RELAY CO-ORDINATION & PROTECTION STUDY

21.March.24 ABB-TEC-CAL-035 V2

RELA O ORDINATION & PROTE TION STUD

CONTROL DE CAMBIOS/ CHANGE CONTROLS

Revisión 0/ Revision 0: Primera emisión/ First Issuance.


Revisión 1/ Revision 1: Segunda emisión/ Second Issuance. Parameters Update
Revisión 2/ Revision 2: Tercera emisión/ Third Issuance. Parameters Update.


FECHA/ ELABORÓ/ REVISÓ/ APROBÓ/ PAGINAS/
No. REV DESCRIPCIÓN/ DESCRPTION
DATE BY REVISED APPROVED N°
PAGES
0 14.Feb.24 RL AD BH Primera emisión/ First issuance 94
1 06.March.24 DC AD BH Segunda Emisión/ Second issuance 84
2 21.March.24 DC AD BH Tercera Emisión/ Third issuance 85

All information contained herein graphic, technical, numerical, etc is the exclusive property of Consortium PBO and SBI,
any total or partial reproduction, allusion or reference must be authorized by Consortium PBO or SBI.

COPIA IMPRESA DE ESTE DOCUMENTO SE CONSIDERA NO CONTROLADA


ALL PRINTED COPIES OF THIS DOCUMENT ARE CONSIDERED UNCONTROLLED

Página 1 de 85
Document Tile Document No. Revision Date Page No.
RELAY COORDINATION &
ABB-TEC-CAL-035 V2 21-March-2024 2 of 85
PROTECTION STUDY

CONTENTS

CONTENTS 2

1 Introduction 3

2 Abbreviations 3

3 Objective 4

4 Software 4

5 List of Protection Relays and Functions 4

6 System Data 6

7 System Description 7

8 Basis for Protection Co-ordination & Setting 8

9 Assumptions 8

10 Transformer Differential Protection (T2WPDIF-87T) 9

11 Conclusion 10

12 List of Annexures 10
Document Tile Document No. Revision Date Page No.
RELAY COORDINATION &
ABB-TEC-CAL-035 V2 21-March-2024 3 of 85
PROTECTION STUDY

1 Introduction

1.1 Purpose of Document

The purpose of this document is to define the protection coordination methodology to be followed for
preparation of the protection coordination and relay settings for the Puerto Bolívar Port Expansion EPC
- Phase 1 project located in Ecuador and to check the sensitivity and selectivity with proposed settings
for 22kV and LV system.

1.2 Reference Documents

IEEE 242 Protection and coordination of Industrial and Commercial power systems
IEEE C37.91 IEEE guide for Protective Relay Applications to Power Transformers
IEC 60909-1 Short Circuit Calculation in three phase AC systems
IEC 60909-2 Electrical Equipment data for short circuit current calculations
ABB-TEC-DGR-003 OVERALL SINGLE LINE DIAGRAM FOR MV SYSTEM
ABB-TEC-DGR-004 OVERALL SINGLE LINE DIAGRAM FOR LV SYSTEM
13.8 KV CCV OUTDOOR MOTORIZED RMU 24 VDC REEFER SUBSTATION-01 To 26
13.8 KV CCV OUTDOOR MOTORIZED RMU 24 VDC CSW SUBSTATION
13.8 KV CCV ID MOTO. RMU 48 VDC ERTG 3 ABB-EQP-PEQ-217A
13.8 KV CCV ID MOTO. RMU 48 VDC ERTG 5 ABB-EQP-PEQ-217B
13.8 KV CCV ID MOTO. RMU 48 VDC ERTG 7 ABB-EQP-PEQ-217C
13.8 KV CCV ID MOTO. RMU 48 VDC ERTG 8 ABB-EQP-PEQ-217D
13.8 KV M+VVCVV+VCVV+ ID MOTO. RMU 48 VDC STS SUBSTATION
13.8 KV VCC INDOOR MOTORIZED RMU 110 VDC MAIN SUBSTATION
Schematics-4202341857-Ecuador Yilport-PAABB-Item10, 20, 30 – Unisec Panel Drawings

2 Abbreviations

AC Alternating Current
CSW Cold Storage warehouse
DG Diesel Generator
EF Earth Fault
ERTG Electrified Rubber Tyred Gantry Crane
ETAP Electrical Transient Analyzer Program
ETU Electronic Trip Unit
IEC International Electro technical Commission
IEEE Institute of Electrical and Electronics Engineers
kV kilo Volt
LV Low Voltage
Document Tile Document No. Revision Date Page No.
RELAY COORDINATION &
ABB-TEC-CAL-035 V2 21-March-2024 4 of 85
PROTECTION STUDY

MSS Main Substation


MV Medium Voltage
MVA Mega Volt Ampere
PF Phase Fault
Rev Revision
RMU Ring Main Unit
RSS Reefer Substation
SLD Single Line Diagram
STS Ship to Shore
TCC Time Current Curve

3 Objective

This Relay Coordination is valid for Incomer Feeder Protection and Outgoing Feeder Protection for the
following,
▪ 20kV Grid Incomer (Pass Module) Relay Settings
▪ 13.8kV Main Substation & feeders (Includes Grid Incomers & Bus couplers)
▪ 13.8kV DG Switchgear-2 (Includes DG & DG Incomers)
▪ MV and LV settings for Reefer Loop 1, 2, 3.
▪ MV and LV settings for STS Substations.
▪ MV and LV settings for MSS and CSW Substations.

4 Software

The Relay Coordination studies are performed with ETAP Version 21.0.2 ETAP – Electrical Transient
Analysis Program developed by Operation Technology Inc, USA. ETAP is powerful tool for modeling of
power system networks and analyzing various studies including Relay Coordination and Real Time
simulations.

5 List of Protection Relays and Functions

Electrical protections are identified with numerical codes. These codes refer to the Standard IEEE C37-
2 (2008). Here below an extract of the numerical codes relevant to the relays used into this study:

FEEDER PROTECTI
RELAY FUNCTION
DESCRIPITON ON RELAY

69KV AIS RET630 50/51, 50N/51N, 50LLB, 64LV, 87T


SUBSTATION REF620 50/51, 50N/51N, 50NS, 86, 27/59
13.8KV AIS
REF615F 50/51, 50N/51N, 50LLB, 27/59
PANEL-FEEDER
Document Tile Document No. Revision Date Page No.
RELAY COORDINATION &
ABB-TEC-CAL-035 V2 21-March-2024 5 of 85
PROTECTION STUDY

13.8KV AIS
REF615N 50/51, 50N/51N, 27/59, 67/67N, 51BF, 32R, 32O, 81, 25
PANEL-INCOMER
REEFER
REJ601 50/51, 50N/51N
SUBSTATION
STS CRANE REF615 50/51, 50N/51N

STS DIST.TRAFO REF615 50/51, 50N/51N, 27/59


MAIN
REJ601 50/51, 50N/51N
SUBSTATION
CSW
REJ601 50/51, 50N/51N
SUBSTATION
ERTG
REJ601 50/51, 50N/51N
SUBSTATION
13.8KV DG
SWITCHGEAR - REF615F 50/51, 50N/51N, 27/59
INCOMER
13.8KV DG
50/51, 50N/51N, 27/59, 67/67N, 46,47, 51BF, 32R, 32O,
SWITCHGEAR - REF615N
81, 25
INCOMER
Table-1: List of Protection Functions

RELAY NUMBERING CODE

ANSI CODE IEC 61850 PROTECTION FUNCTION

25 SESRSYN Synchro check


27 UV2PTUV Undervoltage Protection
32R/O GOPPDOP Directional Overpower Protection
Non-Directional Instantaneous three phase over
50 PHPIOC
current Protection
Non-Directional Instantaneous neutral over current
50N EFPIOC
Protection
Non-Directional IDMT three phase over current Pro-
51 OC4PTOC
tection
Non-Directional IDMT neutral over current Protec-
51N EF4PTOC
tion
59 OV2PTOV Over voltage Protection

64LV REFPDIF Transformer LV Restricted Earth Fault Protection


Directional Instantaneous three phase over current
67 OC4PTOC
Protection
Document Tile Document No. Revision Date Page No.
RELAY COORDINATION &
ABB-TEC-CAL-035 V2 21-March-2024 6 of 85
PROTECTION STUDY

Directional Instantaneous neutral over current Pro-


67N EF4PTOC
tection
81H SAPTUF Under frequency Protection

81L SAPTOF Over frequency Protection

86 TRPPTRC1 Master trip/Lockout Relay

87T T2WPDIF Transformer Differential Protection

50BF Breaker Failure Protection

Table-2: Relay Numbering Code

6 System Data

6.1 DG Set Data


There are 5 number of DG Sets are used for backup purpose. And the existing system has 2 number
of DG sets.
Phase -1 DG SET (5 Nos)
Nominal kV 0.48
Frequency 60 Hz
kW 2000
KVA 2500
PF 80
Ampere 3007
PF Lag/Lead 0.8 / 0.8
Existing DG SET (2 Nos)
Nominal kV 0.48
Frequency 60 Hz
kW 2080
KVA 2600
PF 80
Ampere 3127
PF Lag/Lead 0.8 / 0.8
Table 3: DG Set Data

The impedance and all other parameters are taken from ETAP Library. And DG’s are solid earthing
modelled.
Document Tile Document No. Revision Date Page No.
RELAY COORDINATION &
ABB-TEC-CAL-035 V2 21-March-2024 7 of 85
PROTECTION STUDY

6.2 Transformer Data


All transformer MVA rating, impedance values and other parameters have been taken from the Single
Line Diagram. All transformer star point is modelled as solid earthing type.

Voltage Tap - No. Tap


S.No Transformer ID Rating Impedance
(kV) of Steps Voltage/Step

T1-TMS1-69-1 & T1- 12% @ +10 and -


1 69/13.8 25/30 MVA 1%
TMS1-69-2 25MVA Base 10
Reefer Transformer –
2 13.8/0.494 750 KVA 5% +2 and -2 2.5%
750 KVA Rated

3 Reefer Transformer –
13.8/0.494 850 KVA 5% +2 and -2 2.5%
850 KVA Rated

4 Reefer Transformer –
13.8/0.494 1000KVA 6.5% +2 and -2 2.5%
1000 KVA Rated
5 TR-STS SS 13.8/0.227 315KVA 4% +2 and -2 2.5%
6 TR-MSS Building 13.8/0.227 315KVA 4% +2 and -2 2.5%
7 ERTG Transformers 13.8/0.474 2250KVA 7% +2 and -2 2.5%

8 ERTG Lighting
0.460/0.227 75KVA 4% +2 and -2 2.5%
Transformer (AN)

9 13.8/0.494/ 2250/2000/
TR-CSW SS 7/7/14 % +2 and -2 2.5%
0.227 250 KVA
10 DG Transformers 13.8/0.48 2500KVA 6% +2 and -2 2.5%
Table 4: Transformer Rating

7 System Description

1. Puerto Bolívar Port Expansion EPC - Phase 1 project Electrical system is supplied with two
69kV power feeders from substation Grid.

2. In port, Main power transformer rated 30MVA, 69/13.8 kV is used to step down the voltage to
13.8kV for the feeder / carne load distribution purpose.

3. Reefer substations (26 Nos), 13.8kV voltage is stepped down to 0.48kV by 13.8/0.48kV step-
down transformer and feeding LV loads.

4. ERTG substations (4 Nos), 13.8kV voltage is stepped down to 0.46kV by 13.8/0.4kV step-down
transformer and feeding LV loads.

5. STS, MSS and part of CSW substations are step down the voltages to 0.22kV for the LV loads.

6. 13.8kV system is solidly grounded at 30MVA transformer end.

7. LV system is solidly grounded.


Document Tile Document No. Revision Date Page No.
RELAY COORDINATION &
ABB-TEC-CAL-035 V2 21-March-2024 8 of 85
PROTECTION STUDY

8 Basis for Protection Co-ordination & Setting

8.1 General Methodology


Protection coordination shall be reviewed to achieve sensitivity, speed, selectivity and reliability to iso-
late faults from the rest of the healthy system and prevent power failure and consequent production loss
due to the faults under all foreseen system operation conditions.

Relay characteristics shall be selected to give optimal performance in terms of sensitivity and rapidity of
fault clearance. This has resulted in the use of inverse time schemes supplemented by instantane-
ous/definite time schemes for phase over current protection and earth fault protection of solidly earthed
systems; and definite time schemes for earth fault protection of resistance earthed systems.

Over-currents in a power distribution system can occur as a result of both normal (motor starting, trans-
former inrush, etc.) and abnormal (ground fault, line-to-line fault, etc.) conditions. In either case, the
basic purpose of current-sensing protective devices is to detect the abnormal over-current with proper
coordination, to operate selectively and to protect equipment properly by minimizing the outage of the
remainder of the system.

Relay operating characteristics and their setting must be carefully coordinated in order to achieve se-
lectivity. The aim is to switch off only the fault component and to leave the rest of the power system in
service in order to minimize supply interruptions and to ensure stability. Protection should be as sensitive
as possible to detect faults at the lowest possible current level of both phase and ground faults. However,
it should remain stable under all permissible load, overload and through-fault conditions.

Primary Protection: The protective system, which is normally expected to operate in response to a fault
in the protected zone.

Back-Up Protection: A protective system intended to supplement the main protection in case the later
should be ineffective, or to deal with faults in those parts of the power system that are not readily included
in the operating zones of the main protection.

8.2 Co-ordination time interval


Relay to Relay 0.2 to 0.25sec
Relay to Electronic Trip Unit 0.2 to 0.25Sec
ETU to ETU/Release 0.1Sec
Release to Release 0.1Sec

9 Assumptions

Protection co-ordination and settings are done based on the following assumptions

1. Loads are considered as per Load flow study report.


2. All LV loads are considered as lumped loads.
Document Tile Document No. Revision Date Page No.
RELAY COORDINATION &
ABB-TEC-CAL-035 V2 21-March-2024 9 of 85
PROTECTION STUDY

3. The 13.8kV Main Intake substation settings of phase 1 (TANGIER-CAL-0003, Rev 0.7) is fol-
lowed as upstream setting for the extension feeders.
4. The feeders those load details are not available, minimum available setting has been given.
However the settings to be updated as per site load details.
Any change in the above mentioned assumptions the proposed settings may not be applicable.

