You are on page 1of 5

Integration of Renewable Sources of Energy into

Power Grid
Priyanka Swain, S Jagadish, K N S Uma Mahesh
Power Business Unit
Tata Consulting Engineers Limited
Bangalore, India
pswain@tce.co.in

Abstract—The huge, ever growing demand for electrical generated by capacitors located as close as possible to the load
energy has hitherto been primarily met through the combustion centres, because severe voltage drops are caused by
of fossil fuels, and conversion of heat liberated therefrom. The transmitting reactive power over long distances. The design of
relentless exploitation of these resources has raised questions a distribution system is generally optimized in terms of
regarding emission of green house gases, particulate pollution, parameters such as the quantum of apparent power, the
and their harmful effects on environment. It also brings into distance between the distribution sub-station and the loads,
focus the sustainability of generation to satisfy the demand for and the size of the conductors, keeping in view the normal
energy in the coming decades, from fuels which are not pattern of apparent power flow from the sub-station to the
inexhaustible. Renewable sources of power such as the sun, the
loads, so as to ensure a voltage profile that is in compliance
wind and the tides offer solutions to these issues. The
continuously falling cost of Solar and Wind generation
with the requirement of grid code, across the network.
technology has also made this option economically viable. They The installation of renewable energy sources (RES) in
are rendered even more attractive by governments in many various parts of this network will bring about a change in the
countries, which are keen to promote green and clean energy, by load flow pattern of active and reactive power, resulting in a
adoption of favorable policies. But the large scale use of change in voltage and frequency profile. A gradual increase in
renewable sources of energy give rise to many technical such installations, beyond a point, will completely alter the
challenges for the power system engineers. It is necessary to prevailing profile of voltage. This change may lead to over
overcome them before the renewable sources come into wide use
voltage in different parts of the network. The fact that these
in conjunction with conventional generation based on fossil fuels.
An attempt is made in this paper to identify the issues which
changes are dynamic, depending upon the time of day and
arise as a consequence of integration of the renewable sources weather, adds further to the complexity of the problem. There
with the existing power grids, and look for solutions to some of is hence a need to study the anticipated changes in the pattern
them, particularly the stability of voltage, through the control of of power flow, in order to devise suitable controls for
reactive power and active power. improving system stability, improve reliability and minimize
disruption of service due to operation of built-in protective
Keywords—RES, SPV, WTG, energy storage, DCI, POI, voltage features.
ride through, reactive power control, voltage stability
Studies aimed at quantification of the effects of variation
in all the parameters of the power system which define its
I. INTRODUCTION performance, need to be undertaken. The results obtained
The generation, transmission, distribution and utilization from such studies will aid in the determination of specific
of electrical energy involves both active and reactive power, requirements of inverters in respect of control of active and
the former representing that part which is consumed as true reactive power, and will support programmes to undertake
energy in industrial and transport sectors, lighting, heating and modifications to the existing networks to meet these
cooling of commercial establishments and other buildings, requirements.
residences etc., and the latter, while being not available for
consumption by such loads, is nonetheless essential to deliver II. CHALLENGES
active power to the loads, at or near rated voltages. Reactive The main challenges are the steady state and temporary
power is absorbed by motor loads as well as by the lines and variations in the voltages at the load terminals and at different
transformers in the transmission and distribution network. In parts of the network, and in the frequency, and their effect on
an ideal conventional power system, the reactive power grid stability and power quality. Such variations occur both in
consumed by the transmission system is supplied by the steady state operation which is gradual, and more rapidly and
generators in power plants, while that required by the randomly, over short periods of time due to passing clouds, or
distribution system and loads is met by capacitor bank waxing and waning of wind velocity. Measures should be
installations, which are distributed across the network. It is taken so as to keep the variations in frequency and voltage
desirable that the reactive power absorbed by loads should be within acceptable limits in compliance with grid codes, even

