You are on page 1of 4

The following article was published in ASHRAE Journal, April 2003.

© Copyright 2003 American Society of Heating, Refrigerating and Air-


Conditioning Engineers, Inc. It is presented for educational purposes only. This article may not be copied and/or distributed electronically or in
paper form without permission of ASHRAE.

By William Ryan, Ph.D, P.E. systems with multiple fan coils. All of
these systems are more expensive than
t the beginning of 2002, new technologies for gas cooling and single-zone systems, but provide greater
A cogeneration systems were emerged from the laboratory and comfort. Zoned hydronic heating sys-
tems, whether conventional or in-floor
the minds of designers. Today, some of these systems have been hydronic, provide multi-zone heating
installed and are being tested, including residential, light commercial, comfort but cannot handle cooling.
and central chiller plant systems. This article discusses why there is Gas Air Conditioners
so much interest in these systems and some of the demonstrations Small gas air conditioners, produced
that are currently underway. in large numbers in the 1960s, operated
on an ammonia water absorption cycle.
Large Residential Applications are designed with two independent By code, ammonia is not allowed within
Since 1970, the average new home size single-zone systems, often one upstairs residences in any quantity. Therefore,
has grown from less than 1,600 ft2 (149 and another downstairs. However, by the these systems have always been outdoor
m2) to more than 2,200 ft2 (204 m2). More time the home has increased to 4,000 ft2 air-cooled chillers that delivered chilled
than 10% of all new single-family de- (372 m2), four or more zones may be re- water to indoor cooling coils.
tached homes built today are more than quired. At this point, the conventional Such systems are at a distinct first-cost
4,000 ft2 (372 m2). design becomes complex and expensive disadvantage relative to a simple direct
These larger homes are at the high end with four or more independent condens- expansion system for small 3-ton (10.5
of the luxury market, where “high com- ing units decorating each wall of the kWc) single-zone homes. Although these
fort” heating and cooling options are re- home and operating noisily. Clearly, gas air-conditioning systems often were
quired. In addition, these large homes some other system that addresses the cheaper to operate, the savings were gen-
face some of the same HVAC design is- needs of these large homes is required. erally not enough to justify the added
sues as small commercial buildings. Commercial HVAC systems provide first cost and gas air conditioning fell
Traditionally, homes have been treated some design and equipment direction. from common usage.
as a single-zone system with heating and Novel residential systems that have come The revival of interest in gas air con-
cooling operating on one thermostat. to market for larger homes include: air ditioning is, in part, due to the benefits
When a large home is designed in this systems with power zoned air valves
About the Author
way, uneven temperature distribution (similar to VAV systems), multi-zone, mul- William Ryan, Ph.D., P.E., is senior researcher at
can become extreme. For this reason, tiple evaporator refrigerant-based fan the Energy Resources Center/Midwest CHP Ap-
many homes above 2,000 ft2 (186 m2) coil systems, and electric chilled water plications Center, University of Illinois at Chicago.

