EXCITATION SYSTEM UNITROL5000 UNITROL

Gate Driver Interface GDI


UNS 0881a-P, V1/V2
Datenblatt

FEATURES
• Final pulse stage for a DB6 or B2-thyristor bridge.
• Suitable for disc-type thyristor up to 4".
• internal or external pulse transformer

SHORT DESCRIPTION
The gate driver interface GDI is used for remote operation of a single or 3-phase converter bridge.
All converter control functions have to be included in a previous device (normally in Converter
Interface UNS 0880).
The typical application of this device is in excitation installations with the following functions in
particular:
- Final pulse stage for a DB6- or B2-thyristor bridge with one thyristor per thyristor bridge
branch. The applicable range is 1.5" up to 4" thyristors.

Device Context

CIN GDI

Ausgest: Dok.-Art Format Sprache Seite


Rev.
a c 00-01-07 Ru
Änd. Geprüft:
b d 00-01-12 Ro
Zust. Stelle Übern. Stelle
e Normgepr.:
TA A4 E 1 11
Entst. aus / Ers. f.: Freigeg.:
00-01-13 Ru
ICT1 Ersetzt durch: 3BHS 107542 E01
-2- UNS 0881a-P, V1/V2

TABLE OF CONTENTS

FEATURES .................................................................................................................................... 1
SHORT DESCRIPTION.................................................................................................................. 1

1 DEVICE BLOCK DIAGRAM........................................................................................... 3


2 FUNCTIONAL DESCRIPTION ....................................................................................... 3
2.1 Schematic Diagram ........................................................................................................ 3
2.2 Final Puls Stage ............................................................................................................. 4
2.3 Power Supply ................................................................................................................. 4
3 CONFIGURATION ......................................................................................................... 5
3.1 Pulsinputs and Supply .................................................................................................... 5
3.2 Pulse outputs.................................................................................................................. 5
3.3 Earthing .......................................................................................................................... 5
4 COMMISSIONING AND FUNCTION CONTROL ........................................................... 5
4.1 Connections ................................................................................................................... 5
4.2 Function Check .............................................................................................................. 5
5 TECHNICAL DATA ........................................................................................................ 6
5.1 Input Characteristics....................................................................................................... 6
5.1.1 Power Supply ................................................................................................................. 6
5.1.2 Firing Pulse Inputs.......................................................................................................... 6
5.2 Output Characteristics .................................................................................................... 6
5.2.1 Firing Pulse Outputs ....................................................................................................... 6
5.2.2 External Pulse Transformer ............................................................................................ 7
5.3 Settings .......................................................................................................................... 7
5.4 Environmental Characteristics ........................................................................................ 7
5.4.1 Environmental Values..................................................................................................... 7
5.4.2 Permissible Ambient Temperature.................................................................................. 7
5.4.3 Climatic Stability ............................................................................................................. 7
5.4.4 Mechanical Stability ........................................................................................................ 7
5.4.5 EMC (Electromagnetic Compatibility) Immunity Tests .................................................... 8
5.4.6 Altitude of Installation ..................................................................................................... 8
5.4.7 Protection Means............................................................................................................ 8
5.4.8 Test Voltages ................................................................................................................. 8
5.5 Reliability ........................................................................................................................ 8
6 CONSTRUCTION DATA ................................................................................................ 9
6.1 Dimensions..................................................................................................................... 9
6.2 Weight ............................................................................................................................ 9
6.3 Operating, Indicator and Control Elements ..................................................................... 9
6.4 Connectors ..................................................................................................................... 9
6.5 Connection Assignments, Signal Designation ................................................................ 9
6.6 Mechanical Drawing ..................................................................................................... 11
7 ORDER INFORMATION............................................................................................... 11

3BHS107542 E01
-3- UNS 0881a-P, V1/V2

1 DEVICE BLOCK DIAGRAM


(see operating instructions)

2 FUNCTIONAL DESCRIPTION

2.1 Schematic Diagram

GDI
r- G_R-
X113/7 X11
X113/8 A
C_R-
X12
X13
24V X14
X15

r+ G_R+
X113/1 X21
X113/2 B
C_R+
X22
X23
24V X24
X25

s- G_S-
X113/9 X31
X113/10 C
C_S-
X32
X33
24V X34
X35

s+ G_S+
X113/3 X41
X113/4 D
C_S+
X42
X43
24V X44
X45

t- G_T-
X113/11 X51
X113/12 E
C_T_
X52
X53
24V X54
X55

t+ G_T+
X113/5 X61
X113/6 F
C_T+
X62
X113/19 X63
24V 24V
X113/20 X64
X113/13 X65
X113/14 GND
nur in Var.2

