MAGNETIC FLOWMETERS

Flow Reference Section

INTRODUCTION
Magnetic flowmeters are low
pressure drop, volumetric, liquid
flow measuring devices. The low
maintenance design–with no
moving parts, high accuracy, linear
analog outputs, insensitivity to
specific gravity, viscosity, pressure
and temperature, and the ability to
measure a wide range of difficult-to-
meter fluids (such as corrosives,
slurries and sludges)–differentiates
this type of metering system from
other flowmeters. Two basic styles
of magnetic flowmeter are currently
available from OMEGA Engineering:
1) Wafer-style, where highest
accuracy (up to +0.5% of reading)
measurements are required; and 2)
Insertion-style, for greater economy
and particularly for larger pipe sizes.
Figure 1: In-line magnetic flowmeter operating principle
All OMEGA® magnetic flowmeters
employ the state-of-the-art dc
pulsed magnetic field system. The
following discussion details the
principle of operation, as well as the
advantages, of dc pulsed type
magnetic flowmeters.

PRINCIPLE OF OPERATION
Faraday’s Law
The operation of a magnetic
flowmeter is based upon Faraday’s
Law, which states that the voltage
induced across any conductor as it
moves at right angles through a
magnetic field is proportional to the
velocity of that conductor.
Faraday’s Formula:
E is proportional to V x B x D
where:
E = The voltage generated in a
conductor
V = The velocity of the conductor Figure 2: Insertion-type flowmeter operating principle
B = The magnetic field strength element is exposed to the hydraulic
the magnetic field strength (B) and
D = The length of the conductor the length of the conductor (D) conditions throughout the entire
To apply this principle to flow (which in this instance is the cross-section of the flowmeter. With
measurement with a magnetic distance between the electrodes). insertion-style flowmeters, the
flowmeter, it is necessary first to In the case of wafer-style magnetic magnetic field radiates outward
state that the fluid being measured flowmeters, a magnetic field is from the inserted probe (Figure 2).
must be electrically conductive for established throughout the entire
the Faraday principle to apply. cross-section of the flow tube
As applied to the design of magnetic (Figure 1). If this magnetic field is
flowmeters, Faraday’s Law indicates considered as the measuring
that signal voltage (E) is dependent element of the magnetic flowmeter,
on the average liquid velocity (V) it can be seen that the measuring
H-3
MAGMETER SELECTION 4. Electrical conductivity is a and expanders at the pipe size
The characteristics of the fluid to be function of concentration. transitions. As a rule of thumb,
metered, the liquid flow parameters, Therefore, the concentration of meters should be sized no smaller
and the environment of the meter the solution should always be than one-half of
are the determining factors in the provided. However, avoid what the line size.
selection of a particular type of normally is a logical assumption,
such as: That electrical Because of the wide rangeability of
flowmeter. magnetic flowmeters, it is almost
conductivity increases as
concentration increases. This never necessary to oversize a meter
Conductivity to handle future flow requirements.
is true up to a point in some
Electrical conductivity is simply a solutions, but then reverses. When future flow requirements are
way of expressing the ability of a For example, the electrical known to be significantly higher than
liquid to conduct electricity. Just as conductivity of aqueous solutions start-up flow rates, it is imperative
copper wire is a better conductor of acetic acid increases as that the initial flows be sufficiently
than tin, some liquids are better concentration rises up to 20%, high and that the pipeline remain full
conductors than others. However, but then shows a decrease with under normal flow conditions.
of even greater importance is the increased concentration to the
fact that some liquids have little or extent that, at some Abrasive Slurries
no electrical conductivity (such as concentration above 99%, it falls
hydrocarbons and many non- Mildly abrasive slurries can be
below the minimum requirement. handled by magnetic flowmeters
aqueous solutions, which lack
sufficient conductivity for use with without problems, provided
magmeters). Conversely, most Acid/Caustics consideration is given to the
aqueous solutions are well suited The chemical composition of the abrasiveness of the solids and the
for use with a magmeter. Depending liquid slurry to be metered will be a concentration of the solids in the
on the individual flowmeter, the determining factor in selecting the slurry. The abrasiveness of a slurry
liquid conductivity must be above will affect the selection of the
the minimum requirements
flowmeter with the proper design
and construction. construction materials and the use H
specified. The conductivity of the of protective orifices. Abrasive
liquid can change throughout Operating experience is the best slurries should be metered at
process operations without guide to selection of liner and 6 ft/sec or less in order to minimize
adversely affecting meter electrode materials, especially in flowmeter abrasion damage.
performance, as long as it is industrial applications, because, in Velocities should not be allowed to
homogeneous and does not drop many cases, a process liquid or fall much below 4 ft/sec, since any
below the minimum conductivity slurry will be called by a generic solids will tend to settle out. An ideal
threshold. Several factors should be name, even though it may contain slurry installation would have the
taken into consideration concerning other substances which affect its meter in a vertical position. This
liquids to be metered using corrosion characteristics. Commonly would assure uniform distribution of
magnetic flowmeters. Some of available corrosion guides may also the solids and avoid having solids
these are: prove helpful in selecting the proper settle in the flow tube during
materials of construction. no-flow periods.