978-1-5090-6255-3/17/$31.00 ©2017 IEEE

Authorized licensed use limited to: Punjab Engineering College (Deemed to be University). Downloaded on April 25,2023 at 08:05:34 UTC from IEEE Xplore. Restrictions apply.
2017 IEEE Region 10 Symposium (TENSYMP)
as the output of inverters changes in keeping with the controllers, which automatically regulate the output in order
variations in solar radiation and wind velocity. that the frequency and voltage of the network are maintained
within specified limits at the point of connection.
The maximum current, as also the voltage, should be
known in order to be able to ensure safety of the equipment in The changes in the parameters of V, I, pf, P and Q are
respect of maximum continuous power rating and insulation observed at the locations P1 , P2, P3 ,P4, P5 and P6, shown in
level. Fig. 1.
Power factors at the point of interconnection (POI) will
also vary widely from values usually encountered in networks
without RES. Constraints, if any, imposed on bidirectional
transmission of active and reactive power by in the existing
distribution network should also be examined.

TR. LINE
33 kV
The distortions of voltage and current due to harmonics
(Total Harmonic Distortion and harmonics of certain specific
order), introduced by individual RES may well be within the

11kV LINE
limits laid down in relevant standards, but with their
increasing numbers, the cumulative effect at main busbars
may exceed permissible values. Hence the need for mitigating

INVERTER TRF12
INVERTER TRF1
measures in the form of filters should be investigated.

0.4/11 kV

0.4/11 kV
2 MVA

2 MVA
Fluctuations in solar irradiation and wind cause voltage

INVERTER12
INVERTER1
flicker owing to rapid changes in input power. Steps are

PV ARRAY 12 2 MW
2 MW

DWELLING UNITS
1P SUPPLY TO 32

5kW Load/Unit
3kW PV/Unit
needed to limit it to tolerable levels. Energy storage facilities

=
PV ARRAY 1
and inverters with PQ controls may be necessary so that the
utilization of RES is maximized and the fluctuations due to
variations in weather are smoothened out
The connection between the RES and the grid should not Fig. 1. Typical distribution network considered for study
break during transient system disturbances in the grid, while it
also necessary to ensure the safety of equipment such as the IV. STUDY MODEL
solar panels, wind generators, inverters etc. i.e. inverters The system under study is modeled using a power system
should have high voltage ride through (HVRT) and low modeling and simulation tool.
voltage ride through (LVRT) features.
It is necessary to study each of these issues and evolve A. 24MW Solar PV System Model
satisfactory solutions, in order to promote the use of energy The component models of 24MW SPV system include PV
from renewable sources on a wide scale. This paper mainly array, maximum power point tracker (MPPT) control, 3-phase
deals with the aspect of steady state and short term stability of pulse width modulated (PWM) inverter with associated
voltage. controls, inverter transformers and a step-up transformer for
connection with utility system.
III. SYSTEM DESCRIPTION
B. 24MW WTG System Model
A section of a typical distribution system, as shown in
Fig.1, has been chosen to develop a model to study voltage A doubly-fed induction generator (DFIG) driven by a wind
stability, as well as flow of active and reactive power, after turbine, is chosen for the study model of the WTG. The model
integration of renewable sources with it. includes simplified aerodynamic representation of the turbine
blades, gear box, induction generator, and power electronic
Load flow programme is run on this network, without RES converters.
connected to it, to determine the base parameters of voltage
(V), current (I), power factor (pf), active power (P) and C. Small-scale distributed Rooftop Solar PV Model
reactive power (Q) of various circuits. Load flow simulations
are then repeated each time after connecting a 24 MW solar The PV model of distributed roof-top system is similar to
photo voltaic plant (SPV), a 24 MW farm of wind turbine that of large grid connected solar PV plant. However, the PV
generators (WTG), and distributed roof top SPVs with their inverter in such application is usually single-phase.
contribution increasing in steps. It is possible to predict the
dynamic changes in these parameters by studying their V. RESULTS OF THE STUDY
variation under steady-state with the generation from RES at Tables I to VI and Fig. 2 to 5 indicate the variations in
maximum and minimum, and repeating these studies at grid active power, reactive power, power factor, voltage and
voltages of + 10%, normal and -10%. current flow at measurement locations P1, P2, P3, P4, P5 and
These studies have been conducted with simple inverters P6.
as well as with those having active power and reactive power

