AND10
AND
User Defined Signals.GD1 GAS PR 2ST STG AL [BOOL] X1 Y
User Defined Signals.GD2 GAS PR 2ST STG AL [BOOL] X2
User Defined Signals.GD3 GAS PR 2ST STG AL [BOOL] X3
User Defined Signals.GD8 GAS PR 2ST STG AL [BOOL] X4
Totally Integrated

User Defined Signals.GD9 GAS PR 2ST STG AL [BOOL] X5


Automation Portal

User Defined Signals.GD1 GAS PR 3ST STG AL [BOOL] X6


User Defined Signals.GD2 GAS PR 3ST STG AL [BOOL] X7
User Defined Signals.GD3 GAS PR 3ST STG AL [BOOL] X8
User Defined Signals.GD8 GAS PR 3RD STG AL [BOOL] X9 and10_16
User Defined Signals.GD9 GAS PR 3RD STG AL [BOOL] X10 AND10
AND
X1 Y ISO_89A.Interlocking.>Enable closing [BOOL]
X2
ISO_89A.Disconnector.Position.open [BOOL] X3

and10_1

AND10
AND
CB.Circuit break..Position.open [BOOL] X1 Y
ISO_89B.Disconnector.Position.open [BOOL] X2
ESW_89AE.Disconnector.Position.open [BOOL] X3
User Defined Signals.M1 ESA OPEN [BOOL] X4 or10_1
User Defined Signals.LCC IN REMOTE [BOOL] X5 OR10
User Defined Signals.N/M SWT IN NRML MODE [BOOL] X6 OR
X1 Y
CB/ISO&ESW INTERLOCK - Data flow/Task: Interlocking (1.1 / 3.2)

X2

and10_2

AND10
AND
ESW_89AE.Disconnector.Position.open [BOOL] X1 Y
User Defined Signals.M1 ESA OPEN [BOOL] X2
User Defined Signals.LCC IN REMOTE [BOOL] X3
CB.Circuit break..Position.closed [BOOL] X4
ISO_89B.Disconnector.Position.closed [BOOL] X5

2.1 ( Page1 - 4)
User Defined Signals.N/M SWT IN NRML MODE [BOOL] X6
User Defined Signals.66KV B/C CLOSED [BOOL] X7 and10_17

AND10
AND
X1 Y ISO_89A.Interlocking.>Enable opening [BOOL]
User Defined Signals.GD2 GAS PR 2ST STG AL [BOOL] X2
User Defined Signals.GD2 GAS PR 3ST STG AL [BOOL] X3
ISO_89A.Disconnector.Position.closed [BOOL] X4

1.2 ( Page1 - 3)
1.1 ( Page1 - 2)

and10_5

AND10
AND
Totally Integrated
Automation Portal

ESW_89CE.Disconnector.Position.open [BOOL] X1 Y ISO_89C.Interlocking.>Enable closing [BOOL]


CB.Circuit break..Position.open [BOOL] X2 ISO_89C.Interlocking.>Enable opening [BOOL]
ESW_89_EST.Disconnector.Position.open [BOOL] X3
User Defined Signals.LCC IN REMOTE [BOOL] X4
User Defined Signals.N/M SWT IN NRML MODE [BOOL] X5
User Defined Signals.GD4 GAS PR 2ST STG AL [BOOL] X6
User Defined Signals.GD4 GAS PR 3ST STG AL [BOOL] X7
User Defined Signals.GD5 GAS PR 2ST STG AL [BOOL] X8
User Defined Signals.GD6 GAS PR 2ND STG AL [BOOL] X9

and10_8

AND10
AND
ISO_89C.Disconnector.Position.open [BOOL] X1 Y ESW_89_EST.Interlocking.>Enable closing [BOOL]
User Defined Signals.N/M SWT IN NRML MODE [BOOL] X2 ESW_89_EST.Interlocking.>Enable opening [BOOL]
CB/ISO&ESW INTERLOCK - Data flow/Task: Interlocking (1.2 / 3.2)

User Defined Signals.LCC IN REMOTE [BOOL] X3

2.2 ( Page1 - 5)
and10_14

AND10
AND
Totally Integrated

User Defined Signals.LCC IN REMOTE [BOOL] X1 Y CB.Interlocking.>Enable opening [BOOL]


Automation Portal

User Defined Signals.N/M SWT IN NRML MODE [BOOL] X2


User Defined Signals.GD1 GAS PR 2ST STG AL [BOOL] X3
User Defined Signals.GD1 GAS PR 3ST STG AL [BOOL] X4
CB.Circuit break..Position.closed [BOOL] X5

and10_10

AND10
AND
CB.Circuit break..Position.open [BOOL] X1 Y CB.Interlocking.>Enable closing [BOOL]
X2

and10_9

AND10
AND
User Defined Signals.CB SPR DISCHARGED [BOOL] X1 Y
User Defined Signals.N/M SWT IN NRML MODE [BOOL] X2
User Defined Signals.LCC IN REMOTE [BOOL] X3
User Defined Signals.GD1 GAS PR 2ST STG AL [BOOL] X4
User Defined Signals.86.1 RELAY OPTD [BOOL] X5
User Defined Signals.86.2 RELAY OPTD [BOOL] X6
CB/ISO&ESW INTERLOCK - Data flow/Task: Interlocking (2.1 / 3.2)