1. All water does not have the same
conductivity. Water varies greatly Consideration should also be given
in conductivity due to various ions Velocity to use of a protective orifice on the
present. The conductivity of “tap The maximum (full scale) liquid upstream end of a wafer-style
water” in Maine might be very velocity must be within the specified magnetic flowmeter to prevent
different from that of “tap water” flow range of the meter for proper excessive erosion of the liner. This
in Chicago. operation. The velocity through the is especially true since Tefzel liner
flowhead can be controlled by have excellent chemical resistance,
2. Chemical and pharmaceutical properly sizing the meter. It isn’t but poor resistance to abrasion. In
companies often use deionized or necessary that the flowhead be the lined or non-conductive piping
distilled water, or other solutions same line size, as long as such systems, the upstream protective
which are not conductive enough sizing does not conflict with other orifice can also serve
for use with magnetic flowmeters. system design parameters. as a grounding ring.
3. Electrical conductivity is a Although the meter will increase
function of temperature. hydraulic head loss when sized Sludges and
However, conductivity does not smaller than the line size (because Grease-Bearing Liquids
vary in any set pattern for all the meter is both obstructionless
and of short lay length), the amount Sludges and grease-bearing liquids
liquids as temperature changes. should be operated at higher
Therefore, the temperature of the of increase in head loss is negligible
in most applications. The amount of velocities, about 6 ft/sec minimum,
liquid being considered should in order to reduce the coating
always be known. head loss increase can be further
limited by using concentric reducers tendencies of the material.
H-4
MAGNETIC FLOWMETERS
Flow Reference Section

Viscosity The magnitude of this error signal is frequency) than ac meters. This
Viscosity does not directly affect a function of the number of turns lower frequency eliminates noise
the operation of magnetic in the loop, and the change pickup from nearby ac lines,
flowmeters, but, in highly viscous in magnetic flux per unit time. In a allowing power and signal lines to
fluids, the size should be kept as magnetic flowmeter, the electrode be run in the same conduit and thus
large as possible to avoid excessive wires and the path through the simplifying wiring. Wiring is further
pressure drop across the meter. conductive liquid between the simplified by the use of integral
electrodes represent a single turn signal conditioners to provide
Temperature loop. The flow-dependent voltage is voltage and current outputs. No
in phase with the changing separate wiring to the signal
The liquid’s temperature is generally magnetic field; however, flow- conditioners is required.
not a problem, providing it remains independent voltage is also
within the mechanism’s operating generated, which is 90°out of phase Power
limits. The only other temperature with the changing magnetic field.
considerations would be in the case By design, ac magnetic flowmeters
The flow-independent voltage is typically have high power
of liquids with low conductivities therefore an error voltage which
(below around 3 micromhos per requirements, owing to the fact that
is 90° out of phase with the desired the magnetic field is constantly
centimeter) which are subject signal. This error voltage is often
to wide temperature excursions. being powered. Because of the
referred to as quadrature. In order pulsed nature of the dc pulse
Since most liquids exhibit a to minimize the amount of
positive temperature coefficient magmeter, power is supplied
quadrature generated, the electrode intermittently to the magnetic field
of conductivity, the liquid’s minimum wires must be arranged so that they
conductivity must be determined coil. This greatly reduces both
are parallel with the lines of flux of power requirements and heating
at the lower temperature extreme. the magnetic field. of the electronic circuitry, extending
In ac field magmeters, because the life of the instrument.
Advantages of the
DC Pulse Style the magnetic field alternates
continuously at line frequency,
From the principles of operation, quadrature is significant. It is
it can be seen that a magnetic necessary to employ phase-
flowmeter relies on the voltage sensitive circuitry to detect and
generated by the flow of a reject quadrature.
conductive liquid through its It is this circuitry which makes the
magnetic field for a direct indication ac magnetic meter highly sensitive
of the velocity of the liquid or slurry to coating on the electrodes. Since
being metered. The integrity of this coatings cause a phase shift in the
low-level voltage signal (typically voltage signal, phase-sensitive
measured in hundreds of circuitry leads to rejection of the
microvolts) must be preserved so as true voltage flow signal, thus leading
to maintain the high accuracy to error.
specification of magnetic flowmeters
in industrial environments. The Since dc pulse magmeters are
superiority of the dc pulse over the not sensitive to phase shift and
traditional ac magnetic meters in require no phase-sensitive circuitry,
preserving signal integrity can be coatings on the electrodes have
demonstrated as follows: a very limited effect on
flowmeter performance.
