You are on page 1of 2

Interlocking

Totally Integrated
Automation Portal

Release Disconnector

Q1

AND10

Q0 CB.Circuit break..Position.open [BOOL] X1 Y Q1 DC.Interlocking.>Enable closing [BOOL]


Signal.Interlocking.Release DC [BOOL] X2 Q1 DC.Interlocking.>Enable opening [BOOL]
Signal.Feeder Alarm.MCU OK, Lever not insert [BOOL] X3
Signal.Interlocking.Block all SW operation [BOOL] X4
Q5 ES.Earthing Switch.Position.open [BOOL] X5

Release Earthing Switch

Q5
Interlocking - Data flow/Task: Event-triggered

AND10

Q0 CB.Circuit break..Position.open [BOOL] X1 Y Q5 ES.Interlocking.>Enable closing [BOOL]


Signal.Interlocking.Release ES [BOOL] X2 Q5 ES.Interlocking.>Enable opening [BOOL]
Signal.Interlocking.Block all SW operation [BOOL] X3
Signal.Feeder Alarm.MCU OK, Lever not insert [BOOL] X4
Q1 DC.Disconnector.Position.open [BOOL] X5

Release Circuit Breaker

Q0 close

AND10

Signal.Feeder Alarm.MCU OK, Lever not insert [BOOL] X1 Y Q0 CB.Interlocking.>Enable closing [BOOL]
Signal.CB ready.CB ready [BOOL] X2
Signal.Interlocking.Block all SW operation [BOOL] X3

Q0 open

AND10

Signal.Interlocking.Block all SW operation [BOOL] X1 Y Q0 CB.Interlocking.>Enable opening [BOOL]


1 X2
Totally Integrated
Automation Portal

Interlocking - Control flow/Task: Event-triggered


Run se‐ Object/parameter Operand Type Task Additional Comment
quence tasks
AND10 Q1 AND10 default

AND10 Q5 AND10 default

AND10 Q0 close AND10 default

AND10 Q0 open AND10 default

You might also like