You are on page 1of 17

InteliLite 4

New Single gen-set controllers


Overview

Advanced IL4
› AMF 25 (LT)
› MRS 16 (LT)
› AMF 20
- L3 design -

Standard IL4
› AMF 9
› AMF 8
- IL9 design -
InteliLite 4 Advanced
HW Improvements

› USB Host
› Inbuild RS485 (AMF25 and MRS16)
› U/I/R AIN with +5V output reference
› E-Stop
InteliLite 4 Standard
HW Improvements

› U/I/R AIN with +5V output reference


› E-Stop
› Battery back up (full calendar)
› Unified connector layout
InteliLite 4
Extension modules - plug-in

› Communication modules:
» CM2-4G-GPS (incompatible with IL3)
• AirGate 2.0, SMS, E-mail, Locate, Tracking, Geo-Fencing
• Available Q1/2021

» CM3-Ethernet (incompatibe with IL3)


• AirGate 2.0, Modbus TCP, SNMP, E-mail
• Available Q1/2021

» CM-RS232-485
• direct connection, Modbus RTU

› Extension modules:
» EM-BIO8-EFCP
• 8x Binary input or output, Earth Fault current measurement (1A or 5A CT)
InteliLite 4
Extension modules - CAN

› Inteli AIN8
» 8 analog inputs (voltage, current, resistor)
› Inteli AIN8TC
» 8 analog inputs (Thermocouple)
› Inteli IO8/8
» 8 binary inputs, 8 binary outputs, and 2 analogue outputs
› Inteli IO16/0
» 16 binary inputs and 2 analogue outputs
› Inteli AIO9/1
» 9 Analog Inputs and 1 Analog Output
› IGL-PTM
» 8 binary and 4 analogue inputs, 8 binary and 1 analogue output
› IGL-RA15
» 15 programmable LEDs with configurable colours red-green-yellow
InteliLite 4
Extension modules – Remote Display

› Dedicated Remote Display FW´s


› Possible to upload into any IL4 controller
› Any IL4 controller can do Remote Display
› Connected by RS 485 / RS 232
InteliLite 4
SW improvements

All models support:

› Full remote communication


› AirGate 2.0
› PLC
› User Protections and User Setpoints
› User Access Management and Cyber security improvement
InteliLite 4
SW improvements

AirGate 2.0

› Provides better connectivity (latency, ready for more controllers)


› Improved security
› Redundancy
InteliLite 4
SW improvements

Extended PLC
Model IL4 AMF8 IL4 AMF9 IL4 AMF20 IL4 MRS16 IL4 AMF25

OR / AND 8 16 16 16 16
XOR / RS 1 2 2 8 8
Comp Hyst 1 2 2 4 4
Comp Time 0 2 2 2 2
Timer 0 1 1 2 2
Delay 2 4 4 8 8
Counter 0 0 0 2 2
InteliLite 4
SW improvements

User setpoints and protections


InteliLite 4
SW improvements

User Access Management and Cyber security improvement

› Up to 5 users where each has


» Username and Password (for access via InteliConfig or remote)
» UID and PIN (for access via controller screen)

› New warnings to push customers to set-up their own password and do not keep
controller in Production mode
InteliLite 4
SW improvements

New controller from production

› Production mode
» Is active
» You can upload FW without need to log-in
» => Wrn Production mode (to deactivate you need to swith-off production mode)

› Default user
» Username: „administrator“
» Password: „controller serial number“
» UID: „0001“
» PIN: „0000“
» => Wrn Default password (to deactivate you need to change password)
InteliLite 4
All benefits from IL3 are here

› InteliConfig
› Detailed history log
› Simulator tools (StarterKit)
› Intuitive UI
›…
InteliLite 4 MODEL
Order code
IL-NT AMF25
IL-NT AMF25
IL9
IL3AMF9XBAA
IL4 AMF8
IL4AMF8XBAA
IL4 AMF9
IL4AMF9XBAA
IL4 AMF20
IL4AMF20BAA
IL4 MRS 16 / AMF25
IL4MRS16BAA / IL4AMF25BAA
Back-lit symbols × × × × ● ●
Overview Cut-out IL-NT IL-NT IL-NT / IL9 IL3 / IG200 / IG500
BINs 7 6adsf 6 + 1 6+1 8+1 6+1 8+1
BOUTs 7 1
6 6 8 6 8
AIN (U/I/R) 3 (R) 3 (R) 3 3 3 4
5V reference output × × ● ● ● ●
Magnetic pick-up ● ● ● ● ● ●
RTC (incl. Battery backup) ● ● (no battery) ● ● ● ●
CAN (ECU) ● ● ● ● ● ●
RS485 (on board) × × × × × ●
USB Host (on board) × × × × ● ●
USB Device (on board) × ● ● ● ● ●
Low Temp version ● × × ready × ●
Plug-in modules 1+1 1 1 1 2 2
CAN modules 2 × 2 2 5 5
AirGate / WSV ● × ● ● ● ●
PLC × × PLC - PLC - PLC PLC+
History records 100 150 150 150 350 350
Password level 1 3 3 3 3 3
Alternative configuration 2 3 3 3 3 3
Calendar/Scheduler 2 2 2 2 4 4
Language support 2 5 5 5 5 5
Dual AMF / MRS ● × × ● × ●
Remote display support ● ● ● ● ● ●
Load Shedding × × 2 2 5 5
Maintenance Timers 1 3 3 3 3 3
Analogue switch × × × × × 4
User Setpoints × × 64 64 128 128
User Protections × × 32 32 32 32
User Buttons × × 4 4 4 8
Gas Engine Support ● × × ● × ●
Dual Starter × × × ● × ●
Pulse Counter × × × × × ●

You might also like