10 Transformer Differential Protection (T2WPDIF-87T)

In normal operating condition, differential protection is used as the unit protection for the incomer main
power transformer. It serves as the main protection of transformers in case of winding failure. The pro-
tective zone of a differential protection includes the transformer itself, the bus-work or cables between
the current transformers and the power transformer.

T2WPDIF Setting guidelines:

➢ IdMin: Setting for the operating characteristic with IdMin = 0.3 * IBase is recommended.
➢ EndSection1 is proposed to be set to 1.25 times.
➢ EndSection2 is proposed to be set to about 3 times.
➢ SlopeSection2, defined as the percentage value of Idiff/IBias, is proposed to be set to
40%,
➢ SlopeSection3, defined as the percentage value of Idiff/IBias, is proposed to be set to
80 %, if no deeper analysis is done.
➢ I2/I1Ratio: It is recommended to set at 15% as for Inrush restraint.
➢ I5/I1Ratio: It is recommended to set at 25% as default value for Overexcitation restraint.
➢ IdUnre:
• Unrestrained pickup shall be set more than max (Through fault Current, Inrush
current).
• HV Through fault current
If= HV side Full Load current /%Z
If = 251/0.12 = 2091.7 A
Considering 1.5 times of through fault
If x 1.5 = 2091.7 x 1.5 = 3137.5 A
Corresponding current @ Ibase
= 3137.5 A / CT ratio = 3137.5 A / 400 = 7.84
• Inrush current
Inrush current = 12 x Full Load current (assuming)
In= 251 x 12 = 3012 A
Corresponding current @ Ibase
= 3012 A / CT ratio = 3012A / 400 = 7.53
Document Tile Document No. Revision Date Page No.
RELAY COORDINATION &
ABB-TEC-CAL-035 V2 21-March-2024 10 of 85
PROTECTION STUDY

➢ The highest value of Through Fault current or Inrush current is 7.84.


IdUnre = 7.84 Ibase is selected

11 Conclusion

1. It is observed from the TCC charts that Co-ordination is achieved for minimum fault currents
and partially achieved for maximum fault current.
2. It is observed from the TCC charts that the backup fault clearing time at various switch boards
are well within rated withstand time of various equipment.

12 List of Annexures
ETAP SLD Annexure-1
Relay co-ordination charts for Phase over current & Earth fault coordination Annexure-2
13.8kV AIS Panel Main Substation Protection setting table Annexure-3
13.8kV Reefer Substation Protection setting table Annexure-4
13.8kV STS Substation Protection setting table Annexure-5
13.8kV ERTG, MSS & CSW Substation Protection setting table Annexure-6
13.8kV DG Switchgear Protection setting table Annexure-7
69kV Grid Incomer – Pass Module Protection setting table Annexure-8
LV system Protection Setting table Annexure-9
Overall Single Line Diagram for MV System Annexure-10
Overall Single Line Diagram for LV System Annexure-11
Document Tile Document No. Revision Date Page No.
RELAY COORDINATION &
ABB-TEC-CAL-035 V2 21-March-2024 11 of 85
PROTECTION STUDY

Annexure-1

ETAP SLD
One-Line Diagram - OLV1 (Edit Mode)

INCOMER-2
69 kV
327.462 MVAsc

1250 A
GANG.OPR.DISCONT-GRID
Cable290
33 m
AL
3-1/C 240
Cable128
69kV MAIN I/C-1
100 m AL 1250 A
69 kV RLY_DG SWGR2_H07 GANG.OPR.DISCONT-GRID2
RLY_DG SWGR2_H08
1250 A CT57
CT63
1250 A 6-1/C 750 1250/5 1250/5

CB-PASS MODULE 1250 A


69kV MAIN I/C-2
1250 A HVCB-DG SWGR-2 I/C-B
HVCB-DG SWGR-2 I/C-A Open 69 kV
CT2 RLY_69KV GRID_BACKUP Open 1250 A
400/5
1250 A 13.8 kV
CB SWGR-1 630 A 1250 A 1250 A
13.8 kV DG SWGR-2
CT1 CB-PASS MODULE2
RLY_69KV GRID_MAIN Open Open
400/5
DG SWGR-1
T1-TMS1-69-1
SIEMENS SWGR-1 (Exis ng) 630 A 630 A 630 A 630 A MV BUS EXT.SWGR2 T1-TMS1-69-2
30 MVA 630 A 630 A 630 A 30 MVA
MVCB-EXT.DG-2 MVCB-DG-1 Open Open MVCB-DG-3 Open
69/13.8 kV MVCB-EXT.DG-1 Open Open MVCB-DG-2 Open MVCB-DG-4 MVCB-DG-5 Open 69/13.8 kV
13.8
1250kVA RLY_DG1_H01 RLY_DG2_H02 RLY_DG3_H03 RLY_DG4_H04 RLY_DG5_H05 1250 A
12 %Z Dyn1
CT52 CT58 CT60 CT62 13.8 kV 12 %Z Dyn1
CT61
150/5 150/5 150/5 150/5 150/5
Cable291
12-1/C 240 Cable296
95 m AL AL 71 m AL 71 m Cable337 Cable339 Cable341
Cable5 Cable338 Cable340 82 m 26 m AL
27 m AL 3-1/C 400 Cable76 Cable77 78 m AL 72 m 75 m AL 75 m AL AL
AL 3-1/C 95 3-1/C 95 3-1/C 240 Cable297 Cable68
1-3/C 3/0 1-3/C 3/0 3-1/C 95 3-1/C 95 3-1/C 95
65 m AL 27 m AL
12-1/C 240
3-1/C 400
RLY_GRID I/C-1_H04 RLY_AIS DG SWGR2-A_H09 RLY_EXIST.SWGR-1_H01 RLY_DG-B_H02
CT46 CT45 CT40 CT49
RLY_EXIST.SWGR-2_H10 RLY_GRID I/C-2_H03
1250/5 1250/5 1250/5 1250/5 CT39 CT50
TR EXISTING DG-1 TR DG-2 TR DG-3 TR DG-4 1250/5 1250/5
TR EXISTING DG-2 TR DG-1 TR DG-5
2000 kVA 2500 kVA 2500 kVA 2500 kVA 2500 kVA 2500 kVA
630 A 630 A 630 A 2000 kVA 13.8/0.48 kV 630 A 630 A
13.8/0.48 kV 13.8/0.48 kV 13.8/0.48 kV 13.8/0.48 kV 13.8/0.48 kV 13.8/0.48 kV
HVCB_GRID I/C-1_H04 HVCB_DGSWGR2-A_H09 Open HVCB_EXIST.SWGR-1_H01 Open 6 %Z YNd1 6 %Z YNd1 6 %Z Yd1 6 %Z Yd1 6 %Z YNd1 HVCB_DG-B_H02 Open 630 A HVCB_GRID I/C-2_H03 Open
YNd1 6 %Z YNd1 6 %Z
HVCB_EXIST.SWGR-2_H10 Open
1250 A
AIS-MAIN MV SWGR BUS-A 1250 A AIS-MAIN MV SWGR-2
13.8 kV 13.8 kV