Quadrature
Wiring
Some magnetic flowmeters employ
alternating current to excite the In ac magnetic flowmeters, the
magnetic field coils which generate signal generated by flow through
the magnetic field of the flowmeter the meter is at line frequency.
(ac magnetic flowmeters). As a This makes these meters
result, the direction of the magnetic susceptible to noise pickup from any
field alternates at line frequency, ac lines. Therefore, complicated
i.e., 50 to 60 times per second. wiring systems are typically required
If a loop of conductive wire is to isolate the ac flowmeter signal
located in a magnetic field, a lines from both its own and from any
voltage will be generated in that other nearby power lines, in order to
loop of wire. From physics, we can preserve signal integrity.
determine that this voltage is 90° In comparison, dc pulse magmeters
out of phase with respect to have a pulse frequency much lower
the primary magnetic field. (typically 5 to 10% of ac line Figure 3: Vertical installation of inline meter
H-5
Auto-Zero
In traditional ac magnetic
flowmeters, it is necessary after
installation of the meter to “null”
or “zero” the unit. This is
accomplished by manual
adjustment which requires that the
flowmeter be filled with process
liquid in a no-flow condition.
Any signal present under full pipe,
no-flow conditions is considered
to be an error signal. The ac field
magmeter is therefore “nulled”
to eliminate the impact of these
error signals.
In the case of OMEGA® FMG-400
Series Magmeters, automatic
zeroing circuitry has been included
to eliminate the need for manual
zeroing. When the magnetic field
strength is zero between pulses,
the voltage output from the Figure 4: Horizontal installation of in-line meter
electrodes is measured. If any
voltage is measured during this or can arise by induction from
period, it is considered extraneous threading the piping system into
the tee fitting supplied with the electromagnetic fields in the same
noise in the system and is area as the magmeter. Grounding is
subtracted from the signal voltage meter, or by drilling a tap into the
generated when the magnetic field line to accept the fitting that comes
with the meter.
achieved by connecting the piping
system and the flowmeter to a
H
is on. This feature insures high proper earth ground system.
accuracy, even in electrically noisy Prior to installation of the meter, the
following recommendations and Unfortunately, this is not always
industrial environments. done properly, resulting in
items of general information should
Installation be considered. unsatisfactory meter performance.
In conductive piping systems, a
OMEGA® magnetic flowmeters are First, before installing a magmeter, “third wire” safety ground to the
designed for easy installation. it is important to consider location. power supply and a conductive path
FMG-400 Series Magmeters are Stray electromagnetic or between the meter and the piping
ideal substitutes for the flanged electrostatic fields of high intensity flanges are typically all that is
spool type meter, which are heavier may cause disturbances in normal required. In non-conductive or lined
and significantly more expensive. operation. For this reason, it is piping systems, a protective
The thin wafer style of the FMG-400 desirable to locate the meter away grounding orifice must be supplied
Series allows them to be slipped from large electric motors, to provide access to the potential of
between standard flanges, without transformers, communications the liquid being metered. Dedicated
the need to cut away pipe to make equipment, etc., whenever possible. or sophisticated grounding systems
room for the meter. Furthermore, Second, for proper and accurate are not normally required. Detailed
the low weight of the meter means operation, it is necessary that the information concerning proper
that, in many cases, no additional flowmeter be installed so that the flowmeter grounding is provided
pipe supports are required after pipe will be full of the process liquid with the owner’s manual that comes
meter installation. Recommended under all operating conditions. with each flowmeter.
piping configurations include When the meter is only partially
the installation of by-pass piping, Finally, the position of the flowtube
filled, even though the electrodes in relation to other devices in the
cleanout tees and isolation valves are covered, an inaccurate
around the flowmeter system is also important in assuring
measurement will result. system accuracy. Tees, elbows,
(Figures 3 and 4).
Third, for magnetic flowmeters, valves, etc., should be placed at
With insertion-style magmeters, grounding is required to eliminate least 10 upstream and 5
even greater reductions in weight stray current and voltage which may downstream pipe diameters away
and cost have been achieved. be transmitted through the piping from the meter to minimize any
Installation is accomplished by system, through the process liquid, obstructions or flow disturbances.