18 ASHRAE Journal ashrae.org April 2003


Gas Cooling

‘Traditionally,
homes have
been treated as a single- A California Test Case
zone system.... When a A demonstration of a high-end zoned gas
large home is designed in cooling system is being run in California.
Data monitoring is under sponsorship from
this way, uneven tempera- the Gas Technology Institute Cooling Solu-
tions Collaborative Research Program. Its
ture distribution can be- interest is in the potential for gas cooling to
come extreme.’ reduce peak summer electric demand on
generating and transmission systems.
The California residence is a 6,000 ft2
(557 m2), two-story home that has been
of chilled water. By providing cooling California home is split into 4 zones.
split into four major zones. Separate zones
with chilled water, the systems can be were installed for 1) upstairs bedrooms, 2) located outdoors, and the system is con-
zoned for the high-end residential mar- a family room-kitchen area, 3) an office area, trolled to provide 55°F (13°C)chilled water
ket (Figure 1). Adding a heating boiler and 4) the bathroom areas. Each zone is return water temperature, and 45°F (7°C)
can provide a fully zonable hydronic controlled by a different air handler located supply water to the building. The 45°F (7°C)
heating and cooling solution. In many in the attic space. water provides coil temperatures signifi-
The air handlers are equipped with sepa- cantly below those in most residential sys-
cases, this hydronic approach is close to
rate heating and cooling coils. Hot water is tems, leading to improved dehumidification.
the first cost of “high-end” zoned elec- supplied by small water heating packages The chilled water used in these systems
tric systems, while still maintaining op- with hydronic heating circulating pumps, is a combination of water and glycol that is
erating cost advantages (see sidebar, “A each located at the air handler. The chilled left in the system at all times, providing
California Test Case”). water system is supplied by two gas-fired freeze protection. Such systems have been
absorption air conditioners located together run in much colder climates such as Chi-
Another Approach to Gas Cooling outside the home. cago or Boston.
Each air handler is controlled by the zone The ammonia-water absorption units used
Taking the technology to a more ad-
thermostat and set up with three-way valves in this application have no crystallization is-
vanced stage, a field demonstration in on a bypass system. Controls lock the en- sues. These particular chillers are designed
Ohio is operating a “microcogeneration” tire system into either heating or cooling. for minimal capacity deterioration at higher
system, teaming a microturbine with a Three of the four zones are standard air- temperatures, with only a 6% decrease in
gas air conditioner converted to run on flow systems. The fourth system in the of- listed capacity at 105°F (41°C) and 10% at
the microturbine’s exhaust (Figures 2, 3 fice area is a high-pressure air system with 115°F (46°C), albeit with an increase in chilled
and 4). compact ductwork. water supply temperature. This is less of a
Four separate bathroom areas are each capacity reduction at high temperatures
One novel aspect of this particular
controlled by separate small fan/coil units, than standard electric units, and should al-
chiller is that it can be driven by either
bringing the total air handlers to seven. low less oversizing in hot desert climates, a
the exhaust gas or by direct gas firing, or Outdoors, two 5-ton (17.5 kWc) gas air- concern in much of California.
a combination of the two. This provides conditioning units are linked to act as one 10- One interesting feature of the installation
uninterrupted cooling even if the ton (33 kWc) chiller. At low load, only one of was that the home was completed before
microturbine exhaust is not available. the air conditioners serves the entire chilled the air conditioning was installed. The chilled
This is an important feature. If the gen- water system, while the other unit assists at water connections from the outdoor units to
erator is down for maintenance, the elec- higher loads. the copper piping system in the attic were
Making the system even more respon- done with a flexible plastic piping. This al-
tric load switches to the utility without
sive are the chiller’s air-cooled condenser lowed the chilled water lines to be “snaked”
interfering with building operation. cooling fans. Each unit has two fans, both through existing walls without demolition.
However, owners expect continuous cool- capable of two-speed operation. Controlled Although this particular application is in
ing operation. Providing two ways to fire by condenser pressure, the fans are cycled an unusually large home, such showcase
the cooling system increases reliability. on and the speed controlled in sequence, applications may pave the way for appli-
allowing each condenser to have four dif- cations of this system in the 3.2 million homes
Commercial Cooling ferent possible airflows. in the United States that are more than
Pumps for the chilled water system are 4,000 ft2 (372 m2).
Systems for larger light commercial
applications have been installed in
April 2003 ASHRAE Journal 19
Mexico, New York, and Boston.
T North
These systems deliver chilled wa- Facing
Control Cold Air Exterior
ter from multiple chillers all oper- Signal
Room
ating in sequence to meet varying
Exterior Fan Coil
building loads. Wall T Interior
Return
Water Cold Air Room

Larger Applications Absorption Chilled


Air Conditioner Water Fan Coil
A larger California cooling T South
Facing
plant is taking an entirely differ- Cold Air Exterior
ent approach to gas cooling. Cali- Room
fornia has some of the highest Fan Coil

electric prices in the country and Absorption


Air Conditioner
is still facing a tight electric sup- Circulation Pump
ply situation during hot weather.
Control Signal Aquastat
Gas chillers remove the chiller
load from the electric grid. Elimi- Figure 1: Typical layout for a gas air conditioner in a zoned system.
nating both the cooling system and
the attendant accessories from the
electric grid, and tying these sys- T
North
Facing
tems together for greater efficiency Exterior
improves the situation further. This Room

