You are on page 1of 4

Protect 3.

33 100 kVA

1000001532
1 Material-Nr. 1000001532 -
2 Rectifier unit
3 Number of phases 3 -
4 Nominal voltage 400 VAC
5 Operating range min. For battery trickle voltage 340 VAC
6 Operating range max. For battery recharge voltage 360 VAC
7 Operating range max. 460 VAC
8 Frequency 50/60 Hz ± 10% Hz
9 Input current at nominal load 163 A
10 Input current at nominal load + battery charging 205 A
11 Q1 input switch short circuit capacity (Icc) 6,4 kA
12 Rectifier type , standard 6 pulse -
13 Rectifier input current total harmonic distorsion (THD) 33 %
14 Rectifier reduced harmonics option 12 pulse -
15 Rectifier input current THD with option <8 %
16 Charging characteristic per IEC 478-10 IU A
17 Nominal DC voltage 384 VDC
18 DC-voltage ripple battery output <2% eff / <5% p/p
19 Max. Charging voltage 480 VDC
20 Output current limit 250 A
21 DC current tolerance static rectifier output +/- 2%
22 Overcurrent for max. 1min. 125 %
23 Charge current limit option
24 DC voltage tolerance rectifier output +/- 1%
25 Battery -
28 Lead acid, number of cells min-max 192 / 204
29 Lead acid, float voltage per cell adjustment range 2.13 - 2.32 VDC
30 Lead acid, recharge voltage per cell adjustment range 2.23 - 2.43 VDC
31 Lead acid, equalisation voltage per cell adjustment range 2.23 - 2.58 VDC
32 Lead acid, commissioning voltage per cell adjustment range 1.00 - 2.83 VDC
33 Lead acid, end of discharge voltage per cell adjustment range 1.6 - 2.00 VDC
34 Nickel Cadmium, number of cells nominal 282-320
35 Nickel Cadmium, float voltage per cell adjustment range 1.33 - 1.50 VDC
36 Nickel Cadmium, recharge voltage per adjustment range cell 1.37 - 1.70 VDC
37 Nickel Cadmium, equalisation voltage per cell adjustment range 1.37 - 1.75 VDC
38 Nickel Cadmium, commissioning voltage per cell adjustment range 0.50 - 1.95 VDC
39 Nickel Cadmium, end of discharge volt. Per cell adjustment range 0.65 - 1.20 VDC
40 Equalisation timer adjustment range 1-1999 min
41 Commissioning timer adjustment range 1-1999 min
Protect 3.33 100 kVA

1000001532
42 Inverter unit
43 Nominal DC voltage 384 VDC
44 DC voltage min. 307 VDC
45 DC voltage max. 461 VDC
46 DC input current at Udc nom and no load 5,6 ADC
47 DC input current at Udc nom -15% and Pn 258 ADC
48 DC input current at Udc nom 219 ADC
49 DC input current at Udc nom +20% 183 ADC
50 Efficiency measured on unit serial no. -
51 Efficiency at 10% load cos φ=0,8 ind. nm %
52 Efficiency at 25% load cos φ=0,8 ind. nm %
53 Efficiency at 50% load cos φ=0,8 ind. nm %
54 Efficiency at 75% load cos φ=0,8 ind. nm %
55 Efficiency at 100% load cos φ=0,8 ind. nm %
56 Efficiency typical under nominal conditions 0 %
57 Number of phases 3
58 Nominal AC voltage 400 VAC
59 Adjustable min. 380 VAC
60 Adjustable max. 415 VAC
61 Static response <±1 %
62 Dynamic response <±2 %
63 Dynamic response time 2 ms ms
64 Frequency 50 / 60 HZ
65 Frequency tolerance without mains ± 0,1 %
66 Frequency synchronisation range standard ±1 %
67 Frequency synchronisation range extended option 1 ±2 %
68 Frequency synchronisation range extended option 2 ±3 %
69 Frequency synchronisation speed single UPS 1 Hz/s
70 Frequency synchronisation speed parallel UPS 0,1 Hz/s
71 Power factor range cos φ cap-1-ind
72 Output phase current 145 A
73 Voltage wave form sinus
74 Frequency IGBT-trigger at nominal conditions 4,83 kHz
75 Frequency acoustic at nominal conditions 7,25 kHz
76 Voltage distortion ≤3 %
77 Max.crest factor 3
78 Overload response for 1 min. 150 %
79 Overload response for 10 min. 125 %
80 Short circuit response: Short circuit proof, short circuit current1ph/3ph 2,98/1,83 x Inenn
81 Short circuit duration 0,5 s
82 Static bypass switch
83 Number of phases 3
84 Input voltage tolerance +/-10 %
85 Frequency 50 / 60
86 Nominal power in kva 100 -
87 Overload for 10ms 500 %
88 Transfertime INV-SBS 0
Protect 3.33 100 kVA

