Professional Documents
Culture Documents
Display
Panel
J28 Connector
FIGURE 1. REMOTE HMI220 CONTROL PANEL
J29 Connector
GENERAL PRECAUTIONS
Read these installation instructions completely and
become familiar with safety warnings, cautions, and
the installation procedure before starting.
WARNING Incorrect installation can result in
severe personal injury or death and/or equip-
ment failure or damage. This kit must be
FIGURE 2. REMOTE HMI320 CONTROL PANEL installed by service personnel who are trained
and experienced to perform electrical and me-
Verify that the following items are included in the kit. chanical service.
A041J096 (Issue 3)
Copyright 2016 Cummins Inc. Page 2 of 10
HMI Connections This connector is oriented the same way it is ori-
ented in Figure 4.
Before the installation, become familiar with the
HMI connectors called out in Figure 4. TABLE 2. J28 PIN ASSIGNMENTS
FUNCTION /
PIN DESCRIPTION
CONNECTS TO
J28-1 Fused B+ B+ supply to HMI
J28
J28-2 N/A
TB15 Connections
J29
B+
B+ 3
RS-485+ 4
RS-485−
5 F2
BI_DIR WAKEUP
RXEF025
CON1X5
(In the control board) MOLEX_39870_0505
CON2X2
AMP_1_770174_0 FIGURE 8. TB15 PINS
2
CONNECTS TO
TB15-1 RS-485 Shield Network Shield
TB15-2 N/A
4
TB15-3 RS-485 Data Network Data A
FIGURE 6. J28 PINS A/Modbus
TB15-4 RS-485 Data Network Data B
B/Modbus
TB15-5 System Wakeup
6 1A Inrush
30 VDC
100A Off State Leakage
1
J29-5 B+ Return
J29-7 N/A
J29-8 N/A
J29-11 N/A
J29-12 N/A
J29-13 N/A
J29-14 N/A
J29-15 N/A
INSTALLATION 4. Depending upon the distance from the
genera-tor set, complete the wiring appropriate
1. Make sure the generator set is shut down and for your installation.
disabled. Less than 200 feet (61 meters) − go to
step 5
a. Place the generator set control in the Off
mode. Between 200 feet (61 meters) and 500
feet (152.4 meters) − go to step 6.
b. Turn off and disconnect the battery char- More than 500 feet (152.4 meters) − go
ger (if equipped). to step 7.
c. Disconnect the negative (−) cable from the 5. If the HMI is installed less than 200 feet (61
battery to prevent accidental starting. me-ters) from the generator set, complete the
wir-ing from the HMI to the control on the
WARNING Ignition of explosive battery generator set.
gases can cause severe personal injury. Do
not smoke or cause any spark, arc, or flame a. Install socket contact pins on the ends of
while servicing batteries. the wires that will be installed on the J28
and J29 connectors.
2. Mark and cut out an area for mounting the con-
trol panel, using the template provided in Fig-ure b. Install the wires with the contact pins in
14. Drill holes for securing the control pan-el. the appropriate locations on the J28 and J29
connectors (see Figure 13).
3. Mount the control panel and secure it with eight
M4 x 0.7 x 10mm pan head machine screws and c. Connect the other ends of the wires to
#10 split lock washers. the control base board (see Figure 13).
A041J096 (Issue 3)
Copyright 2016 Cummins Inc. Page 4 of 10
Remote HMI Terminal Block Control Base Board
At the Generator Set
Remote Start (Wake-Up)
J29-6 TB1-11
J28-1
B+ Return
J28-3 TB1-10
2 2
Short 16 AWG (1.31mm ) 14 AWG (2.08mm ) or Larger
FIGURE 10. HMI CONNECTIONS WITH TERMINAL BLOCK
6. If the HMI is installed more than 200 feet (61 tween the HMI and the terminal block for
meters) from the generator set, a terminal block the J29 connector and pin 3 on the J28
must be installed (see Figure 10). connector.
a. Install a terminal block near the remote c. Install socket contact pins on the ends of
HMI. all wires that will be installed on the J28
2 and J29 connectors.
b. Cut 16 AWG (1.31mm ) wire of the ap-
d. Install the wires with the contact pins in
propriate length for the connections be-tween the
HMI and the terminal block. the appropriate locations on the J28 and J29
connectors (see Figure 13).
c. Install socket contact pins on the ends of
e. Install wires of the appropriate size (see
the wires that will be installed on the J28 and J29
Table 1) from the terminal block to the con-trol
connectors. base board (see Figure 13) for the J29 and J28-3
d. Install the wires with the contact pins in connections. Connect J28-3 to TB1-10.
the appropriate locations on the J28 and J29 2
f. Use 16 AWG (1.31mm ) wire, connect
connectors (see Figure 13). wir-ing from the J28-3 to Iso(−) and J28-1 to
e. Connect the other ends of the wires to Iso(+) on the isolated power supply.
the terminal block. 8. Plug the J28 connector into the HMI and apply
power to the HMI through the J28 connector.
f. Install wires of the appropriate size (see
Table 1) from the terminal block to the con-trol 9. With J28 connected and J29 disconnected, ac-
base board (see Figure 13). cess the Cummins Power Generation InCal website
(http://www.cumminspower.com) and download
7. If the HMI is installed more than 500 feet from the latest InCal calibration file for your HMI.
the generator set, an isolated power supply must You must update the remote HMI cal-
be installed (see Figure 11).
libration with the same part number as
a. Install a terminal block near the remote the local HMI!
HMI.
10. Plug the J29 connector into the HMI.
2
b. Cut 16 AWG (1.31mm ) wire of the ap-
propriate length for the connections be-
Copyright 2016 Cummins Inc. Page 5 of 10 A041J096 (Issue 3)
When a remote HMI is installed that requires its own power supply, the remote power supply MUST
be a floating power supply.
PCC Remote HMI
J28-1
Internal (Power +)
Ground
A041J096 (Issue 3)
Copyright 2016 Cummins Inc. Page 6 of 10
POWER COMMAND 1.1/1.2/2.2/2.3
CUSTOMER CONNECTIONS
PCCNet must be
removed for the PC
tool to work.
NOTE: REMOTE HMI220 WILL NOT WORK WITH THE 3.3 CONTROL.
REMOTE HMI320 WILL WORK WITH THE 2.2/2.3/3.3 CONTROLS.
REMOTE HMI320 WILL NOT WORK WITH THE 1.1/1.2 CONTROLS.
A041J096 (Issue 3)
Copyright 2016 Cummins Inc. Page 8 of 10
R7
6mm 276mm
212mm
110.4mm
4.3mm
142.3mm
288mm
FIGURE 14. HMI CUTOUT TEMPLATE
A041J096 (Issue 3)
Copyright 2016 Cummins Inc. Page 10 of 10