AL 10 m AL 10 m AL 10 m AL 10 m AL 10 m
630 A 630 A 630 A Cable147 18-1/C 400
2500 A 2500 A Cable146 18-1/C 400 Cable148 18-1/C 400 Cable149 18-1/C 400 Cable150 18-1/C 400 630 A
630 A HVCB_RSSL-3A_H08 HVCB_RSSL-2A_H05 HVCB_RSSL-1A_H06 630 A 630 A LVCB-DG SET-6 Open LVCB-DG SET-7 Open 630 A
Open HVCB_STS-A_H03 HVCB_CSW+MSS-A_H02 0A 0A 630 A 0A HVCB_ERTG8_H05 HVCB_CSW+MSS-B_H04
630 A HVCB_ERTG7_H07 CB226 0A 630 A 630 A 630 A 630 A
CB143 HVCB_MAIN B/C_H11 4000 A 4000 A 4000 A CB145 Open
RLY_ERTG8-H05 CB247 HVCB_RSSL-3B_H08 630 A
CB A-FUT.R.LOOP4A 4000 A Open Open 4000 A Open HVCB_RSSL-1B_H06 HVCB_RSSL-2B_H07 HVCB_STS-B_H09
RLY_RSSL-3A_H08 RLY_ERTG7-H07 Open LVCB-DG SET-1 Open LVCB-DG SET-2 LVCB-DG SET-3 LVCB-DG SET-4 Open LVCB-DG SET-5 Open CT53 Open Open Open CB-FUTURE REEFER LOOP4B
RLY_RSSL-2A_H05 RLY_RSSL-1A_H06 600/5 Open Open Open
CT44 CT41 CT42 CT43
RLY_STS-A_H03 600/5 RLY_CSW+MSS-A_H02 RLY_MAIN B/C_H11 RLY_CSW+MSS-B_H04
CT38 600/5 600/5 600/5 CT35 CT48 CT51
RLY_RSSL-1B_H06 RLY_RSSL-2B_H07 RLY_STS-B_H09
600/5 200/5 1250/5 200/5 CT54 CT55 RLY_RSSL-3B_H08 CT47
Cable143 CT56
EXISTING DG-2 DG SET-1 DG SET-2 DG SET-4 600/5 600/5 600/5
EXISTING DG-1 DG SET-3 DG SET-5 600/5
2080 kW 2000 kW 2000 kW 2000 kW 2000 kW 265 m AL
2080 kW 2000 kW
0.48 kV 0.48 kV 0.48 kV 0.48 kV 0.48 kV 0.48 kV 0.48 kV 3-1/C 240 Cable295
Cable8
Cable248 Cable69 770 m AL
485 m AL Cable129 Cable292 485 m AL
Cable156 Cable133 Cable131 Cable144 3-1/C 120
3-1/C 1000 472 m AL 430 m 25 m AL 3-1/C 1000
610 m AL 603 m AL 610 m AL AL FUTURE LOAD2 10 m AL FUTURE LOAD3
3-1/C 240 3-1/C 240 3-1/C 240 3-1/C 240 3-1/C 120
3-1/C 240 FUTURE LOAD1 2 MVA 12-1/C 240 2 MVA
Cable29 Cable45 Cable50
3 MVA Cable293
Cable117 95 m AL 95 m AL 95 m AL
Cable134
Cable120 Cable126
865 m AL 625 m AL
485 m AL 385 m AL 630 m AL
Cable289 Cable288 Cable287 3-1/C 120 3-1/C 240 3-1/C 240 3-1/C 1000 3-1/C 1000 3-1/C 1000
3-1/C 240 3-1/C 240 630 A 630 A 630 A
600 A 600 A 600 A 630 A 630 A 630 A 630 A 630 A
195 m AL 230 m AL 195 m AL 600 A LBS-RSS7-6 LBS-RSS7-7 LBS-RSS7-9
600 A LBS-MSS-K01 Open LBS-RSS7-3 LBS-RSS7-4 LBS-RSS7-5 LBS-RSS7-8 LBS-RSS7-10
600 A 600 A 3-1/C 240 600 A 600 A 3-1/C 240 600 A 600 A 3-1/C 240 600 A LBS-MSS-K02 LBS-CSW-K01
LBS-ERTG5-K01 LBS-ERTG8-K01
LBS-ERTG7-K01 LBS-ERTG7-K02 LBS-ERTG3-K01 LBS-ERTG3-K02 LBS-ERTG5-K02 LBS-ERTG8-K02 LBS-CSW-K02
Open
13.8 kV
13.8 kV 13.8 kV 13.8 kV 13.8 kV
13.8 kV 13.8 kV 13.8 kV 13.8 kV 13.8 kV
600 A
600 A 600 A 600 A Bus-13.8kV ERTG-5 600 A 630 A 630 A 630 A
Bus-13.8kV ERTG-7 Bus-13.8kV ERTG-3 Bus-13.8kV ERTG-8 600 A Bus-13.8kV MSS Bus-13.8kV CSW 630 A
200 A 200 A Bus-13.8kV RSS-27 200 A Bus-13.8kV RSS-28 200 A Bus-13.8kV RSS-29
600 A Bus-13.8kV RSS-26.
DISCONNECTOR-RSS27 DISCONNECTOR-RSS28 DISCONNECTOR-RSS29
HVCB-ERTG 07-K03 HVCB-ERTG 03-K03 HVCB-ERTG 05-K03 HVCB-ERTG 08-K03 HVCB-MSS-K03 HVCB-CSW-K03 DISCONNECTOR-RSS26 125 A 125 A 125 A
125 A
600 A 600 A 600 A 600 A 600 A
FUSE RSS-27 FUSE RSS-28 FUSE RSS-29
CT37 FUSE RSS-26
CT36 150/1
CT34
CT32 CT31 CT33 50/1 RLY-CSW-K03 Cable31 Cable44 Cable49
150/1 150/1 150/1 150/1 RLY-MSS-K03 Cable9
10 m AL 10 m AL 10 m AL
RLY-ERTG 07-K03 RLY-ERTG 03-K03 RLY-ERTG 05-K03 RLY-ERTG 08-K03 Cable298 10 m AL
1-3/C 2/0 1-3/C 2/0 1-3/C 2/0
10 m AL 1-3/C 2/0
Cable333 Cable196 Cable331 3-1/C 70
10 m AL 33 m AL
Cable332 Cable335
10 m AL 3-1/C 95 3-1/C 95 TR-RSS27 TR-RSS28 TR-RSS29
10 m AL 3-1/C 95 13.8/0.494/0.227 kV TR-RSS26. 13.8/0.494 kV 13.8/0.494 kV 13.8/0.494 kV
10 m AL 13.8/0.494 kV 5 %Z Dyn1 5 %Z Dyn1 5 %Z Dyn1
3-1/C 95 2250/2000/250 kVA 5 %Z Dyn1
3-1/C 95 750 kVA 750 kVA 750 kVA
7/7/14 %Z 750 kVA
TR1-ERTGSS-8
TR1-ERTGSS-3 TR1-ERTGSS-5 13.8/0.474 kV
13.8/0.474 kV 13.8/0.474 kV 7 %Z Dyn1 TR-MSS BUILDING
13.8/0.474 kV TR1-ERTGSS-7 7 %Z Dyn1 7 %Z Dyn1 TR2-ERTGSS-5 Dyn1 6m CU 6m CU 6m CU 6m
7 %Z Dyn1 2250 kVA 2250 kVA 4 %Z CU Cable32 2-3/C 750 Cable43 2-3/C 750 Cable48 2-3/C 750
TR2-ERTGSS-7 2250 kVA 4 %Z Dyn1 315 kVA Cable10 2-3/C 750
2250 kVA TR2-ERTGSS-3
4 %Z Dyn1 75 kVA TR2-ERTGSS-8 13.8/0.227 kV TR-CSW SS
4 %Z Dyn1 75 kVA
18-1/C 400 75 kVA Dyn1 0.46/0.227 kV
75 kVA 0.46/0.227 kV Cable145 15 m AL
10 m AL 0.46/0.227 kV 4 %Z AL 1000 A LVCB-RSS27 1000 A LVCB-RSS28 1000 A LVCB-RSS29
AL 10 m 0.46/0.227 kV 18-1/C 400 Cable229 6-1/C 240 10 m Cable13 1000 A LVCB-RSS26
Cable139 Cable140 18-1/C 400 Cable225 6 m CU AL 10 m 15 m AL 18-1/C 400
Cable222 Cable223 10 m AL Cable142 18-1/C 400 Cable226 Cable230 6-1/C 240
Cable227 6 m CU Cable228 Cable141 6 m CU 1-4/C 95 Cable153
6 m CU 6 m CU 1-4/C 35 6 m CU 6 m CU
1-4/C 35 1-4/C 35 6 m CU 1-4/C 35 1-4/C 95 LV BUS-RSS27 0.48 kV LV BUS-RSS28 0.48 kV LV BUS-RSS29 0.48 kV
3200 A 1-4/C 95 1-4/C 95 LV BUS-RSS26. 0.48 kV
3200 A 3200 A CB-MSS-QF1
CB-ERTG7-QF1 3200 A CB-220V-ERTG5-QF1 2500 A 1000 A
CB-220V-ERTG7-QF1 250 A CB-ERTG5-QF1 CB-ERTG8-QF1 1000 A
125 A CB-ERTG3-QF1 CB-220V-ERTG3-QF1 250 A CB-ERTG8-QF7 CB-220V-ERTG8-QF1 CB-CSW_0.48KV-QF1 CB-CSW_0.22KV-QF1
CB-ERTG3-QF7 CB-ERTG5-QF7 125 A
CB-ERTG7-QF6 160 A 250 A 3200 A 160 A
0.46 kV LVBUS-ERTG5-0.22KV 3200 A LVBUS-ERTG8-0.46KV 1000 A 1000 A 1000 A
3200 A LVBUS-ERTG7-0.46KV 3200 A LVBUS-ERTG3-0.22KV LVBUS-ERTG5-0.46KV 0.22 kV 0.46 kV 0.22 kV LV BUS-MSS LVBUS-CSW-0.48KV 1000 A
0.46 kV LVBUS-ERTG7-0.22KV 0.46 kV LVBUS-ERTG3-0.46KV 0.22 kV 0.22 kV LVBUS-ERTG8-0.22KV 1000 A 0.22 kV LVBUS-CSW-0.22KV
0.22 kV 630 A 630 A 630 A 630 A 630 A 630 A 630 A
0A 250 A 630 A CB169 CB176 CB181
0A 0A CB239 1000 A 2500 A CB162 CB170 CB174 CB179
0A CB240 250 A 0.48 kV 400 A 0A 800 A CB165
CB243 0A CB-ERTG3-QF2 CB-ERTG3-QF4 CB-ERTG3-QF5 CB241 0A CB40 CB141 250 A 250 A 250 A 250 A 250 A
CB231 250 A CB-ERTG7-QF2 CB-ERTG7-QF3 CB-ERTG7-QF4 CB-ERTG7-QF5 CB242 CB-ERTG3-QF3 Open 250 A 250 A CB-ERTG5-QF2 CB-ERTG5-QF3 CB-ERTG5-QF4 250 A CB238 250 A 0A CB-CSW_0.48KV-QF2 CB167 CB172 CB177
250 A 250 A 1000 A 1000 A 1000 A 1000 A 250 A CB8 CB-ERTG5-QF5 250 A 0A CB-CSW_0.22KV-QF2 CB233 CB158
CB37 1000 A 1000 A 1000 A 1000 A Open Open Open Open Open 1000 A 1000 A 1000 A Open Open 1000 A 1000 A 1000 A 1000 A 0A 0A CB-MSS-QF32 CB147
Open Open Open Open 250 A 250 A CB229 Open Open 1000 A CB-ERTG8-QF2
Open CB-ERTG8-QF3
Open CB-ERTG8-QF4 CB-ERTG8-QF5
Open CB236 CB232 Open 21 m 21 m CU 21 m 21 m CU 21 m 21 m CU 21 m
Open CB228 CB237 250 A CU 21 m Cable40 CU Cable41 CU Cable46 CU
CB230 CB34 LUMP-ERTG5-0.22KV Open Open Cable25 CU Cable33 Cable42 Cable47
Open Cable22 1-3/C 500 1-3/C 500 1-3/C 500
65 kVA Cable23 1-3/C 500 CAP83 1-3/C 500 CAP86 1-3/C 500 CAP89 1-3/C 500
200 kVA LUMP RSS7A1 CAP80 1-3/C 500 LUMP RSS7A2 LUMP RSS7A3 LUMP RSS7A4
CU 500 m 700 kVA 600 kVA 50 kVA 200 kVA 4x25 kvar 200 kVA 4x25 kvar 200 kVA 4x25 kvar
200 kVA 4x25 kvar 630 A 630 A 630 A
LUMP-ERTG7-0.22KV CAP30 2-4/C 150 LUMP-CSW1 0.48KV LUMP-CSW 0.48KV LUMP-CSW 0.22KV LUMP1-CSW 0.22KV 630 A
CAP121 CAP31 65 kVA CAP120 LUMP-ERTG3-0.22KV 50 kVA CAP26 CAP32 ERTG8-0.46KV2 ERTG8-0.46KV3 LUMP1-ERTG8-0.22KV ISO-RSS7-RP2B4 630 A ISO-RSS7-RP2B7 630 A ISO-RSS7-RP2B9
2x25 kvar 50 kVA 4x25 kvar 2x25 kvar ERTG3-0.46KV2 ERTG3-0.46KV3 CAP119 ERTG5-0.46KV1 ERTG5-0.46KV2 ERTG5-0.46KV3 LUMP1-ERTG5-0.22KV CAP118 ERTG8-0.46KV1 ERTG8-0.46KV4 630 A ISO-RSS7-RP2B2 630 A
4x25 kvar ERTG7-0.46KV2 ERTG7-0.46KV3 ERTG3-0.46KV1 ERTG3-0.46KV4 65 kVA LUMP1-ERTG3-0.22KV 4x25 kvar 2x25 kvar 300 kVA ERTG5-0.46KV 2x25 kvar 150 kVA 300 kVA 450 kVA 450 kVA 50 kVA LUMP MSS LUMP1 MSS ISO-RSS7-RP2B5 ISO-RSS7-RP2B6 ISO-RSS7-RP2B8
ERTG7-0.46KV ERTG7-0.46KV1 LUMP1-ERTG7-0.22KV 150 kVA 450 kVA 450 kVA 300 kVA 150 kVA 450 kVA 450 kVA 50 kVA 4x25 kvar LUMP-ERTG8-0.22KV ISO-RSS7-RP2B3
150 kVA 450 kVA 450 kVA 300 kVA 184 kVA 100 kVA
65 kVA RSS7-RP2C2 RSS7-RP2C3 RSS7-RP2C4
55 kW RSS7-RP2C1 630 A 630 A 630 A
630 A RSS7-RP2B2 RSS7-RP2B3 RSS7-RP2B4
LV MOTOR-MSS RSS7-RP2B1 0.48 kV 630 A 0.48 kV 630 A 0.48 kV 630 A 0.48 kV
630 A

0.48 kV 0.48 kV 0.48 kV


0.48 kV

250 A
250 A 250 A 250 A
CB168 CB175 CB180
CB159 250 A LUMP RSS7D2 250 A LUMP RSS7D3 250 A LUMP RSS7D4
250 A LUMP RSS7D1 CB171 CB173 CB178
CB166 200 kVA 200 kVA 200 kVA 200 kVA
LUMP RSS7C1 LUMP RSS7C2 LUMP RSS7C3 LUMP RSS7C4
Cable90 200 kVA 200 kVA 200 kVA
Cable72 Cable82 200 kVA
Cable65 CAP84 CAP88 CAP91
Cable282 Cable280 Cable281 Cable61 50 m AL 50 m CAP81
50 m AL AL 4x25 kvar 4x25 kvar 4x25 kvar
50 m 50 m AL 3-1/C 240 4x25 kvar CAP85 CAP87 CAP90
65 m AL 65 m AL 50 m AL AL 3-1/C 240 600 A 600 A 3-1/C 240 600 A CAP82 4x25 kvar 4x25 kvar 4x25 kvar
3-1/C 240 3-1/C 240 3-1/C 240 3-1/C 240 3-1/C 240 630 A 4x25 kvar
600 A 600 A 600 A 600 A 600 A 600 A 600 A 600 A LBS-RSS02-K01 LBS-RSS02-K02 LBS-RSS03-K01
600 A 600 A 600 A 600 A 600 A 600 A LBS-RSS01-K01 LBS-RSS01-K02 LBS-RSS3-K02
LBS-RSS11-K01 LBS-RSS11-K02 LBS-RSS06-K01 LBS-RSS09-K01 LBS-RSS09-K02 LBS-RSS05-K01 LBS-RSS05-K02
LBS-RSS07-K01 LBS-RSS07-K02 LBS-RSS10-K01 LBS-RSS10-K02 LBS-RSS06-K02 Open
600 A 13.8 kV 600 A 13.8 kV
600 A 13.8 kV
600 A 13.8 kV 600 A 13.8 kV 600 A 13.8 kV 600 A 13.8 kV 600 A 13.8 kV 600 A 13.8 kV
Bus-13.8kV RSS-02 Bus-13.8kV RSS-03
95 m
Bus-13.8kV RSS-05 Bus-13.8kV RSS-01 AL
Bus-13.8kV RSS-11 Bus-13.8kV RSS-07 Bus-13.8kV RSS-10 Bus-13.8kV RSS-06 Bus-13.8kV RSS-09 Cable55
3-1/C 1000
HVCB-RSS02-K03 HVCB-RSS03-K03 Cable100 Cable101 Cable87
HVCB-RSS01-K03 Cable81
HVCB-RSS11-K03 HVCB-RSS07-K03 HVCB-RSS10-K03 HVCB-RSS06-K03 HVCB-RSS09-K03 HVCB-RSS05-K03 600 A 600 A 60 m AL 80 m AL 80 m AL
600 A 600 A 60 m AL
600 A 600 A 600 A 600 A 600 A
RLY-RSS02-K03 RLY-RSS03-K03
3-1/C 1000 3-1/C 1000 3-1/C 1000
RLY-RSS09-K03 RLY-RSS05-K03 RLY-RSS01-K03 CT18 CT19 3-1/C 1000
RLY-RSS11-K03 RLY-RSS07-K03 RLY-RSS10-K03 RLY-RSS06-K03 630 A 630 A
CT11 CT16 CT17 75/1 75/1 630 A 630 A
CT12 CT13 CT14 CT15 75/1 630 A 630 A LBS-RSS7-13 LBS-RSS7-14 LBS-RSS7-11
75/1 75/1 75/1 75/1 75/1 75/1 630 A 630 A LBS-RSS7-12
LBS-RSS4-5 LBS-RSS4-6 LBS-RSS4-3
LBS-RSS4-4
Cable89
Cable80
Cable64 Cable71 10 m AL 10 m AL
Cable2 Cable21 Cable4 Cable36 Cable60
10 m AL 10 m AL 10 m AL 3-1/C 70 3-1/C 70 13.8 kV 13.8 kV
10 m AL 10 m AL 10 m AL 10 m AL 3-1/C 70 13.8 kV
3-1/C 70 3-1/C 70 3-1/C 70 3-1/C 70 3-1/C 70 13.8 kV
3-1/C 70
630 A 630 A 630 A 630 A
TR-RSS03 200 A
TR-RSS02 Bus-13.8kV RSS-32 Bus-13.8kV RSS-33 Bus-13.8kV RSS-31 200 A Bus-13.8kV RSS-30
TR-RSS05 TR-RSS01 5 %Z 5 %Z Dyn1 200 A 200 A
TR-RSS11 TR-RSS07 TR-RSS10 TR-RSS06 TR-RSS09 Dyn1 DISCONNECTOR-RSS33 DISCONNECTOR-RSS30
5 %Z 5 %Z Dyn1 5 %Z Dyn1 850 kVA 850 kVA DISCONNECTOR-RSS32 125 A DISCONNECTOR-RSS31
5 %Z Dyn1 5 %Z Dyn1 5 %Z Dyn1 5 %Z Dyn1 Dyn1 850 kVA 13.8/0.494 kV 125 A 125 A
850 kVA 850 kVA 13.8/0.494 kV 125 A
850 kVA 850 kVA 850 kVA 850 kVA 13.8/0.494 kV 13.8/0.494 kV FUSE RSS-33 FUSE RSS-30
13.8/0.494 kV 13.8/0.494 kV 13.8/0.494 kV 13.8/0.494 kV 13.8/0.494 kV FUSE RSS-32
FUSE RSS-31
Cable108 Cable54
6 m AL 6 m AL Cable98 Cable78
6 m AL Cable79 Cable86 10 m AL 10 m AL
6 m AL 6 m AL 6 m AL 6 m AL 6 m AL 6 m AL 10 m AL 10 m AL
Cable62 Cable70 12-1/C 240 12-1/C 240 1-3/C 2/0 1-3/C 2/0 1-3/C 2/0
Cable20 Cable27 Cable6 Cable35 Cable39 12-1/C 240 1-3/C 2/0
12-1/C 240 12-1/C 240 12-1/C 240 12-1/C 240 12-1/C 240
12-1/C 240

