CHECK PLUG

CHECK PLUG
13A SOCKET TESTER
The Martindale Check Plug Socket Tester is designed for the
fast and safe checking of 13Amp BS1363 sockets.
13A SOCKET TESTER Three indicator LED’s across the front of the unit provide a
clear indication of a correctly wired socket. A total of 32
CP501 Rapidly indicates wiring conditions are revealed, of which 28 are faults that
socket status require investigation.
SHOWS
The Check Plug’s moulded body gives lasting durability and
28 is maintenance free.
LONG FAULTS
LIFE LED’S
2 YEAR WARRANTY
2 MILLION INSTRUCTIONS INSIDE
SOLD INSTANT
ANSWER
PROVEN
DESIGN DROP
PROOF
Made in Philippines
EASY
TO USE

www.martindale-electric.co.uk
Tel: 01923 441717 Fax: 01923 446900
www.martindale-electric.co.uk
© 2012 Martindale Electric Co. Ltd.
Ver. 6
CHECK PLUG
N E L
Socket Wires CP LED’s
N E L OK G G G
N N L Note 1 G G G
E E L Note 1 G G G
13A SOCKET TESTER E N L Note 1 G G G
L E N LN Reverse G T T Note 2
L E E LN Reverse G T T Note 2
SAFETY WARNING L N E LN Reverse G T T Note 2
Proper safety measures should be taken when working with voltages exceeding 30V AC rms, 42V AC L N N LN Reverse G T T Note 2
peak or 60V DC. Your socket tester is not intended to replace good electrical practices. This unit must
only be used under the conditions and for the purposes for which it has been constructed. Pay attention
E L L LN Reverse G T T Note 2
to these safety instructions, the technical specification and the use of the unit in dry surroundings. N L L LN Reverse G T T Note 2
N OPEN L No Earth G G T Note 2
PRE-TEST CHECK
Visually inspect the tester for any signs of physical damage, e.g. cracks, splits, loose pins or damaged
E OPEN L No Earth G G T Note 2
indicators, etc. In the unlikely event of the socket tester sustaining physical damage, it should not be L OPEN E No Earth G G T Note 2
used. For good electrical practice it is recommended that you verify the function of the tester on a known L OPEN N No Earth G G T Note 2
correctly-wired live socket before & after use.
OPEN E L N Fault T G G Note 2
OPERATING INSTRUCTIONS OPEN N L N Fault T G G Note 2
Simply plug the Check Plug Socket Tester into a live 13A socket and switch the socket on. Three OPEN L E N Fault T G G Note 2
indicator LED’s across the front of the unit provide a clear indication of a correctly wired socket. Fault
indications are quickly identified using the key on the face label. Additional information can be found in
OPEN L N N Fault T G G Note 2
the table opposite, showing 32 wiring conditions, of which 28 are faults that require investigation. In the N L E LE Reverse T T G Note 2
event that a fault is indicated, investigation should only be carried out by a suitably qualified electrician. E L E LE Reverse T T G Note 2
E L N LE Reverse T T G Note 2
STORAGE AND MAINTENANCE
The socket tester should be kept in dry conditions and should be protected from moisture, condensation, N L N LE Reverse T T G Note 2
physical damage and direct sources of heat. Ensure the unit is dry before use. L E L LE Reverse T T G Note 2
L N L LE Reverse T T G Note 2
Cleaning: After removal from any socket, the unit may be cleaned using a soft, dry cloth. Solvents,
liquids, detergents, surfactants and waxes should not be used.
OPEN OPEN L EN Fault T T T Note 3
OPEN L OPEN LEN Fault T T T Note 3
There are no user serviceable parts inside. L OPEN OPEN LEN Fault T T T Note 3
WARRANTY
OPEN L L LEN Fault T T T Note 3
This item is warranted against defects in materials and manufacture for 24 months from the date of L OPEN L LEN Fault T T T Note 3
purchase. Return to Martindale Electric if faulty. L L OPEN LEN Fault T T T Note 3
OPEN OPEN OPEN LEN Fault T T T Note 3
Equipment complies with CAT II is for equipment intended to be L L L L Fault T T T Note 3
relevant EU Directives supplied from the building
wiring. It applies both to plug-
Caution - risk of danger & connected equipment and to
refer to instructions permanently connected
equipment.
Equipment protected by
double or reinforced Alternating Current (ac)
insulation (Class II)

End of life disposal of this


equipment should be in
accordance with relevant EU
Directives
With reference to table:
TECHNICAL SPECIFICATION Martindale Electric Co Ltd Note 1
Operating voltage range: 200-250V Metrohm House EN reversal not detectable.
Frequency range: 30-70Hz Penfold Trading Estate Note 2
Power consumption: <1.8W Imperial Way Investigation required by qualified electrician.
Temperature range: -10 to 40°C at max, 60% RH Watford
Pollution degree: 2 WD24 4YY Note 3 Caution!
Power supply: from mains Investigate with care. Socket wire(s) may be live, but LED’s will not light.
Open Earth if Earth resistance > 50k Ohm nom at 230VAC nom Investigation required by qualified electrician.
Open Neutral if Neutral resistance > 50k Ohm nom at 230VAC nom NOTE: This unit, in common with other simple socket testers, cannot detect Earth / Neutral reversal.
Complies with BS EN61010