Authorized licensed use limited to: Punjab Engineering College (Deemed to be University). Downloaded on April 25,2023 at 08:05:34 UTC from IEEE Xplore. Restrictions apply.
2017 IEEE Region 10 Symposium (TENSYMP)
It can be seen from tables I, II, and III that with grid The effect of connecting a 24 MW wind farm on the
voltage at 100 %, the inverters can be operated at full voltage at locations P5 and P6 is shown in tables IV, V, and
generation and the power factor remains close to unity. If the VI. It is assumed that both SPV and WTG plants are
grid voltage rises to 110% inverters with capability to operate connected to the grid and operate together.
at 0.95 lead will restrict the voltage rise to 109%, which
otherwise would have been 112%. It is obvious that the The voltage at P5 and P6 remain at or near 100% without
inverter should have a higher capability to operate at still PQ controllers with the grid voltage also at 100%, but when
lower power factors. If the 132kV/33 kV transformer be fitted the grid voltage attains values of 90% or 110% of the rated
with On Load Tap Changer (OLTC) controlled by an voltage, a reactive power controlling range of +/- 0.95pu, is
automatic voltage regulator (AVR), it may be used in not adequate to control the bus voltage at P5 and P6. OLTC
conjunction with reactive power controller of the inverters. with AVR and, automatically regulated capacitor bank or
The same means of voltage control may be used when the grid wider range of reactive power control in Dynamically
voltage falls to 90%. It is also advantageous to install suitably Controlled Inverters (DCI) is necessary in this case as well.
sized and automatically regulated capacitor bank in the RES TABLE IV. VARIATIONS IN STEADY STATE PARAMETERS WITH AND
plant to provide reactive power compensation during periods WITHOUT 24MW WTG AT GRID VOLTAGE 100%
of low voltage in the grid. This approach will allow the
optimization of inverters in respect of their reactive power
capability and cost, instead of sizing them to provide full
compensation i.e 0.9 lag or lower still.

TABLE I. VARIATIONS IN STEADY STATE PARAMETERS WITH AND


WITHOUT 24MW SPV AT 100% GRID VOLTAGE

TABLE V. VARIATIONS IN STEADY STATE PARAMETERS WITH AND


WITHOUT 24MW WTG AT 110% GRID VOLTAGE

TABLE II. VARIATIONS IN STEADY STATE PARAMETERS WITH AND


WITHOUT 24MW SPV AT 110% GRID VOLTAGE

TABLE VI. VARIATIONS IN STEADY STATE PARAMETERS WITH AND


WITHOUT 24MW WTG AT 90% GRID VOLTAGE

TABLE III. VARIATIONS IN STEADY STATE PARAMETERS WITH AND


WITHOUT 24MW SPV AT 90% GRID VOLTAGE

Fig. 2 to 5 illustrate the variations in voltage and other


parameters as the contribution from roof top RES installations
increase in stages from 0% to 75% of the power demand of the
network. They too are assumed to operate concurrently with
SPV and WTG plants. It can be seen from the results that until