TR-RSS32 TR-RSS30
1000 A 1000 A TR-RSS33 13.8/0.494 kV TR-RSS31 13.8/0.494 kV
1000 A CB-RSS02-QF1 CB-RSS03-QF1 13.8/0.494 kV 5 %Z Dyn1 13.8/0.494 kV 5 %Z Dyn1
1000 A 1000 A 1000 A 1000 A 1000 A 1000 A 6.5 %Z Dyn1 6.5 %Z Dyn1
CB-RSS09-QF1 CB-RSS05-QF1 CB-RSS01-QF1 750 kVA 750 kVA
CB-RSS11-QF1 CB-RSS07-QF1 CB-RSS10-QF1 CB-RSS06-QF1 1000 kVA 1000 kVA

LV BUS-RSS02 LV BUS-RSS03 0.48 kV 1000 A


LV BUS-RSS01 0.48 kV 1000 A
LV BUS-RSS09 LV BUS-RSS05 0.48 kV 1000 A 0.48 kV 1000 A CU 6m CU 6m
LV BUS-RSS11 0.48 kV 1000 A LV BUS-RSS07 0.48 kV 1000 A LV BUS-RSS10 0.48 kV 1000 A LV BUS-RSS06 0.48 kV 1000 A 0.48 kV 1000 A CU 6m Cable104 2-3/C 750 Cable53
CU 6m 2-3/C 750
Cable97 2-3/C 750 Cable75 2-3/C 750

630 A
630 A 630 A
630 A 630 A 250 A 630 A 250 A 1000 A LVCB-RSS33 1000 A LVCB-RSS30
630 A 630 A 630 A 630 A 630 A 250 A 630 A 250 A 630 A CB-RSS02-QF3 CB-RSS02-QF2 CB-RSS04-QF4 CB-RSS03-QF3 CB-RSS03-QF2 CB-RSS03-QF4 1600 A LVCB-RSS32 1600 A LVCB-RSS31
250 A 630 A 250 A 630 A 250 A 630 A 250 A 630 A 250 A 630 A CB-RSS01-QF3 CB-RSS01-QF2
CB-RSS11-QF3 CB-RSS11-QF2 CB-RSS07-QF3 CB-RSS10-QF3 CB-RSS10-QF2 CB-RSS06-QF3 CB-RSS06-QF2 CB-RSS09-QF3 CB-RSS09-QF2 CB-RSS09-QF4 CB-RSS05-QF3 CB-RSS05-QF2 CB-RSS05-QF4 CB-RSS01-QF4
CB-RSS11-QF4 CB-RSS07-QF2 CB-RSS07-QF4 CB-RSS10-QF4 CB-RSS06-QF4
LV BUS-RSS32 0.48 kV LV BUS-RSS31
LV BUS-RSS33 0.48 kV 0.48 kV LV BUS-RSS30 0.48 kV
LUMP RSS02A LUMP RSS03A
LUMP RSS01A 21 m 200 kVA 21 m AL 21 m AL 200 kVA 21 m AL
LUMP RSS11A LUMP RSS07A LUMP RSS10A LUMP RSS06A LUMP RSS09A LUMP RSS05A AL
21 m 200 kVA 21 m AL 200 kVA 21 m AL 21 m AL 200 kVA 21 m AL Cable73 Cable57 Cable85 Cable84
21 m AL 200 kVA 21 m AL 21 m AL 200 kVA 21 m AL 21 m AL 200 kVA 21 m AL 21 m AL 200 kVA 21 m AL AL 21 m AL
Cable38 Cable17 Cable37 Cable1 Cable67 Cable66 3-1/C 400 3-1/C 400 3-1/C 400 3-1/C 400 1600 A 1600 A
Cable19 Cable16 Cable26 Cable24 Cable28 Cable7 Cable34 Cable30 3-1/C 400
3-1/C 400 3-1/C 400 3-1/C 400 3-1/C 400 3-1/C 400 1000 A 1000 A
3-1/C 400 3-1/C 400 3-1/C 400 3-1/C 400 3-1/C 400 3-1/C 400 3-1/C 400 3-1/C 400 CAP40 CAP149 630 A 630 A
CAP140 2x12.5 kvar 2x12.5 kvar 630 A 630 A 630 A
CAP51 CAP132 CAP12 CAP49 CAP56 CAP5 CB200 CB196 630 A 630 A CB193 CB189 630 A 630 A
2x12.5 kvar 2x12.5 kvar 2x12.5 kvar 250 A CB198 CB205 250 A 630 A
2x12.5 kvar 2x12.5 kvar 2x12.5 kvar 2x12.5 kvar 630 A CAP8 630 A CAP148 CB194 CB203 CB191 CB186
4x25 kvar 630 A 250 A CB187 CB184
CAP11 630 A CAP1 630 A CAP139 CB-RSS02-RP2A-QF1 4x25 kvar 630 A CB-RSS03-RP2A-QF1 250 A
630 A CAP14 630 A CAP131 630 A CAP7 630 A CAP10 630 A 4x25 kvar 4x25 kvar 630 A CB-RSS03-RP2B-QF1 LUMP RSS4A2 CB201 LUMP RSS4A1
4x25 kvar 630 A 4x25 kvar 630 A 4x25 kvar 630 A 4x25 kvar 630 A CB-RSS09-RP2A-QF1 4x25 kvar 630 A CB-RSS05-RP2A-QF1 630 A CB-RSS01-RP2A-QF1 CB-RSS02-RP2B-QF1 200 kVA 200 kVA CB182
CB-RSS11-RP2A-QF1 CB-RSS07-RP2A-QF1 CB-RSS10-RP2A-QF1 CB-RSS06-RP2A-QF1 CB-RSS05-RP2B-QF1 CB-RSS01-RP2B-QF1 21 m
CB-RSS11-RP2B-QF1 CB-RSS07-RP2B-QF1 CB-RSS10-RP2B-QF1 CB-RSS06-RP2B-QF1 CB-RSS09-RP2B-QF1 RSS02-RP2A RSS02-RP2B RSS03-RP2A 630 A RSS03-RP2B 21 m 32 m CU 21 m 21 m CU
RSS01-RP2B 630 A 630 A 630 A CU CU 47 m CU Cable102 CU 21 m CU 32 m CU 47 m CU 21 m CU
RSS11-RP2B RSS07-RP2B RSS10-RP2B RSS06-RP2B RSS09-RP2B RSS05-RP2A 630 A RSS05-RP2B 630 A RSS01-RP2A 630 A Cable94 Cable92 CAP99 Cable93 Cable103 Cable56 CAP95 Cable51
630 A RSS11-RP2A 630 A 630 A RSS07-RP2A 630 A 630 A RSS10-RP2A 630 A 630 A RSS06-RP2A 630 A 630 A RSS09-RP2A 630 A 630 A 0.48 kV 0.48 kV 0.48 kV 0.48 kV 4x25 kvar 1-3/C 500 Cable74 Cable63 1-3/C 500 Cable52
0.48 kV 0.48 kV 1-3/C 500 1-3/C 500 1-3/C 500 CAP103 1-3/C 500 1-3/C 500 1-3/C 500 4x25 kvar 1-3/C 500 1-3/C 500
0.48 kV 0.48 kV 0.48 kV 0.48 kV 0.48 kV 0.48 kV 0.48 kV LUMP RSS7A6 LUMP RSS7A5 CAP92
0.48 kV 0.48 kV 0.48 kV 0.48 kV 0.48 kV 200 kVA 4x25 kvar
250 A 250 A 250 A 630 A 200 kVA 4x25 kvar
250 A CB-RSS03-RP2B-QF2 630 A 630 A 630 A 630 A 630 A 630 A
250 A 250 A 250 A 250 A 250 A CB-RSS02-RP2A-QF2 CB-RSS02-RP2B-QF2 CB-RSS03-RP2A-QF2 630 A ISO-RSS7-RP2B13 630 A ISO-RSS7-RP2B11
250 A 250 A 250 A 250 A 250 A 250 A 250 A 250 A 250 A CB-RSS05-RP2B-QF2 CB-RSS01-RP2A-QF2 CB-RSS01-RP2B-QF2 ISO-RSS4-RP2A2 ISO-RSS4-RP2B2 ISO-RSS4-RP2C2 ISO-RSS4-RP2B1 ISO-RSS4-RP2C1 630 A
CB-RSS11-RP2A-QF2 CB-RSS11-RP2B-QF2 CB-RSS07-RP2A-QF2 CB-RSS07-RP2B-QF2 CB-RSS10-RP2A-QF2 CB-RSS10-RP2B-QF2 CB-RSS06-RP2A-QF2 CB-RSS06-RP2B-QF2 CB-RSS09-RP2A-QF2 CB-RSS09-RP2B-QF2 CB-RSS05-RP2A-QF2 ISO-RSS7-RP2B12 ISO-RSS4-RP2A1 ISO-RSS7-RP2B10
LUMP RSS02C LUMP RSS03C
LUMP RSS03B RSS7-RP2C6
LUMP RSS05C LUMP RSS01C LUMP RSS02B 200 kVA 200 kVA 630 A RSS7-RP2C5
LUMP RSS11C LUMP RSS07C LUMP RSS10C LUMP RSS06C LUMP RSS09C LUMP RSS05B LUMP RSS01B 200 kVA 200 kVA 200 kVA RSS7-RP2A2 RSS4-RP2B2 RSS4-RP2C2 RSS7-RP2B6 0.48 kV RSS7-RP2A1 RSS4-RP2B1 RSS4-RP2C1 RSS7-RP2B5 630 A
LUMP RSS11B LUMP RSS07B LUMP RSS10B LUMP RSS06B LUMP RSS09B 200 kVA 200 kVA 630 A 630 A 630 A 630 A 630 A 630 A 630 A 0.48 kV
200 kVA 200 kVA 200 kVA 200 kVA 200 kVA 200 kVA 200 kVA 630 A
200 kVA 200 kVA 200 kVA 200 kVA
0.48 kV
0.48 kV 0.48 kV
0.48 kV 0.48 kV 0.48 kV
0.48 kV
0.48 kV
CAP146 CAP147 CAP41 CAP145 CAP152 CAP153 CAP150 CAP151 250 A 250 A
CAP142 2x12.5 kvar 2x12.5 kvar 250 A 250 A
CAP128 CAP134 CAP45 CAP53 CAP138 CAP125 CAP38 CAP39 CAP34 CAP35 CAP143 CAP144 CAP141 4x25 kvar 2x12.5 kvar 4x25 kvar 2x12.5 kvar 4x25 kvar 4x25 kvar CB199 250 A 250 A CB204 250 A
CAP129 CAP130 CAP52 CAP135 CAP136 CAP133 CAP47 CAP48 CAP13 CAP54 CAP55 CAP50 CAP137 CAP57 2x12.5 kvar 2x12.5 kvar 4x25 kvar 2x12.5 kvar 4x25 kvar 2x12.5 kvar CB195 250 A LUMP RSS7D6 CB192 250 A 250 A CB185
4x25 kvar 2x12.5 kvar 4x25 kvar 2x12.5 kvar 4x25 kvar 2x12.5 kvar 4x25 kvar 2x12.5 kvar 4x25 kvar 2x12.5 kvar 4x25 kvar 2x12.5 kvar 4x25 kvar 2x12.5 kvar 4x25 kvar 2x12.5 kvar 4x25 kvar 2x12.5 kvar 4x25 kvar 2x12.5 kvar 4x25 kvar 4x25 kvar CB197 CB202 CB188 CB190 LUMP RSS7D5
LUMP RSS7B2 LUMP RSS4B2 LUMP RSS4C2 LUMP RSS7C6 200 kVA LUMP RSS4C1 CB183 200 kVA
200 kVA LUMP RSS7B1 LUMP RSS4B1 LUMP RSS7C5
200 kVA 200 kVA 200 kVA 200 kVA 200 kVA 200 kVA 200 kVA
CAP105
CAP94
CAP102 CAP100 CAP101 4x25 kvar CAP98 CAP96 CAP97
4x25 kvar CAP104 CAP93 4x25 kvar
4x25 kvar 4x25 kvar 4x25 kvar 4x25 kvar 4x25 kvar 4x25 kvar
4x25 kvar
Cable278 Cable277 Cable276 Cable275 Cable272 Cable154 Cable152 Cable167

35 m AL 35 m AL 53 m AL 35 m AL 35 m AL 35 m AL 35 m AL 35 m AL
3-1/C 240
3-1/C 240 3-1/C 240 3-1/C 240 3-1/C 240 3-1/C 240 3-1/C 240 3-1/C 240
600 A 600 A 600 A 600 A
600 A 600 A
LBS-RSS12-1 LBS-RSS12-2 LBS-RSS08-1 LBS-RSS04-1 LBS-RSS04-2 600 A 600 A 600 A Cable242 Cable241 Cable240
LBS-RSS08-2 600 A 600 A 600 A 600 A 600 A 600 A 600 A 600 A 600 A 95 m 95 m 95 m
LBS-RSS13-K01 LBS-RSS13-K02 LBS-RSS14-K02 Open AL AL AL
LBS-RSS20-K01 LBS-RSS20-K02 LBS-RSS16-K01 LBS-RSS16-K02 LBS-RSS14-K01 LBS-RSS15-K01 LBS-RSS15-K02 LBS-RSS19-K01 LBS-RSS19-K02

13.8 kV 3-1/C 1000 3-1/C 1000 3-1/C 1000


600 A 600 A 600 A 600 A 600 A 13.8 kV 600 A 13.8 kV 600 A 13.8 kV
13.8 kV 13.8 kV 13.8 kV 600 A 13.8 kV 600 A 13.8 kV 630 A 630 A 630 A 630 A 630 A 630 A 630 A
630 A
Bus-13.8kV RSS-13 LBS-RSS7-22 LBS-RSS7-21 LBS-RSS7-20 LBS-RSS7-19 LBS-RSS7-18 LBS-RSS7-17 LBS-RSS7-16
Bus-13.8kV RSS-20 Bus-13.8kV RSS-16 Bus-13.8kV RSS-14 Bus-13.8kV RSS-15 Bus-13.8kV RSS-19 LBS-RSS7-15
Bus-13.8kV RSS-12 Bus-13.8kV RSS-08 Bus-13.8kV RSS-04

