Professional Documents
Culture Documents
FOR
18/30(36))kV NA2XSEY 3×(1×150mm2)
2. STANDARDS
The cable which EES CABLE offered shall be designed, manufactured and tested according to
international standards as follows:
IEC 60060-1 High-voltage test techniques – Part 1: General definitions and test requirements
High-voltage test techniques – Part 3: Definitions and requirements for on-site
IEC 60060-3
testing
IEC 60183 Guide to the selection of high-voltage cables
Conductor
Conductor Shield
XLPE Insulation
Insulation Shield
Copper tape metal shield
Spacer layer
Outer sheath
Value
Parameter Unit
3×(1×150)
Max. D.C. conductor resistance at 20’C Ω/km 0.206
Capacitance μF/km 0.192
Approximate Diameter of cable mm 82.6
Approximate Weight of the finished cable kg/km 4750
Normal operating temperature °C 90
Current carrying capacity(in Ground) A 254
Current carrying capacity(in Air) A 318
No Item Reference