User Defined Signals.96 RELAY OPTD [BOOL] X7


X8
X9
User Defined Signals.GD1 GAS PR 3ST STG AL [BOOL] X10

or10_3

OR10
OR
User Defined Signals.TC-1 FAULTY [BOOL] X1 Y

3.1 ( Page1 - 6)
1.1 ( Page1 - 2)

User Defined Signals.TC-2 FAULTY [BOOL] X2

and10_6

AND10
AND or10_4
ISO_89A.Disconnector.Position.open [BOOL] X1 Y OR10
ISO_89B.Disconnector.Position.closed [BOOL] X2 OR
ISO_89C.Disconnector.Position.closed [BOOL] X3 X1 Y
X2

and10_7

AND10
AND
ISO_89A.Disconnector.Position.closed [BOOL] X1 Y
ISO_89B.Disconnector.Position.open [BOOL] X2
ISO_89C.Disconnector.Position.closed [BOOL] X3

2.2 ( Page1 - 5)
2.1 ( Page1 - 4)

and10_11

AND10
AND
User Defined Signals.GD1 GAS PR 2ST STG AL [BOOL] X1 Y
User Defined Signals.GD2 GAS PR 2ST STG AL [BOOL] X2
Totally Integrated
Automation Portal

User Defined Signals.GD3 GAS PR 2ST STG AL [BOOL] X3


User Defined Signals.GD8 GAS PR 2ST STG AL [BOOL] X4
User Defined Signals.GD9 GAS PR 2ST STG AL [BOOL] X5
User Defined Signals.GD1 GAS PR 3ST STG AL [BOOL] X6
User Defined Signals.GD2 GAS PR 3ST STG AL [BOOL] X7
User Defined Signals.GD3 GAS PR 3ST STG AL [BOOL] X8
User Defined Signals.GD8 GAS PR 3RD STG AL [BOOL] X9 and10_12
User Defined Signals.GD9 GAS PR 3RD STG AL [BOOL] X10 AND10
AND
X1 Y ISO_89B.Interlocking.>Enable closing [BOOL]
ISO_89B.Disconnector.Position.open [BOOL] X2
X3

and10_3

AND10
AND
CB.Circuit break..Position.open [BOOL] X1 Y
ISO_89A.Disconnector.Position.open [BOOL] X2
ESW_89AE.Disconnector.Position.open [BOOL] X3
User Defined Signals.M2 ESB OPEN [BOOL] X4
User Defined Signals.LCC IN REMOTE [BOOL] X5
User Defined Signals.N/M SWT IN NRML MODE [BOOL] X6 or10_2
CB/ISO&ESW INTERLOCK - Data flow/Task: Interlocking (2.2 / 3.2)

OR10
OR
X1 Y
and10_4 X2

AND10
AND
ESW_89AE.Disconnector.Position.open [BOOL] X1 Y
User Defined Signals.M2 ESB OPEN [BOOL] X2
User Defined Signals.LCC IN REMOTE [BOOL] X3

3.2 ( Page1 - 7)
1.2 ( Page1 - 3)

User Defined Signals.N/M SWT IN NRML MODE [BOOL] X4


CB.Circuit break..Position.closed [BOOL] X5
ISO_89A.Disconnector.Position.closed [BOOL] X6
User Defined Signals.66KV B/C CLOSED [BOOL] X7 and10_13

AND10
AND
X1 Y ISO_89B.Interlocking.>Enable opening [BOOL]
User Defined Signals.GD3 GAS PR 2ST STG AL [BOOL] X2
User Defined Signals.GD3 GAS PR 3ST STG AL [BOOL] X3
ISO_89B.Disconnector.Position.closed [BOOL] X4
Totally Integrated
Automation Portal

CB/ISO&ESW INTERLOCK - Data flow/Task: Interlocking (3.1 / 3.2)


2.1 ( Page1 - 4)

3.2 ( Page1 - 7)
Totally Integrated
Automation Portal

CB/ISO&ESW INTERLOCK - Data flow/Task: Interlocking (3.2 / 3.2)


2.2 ( Page1 - 5)
3.1 ( Page1 - 6)
Totally Integrated
Automation Portal
Totally Integrated
Automation Portal

CB/ISO&ESW INTERLOCK - Control flow/Task: Interlocking


Run se‐ Object/parameter Operand Type Task Additional Comment
quence tasks
AND10 and10_6 AND10 default

AND10 and10_7 AND10 default

AND10 and10_1 AND10 default

AND10 and10_2 AND10 default

AND10 and10_3 AND10 default

AND10 and10_4 AND10 default

OR10 or10_4 OR10 default

OR10 or10_3 OR10 default

OR10 or10_1 OR10 default

OR10 or10_2 OR10 default

AND10 and10_11 AND10 default

AND10 and10_15 AND10 default

AND10 and10_9 AND10 default

AND10 and10_8 AND10 default

AND10 and10_5 AND10 default

AND10 and10_12 AND10 default

AND10 and10_13 AND10 default

AND10 and10_14 AND10 default

AND10 and10_16 AND10 default

AND10 and10_17 AND10 default

AND10 and10_10 AND10 default

You might also like