200 A
HVCB-RSS13-K03
HVCB-RSS14-K03 HVCB-RSS15-K03 DISCONNECTOR-RSS19
200 A 200 A 200 A HVCB-RSS20-K03 HVCB-RSS16-K03 600 A 13.8 kV 13.8 kV 13.8 kV 13.8 kV
600 A 600 A
DISCONNECTOR-RSS12 DISCONNECTOR-RSS08 DISCONNECTOR-RSS04 600 A 600 A
630 A 630 A 630 A
630 A
RLY-RSS13-K03 RLY-RSS14-K03 125 A
RLY-RSS20-K03 RLY-RSS16-K03 RLY-RSS15-K03 200 A Bus-13.8kV RSS-36 200 A Bus-13.8kV RSS-35 200 A Bus-13.8kV RSS-34
CT21 CT23 HV FUSE RSS-19 200 A Bus-13.8kV RSS-37
CT20 CT22 CT24 DISCONNECTOR-RSS34 DISCONNECTOR-RSS35 DISCONNECTOR-RSS36
125 A 125 A 125 A 75/1 75/1 75/1 DISCONNECTOR-RSS37
HV FUSE RSS-12 HV FUSE RSS-08 HV FUSE RSS-04 75/1 75/1 125 A 125 A 125 A
125 A
FUSE RSS-34 FUSE RSS-35 FUSE RSS-36
FUSE RSS-37
Cable115
Cable15 Cable95 Cable105 Cable111 Cable123 Cable137 Cable162
10 m AL 10 m AL Cable166 Cable158 Cable235 Cable239
10 m AL 10 m AL 10 m AL 10 m AL 10 m AL 10 m AL 10 m AL Cable243
3-1/C 70 3-1/C 70 10 m 10 m 10 m
3-1/C 70 3-1/C 70 3-1/C 70 3-1/C 70 3-1/C 70 3-1/C 70 3-1/C 70 10 m AL AL AL AL
1-3/C 2/0 1-3/C 2/0 1-3/C 2/0
1-3/C 2/0

TR-RSS13
TR-RSS12 (Exis ng) TR-RSS08 (Exis ng) TR-RSS04 (Exis ng) TR-RSS20 TR-RSS16 TR-RSS14 TR-RSS15
5 %Z Dyn1 5 %Z TR-RSS19 (Exis ng) TR-RSS36
5 %Z Dyn1 5 %Z Dyn1 5 %Z Dyn1 5 %Z Dyn1 5 %Z Dyn1 Dyn1 5 %Z Dyn1 6.5 %Z Dyn1 TR-RSS37 TR-RSS34 TR-RSS35
850 kVA 850 kVA 13.8/0.494 kV 5 %Z 13.8/0.494 kV 5 %Z 13.8/0.494 kV 5 %Z Dyn1 13.8/0.494 kV
750 kVA 750 kVA 750 kVA 850 kVA 850 kVA 13.8/0.494 kV 850 kVA 1000 kVA 5 %Z Dyn1 Dyn1 Dyn1
13.8/0.494 kV 13.8/0.494 kV 13.8/0.494 kV 13.8/0.494 kV 13.8/0.494 kV 13.8/0.494 kV 13.8/0.494 kV 750 kVA 750 kVA 750 kVA
13.8/0.494 kV 750 kVA

6 m AL 6 m AL AL CU 6m CU 6m CU 6m
6 m AL 6 m AL 6 m AL 6 m AL 6 m AL Cable114 6m 6 m AL CU 6m
Cable14 Cable91 Cable99 Cable107 Cable119 Cable132 Cable161 Cable165 Cable244 Cable127 2-3/C 750 Cable234 2-3/C 750 Cable238 2-3/C 750
12-1/C 240 12-1/C 240 2-3/C 750
12-1/C 240 12-1/C 240 12-1/C 240 12-1/C 240 12-1/C 240 12-1/C 240 12-1/C 240

1000 A 1000 A 1000 A


1000 A LVCB-RSS37 LVCB-RSS34 LVCB-RSS35 LVCB-RSS36
1000 A 1000 A 1000 A
1000 A 1000 A 1000 A 1000 A 1000 A CB-RSS13-QF1 1000 A
CB-RSS12-QF1 CB-RSS08-QF1 CB-RSS04-QF1 CB-RSS20-QF1 CB-RSS16-QF1 CB-RSS14-QF1 CB-RSS15-QF1 CB-RSS19-QF1
0.48 kV 0.48 kV 0.48 kV
LV BUS-RSS37 0.48 kV LV BUS-RSS36 LV BUS-RSS35 LV BUS-RSS34
LV BUS-RSS13 0.48 kV 1000 A LV BUS-RSS14
0.48 kV 1000 A 0.48 kV 1000 A 0.48 kV 1000 A LV BUS-RSS20 0.48 kV 1000 A LV BUS-RSS16 0.48 kV 1000 A 0.48 kV 1000 A LV BUS-RSS15 0.48 kV 1000 A LV BUS-RSS19 0.48 kV 1000 A
LV BUS-RSS12 LV BUS-RSS08 LV BUS-RSS04

1000 A 1000 A 1000 A 1000 A


630 A 630 A 630 A 630 A
630 A 630 A 250 A 630 A 630 A 630 A 630 A 630 A 630 A 630 A 630 A
630 A 630 A 630 A 630 A CB-RSS13-QF3 250 A 630 A 250 A 630 A 630 A 630 A 630 A CB210 CB215 CB220
630 A 250 A 250 A CB-RSS13-QF2 CB-RSS13-QF4 CB-RSS14-QF3 CB-RSS14-QF2 CB-RSS14-QF4 CB-RSS15-QF3 250 A CB223 CB208 CB213 CB218
250 A 250 A 250 A CB-RSS20-QF3 CB-RSS20-QF2 CB-RSS20-QF4 CB-RSS16-QF3 CB-RSS16-QF2 CB-RSS16-QF4 CB-RSS15-QF2 CB-RSS15-QF4 CB-RSS19-QF3 CB-RSS19-QF2 CB-RSS19-QF4 CB-RSS19-QF5 CB224 250 A 250 A 250 A
CB-RSS12-QF3 CB-RSS12-QF2 CB-RSS08-QF3 CB-RSS08-QF2 CB-RSS04-QF3 CB-RSS04-QF2 250 A
CB221 CB206 CB211 CB216
21 m CU 21 m CU 21 m CU
LUMP RSS13A LUMP RSS14A LUMP RSS15A 21 m CU 21 m CU 21 m CU 21 m CU
LUMP RSS20A LUMP RSS16A 21 m AL 200 kVA 21 m AL 200 kVA LUMP RSS19A 21 m CU Cable109 Cable159 Cable236
21 m AL LUMP RSS12A 21 m AL LUMP RSS08A 21 m AL LUMP RSS04A 21 m AL 200 kVA 21 m AL 21 m AL 200 kVA 21 m AL 21 m AL 21 m AL 21 m AL 200 kVA 21 m AL 21 m AL 200 kVA 21 m AL 21 m Cable246 Cable245 1-3/C 500 Cable110 1-3/C 500 Cable160 1-3/C 500 Cable237
200 kVA 200 kVA 200 kVA Cable113 Cable112 Cable59 Cable58 AL 1-3/C 500 1-3/C 500 1-3/C 500 1-3/C 500
Cable12 Cable88 Cable96 Cable106 Cable83 Cable118 Cable116 Cable157 Cable155 Cable164 Cable163 Cable169 1-3/C 500 LUMP RSS7A7 CAP106 LUMP RSS7A8 CAP109 LUMP RSS7A9 CAP112
3-1/C 400 3-1/C 400 3-1/C 400 3-1/C 400 LUMP RSS7A10 CAP115 4x25 kvar
3-1/C 400 3-1/C 400 3-1/C 400 3-1/C 400 3-1/C 400 3-1/C 400 3-1/C 400 3-1/C 400 3-1/C 400 3-1/C 400 3-1/C 400 3-1/C 400 200 kVA 4x25 kvar 200 kVA 4x25 kvar 200 kVA 4x25 kvar 200 kVA
630 A 630 A 630 A 630 A
CAP73 CAP19 ISO-RSS7-RP2B15 ISO-RSS7-RP2B17 ISO-RSS7-RP2B19
CAP27 CAP163 2x12.5 kvar CAP169 CAP175 ISO-RSS7-RP2B20 630 A 630 A 630 A
CAP44 CAP6 CAP43 2x12.5 kvar 2x12.5 kvar 2x12.5 kvar 2x12.5 kvar 2x12.5 kvar 630 A
2x12.5 kvar 2x12.5 kvar 2x12.5 kvar ISO-RSS7-RP2B21 ISO-RSS7-RP2B14 ISO-RSS7-RP2B16 ISO-RSS7-RP2B18
630 A CAP20 CAP15
630 A CAP3 630 A CAP162 4x25 kvar 630 A 630 A CAP168 630 A CAP174
630 A CAP9 630 A CAP2 630 A CAP42 4x25 kvar 4x25 kvar CB-RSS13-RP2A-QF1 630 A CB-RSS14-RP2A-QF1 4x25 kvar 630 A 4x25 kvar 4x25 kvar 630 A RSS7-RP2C7 630 A RSS7-RP2C8 630 A RSS7-RP2C9
CB-RSS20-RP2A-QF1 630 A CB-RSS16-RP2A-QF1 630 A CB-RSS13-RP2B-QF1 CB-RSS15-RP2A-QF1 630 A CB-RSS19-RP2A-QF1 630 A 630 A 630 A RSS7-RP2C10 RSS7-RP2B7 RSS7-RP2B8 RSS7-RP2B9
CB-RSS12-RP2A-QF1 4x25 kvar CB-RSS08-RP2A-QF1 4x25 kvar CB-RSS04-RP2A-QF1 4x25 kvar CB-RSS20-RP2B-QF1 CB-RSS16-RP2B-QF1 CB-RSS14-RP2B-QF1 CB-RSS15-RP2B-QF1 CB-RSS19-RP2B-QF1 RSS7-RP2B10 0.48 kV 0.48 kV 0.48 kV
CB-RSS19-RP2C-QF1 0.48 kV 630 A 630 A 630 A
RSS13-RP2A 630 A RSS13-RP2B RSS14-RP2B 630 A
RSS20-RP2A 630 A RSS20-RP2B RSS16-RP2A 630 A RSS16-RP2B 630 A 630 A RSS14-RP2A 630 A 630 A RSS15-RP2A 630 A RSS15-RP2B RSS19-RP2A 630 A RSS19-RP2B RSS19-RP2C
RSS12-RP2A RSS08-RP2A RSS04-RP2A 630 A 630 A 0.48 kV 630 A 630 A
630 A 630 A 630 A 0.48 kV 0.48 kV 0.48 kV 0.48 kV 0.48 kV 0.48 kV
0.48 kV 0.48 kV 0.48 kV 0.48 kV 0.48 kV 0.48 kV 0.48 kV 0.48 kV 0.48 kV 0.48 kV
0.48 kV 0.48 kV 0.48 kV
250 A 250 A 250 A
250 A 250 A 250 A 250 A CB-RSS13-RP2B-QF2 250 A 250 A 250 A 250 A 250 A 250 A 250 A 250 A 250 A
250 A CB-RSS20-RP2B-QF2 CB-RSS16-RP2B-QF2 CB-RSS13-RP2A-QF2 CB-RSS14-RP2A-QF2 CB-RSS14-RP2B-QF2 CB-RSS15-RP2B-QF2 CB-RSS19-RP2B-QF2 250 A CB214 CB219
250 A 250 A CB-RSS20-RP2A-QF2 CB-RSS16-RP2A-QF2 CB-RSS15-RP2A-QF2 CB-RSS19-RP2A-QF2 CB-RSS19-RP2C-QF2 CB222 250 A CB209 250 A 250 A
CB-RSS12-RP2A-QF2 CB-RSS08-RP2A-QF2 CB-RSS04-RP2A-QF2 250 A LUMP RSS7D7 LUMP RSS7D8 LUMP RSS7D9
LUMP RSS7D10 CB207 200 kVA CB212 200 kVA CB217 200 kVA
LUMP RSS13C CB225 200 kVA LUMP RSS7C8 LUMP RSS7C9 LUMP RSS7C10
LUMP RSS20C LUMP RSS16C LUMP RSS13B LUMP RSS14C LUMP RSS15C LUMP RSS19C LUMP RSS19D LUMP RSS7C7 200 kVA 200 kVA 200 kVA
LUMP RSS20B LUMP RSS16B 200 kVA LUMP RSS14B 200 kVA LUMP RSS15B LUMP RSS19B 200 kVA
LUMP RSS12B 200 kVA 200 kVA 200 kVA 200 kVA 200 kVA 200 kVA 200 kVA
LUMP RSS08B LUMP RSS04B 200 kVA 200 kVA 200 kVA 200 kVA CAP108 CAP111 CAP114
200 kVA 200 kVA 200 kVA CAP116 4x25 kvar 4x25 kvar 4x25 kvar
4x25 kvar CAP107 CAP110 CAP113
CAP117
4x25 kvar 4x25 kvar 4x25 kvar
4x25 kvar

CAP160 CAP161 CAP74 CAP159 CAP79 CAP77


CAP126 CAP127 CAP29 CAP33 CAP154 CAP155 CAP157 CAP158 CAP28 CAP156 CAP166 CAP167 CAP164 CAP165 2x12.5 kvar 2x12.5 kvar CAP78 CAP68 CAP172 CAP173 CAP170 CAP171 CAP178 CAP179 CAP176 CAP177 CAP180 CAP181
2x12.5 kvar 2x12.5 kvar 2x12.5 kvar 2x12.5 kvar 2x12.5 kvar 2x12.5 kvar 4x25 kvar 4x25 kvar 4x25 kvar 2x12.5 kvar 4x25 kvar 2x12.5 kvar 4x25 kvar 2x12.5 kvar 4x25 kvar 2x12.5 kvar 2x12.5 kvar 2x12.5 kvar
4x25 kvar 4x25 kvar 2x12.5 kvar 4x25 kvar 4x25 kvar 4x25 kvar 4x25 kvar 4x25 kvar 4x25 kvar 4x25 kvar 4x25 kvar 2x12.5 kvar