Authorized licensed use limited to: Punjab Engineering College (Deemed to be University). Downloaded on April 25,2023 at 08:05:34 UTC from IEEE Xplore. Restrictions apply.
2017 IEEE Region 10 Symposium (TENSYMP)
the contribution from these sources exceed 50% of the total The voltage at location P1 increases to about 106% at the
consumption the voltage rise is within tolerable limits, when level of deployment of 50%, with the grid voltage being at
the grid voltage is at rated value. 100%. The rise in voltage is mainly due to fall in its drawl of
active power from the grid. The impact is maximum at 400 V
level, and as one moves upstream in the network from P1, to
the first sub-station, and further up to higher voltage levels,
the change in the magnitude of these parameters progressively
diminishes. Although the permissible upper limit at 400V is
10%, corrective action may be initiated at this point.
The voltage variations brought about by the RES should be
controlled by provision of PQ controllers in DCI, but those in
the grid, which is liable to vary between +/- 10% of the rated
voltage, should be regulated with the aid of OLTC in the 25
MVA 33 kV/11 kV transformer. Combined use of inverter
Fig. 2. Voltage variation at P1, P2, P3 and P6 at 100% grid voltage w/t Q control and OLTC is more effective than any one of them. For
control (UPF) instance, when the grid voltage is 110%, the voltage at P1
rises to an uncontrolled magnitude of 115%. With inverter
control i.e. operating the inverter at a pf of 0.95 lead, the
voltage can be brought down to 109%. If the secondary side
voltage of the 33 kV/11 kV transformer is maintained at 100
% by means of the OLTC, the voltage at P1 is almost 100%
with inverter control. On the contrary, if the grid voltage goes
down to 90%, voltage at P1, without RES connected, will
follow the grid voltage. At 10% and 20% of RES operating at
UPF, the voltage improves but not to the desired level. It
becomes necessary to turn on the Q control and set it at 0.95
pf lag, in order to improve the voltage further by 2% to 3%.
As the power from RES increases to 50% and beyond, the
Fig. 3. Voltage variation at P1, P2, P3 and P6 at 110% grid voltage w/t Q voltage, with inverter control switched off, is close to 100%.
control (UPF)
The power factor may reach unusually low values of the
order of 0.35 at P1 and 0.7 at P2. It should cause no concern
since it is more a consequence of the fall in drawl of active
power rather than an increase in reactive power.

With the increasing use of RES, a reducing trend is


observed in respect of load carried by the equipment in the
distribution system. The adequacy of the conductors and
transformers to transmit power, whose magnitude and
direction may change as a consequence of large scale use of
RES, does not appear to present any problems, since they are
able to carry current equal to their rating in either direction. In
theoretical sense, one section of the grid may have generation
Fig. 4. Voltage variation at P1, P2, P3 and P6 at 110% grid voltage with Q from RES (SR) up to the sum of 100% capacity of the supply
control (lead) transformer (ST) and the minimum demand in the network
(SM), whereby the entire load in that section, is met by the
RES, while the surplus power during minimum load
conditions is exported and used elsewhere, without causing
over load in any equipment in that section. Only the OLTC
needs to have bi-directional capability in order to be able to
cope with this contingency. But as discussed in the foregoing
paragraphs, the prospective voltage profile must be studied
before deciding upon the acceptable level of RES penetration.
The frequency may be expected to rise with increase in
active power availability, but the governing action of the
conventional generators in the grid will aid in keeping it
Fig. 5. Voltage variation at P1, P2, P3 and P6 at 90% grid voltage w/t Q substantially constant, if its rise is gradual. These generators,
control (UPF) operating in droop governing mode, will reduce their output in
keeping with rise in active power output from RES.

