31 7.537 7.71 7.885
-2 35.38 36.56 37.78 32 7.221 7.39 7.56
-1 33.6 34.71 35.85 33 6.92 7.085 7.251
0 31.93 32.97 3402 34 6.633 6.794 6.956
1 30.35 31.32 32.3 35 6.36 6.517 6.675
2 28.85 29.76 30.68 36 6.099 6.252 6.407
3 27.44 28.29 29.15 37 5.85 6.000 6.151
66
HYDRONIC DUCTED FAN COIL
R25: 10K±1%
B25/85: 3977±1%
T Rmin Rnom Rmax T Rmin Rnom Rmax
(ć ) (K) (K) (K) (ć) (K) (K) (K)
38 5.614 5.759 5.907 75 1.417 1.474 1.532
39 5.387 5.53 5.673 76 1.37 1.426 1.482
40 5.172 5.31 5.451 77 1.326 1.379 1.434
41 4.966 5.101 5.238 78 1.282 1.335 1.389
42 4.769 4.901 5.034 79 1.241 1.292 1.344
43 4.582 4.71 4.84 80 1.201 1.25 1.302
44 4.402 4.527 4.654 81 1.162 1.211 1.261
45 4.231 4.353 4.477 82 1.125 1.172 1.221
46 4.067 4.186 4.307 83 1.089 1.135 1.183
47 3.911 4.027 4.144 84 1.055 1.1 1.146
48 3.761 3.874 3.989 85 1.021 1.065 1.111
49 3.618 3.728 3.84 86 0.9891 1.032 1.077
50 3.481 3.588 3.697 87 0.9582 1 1.044
51 3.35 3.454 3.561 88 0.9284 0.9697 1.012
52 3.225 3.326 3.43 89 0.8998 0.9401 0.9818
53 3.105 3.204 3.305 90 0.8721 0.9115 0.9522
54 2.99 3.086 3.185 91 0.8455 0.8839 0.9237
55 2.88 2.974 3.07 92 0.8198 0.8573 0.8961
56 2.774 2.866 2.959 93 0.795 0.8316 0.8696
57 2.673 2.762 2.854 94 0.7711 0.8069 0.8439
58 2.576 2.663 2.752 95 0.748 0.783 0.8192
59 2.483 2.568 2.655 96 0.7258 0.7599 0.7953
60 2.394 2.477 2.562 97 0.7043 0.7376 0.7722
61 2.309 2.39 2.472 98 0.6836 0.7161 0.7499
62 2.227 2.306 2.386 99 0.6635 0.6953 0.7283
63 2.149 2.225 2.304 100 0.6442 0.6752 0.7075
64 2.073 2.148 2.224 101 0.6255 0.6558 0.6874
65 2.001 2.074 2.148 102 0.6075 0.6371 0.6679
66 1.931 2.002 2.075 103 0.59 0.619 0.6491
67 1.865 1.934 2.005 104 0.5732 0.6015 0.631
68 1.801 1.868 1.937 105 0.5569 0.5846 0.6134
69 1.739 1.805 1.872
70 1.68 1.744 1.81
71 1.623 1.686 1.75
72 1.569 1.63 1.692
73 1.516 1.576 1.637
74 1.466 1.524 1.583
67
HYDRONIC DUCTED FAN COIL
MOTORIZED VALVE (OPTIONAL)
Valve kit complete with electro-thermal servo control suitable for every version (vertical units with cabinet, horizontal
units with cabinet, vertically embedded and horizontally embedded),
60
40
20
0
0 0.5 1 1.5 2 2.5
KV [m3/h]
'1.9 '1.9
68
HYDRONIC DUCTED FAN COIL
2-Way Valve
100
80
P [K P a ]
60
40
20
0
0 0.5 1 1.5 2 2.5 3
'1.9
KV [m3/h] '1.9
69
HYDRONIC DUCTED FAN COIL
AIR PURIFIER (OPTIONAL)
GENERAL DESCRIPTION
This air purifier uses a negative ion generator that disperses a steam of negative ions into the air
throughout the room. The negative ions generated will charge airborne particles so they become
attracted to and settle on room surfaces, effectively removing harmful particles from the air you
breathe. Ion generator is very quiet; it does not release chemicals into the air, and is energy
efficient.
CHARACTERISTICS
Ions concentration: > 1 x 106 n/cm3
Power consumption: 1W
Power: 220VAC / 50Hz
Operation Temperature: <80oC
PRECAUTIONS
1. This ion generator is maintenance free.
2. It should be installed in a place at least 20mm away from any metal parts.
3. When ion generator is in use, plenum filter need to be cleaned more frequently.
WIRING DIAGRAM
70
HYDRONIC DUCTED FAN COIL
TWO-WAY INTAKE PLENUM WITH DAMPER (OPTIONAL)
The two-way intake plenum with damper enables the room air intake duct and the external air intake duct to be
connected when required. The cross section of the external air intake duct is accounted for 25% of the total cross
section.