Cable184
Cable269 Cable171 Cable172 Cable189 Cable190 Cable195
35 m AL 35 m 35 m 35 m AL 35 m AL 35 m AL 35 m AL
AL AL
3-1/C 240 3-1/C 240 3-1/C 240 3-1/C 240 3-1/C 240 3-1/C 240 3-1/C 240
600 A 600 A 600 A 600 A 600 A 600 A
LBS-RSS21-K01 600 A 600 A 600 A 600 A 600 A 600 A 600 A 600 A 600 A 600 A
LBS-RSS21-K02 LBS-RSS17-K01 LBS-RSS22-K01 LBS-RSS18-K01 LBS-RSS26-K01 LBS-RSS25-K01
LBS-RSS17-K02 LBS-RSS22-K02 LBS-RSS18-K02 LBS-RSS23-K01 LBS-RSS23-K02 LBS-RSS26-K02 LBS-RSS25-K02 LBS-RSS24-K01 LBS-RSS24-K02 Open
630 A
630 A
STS-SS LBS-1 STS-SS LBS-2
600 A Open
13.8 kV 600 A 13.8 kV 600 A 13.8 kV 600 A 13.8 kV 600 A 13.8 kV 600 A 13.8 kV 600 A 13.8 kV
600 A 13.8 kV

Bus-13.8kV RSS-21 Bus-13.8kV RSS-17 Bus-13.8kV RSS-23


Bus-13.8kV RSS-22 Bus-13.8kV RSS-18 Bus-13.8kV RSS-26 Bus-13.8kV RSS-25 Bus-13.8kV RSS-24 13.8 kV
Bus-13.8kV STS RMU
200 A 630 A
HVCB-RSS21-K03 DISCONNECTOR-RSS23
HVCB-RSS17-K03 HVCB-RSS22-K03 HVCB-RSS18-K03 HVCB-RSS26-K03 HVCB-RSS25-K03
600 A 600 A 600 A 600 A 600 A 600 A HVCB-RSS24-K03 200 A
600 A 200 A 200 A 200 A 200 A 200 A 200 A
CB-STS-TRAFO 200 A 200 A
CB-STS-1 CB-STS-2 CB-STS-3 CB-STS-4 CB-STS-5
RLY-RSS21-K03 CB-STS-6 CB-STS-7 CB-STS-8
RLY-RSS17-K03 RLY-RSS22-K03 RLY-RSS18-K03 125 A RLY-RSS26-K03 RLY-RSS25-K03 RLY-RSS24-K03
CT10 HV FUSE RSS-23 Open Open
CT25 CT26 CT27 CT28 CT29 CT30 Relay STS TRAFO
75/1 75/1 75/1 75/1 Relay STS-1 Relay STS-2 Relay STS-3 Relay STS-4 Relay STS-5 Relay STS-6
75/1 75/1 75/1
CT4 CT5 CT6 CT7 CT8 CT9 CT3
100/1 100/1 100/1 100/1 100/1 100/1 50/1

Cable11 Cable125 Cable170 Cable174 Cable188 Cable175


10 m AL Cable183 Cable194
10 m AL 10 m AL 10 m AL 10 m AL 10 m AL 10 m AL
3-1/C 70 3-1/C 70 10 m AL
3-1/C 70 3-1/C 70 3-1/C 70 3-1/C 70 3-1/C 70 3-1/C 70

Cable232
Cable325 Cable326 Cable328 Cable330 Cable329 Cable336 Cable233
TR-RSS21 TR-RSS17 TR-RSS22 TR-RSS18 TR-RSS26 TR-RSS25 Cable327 235 m AL 130 m AL
5 %Z TR-RSS23 (Exis ng) TR-RSS24 160 m AL 160 m AL 235 m AL AL 395 m AL 395 m AL 10 m AL 130 m
Dyn1 5 %Z Dyn1 5 %Z Dyn1 5 %Z Dyn1 Dyn1 5 %Z Dyn1 5 %Z Dyn1 5 %Z 3-1/C 70 3-1/C 70 1-3/C 2/0 1-3/C 2/0
850 kVA 850 kVA 6.5 %Z Dyn1 3-1/C 70 3-1/C 70 3-1/C 70 3-1/C 70 3-1/C 95
850 kVA 850 kVA 1000 kVA 850 kVA 850 kVA 850 kVA
13.8/0.494 kV 13.8/0.494 kV 13.8/0.494 kV 13.8/0.494 kV 13.8/0.494 kV 13.8/0.494 kV
13.8/0.494 kV 13.8/0.494 kV
TR-STS
4 %Z 315 kVA
Dyn1
6 m AL 6 m AL 6 m AL 6 m AL 13.8/0.227 kV
Cable138 6 m AL 6 m AL 6 m AL 6 m AL
Cable124 Cable136 Cable178 Cable182 Cable187 Cable173
12-1/C 240 12-1/C 240 12-1/C 240 12-1/C 240 Cable193
12-1/C 240 12-1/C 240 12-1/C 240 12-1/C 240
LUMP-STS-3 LUMP-STS-4 LUMP-STS-6
LUMP-STS-1 LUMP-STS-2 LUMP-STS-5 LUMP-STS-7 LUMP-STS-8
630 kVA 630 kVA 630 kVA 630 kVA 630 kVA 630 kVA
AL 15 m 630 kVA 630 kVA
1000 A 1000 A 1000 A 1000 A Cable151 6-1/C 240
1000 A 1000 A 1000 A 1000 A
CB-RSS21-QF1 CB-RSS17-QF1 CB-RSS22-QF1 CB-RSS18-QF1 CB-RSS23-QF1 CB-RSS26-QF1 CB-RSS25-QF1
CB-RSS24-QF1
CB-STS-QF1
1000 A
LV BUS-RSS21 LV BUS-RSS17
0.48 kV 1000 A 0.48 kV 1000 A LV BUS-RSS22 0.48 kV 1000 A LV BUS-RSS18 0.48 kV 1000 A LV BUS-RSS23 1000 A LV BUS-RSS26 0.48 kV 1000 A LV BUS-RSS25 0.48 kV 1000 A LV BUS-RSS24
0.48 kV 0.48 kV 1000 A
LV BUS-STS
0.22 kV 1000 A

630 A 630 A 630 A 630 A 630 A 630 A


250 A 630 A 250 A 630 A 250 A 630 A 250 A 630 A 630 A 630 A 250 A 630 A 250 A 630 A 630 A 0A 0A
CB-RSS21-QF3 CB-RSS21-QF2 CB-RSS21-QF4 CB-RSS17-QF3 CB-RSS22-QF3 CB-RSS18-QF3 250 A 630 A CB-RSS26-QF3 CB-RSS25-QF3 250 A 630 A 250 A
CB-RSS17-QF2 CB-RSS17-QF4 CB-RSS22-QF2 CB-RSS22-QF4 CB-RSS18-QF2 CB-RSS18-QF4 CB-RSS23-QF3 CB-RSS23-QF2 CB-RSS23-QF4 CB-RSS23-QF5 CB-RSS26-QF2 CB-RSS26-QF4 CB-RSS25-QF2 CB-RSS25-QF4 CB-RSS24-QF3 CB-RSS24-QF4 CB1 CB2 Open
CB-RSS24-QF2 CB-STS-QF2

LUMP RSS21A LUMP RSS17A LUMP RSS22A LUMP RSS18A


21 m AL 200 kVA 200 kVA LUMP RSS23A LUMP RSS26A LUMP RSS25A LUMP RSS24A
21 m AL 21 m AL 21 m AL 21 m AL 200 kVA 21 m AL 21 m AL 200 kVA 21 m AL 21 m AL 200 kVA 21 m AL 21 m AL 200 kVA 21 m AL 21 m AL 200 kVA 21 m AL AL 200 kVA Cable3
Cable197 Cable198 Cable122 21 m AL 21 m 21 m AL
Cable121 Cable135 Cable130 Cable177 Cable176 Cable180 Cable179 Cable181 Cable186 Cable185 Cable168 Cable18 Cable192 Cable191 CU 500 m
3-1/C 400 3-1/C 400 3-1/C 400 2-4/C 150
3-1/C 400 3-1/C 400 3-1/C 400 3-1/C 400 3-1/C 400 3-1/C 400 3-1/C 400 3-1/C 400 3-1/C 400 3-1/C 400 3-1/C 400 3-1/C 400 3-1/C 400 3-1/C 400 LUMP STS-TRAFO LUMP1 STS-TRAFO
184 kVA 50 kVA
CAP123 CAP18 CAP58 CAP64
2x12.5 kvar CAP71 CAP188 CAP36 CAP196 VFD1
2x12.5 kvar 2x12.5 kvar 2x12.5 kvar 2x12.5 kvar 2x12.5 kvar 2x12.5 kvar 2x12.5 kvar
CAP16
630 A 630 A CAP17 630 A CAP25 630 A CAP63 630 A CAP70 630 A CAP187 630 A CAP4 CAP195
CB-RSS21-RP2A-QF1 4x25 kvar 630 A 4x25 kvar 630 A 4x25 kvar 630 A 4x25 kvar 630 A 4x25 kvar 4x25 kvar 630 A
CB-RSS17-RP2A-QF1 CB-RSS22-RP2A-QF1 CB-RSS18-RP2A-QF1 CB-RSS23-RP2A-QF1 4x25 kvar 630 A 630 A CB-RSS26-RP2A-QF1 630 A CB-RSS25-RP2A-QF1 630 A CB-RSS24-RP2A-QF1 4x25 kvar 630 A
CB-RSS21-RP2B-QF1 CB-RSS17-RP2B-QF1 CB-RSS22-RP2B-QF1 CB-RSS18-RP2B-QF1 CB-RSS26-RP2B-QF1 CB-RSS25-RP2B-QF1
CB-RSS23-RP2B-QF1 CB-RSS23-RP2C-QF1 CB-RSS24-RP2B-QF1
RSS21-RP2B RSS17-RP2B RSS22-RP2B RSS18-RP2B
630 A RSS21-RP2A 630 A 630 A RSS17-RP2A 630 A 630 A RSS22-RP2A 630 A 630 A RSS18-RP2A 630 A RSS23-RP2A RSS23-RP2B RSS23-RP2C RSS26-RP2A 630 A RSS26-RP2B RSS25-RP2A 630 A RSS25-RP2B RSS24-RP2B
630 A 630 A 630 A 630 A 630 A 630 A RSS24-RP2A 630 A 55 kW
0.48 kV 0.48 kV 0.48 kV 0.48 kV 0.48 kV 0.48 kV
0.48 kV 0.48 kV 0.48 kV 0.48 kV 0.48 kV 0.48 kV 0.48 kV 0.48 kV 0.48 kV LV MOTOR-STS
0.48 kV 0.48 kV
250 A
250 A 250 A 250 A 250 A 250 A 250 A 250 A 250 A 250 A 250 A 250 A 250 A 250 A 250 A
CB-RSS21-RP2A-QF2 CB-RSS21-RP2B-QF2 CB-RSS17-RP2A-QF2 CB-RSS17-RP2B-QF2 CB-RSS22-RP2A-QF2 CB-RSS22-RP2B-QF2 CB-RSS18-RP2A-QF2 CB-RSS18-RP2B-QF2 250 A CB-RSS26-RP2B-QF2 CB-RSS25-RP2B-QF2 250 A
CB-RSS23-RP2A-QF2 CB-RSS23-RP2B-QF2 CB-RSS23-RP2C-QF2 CB-RSS26-RP2A-QF2 CB-RSS25-RP2A-QF2 CB-RSS24-RP2A-QF2 CB-RSS24-RP2B-QF2

LUMP RSS21C LUMP RSS17C LUMP RSS22C LUMP RSS18C LUMP RSS23C LUMP RSS26C LUMP RSS25C
LUMP RSS21B 200 kVA LUMP RSS17B 200 kVA LUMP RSS22B LUMP RSS18B LUMP RSS23D LUMP RSS26B LUMP RSS25B LUMP RSS24C
200 kVA 200 kVA 200 kVA 200 kVA LUMP RSS23B 200 kVA 200 kVA 200 kVA 200 kVA LUMP RSS24B 200 kVA
200 kVA 200 kVA 200 kVA 200 kVA 200 kVA 200 kVA

CAP76 CAP124 CAP22 CAP60 CAP66


CAP75 CAP122 CAP23 CAP24 CAP21 CAP61 CAP62 CAP59 CAP67 CAP69 CAP65 CAP183 CAP184 CAP72 CAP182 CAP186 CAP191 CAP192 CAP189 CAP190 CAP193 CAP194 CAP37 CAP46 CAP200 CAP198
4x25 kvar 2x12.5 kvar 4x25 kvar 2x12.5 kvar 4x25 kvar 2x12.5 kvar 4x25 kvar 2x12.5 kvar 4x25 kvar 2x12.5 kvar 4x25 kvar 2x12.5 kvar 4x25 kvar 2x12.5 kvar 4x25 kvar 2x12.5 kvar CAP185 2x12.5 kvar 2x12.5 kvar 2x12.5 kvar 2x12.5 kvar CAP199 CAP197
4x25 kvar 2x12.5 kvar 4x25 kvar 2x12.5 kvar 4x25 kvar 2x12.5 kvar 4x25 kvar 4x25 kvar 4x25 kvar 4x25 kvar 4x25 kvar 2x12.5 kvar 4x25 kvar 2x12.5 kvar
Document Tile Document No. Revision Date Page No.
RELAY COORDINATION &
ABB-TEC-CAL-035 V2 21-March-2024 28 of 85
PROTECTION STUDY

Annexure-3

13.8kV AIS Panel Main Substation Protection setting


table
Amps X 100 69kV MAIN I/C-1 (Nom. kV=69, Plot Ref. kV=69)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K ∆0s 1K
T1-TMS1-69-1
FLA - ONAF 65
500 500
AIS-MAIN MV SWGR BUS-A INCOMER-1
300 300 69 kV
RLY_LINE_SE_LOS_PINOS - P 522.504 MVAsc
OC1
ABB
2000 A
REF 620
100 100
CT Ratio 600:5 RLY_69KV GRID_BACKUP - P CB-CNEL_SE_LOS_PINOS
IEC Very Inverse
±