Authorized licensed use limited to: Punjab Engineering College (Deemed to be University). Downloaded on April 25,2023 at 08:05:34 UTC from IEEE Xplore. Restrictions apply.
2017 IEEE Region 10 Symposium (TENSYMP)
VI. CONCLUSION consumed by RES, particularly when the grid voltage is low.
The immediate consequences of concern with integrated Both the inverters and capacitor banks should be regulated by
operation of RES on a large scale are the variations in voltage automatic controllers. The inverter should maintain the power
due to a) diurnal cycle of solar radiation in case of SPV factor close to the desired value at POI, while the controller
generation or seasonal variations of wind direction and associated with the capacitor bank should respond to changes
velocity in case of generation from WTG, both of which give in grid voltage, and switch the bank in stages as required. The
rise to relatively slow, cyclic and reasonably predictable two control actions need to be coordinated as well.
changes, and b) changes during a day, in a time window There is the possibility that with rapid increase in RES,
lasting few minutes to several hours, due to passing clouds, or both at plant level and at distribution level, the active power
changes in wind velocity affecting the output from RES. may flow back into the grid, particularly at light load
The analysis of the results shows that in the steady state conditions. The OLTC needs to have bi-directional capability
the parameters of V, I, P, Q and pf deviate considerably from in order to be able to cope with this contingency.
their normal values. The voltage at POI increases the most, The harmonics generated by the process of rectification
and its rise is lower at other locations in the grid, the less and inversion, and their cumulative effect at the network level,
pronounced the farther the location is from POI. The voltage as also the voltage fluctuations caused by corresponding
rise is mainly due to reduced flow of active power through the variations in power output of RES may give rise to power
supply transformer, as a consequence of an equivalent quantity quality issues. The distortion due to harmonics should be
of active power being generated by RES within the section assessed, and counter measures to contain them devised. In the
itself. Slow variations of this kind in steady state can be initial phases this need is addressed on case by case basis, and
handled by provision of OLTCs and capacitor banks along filters provided if warranted. In the longer term, it may be
with automatic regulators. All transformers in the distribution necessary to lower the allowable limit of harmonic distortion
system rated 33 kV and below may be fitted with OLTC and for inverters. Short duration voltage fluctuations give rise to
AVR, to maintain the voltage close to rated value. irritable flicker in lighting and may adversely affect voltage
Temporary fluctuations in voltage, which are caused due to sensitive loads. The PQ controllers in DCI along with energy
reasons stated heretofore, are much faster and random in storage will mitigate this problem.
occurrence, cannot be dealt with in the manner described The frequency may tend to rise with increase in active
above. This issue can be only partly addressed by building power availability, but the governing action of the
some reactive power capability into the inverters. But the conventional generators in the grid will aid in keeping it
unsteady nature of the power from renewable sources requires substantially constant, as it tends to rise gradually during the
DCI which controls both active power and reactive power in course of the day. But the rapid fluctuations in power output
real time so as to be able to respond to varying conditions of of RES give rise to frequency variations that cannot be
solar irradiation and wind velocity. Addition of fast, automatic regulated by the aforesaid droop control. These rapid
and intelligent controllers to inverters, in combination with fluctuations in frequency, as those of voltage, is also remedied
energy storage facilities, enables control of voltage as well as by providing energy storage facilities with inverters featuring
the full utilization of renewable sources, and the operation of active and reactive power controllers, and high speed
inverters at an optimal level. switching (DCI).
It should also be noted that the roles played by the DCI The inverters should have ride through features which
and the automatically regulated OLTC are distinct and enable them to remain connected to the grid during voltage
complementary but not necessarily simultaneous. The OLTC dips caused by external short circuit faults, as well as during
helps to regulate voltage variations in steady state occurring at voltage swells due to switching operations elsewhere in the
grid level while the controllers integral to the inverters, with grid. The duration of LVRT should depend on the maximum
their fast response time, can effectively control more rapid but fault clearing time for short circuit faults in the
temporary variations brought about by the inverters neighbourhood. The HVRT period should be sufficient taking
themselves owing to changes in their input power. DCI will into account the time of operation of inverter controls but not
also respond to similar voltage variations originating in the higher than the withstand capability of inverter components.
grid and complement the conventional controllers.
The issue of over loading of the components of the References
distribution system, such as transformers and lines, does not
arise until the contribution from RES does not exceed the sum [1] "IEEE Standard for Interconnecting Distributed Resources with Electric
of the capacity of the transformer supplying the local network Power Systems," IEEE Std 1547.1-2005
and the minimum demand of the network. [2] "IEEE Draft Guide to Conducting Distribution Impact Studies for
Distributed Resource Interconnection,” IEEE P1547.7
The transformers in RES plants consume some reactive [3] National Renewable Energy Laboratory (NREL), “Technical Report
power. It is hence necessary to specify a minimum reactive NREL/TP-5500-58189”, August 2013
power capability for the inverters used in RES plants, [4] Ministry of Power, Government of India, “Report of the technical
consistent with economical design, and to determine the need, committee on large scale integration of renewable energy, need for
size and number of stages of capacitor bank by conducting balancing, deviation settlement mechanism and associated issues,” April
2016
studies so that the grid is not loaded with the reactive power

Authorized licensed use limited to: Punjab Engineering College (Deemed to be University). Downloaded on April 25,2023 at 08:05:34 UTC from IEEE Xplore. Restrictions apply.

You might also like