The discharge and intake plenum is supplied when the incoming or outgoing airflow must be directed to or from the
bottom of the unit. It has a flange for connection to the basic unit or other accessories and blanked panels for
optimum and flexible use.
The discharge plenum for round ducting enables the air to be distributed through flexible ducts. Distribution takes
place through three 130mm diameter ducts in sizes PDW(H)-12/15/18, three 190 mm diameter ducts in sizes
PDW(H)-24/30, four 190 mm diameter ducts in sizes PDW(H)-40/44, four 200 mm diameter ducts in sizes
PDW(H)-50/66 The number of ducts is calculated so as to obtain an air speed of 5.0 m/s in the ducts with rated
airflow and the ducts fully open.
71
HYDRONIC DUCTED FAN COIL
AUXILIARY 1 ROW HEATING COIL MODULE FOR 4-PIPE SYSTEM (OPTIONAL)
Install the auxiliary 1 row heating coil module to the unit with 8 screws as shown above.
The electric heater module is supplied for winter heating as an alternative to the auxiliary hot water coil.
The maximum outputs available with 230V~50 are 3.0 KW for sizes PDW(H)-12/15/18/24/30, and 4.5 kW for sizes
PDW(H)-40/44/50/66. The module must be installed downstream of the basic unit directly in the outflow of air. The
stainless steel spiral heaters are mounted on a removable frame independent from the module. The heaters feature
ON-OFF operation.
Install the electrical heater module to the unit with 8 screws as same as the auxiliary coil module for 4 pipe system.
Note: For correct operation of the heaters, make sure airflow is not less than the values for minimum speed.
72
HYDRONIC DUCTED FAN COIL
JP2 DIP-SWIT
CH
“S” stand for the wiring distance between the first data logger to the last data logger (Data Logger Bus)
“T” stand for the wiring distance between the first fan coil to the last fan coil (Fan Coil Bus)
Table below shows the jumper shorting position on JP2 (Data Logger) and S7 (PCB) under different
distance situation to the bus connection.
RS232 to RS485 converter with RS232 to RS485 converter without
120ohm termination resistor in built 120ohm termination resistor in built
Fan Coil Bus “T” < 150m Do not short S7 on PCB Short S7 on PCB
Fan Coil Bus “T” >= 150m Short S7 on PCB Short S7 on PCB
Note: the above wiring distance of 300m is just for the reference. Short position 1 &2 or 2 & 3 for the last
data logger and S7 on PCB depends on the actual installation and quality of connection.
76
HYDRONIC DUCTED FAN COIL
APPENDIX IV
2) Please login to the system – for testing please choose “Maintenance” with password “666666”
77
HYDRONIC DUCTED FAN COIL
3) If fan coils were successfully connected to BMS system, their ID (according to the Dip-Switch setting
on the unit) will shown on the program with status of the air-con e.g. On/Off, Mode etc.
4) Set the Addressable communication by first clicking the “SET BY UNIT”, select the target ID and
provide them setting as same as below:
e.g. Select ID 1 & 5 as above means the setting will only send to unit with Dip-Switch setting no. 5 under
the first group of Data Logger Bus network.
78
HYDRONIC DUCTED FAN COIL
5) Set the Global Control communication by first clicking the “SET BY GROUP”, select the target group
of Data Logger Bus, “Tick” the target group no. and provide them setting as same as below:
e.g. Select G1-16 and “Tick” Group 1 as above means the setting will only send to the units within the
Data Logger Bus with Dip-Switch setting no. 1.
79
HYDRONIC DUCTED FAN COIL
6) If more than 1 Data Loggers are used, please enable the function of the other data logger(s) by first
click the “Select Group” and click “Select Group” as same as below:
80
HYDRONIC DUCTED FAN COIL
7) “Tick” the Group no. of Data Loggers which have connected to the BMS system according to the
Dip-Switch setting on the Data Loggers.
Note: Please do not “tick” the group which has no connection to the BMS system as this will slow down
the operation speed.
e.g. If there are only 2 data loggers connected to the BMS system which according to the Dip-Switch
setting is no.7 and no.10 respectively. From the program as shows above, please tick the group no.7 and
group no.10 so that both no.7 and no.10 data loggers are functioning.
81
HYDRONIC DUCTED FAN COIL
8) Set the timer on/off by clicking “System”, select “Set ON/OFF” as below:
82
HYDRONIC DUCTED FAN COIL
9) A box shows up with 7days selection. “Tick” the desired date of week.
83
HYDRONIC DUCTED FAN COIL
10) After selecting the desired date of week, select the target unit either by a Group, a particular unit or a
unit range. “Tick” the Auto On / Off Time to set the on/off timing of the desired date. Click “OK” to apply
the setting.
84
HYDRONIC DUCTED FAN COIL