OC1 CT72 R RLY_LINE_SE_LOS_PINOS


Pickup = 0.333 (0.05 - 5 xCT Sec) 600/5
50 ABB 50
Time Dial = 0.52
REF 620
3x = 3.51 s, 5x = 1.75 s, 8x = 1 s
30 CT Ratio 400:5 30
Inst = 6.333 (1 - 40 xCT Sec)
IEC Very Inverse
Time Delay = 0.02 s
Pickup = 0.425 (0.05 - 5 xCT Sec)
Time Dial = 0.3 1250 A
3x = 2.03 s, 5x = 1.01 s, 8x = 0.579 s GANG.OPR.DISCONT-GRID
10 Inst = 7.5 (1 - 40 xCT Sec) 10
69kV MAIN I/C-1
Time Delay = 0.02 s
RLY_GRID I/C-1_H04 - P 69 kV
5 5 1250 A
OC1
Seconds

Seconds
ABB 1250 A
3 3
REF 615 CB-PASS MODULE
T1-TMS1-69-1 CT Ratio 1250:5
Withstand Group 1 ±

IEC Very Inverse CT2 R RLY_69KV GRID_BACKUP


400/5
1 Pickup = 0.68 (0.05 - 5 xCT Sec) 1
Cable5 - P Time Dial = 0.2
3x = 1.35 s, 5x = 0.675 s, 8x = 0.386 s ±

Inst = 5.5 (1 - 40 xCT Sec) CT1 R RLY_69KV GRID_MAIN


.5 .5
400/5
Time Delay = 0.2 s
∆ 0.258 s
.3 .3
T1-TMS1-69-1
30 MVA
3000 A, 0.502 s 69/13.8 kV
3000 A, 0.243 s 12 %Z Dyn1
.1 .1
T1-TMS1-69-1
Inrush
.05 .05
12-1/C 240
.03 .03 Cable5
25 m AL
RLY_GRID I/C-1_H04 - 3P
RLY_LINE_SE_LOS_PINOS - 3P
RLY_GRID I/C-1_H04
RLY_69KV GRID_BACKUP - 3P ±

.01 .01
CT46 R
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K 1250/5

Amps X 100 69kV MAIN I/C-1 (Nom. kV=69, Plot Ref. kV=69) ETAP Star 22.5.0N

1250 A
HVCB_GRID I/C-1_H04

Project: PROTECTION STUDY Date: 06-03-2024


AIS-MAIN MV SWGR BUS-A 1250 A
Location: PUERTO BOLIVAR - ECUADOR Fault: Phase
Contract: ABB 13.8 kV
Engineer: RL
Amps X 10 Bus187 (Nom. kV=69, Plot Ref. kV=69)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K

500 CNEL_I/C_LINE_69KV Cable5 500


Ampacity Ampacity INCOMER-1
300 300 69 kV
522.504 MVAsc
RLY_69KV GRID_BACKUP - G
OC1 2000 A
100 ABB 100
CB-CNEL_SE_LOS_PINOS
REF 620 ±

CT Ratio 400:5 CT72 R RLY_LINE_SE_LOS_PINOS


IEC Very Inverse 600/5
50 50
Pickup = 0.155 (0.01 - 5 xCT Sec)
Time Dial = 0.35
30 30
3x = 2.36 s, 5x = 1.18 s, 8x = 0.675 s
Inst = 5 (1 - 40 xCT Sec)
Time Delay = 0.02 s 1250 A
GANG.OPR.DISCONT-GRID
10 RLY_LINE_SE_LOS_PINOS - G 10
OC1 69kV MAIN I/C-1
ABB 69 kV
5 REF 620 5 1250 A
Seconds

Seconds
CT Ratio 600:5
IEC Very Inverse
1250 A
3 3
Pickup = 0.167 (0.01 - 5 xCT Sec) CB-PASS MODULE
Time Dial = 0.56
3x = 3.78 s, 5x = 1.89 s, 8x = 1.08 s ±
CT2 RLY_69KV GRID_BACKUP
Inst = 4 (1 - 40 xCT Sec) 400/5
R
1 Time Delay = 0.02 s 1

RLY_GRID I/C-1_H04 - G ±

OC1 CT1 R RLY_69KV GRID_MAIN


.5 .5
400/5
ABB
.3 REF 615 .3
CT Ratio 1250:5 ∆ 0.247 s T1-TMS1-69-1
Group 1 30 MVA
IEC Very Inverse 69/13.8 kV
Pickup = 0.24 (0.01 - 5 xCT Sec)
12 %Z Dyn1
.1 Time Dial = 0.35 .1
3x = 2.36 s, 5x = 1.18 s, 8x = 0.675 s
Inst = 10 (1 - 40 xCT Sec)
.05 Time Delay = 0.04 s .05
12-1/C 240
.03 .03 Cable5
25 m AL

RLY_LINE_SE_LOS_PINOS - G - LG
RLY_69KV GRID_BACKUP - G - LG
RLY_GRID I/C-1_H04
RLY_GRID I/C-1_H04 - G - LG ±

.01 .01
CT46 R
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K 1250/5

Amps X 10 Bus187 (Nom. kV=69, Plot Ref. kV=69) ETAP Star 22.5.0N

1250 A
HVCB_GRID I/C-1_H04

Project: PROTECTION STUDY Date: 06-03-2024


AIS-MAIN MV SWGR BUS-A 1250 A
Location: PUERTO BOLIVAR - ECUADOR Fault: Ground
Contract: ABB 13.8 kV
Engineer: RL
Amps X 100 AIS-MAIN MV SWGR BUS-A (Nom. kV=13.8, Plot Ref. kV=13.8)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
Cable131 AIS-MAIN MV SWGR BUS-A
Ampacity RLY_MAIN B/C_H11 - P
500 RLY_GRID I/C-1_H04 - P OC1 500

OC1 ABB
300 ABB REF 615 300
REF 615 CT Ratio 1250:5
CT Ratio 1250:5 Group 1
Group 1 IEC Very Inverse
IEC Very Inverse Pickup = 0.6 (0.05 - 5 xCT Sec)
100 Time Dial = 0.23 100
Pickup = 0.68 (0.05 - 5 xCT Sec)
Time Dial = 0.2 3x = 1.55 s, 5x = 0.776 s, 8x = 0.444 s
3x = 1.35 s, 5x = 0.675 s, 8x = 0.386 s Inst = 5.57 (1 - 40 xCT Sec)
50 Time Delay = 0.15 s 50
Inst = 5.5 (1 - 40 xCT Sec)
Time Delay = 0.2 s
30 30
RLY_RSSL-1A_H06 - P
RLY_RSSL-2A_H05 - P
OC1
OC1
ABB
RLY_RSSL-3A_H08 - P REF 615
10 OC1 CT Ratio 600:5 10
Group 1
IEC Normal Inverse
5 Pickup = 0.34 (0.05 - 5 xCT Sec) 5
Seconds

Seconds
Time Dial = 0.15
3 3x = 0.945 s, 5x = 0.642 s, 8x = 0.495 s 3
Inst = 6 (1 - 40 xCT Sec)
12-1/C 240

Time Delay = 0.2 s Cable5


25 m AL

±
RLY_GRID I/C-1_H04 ±
RLY_AIS DG SWGR2-A_H09 ±
RLY_EXIST.SWGR-1_H01
CT46 R
CT45 R
CT40 R
1250/5 1250/5 1250/5

1250 A 1250 A 630 A


1 RLY_ERTG7-H07 - P 1 HVCB_GRID I/C-1_H04 HVCB_DGSWGR2-A_H09 Open HVCB_EXIST.SWGR-1_H01 Open

1250 A AIS-MAIN MV SWGR BUS-A

OC1
13.8 kV

630 A 630 A

ABB
630 A
630 A HVCB_RSSL-3A_H08 HVCB_RSSL-2A_H05 630 A 630 A
Open HVCB_STS-A_H03 HVCB_RSSL-1A_H06 0A
HVCB_MSS+CSW+PSS-A_H02 0A 630 A
.5 .5 630 A HVCB_ERTG7_H07 CB143 CB226 HVCB_MAIN B/C_H11 Open

REF 615
CB A-FUT.R.LOOP4A Open
±
RLY_RSSL-3A_H08 RLY_RSSL-2A_H05 RLY_RSSL-1A_H06 ±
RLY_ERTG7-H07
CT44 CT41
±
CT42
±
CT43

RLY_STS-A_H03 - P
RLY_STS-A_H03 R R R RLY_CSW+PUMPSS-A_H02 RLY_MAIN B/C_H11
± 600/5 600/5
R
600/5 600/5 ± ±

CT Ratio 600:5
CT38 R
CT35 R
CT48 R
600/5 200/5 1250/5

.3 OC1 Group 1 .3
Cable69

ABB IEC Very Inverse Cable156


830 m AL
Cable133
500 m AL
Cable131
590 m AL
Cable129
720 m AL
3-1/C 240
Cable144
535 m AL FUTURE LOAD1 FUTURE LOAD2 13 m AL
3-1/C 240
Pickup = 0.4 (0.05 - 5 xCT Sec)
3-1/C 240 2 MVA 12-1/C 240

REF 615 3-1/C 240 3-1/C 500 3 MVA

CT Ratio 600:5 Time Dial = 0.3


Group 1 3x = 2.03 s, 5x = 1.01 s, 8x = 0.579 s
.1 .1
IEC Very Inverse Inst = 10 (1 - 40 xCT Sec)
Pickup = 0.35 (0.05 - 5 xCT Sec) Time Delay = 0.16 s Cable131 - P
Time Dial = 0.24 RLY_RSSL-2A_H05 - 3P
.05 .05
3x = 1.62 s, 5x = 0.81 s, 8x = 0.463 s RLY_GRID I/C-1_H04 - 3P
Inst = 10 (1 - 40 xCT Sec) Cable5 - P
.03 .03
Time Delay = 0.1 s
RLY_STS-A_H03 - 3P RLY_ERTG7-H07 - 3P
Cable133 - P
FUTURE LOAD2 FUTURE LOAD1 RLY_MAIN B/C_H11 - 3P

LRC LRC RLY_RSSL-3A_H08 - 3P RLY_RSSL-1A_H06 - 3P

.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 100 AIS-MAIN MV SWGR BUS-A (Nom. kV=13.8, Plot Ref. kV=13.8) ETAP Star 22.5.0N

Project: PROTECTION STUDY Date: 06-03-2024


Location: PUERTO BOLIVAR - ECUADOR Fault: Phase
Contract: ABB
Amps X 10 AIS-MAIN MV SWGR BUS-A (Nom. kV=13.8, Plot Ref. kV=13.8)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
Cable129 RLY_ERTG7-H07 - G
Ampacity OC1
500 500
ABB
REF 615
300 300
CT Ratio 600:5
Group 1
IEC Very Inverse
Pickup = 0.09 (0.01 - 5 xCT Sec)
Time Dial = 0.6
100 100
3x = 4.05 s, 5x = 2.03 s, 8x = 1.16 s
Inst = 12.5 (1 - 40 xCT Sec)
Time Delay = 0.04 s
50 50
RLY_GRID I/C-1_H04 - G
OC1
30 30
ABB
REF 615
CT Ratio 1250:5
Group 1
10 IEC Very Inverse 10
RLY_RSSL-1A_H06 - G
Pickup = 0.24 (0.01 - 5 xCT Sec)
OC1 Time Dial = 0.35
5 3x = 2.36 s, 5x = 1.18 s, 8x = 0.675 s 5
RLY_RSSL-3A_H08 - G
Seconds

Seconds
Inst = 10 (1 - 40 xCT Sec)
OC1 Time Delay = 0.04 s
3 3
RLY_STS-A_H03 - G
OC1
12-1/C 240
Cable5
25 m AL

RLY_RSSL-2A_H05 - G ABB CT46


±
RLY_GRID I/C-1_H04
CT45
±
RLY_AIS DG SWGR2-A_H09
CT40
±
RLY_EXIST.SWGR-1_H01

OC1
R R R
1250/5 1250/5 1250/5

REF 615
1250 A 630 A
ABB
1250 A
1 CT Ratio 600:5 1 HVCB_GRID I/C-1_H04 HVCB_DGSWGR2-A_H09 Open HVCB_EXIST.SWGR-1_H01 Open

1250 A

REF 615
AIS-MAIN MV SWGR BUS-A

Group 1 13.8 kV

CT Ratio 600:5 IEC Very Inverse Open


630 A
630 A
HVCB_RSSL-3A_H08
630 A
HVCB_RSSL-2A_H05
630 A
HVCB_RSSL-1A_H06 630 A 630 A
HVCB_STS-A_H03 HVCB_MSS+CSW+PSS-A_H02 0A 0A 630 A
.5 Group 1 Pickup = 0.05 (0.01 - 5 xCT Sec) .5 630 A
CB A-FUT.R.LOOP4A
RLY_RSSL-3A_H08 RLY_RSSL-2A_H05
HVCB_ERTG7_H07

RLY_RSSL-1A_H06 RLY_ERTG7-H07
CB143
Open
CB226 HVCB_MAIN B/C_H11 Open

IEC Very Inverse


± ±
CT44 ±
CT43
Time Dial = 1
CT42
±

RLY_STS-A_H03 R CT41 R R RLY_CSW+PUMPSS-A_H02 RLY_MAIN B/C_H11


± 600/5 600/5
R
600/5 600/5 ± ±
CT38 R
CT35 R
CT48 R
600/5 200/5 1250/5

.3 Pickup = 0.05 (0.01 - 5 xCT Sec) 3x = 6.75 s, 5x = 3.38 s, 8x = 1.93 s .3


Time Dial = 1 Inst = 6.667 (1 - 40 xCT Sec) Cable133 Cable131 Cable129
Cable69

Cable156 720 m AL Cable144

3x = 6.75 s, 5x = 3.38 s, 8x = 1.93 s Time Delay = 0.1 s


500 m AL 590 m AL FUTURE LOAD1 FUTURE LOAD2 13 m AL
830 m AL 3-1/C 240 3-1/C 240 535 m AL
3-1/C 240 3 MVA 2 MVA 12-1/C 240
3-1/C 240 3-1/C 500