is just what has been done in one Exterior Fan Coil


Wall T Interior
smaller central plant in California. 30 kW Return
Micro- Room
Water
The system is shown in Figure 5. turbine Chilled
Water
Inside the cooling plant, a Hot Fan Coil South
Exhaust T
microturbine generates just Facing
Exterior
enough electricity to operate the Room
plant’s chilled water pump, chiller Fan Coil
solution pump and controls, and
Absorption
cooling tower pump and fan. The Air Conditioner
Circulation
exhaust heat from the microturbine Pump
passes to a double effect direct
fired absorption chiller. Figure 2: A microturbine produces enough exhaust to provide 8 to 10 tons of cooling.
This chiller, unlike units dis-
cussed previously, is of the more typical lithium bromide solu- above that seen in most cogeneration arrangements.
tion water-cooled variety. The unit used in this plant is a Looking at this system from the outside, this plant is a self-
customized version of a direct-fired double effect absorber. contained gas cooling “system.” Gas goes in — chilled water
The modifications allow the chiller to, once again, use a com- comes out. The system is installed as a freestanding central
bination of microturbine exhaust heat and direct gas firing. plant, feeding chilled water to other buildings.
However, this is a much larger capacity unit at 300 tons (1,050 The high-efficiency and self-contained nature of this sys-
kWc). The chiller is also a “chiller/heater” system, producing tem may be attractive for third-party owner or leasing arrange-
hot water when cooling is not needed. This makes the plant a ments. The system can also be viewed as a cogeneration option
self-contained, self-powered heating and cooling package. that requires none of the complexities or expense of grid inter-
The exhaust from the 60 kW microturbine is in the 550°F connection.
(288°F) range and carries enough unburned oxygen to serve as The chiller/microturbine plant began operation late Novem-
preheated combustion air for the chiller. ber 2001 (Figure 6). In this particular application, the
This layout resembles a cogeneration system. However, un- microturbine can also send power to other buildings when
like most cogeneration schemes, the electric load and the ther- cooling is not required, allowing the microturbine to operate
mal load are coincident as both follow the cooling load. As the full time. After some initial compatibility problems with other
microturbine exhaust heat is well below the overall heat re- controls systems at the site were settled, the turbine reached
quirements for this chiller, and the operation of the turbine and 5,400 hours of operation last July without incident.
chiller are coincident, the useful heat recovery can be well The chiller, which operates only as the cooling load occurs,
20 ASHRAE Journal ashrae.org April 2003
Gas Cooling

Figure 3: Test site for microturbine exhaust-driven cooling. Figure 4: Microturbine and exhaust-driven air conditioner.

operated for fewer hours. It has experienced no mechanical Tower Pump Chilled Water Pump
problems though controls required some fine adjustment in Electricity
midsummer. To
From Chilled
The task of defining an overall efficiency for this plant is Microturbine Water to
Tower
unusual — the outputs can be both cooling and power. How- Fan Building
ever, to focus on the cooling operation, the waste heat intro-
duced even by this comparatively small gas turbine contributed 300 ton
significantly enough to allow the gas only COP of the direct Absorption
Chiller on
fired absorber to frequently exceed 1.2 in actual run-of-plant Both
operation. Exhaust
60 Exhaust &
Heat to
kW Direct Gas
Absorber
Microturbine Firing
Conclusions Natural Gas
New gas cooling technologies and system arrangements are
finding their way into new applications such as high comfort Figure 5: A self-contained gas cooling system.
Power from microturbine drives chilled water pump, tower pump and
residential systems, small cogeneration systems, and even us-
fans. Microturbine exhaust heat aids in driving chiller.
ing a “cogeneration approach” to produce a higher efficiency
central cooling plant. The common message is the need to
take new technologies to the market in novel cooling system
designs that can truly capture their benefits.
In the long run, these systems demonstrate new thinking for
thermally activated cooling, ready for a future where the most
desirable heat source may be a gas burner, the generator in a
cogeneration system, or solar.
Will these systems find wider application? There is no way
to know which direction the market will take, but in changing
times the greatest risk is the risk not taken. With changes con-
tinuing in the energy industry, believing that the current, of-
ten “cookie cutter” approach, to HVAC design can continue in
the future may be the biggest risk of all.
Figure 6: Inside the chiller/microturbine plant.
Acknowledgments View shows the absorber (center) and microturbine (right).
The author would like to extend his thanks to the following
people for information used in the development of this ar- ing Technologies Corp.
ticle: Dave Kalensky at the Gas Technology Institute, Richard Figures 1, 2 and 5 are courtesy of UIC. Figures 3 and 4 are
Hobbs, Randall Higa, and Henry Mak of the Southern Califor- courtesy of Cooling Technologies. Figure 6 is courtesy of the
nia Gas Company, and Ronald Soka and Mark Birge of Cool- Southern California Gas Company.

April 2003 ASHRAE Journal 21

You might also like