X1 X2

3BHS107542 E01
-4- UNS 0881a-P, V1/V2

2.2 Final Puls Stage


The module contains six identical 24 Volt final stages for controlling the corresponding disc-type
thyristors (1.5" up to 4" disc diameter).
The pulse inputs are intended to be used with the control unit CIN (UNS 0880) but can be
connected to any other pulse source which provides similar pulse chains.
The amplified and adapted to 24 Volt level pulses are passed to a circuit to increase their
steepness. The circuit comprises RC elements. The module transfers the output pulses to the
Faston 6,3 mm terminals

The device is available in two versions. The version 1 includes the pulse transformers which have
a maximum of 5kV isolation voltage. The module is equipped with demagnetizing cirquits adapted
to the pulse transformers.

The version 2 must be used for higher isolation voltages. In this version the pulse transformers are
not fitted and therefore, must be mounted externally. For this purpose, corresponding connectors
are provided.

detailed Schematic Diagram of one channel

in Var.1

+ 24 V

GND

Pulse

2.3 Power Supply


The 24 V input voltage is buffered by a capacitor to minimise the feedback to the 24 V supply due
to the firing pulses

3BHS107542 E01
-5- UNS 0881a-P, V1/V2

3 CONFIGURATION

3.1 Pulsinputs and Supply


The pulse as well as the supply are to be connected to the connector X113 through the flat cable.
This cable should be as short as possible.

3.2 Pulse outputs


The pulse outputs are normally wired to the thyristors directly by means of Faston connectors. In
version 2, an additional earthing contact is provided for the connection of a shielded cable.

3.3 Earthing
The earthing is available on one hand via the fixing bolts and on the other hand, a Faston
connector to earthing.

4 COMMISSIONING AND FUNCTION CONTROL

4.1 Connections
Check of all external connections
Check of flatcable according to the specification in chapter 6
Check of correct earthing

4.2 Function Check


A separate function check of the device is not necessary. A probable malfunction is detected by
the system.

3BHS107542 E01
-6- UNS 0881a-P, V1/V2

5 TECHNICAL DATA

5.1 Input Characteristics

5.1.1 Power Supply


rated voltage Un 24 V
permissible voltage range 22,8...26,4 V
current consumption (all pulses activated = fire all) 1,4 A

5.1.2 Firing Pulse Inputs


"0" signal (active pulse) Gnd + 1,5V
"1" signal (dip pulse) open
8us
8us

120°el

Pulse shapes of pulse input signals (Pulse train)

5.2 Output Characteristics

5.2.1 Firing Pulse Outputs


Typical characteristics of the pulse current with the RC-circuit on:

Gatecurrent on 4 inch Thyristor


(minimum values)
ip1 >2,0A
edge >1,5A/µs
ip2 (5.Puls) >0,8A

3BHS107542 E01
-7- UNS 0881a-P, V1/V2

5.2.2 External Pulse Transformer


Type T60407-B4803-X010

5.3 Settings
not applicable.

5.4 Environmental CharacteristicsEnvironmental Values


Remark:
[HQ SN-62.1008d] is a Hydro Quebec Product Standard
[EN 50081-2, EN 50082-2] are European Generic Standards
IEC/EN 60…, IEC/EN 61…, IEEE-STD are Basic Standards
The UN 5000 system fulfils all the requirements of the above product and generic standards.

5.4.2 Permissible Ambient Temperature


Keeping the technical data 0 ... + 55 °C
Operable 0 ... + 70 °C
Storage temperature - 25 ... + 85 °C

5.4.3 Climatic Stability


Cold Test
according to: IEC 60068-2-1 [HQ SN-62.1008d] Test Ad
-25 °C, 2h
Dry Heat
according to: IEC 60068-2-2 [HQ SN-62.1008d] Test Bd
55 °C, 16h
Damp Heat
according to: IEC 60068-2-3 [HQ SN-62.1008d] Test Ca
40 °C, 4 days
93 +2/-3 %

5.4.4 Mechanical Stability


Vibration test
according to IEC 60255-21-1 [HQ SN-62.1008d]
Response test, Class 2 2…150 Hz, a=2g
Endurance test, Class 2 2…150 Hz, a=2g
Seismic test 2…35 Hz
according to IEC 60255-21-3 and IEEE-STD 344-1987 2 g in each axis
according to IEEE-STD 344-1987 5 g in each axis

3BHS107542 E01
-8- UNS 0881a-P, V1/V2

5.4.5 EMC (Electromagnetic Compatibility) Immunity Tests

Radiated Interference Immunity


according to IEC/EN 61000-4-3 [EN 50082-2 / HQ SN-62.1008d]
Class 3 10 V/m
80 ... 1000 MHz
Performance criteria [IEC/EN] A
[HQ SN-62.1008d] N1

5.4.6 Altitude of Installation


according to IEC 68-2-13 max. 2'000 meters above sea-level
(without derating)

5.4.7 Protection Means


according to DIN 40050 IP 10

5.4.8 Test Voltages


Test AC voltage (frequency/duration) 50 Hz / 1 min.