1000001532
90 General data
91 Efficiency measured on unit serial no. -
92 Global efficiency at 10% load cos φ=0,8 ind. 78,4 %
93 Global efficiency at 25% load cos φ=0,8 ind. 89,4 %
94 Global efficiency at 50% load cos φ=0,8 ind. 92,2 %
95 Global efficiency at 75% load cos φ=0,8 ind. 92,2 %
96 Global efficiency at 100% load cos φ=0,8 ind. 91,4 %
97 Global efficiency at 110% load cos φ=0,8 ind. 90,7 %
98 Global efficiency typical under nominal conditions 93 %
99 Power loss 0 -
100 Noise level measurement on unit serial no. -
101 Noise level at 100% load cos φ=0,8 66,4 dB(A)
102 Noise level at 100% load cos φ=0,8 typical 66 dB(A)
103 EMC compatibility acc. EN 62040-2 C2 -
104 Air cooling with redundant / monitored fans ja -
105 Operating-temperature range min. / max. - 5 / +40 °C
106 Storage-temperature range min. / max. -30 / +75 °C
107 Maximum installation altitude (above sea level) 1000 m
108 Protection degree acc. IEC 529 / en 60529 IP20
109 Optional protection degree max. IP31
110 Equipment colour (powder coated) RAL 7035
111 Powder coating thickness 70-90 µm
112 Zinc plated internal plates coating thickness 20 µm
113 Side, rear-and top panels thickness 1,5 mm
114 Door thickness 1,5 mm
115 Frame thickness 3 mm
116 Temperature class magnetics H mm
117 Max.requested air flow 1800 m3/h
118 Dimensions
119 Height standard device 1710 mm
120 Height with max. Options 1815 mm
121 Width 1200 mm
122 Depth 735 mm
123 Weight 900 kg
124 Weight at max. Protection degreee 0 kg
125 Connections
126 Cable entry Bottom
127 Min.required section rectifier input 2x35 mm2
128 Max.possible section rectifier input 2x95 mm2
129 Min.required section battery cables 2x50 mm2
131 Max.possible section battery cables 2x50 mm2
132 Min.required section load cables 2x25 mm2
133 Max.possible section load cables 2x50 mm2
134 Min.required section mains cables SBS 2x25 mm2
135 Max.possible section mains cables SBS 2x50 mm2
136
Cross section M10

137 Recommended protections -


138 Rectifier mains fuse 200 A
139 Max. Load fuse 63 A
140 SBS mains fuse 160 A
141 Battery fuse 315 A
Protect 3.33 100 kVA

1000001532
142 Remote alarms card Option
143 Number of relais 5
144 Maximum switchable AC voltage 380 VAC
145 Max. Inductive current at 250vac and cos φ=0,8 6 AAC
146 Max. Resistive current at 250vac 8 AAC
147 Max. Inductive current at 50vdc 0,4 ADC
148 Max. Resistive current at 50vdc 0,9 ADC
149 Max. Inductive current at 120vdc 0,2 ADC
150 Max. Resistive current at 120vdc 0,35 ADC
151 Max. Inductive current at 240vdc 0,1 ADC
152 Max. Resistive current at 240vdc 0,18 ADC
153 Number of optocoupler 1 -
154 Optocoupler maximum DC input voltage 24 VDC
155 Optocoupler maximum AC input voltage 24 VAC
156 Optpocoupler input current 20 mA
157 Options
158 Remote alarms relays and commands extension card
159 Number of relays 3 -
160 Number of optocouplers 2
161 Battery monitoring BLU PRO
162 Monitoring value level 1 (symmetry alarm) >2 VDC
163 Monitoring value level 2 (battery fault) >3.5 VDC
164 Monitoring value level 3 (monitoring fault) <0.1 or >4.5 VDC
165 Number of strings monitored 1
166 Battery temperature compensation option
167 Temperature coefficient 5 mV/°C/cell
168 Minimum compensation temperature 5 °C
169 Maximum compensation temperature 60 °C
170 Probe type PT100
171 Max distance UPS to probe 100 m
172 Space heater option
173 Nominal power rating 200 W
174 Nominal voltage 230 VAC
175 Themostat adjustment range 10 - 60 °C
176 JBUS communication option
177 Maximum transfer rate 19,2 kbit/s
178 Mininmum transfer rate 1,2 kbit/s
179 Transmission mode Half Duplex -
180 Data format RTU -
181 PROFIBUS communication option m
182 Max. Profibus transfer rate 12 Mbit/s
183 Remote control panel option Y/N
184 Type of communication CAN Y/N
185 Maximum number of single units monitored 8 Y/N
186 Maximum number of parallel units monitored 8 Y/N
187 Maximum connection length 1000 m
188 Manual bypass Y/N
189 Integrate manual bypass standard? Y Y/N