Pulse channels Var.1 with pulsetransformer


input output 5 kV eff
between outputs 5 kV eff
Insulation distance
Clearance in respect to mass 12 mm
between phases 14 mm
in respect to electronics 21 mm
Creepage distance in respect to mass 17 mm
between phases 14 mm
in respect to electronics 21 mm

5.5 Reliability
Failure rate
Condition: GB, 40 °C 712 FIT

3BHS107542 E01
-9- UNS 0881a-P, V1/V2

6 CONSTRUCTION DATA
6.1 Dimensions
PCB (LxWxH) 270x100x40 [mm]

6.2 Weight
Mass depending on variants: Var. 1 0.32 kg
Var. 2 0.12 kg

6.3 Operating, Indicator and Control Elements


not applicable

6.4 Connectors
Puls and Supply inputs X113 20-pole flat cable
Grounding Terminals X1, X2 Faston 6,3 mm
Pulse outputs 6-channels Double Faston block 6,3 mm

6.5 Connection Assignments, Signal Designation

X113 Flatcable Connection to UNS 0880


Pin Designation Signal-Designation Function Signal
1 r+ pulse input r+ in
2 r+ pulse input r+ in
3 s+ pulse input s+ in
4 s+ pulse input s+ in
5 t+ pulse input t+ in
6 t+ pulse input t+ in
7 r- pulse input r- in
8 r- pulse input r- in
9 s- pulse input s- in
10 s- pulse input s- in
11 t- pulse input t- in
12 t- pulse input t- in
13 GND Ground in
14 GND Ground in
15 NC
16 NC
17 NC
18 NC
19 + 24 V supply input in
20 + 24 V supply input in

3BHS107542 E01
- 10 - UNS 0881a-P, V1/V2

X113 Faston Connection to Thyristor / Pulse Transformer


Pin Designation Signal-Designation Function Signal flow
X11 G_R- Gate R- out Var.1 only
X12 C_R- Cathode R- out Var.1 only
X13 R- output to Pulse transformer out Var.2 only
X14 +24V supply Pulse transformer out Var.2 only
X15 PE Ground out Var.2 only
X21 G_R+ Gate R+ out Var.1 only
X22 C_R+ Cathode R+ out Var.1 only
X23 R+ output to Pulse transformer out Var.2 only
X24 +24V supply Pulse transformer out Var.2 only
X25 PE Ground out Var.2 only
X31 G_S- Gate S- out Var.1 only
X32 C_S- Cathode S- out Var.1 only
X33 S- output to Pulse transformer out Var.2 only
X34 +24V supply Pulse transformer out Var.2 only
X35 PE Ground out Var.2 only
X41 G_S+ Gate S+ out Var.1 only
X42 C_S+ Cathode S+ out Var.1 only
X43 S+ output to Pulse transformer out Var.2 only
X44 +24V supply Pulse transformer out Var.2 only
X45 PE Ground out Var.2 only
X51 G_T- Gate T- out Var.1 only
X52 C_T- Cathode T- out Var.1 only
X53 T- output to Pulse transformer out Var.2 only
X54 +24V supply Pulse transformer out Var.2 only
X55 PE Ground out Var.2 only
X61 G_T+ Gate T+ out Var.1 only
X62 C_T+ Cathode T+ out Var.1 only
X63 T+ output to Pulse transformer out Var.2 only
X64 +24V supply Pulse transformer out Var.2 only
X65 PE Ground out Var.2 only

3BHS107542 E01
- 11 - UNS 0881a-P, V1/V2

6.6 Mechanical Drawing

X2

262,5

X65
X63
X61

X62
F

X53 X64
X55
X51
X52
E

X43 X54
177,5

X45

X41
X42
D

X33 X44

270
X35

X31
X32
C

X23 X34
X25
92,5

X21
X22
B

X13 X24
X15

X11
X12

X113
A

X14

X1
7,5

10
90
100,2

7 ORDER INFORMATION
Order information for UNS 0881a-P, V1: 3BHB 006338R0001
UNS 0881a-P, V2: 3BHB 006338R0002

external pulse transformer 3BHB 004719R0001

3BHS107542 E01