Inst = 15 (1 - 40 xCT Sec)


Time Delay = 0.04 s
.1 .1

.05 .05

.03 RLY_STS-A_H03 - G - LG .03


RLY_RSSL-1A_H06 - G - LG RLY_ERTG7-H07 - G - LG
RLY_RSSL-3A_H08 - G - LG
RLY_GRID I/C-1_H04 - G - LG
RLY_RSSL-2A_H05 - G - LG
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 10 AIS-MAIN MV SWGR BUS-A (Nom. kV=13.8, Plot Ref. kV=13.8) ETAP Star 22.5.0N

Project: PROTECTION STUDY Date: 06-03-2024


Location: PUERTO BOLIVAR - ECUADOR Fault: Ground
Contract: ABB
Amps X 10 Bus-13.8kV STS RMU (Nom. kV=13.8, Plot Ref. kV=13.8)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K

LV BUS-STS
500 LUMP-STS-1 Cable80 AIS-MAIN MV SWGR
Cable336
BUS-A 500
FLA Ampacity Ampacity 1250 A AIS-MAIN MV SWGR BUS-A
13.8 kV
300 300
630 A
HVCB_STS-A_H03
RLY_STS-A_H03 - P
OC1
ABB
±
CT38 RLY_STS-A_H03
600/5
100 REF 615 100 R

CT Ratio 600:5
Group 1
50 IEC Very Inverse 50
Pickup = 0.35 (0.05 - 5 xCT Sec) Cable156
830 m AL
30 Time Dial = 0.24 30 3-1/C 240
630 A
3x = 1.62 s, 5x = 0.81 s, 8x = 0.463 s
STS-SS LBS-1
Inst = 10 (1 - 40 xCT Sec) Bus-13.8kV
13.8 kV STS RMU
630 A
Time Delay = 0.1 s

10 RLY_K01_STS-1 - P 10
OC1
200 A
ABB 200 A
CB-K09-STS-TRAFO
CB-K01-STS-1
5 REF 615 5
Seconds

Seconds
TR-STS CT Ratio 100:1 RLY-K09-STS-TRAFO
RLY_K01_STS-1
3 Withstand Group 1 3 CT4
±

R
CT3
±

R
100/1 50/1
RLY-K09-STS-TRAFO - P IEC Very Inverse
Pickup = 0.65 (0.05 - 5 xCT Sec)
OC1 Cable336
Time Dial = 0.2 10 m AL
ABB
3x = 1.35 s, 5x = 0.675 s, 8x = 0.386 s 3-1/C 120
REF 615
1 Inst = 10 (1 - 40 xCT Sec) 1 Cable80
CT Ratio 50:1 180 m AL
Time Delay = 0.02 s 1-3/C 95
Group 1 458.3 A, 0.447 s
.5 IEC Extremely Inverse .5
Pickup = 0.29 (0.05 - 5 xCT Sec) TR-STS
Time Dial = 1.5 Dyn1
4 %Z 315 kVA
.3 .3
3x = 15 s, 5x = 5 s, 8x = 1.9 s 13.8/0.227 kV

Inst = 5 (1 - 40 xCT Sec) 5639 A, 0.125 s AL 12 m


Time Delay = 0.03 s LUMP-STS-1 Cable151 6-1/C 240
675 kVA

.1 .1
CB-STS-QF1
TR-STS 1000 A

Inrush 0.22 kV LV BUS-STS 1000 A


.05 .05
0A

.03
LUMP-STS-1 RLY_STS-A_H03 - 3P
.03 250 A
CB1 0A
CB2
LRC RLY_K01_STS-1 - 3P CB-STS-QF2
Open

Cable3
LUMP STS-TRAFO CU 500 m
LRC RLY-K09-STS-TRAFO - 3P
2-4/C 150
LUMP STS-TRAFO
.01 .01 184 kVA LUMP1 STS-TRAFO
VFD1 50 kVA
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 10 Bus-13.8kV STS RMU (Nom. kV=13.8, Plot Ref. kV=13.8) ETAP Star 22.5.0N

55 kW
LV MOTOR-STS
Project: PROTECTION STUDY Date: 06-03-2024
Location: PUERTO BOLIVAR - ECUADOR Fault: Phase
Contract: ABB
Amps Bus-13.8kV STS RMU (Nom. kV=13.8, Plot Ref. kV=13.8)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K

500 Cable80 Cable156 Cable336 500


Ampacity Ampacity Ampacity 1250 A AIS-MAIN MV SWGR BUS-A
13.8 kV
300 300
630 A
HVCB_STS-A_H03

RLY_STS-A_H03 - G CT38
±

RLY_STS-A_H03
600/5
100 OC1 100 R

ABB
REF 615
50 50
CT Ratio 600:5
Cable156
Group 1 830 m AL
30 IEC Very Inverse 30 3-1/C 240
630 A
Pickup = 0.05 (0.01 - 5 xCT Sec) STS-SS LBS-1
Time Dial = 1 630 A
Bus-13.8kV
13.8 kV STS RMU
3x = 6.75 s, 5x = 3.38 s, 8x = 1.93 s
Inst = 6.667 (1 - 40 xCT Sec)
10 10
Time Delay = 0.1 s
200 A
200 A
CB-K09-STS-TRAFO
5 5 CB-K01-STS-1
Seconds

Seconds
RLY-K09-STS-TRAFO
3
RLY_K01_STS-1 - G 3 CT4
±
RLY_K01_STS-1
CT3
±

OC1 100/1 R
50/1 R

ABB
Cable336
REF 615 10 m AL
CT Ratio 100:1 3-1/C 120

1 Group 1 1 Cable80
180 m AL
IEC Very Inverse 1-3/C 95
Pickup = 0.09 (0.01 - 5 xCT Sec)
.5 Time Dial = 0.4 .5
3x = 2.7 s, 5x = 1.35 s, 8x = 0.771 s TR-STS
4 %Z 315 kVA
Inst = 10 (1 - 40 xCT Sec) Dyn1
.3 .3 13.8/0.227 kV
Time Delay = 0.04 s
RLY-K09-STS-TRAFO - G LUMP-STS-1
AL
Cable151
12 m
6-1/C 240
OC1 675 kVA

.1
ABB .1
REF 615 CB-STS-QF1
1000 A
CT Ratio 50:1
LV BUS-STS
Group 1 0.22 kV 1000 A
.05 .05
IEC Very Inverse
0A
Pickup = 0.07 (0.01 - 5 xCT Sec) CB1 0A
.03 .03 250 A
Time Dial = 1 RLY_STS-A_H03 - G - LG CB-STS-QF2
CB2 Open
3x = 6.75 s, 5x = 3.38 s, 8x = 1.93 s RLY_K01_STS-1 - G - LG Cable3
Inst = 20 (1 - 40 xCT Sec) RLY-K09-STS-TRAFO - G - LG CU 500 m
2-4/C 150
Time Delay = 0.04 s
LUMP STS-TRAFO
.01 .01 184 kVA LUMP1 STS-TRAFO
VFD1 50 kVA
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps Bus-13.8kV STS RMU (Nom. kV=13.8, Plot Ref. kV=13.8) ETAP Star 22.5.0N

55 kW
LV MOTOR-STS
Project: PROTECTION STUDY Date: 06-03-2024
Location: PUERTO BOLIVAR - ECUADOR Fault: Ground
Contract: ABB
Amps X 100 LV BUS-STS (Nom. kV=0.22, Plot Ref. kV=0.227)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K RLY-K09-STS-TRAFO
LV BUS-STS Cable336 CT3
±

R
TR-STS Ampacity 50/1
500 500
LUMP1 STS-TRAFO FLA - ONAN 65
RLY-K09-STS-TRAFO - P
300 FLA 300
Cable336
OC1
ABB 10 m AL
REF 615 3-1/C 120
CT Ratio 50:1
100 Group 1 100
IEC Extremely Inverse
Pickup = 0.29 (0.05 - 5 xCT Sec)
50 Time Dial = 1.5 50
3x = 15 s, 5x = 5 s, 8x = 1.9 s
Inst = 5 (1 - 40 xCT Sec)
30 30
Time Delay = 0.03 s TR-STS
4 %Z 315 kVA
Dyn1
13.8/0.227 kV
10 10
AL 12 m
CB-STS-QF1 Cable151 6-1/C 240
5 ABB Ekip Touch LSI (IEC) 5
Seconds

Seconds
Sensor = 1000 Plug = 1000 Amps
3 I1 = 0.88 (880 Amps) 3
CB-STS-QF2 t1 = 12 t = k/I^2 CB-STS-QF1
ABB I2 = 2.5 (2500 Amps)
XT4 250 TMA
1000 A
t2 = 0.1 t = I^2T OUT
Size = 250 Amps I3 = 15 (15000 Amps)
0.22 kV LV BUS-STS 1000 A
1 Thermal Trip = 79% (197.5 Amps) TR-STS 1
Magnetic Trip = 5X (1250 Amps) Withstand
Cable336 - P 0A
.5 .5
CB1 0A
250 A
.3 .3
CB2 Open
CB-STS-QF2
Cable3
CU 500 m
2-4/C 150
.1 Cable3 - P .1
LUMP STS-TRAFO
184 kVA LUMP1 STS-TRAFO
.05 .05
VFD1 50 kVA
TR-STS
.03
LUMP1 STS-TRAFO Inrush .03
LRC
LUMP STS-TRAFO
LRC CB-STS-QF1 - 3P
CB-STS-QF2 - 3P RLY-K09-STS-TRAFO - 3P
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 100 LV BUS-STS (Nom. kV=0.22, Plot Ref. kV=0.227) ETAP Star 22.5.0N

55 kW
Project: PROTECTION STUDY Date: 06-03-2024 LV MOTOR-STS
Location: PUERTO BOLIVAR - ECUADOR Fault: Phase
Contract: ABB
Amps X 100 Bus-13.8kV ERTG-7 (Nom. kV=13.8, Plot Ref. kV=13.8)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K

Cable332 RLY_ERTG7-H07 - P
500 Ampacity OC1 500
AIS-MAIN MV SWGR BUS-A ABB
300 REF 615 300
TR1-ERTGSS-7 CT Ratio 600:5
FLA - ONAN 65 1250 A AIS-MAIN MV SWGR BUS-A
Group 1
13.8 kV
IEC Very Inverse
Pickup = 0.4 (0.05 - 5 xCT Sec)
100 Time Dial = 0.3 100
630 A
3x = 2.03 s, 5x = 1.01 s, 8x = 0.579 s
HVCB_ERTG7_H07
Inst = 10 (1 - 40 xCT Sec) ±
RLY_ERTG7-H07
50 Time Delay = 0.16 s 50 CT43 R
600/5

30 30
Cable144
535 m AL
RLY-ERTG 07-K03 - P
3-1/C 500
OC1 600 A 600 A
10
ABB 10
LBS-ERTG7-K01 LBS-ERTG7-K02
REF 611
TR1-ERTGSS-7 CT Ratio 150:1
Withstand IEC Extremely Inverse 13.8 kV
5 5
Pickup = 0.692 (0.05 - 5 xCT Sec)
Seconds

Seconds
600 A
Time Dial = 0.4 Bus-13.8kV ERTG-7
3 3
3x = 4 s, 5x = 1.33 s, 8x = 0.508 s
Inst = 10 (1 - 40 xCT Sec)
HVCB-ERTG 07-K03
Time Delay = 0.03 s
600 A

1 1 CT32 R
Cable139 - P 150/1 ±

RLY-ERTG 07-K03
.5 Cable332 - P .5
Cable332
10 m AL
.3 .3
3-1/C 120
TR1-ERTGSS-7
TR1-ERTGSS-7 13.8/0.474 kV
Inrush 7 %Z Dyn1
2250 kVA
.1 .1
CB-ERTG7-QF1
ABB Ekip Touch LSI (IEC) 18-1/C 400
.05 Sensor = 3200 Plug = 3200 Amps .05 8m AL
I1 = 0.943 (3018 Amps) Cable139
.03 t1 = 3 t = k/I^2 .03
3200 A
I2 = 4.2 (13440 Amps) CB-ERTG7-QF1
t2 = 0.2 t = I^2T OUT RLY_ERTG7-H07 - 3P
I3 = 10 (32000 Amps) CB-ERTG7-QF1 - 3P
RLY-ERTG 07-K03 - 3P 3200 A
LVBUS-ERTG7-0.46KV
.01 .01 0.46 kV
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 100 Bus-13.8kV ERTG-7 (Nom. kV=13.8, Plot Ref. kV=13.8) ETAP Star 22.5.0N

Project: PROTECTION STUDY Date: 06-03-2024


Location: PUERTO BOLIVAR - ECUADOR Fault: Phase
Contract: ABB
Amps X 10 Bus-13.8kV ERTG-7 (Nom. kV=13.8, Plot Ref. kV=13.8)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K

Cable332
500 Ampacity 500
Cable144
300
Ampacity 300

1250 A AIS-MAIN MV SWGR BUS-A


13.8 kV
RLY_ERTG7-H07 - G
100 OC1 100
630 A
ABB
HVCB_ERTG7_H07
REF 615 ±
RLY_ERTG7-H07
50 CT Ratio 600:5 50 CT43 R
600/5
Group 1
30 IEC Very Inverse 30
Pickup = 0.09 (0.01 - 5 xCT Sec) Cable144
Time Dial = 0.6 535 m AL
3x = 4.05 s, 5x = 2.03 s, 8x = 1.16 s 3-1/C 500
Inst = 12.5 (1 - 40 xCT Sec) 600 A 600 A
LBS-ERTG7-K01 LBS-ERTG7-K02
10 Time Delay = 0.04 s 10

13.8 kV
5 5
Seconds

Seconds
600 A
Bus-13.8kV ERTG-7
RLY-ERTG 07-K03 - G
3 3
OC1
ABB HVCB-ERTG 07-K03
REF 611 600 A
CT Ratio 150:1
1 IEC Very Inverse 1 CT32 R
Pickup = 0.08 (0.01 - 5 xCT Sec) 150/1 ±

Time Dial = 0.4 RLY-ERTG 07-K03


.5 3x = 2.7 s, 5x = 1.35 s, 8x = 0.771 s .5
Inst = 10 (1 - 40 xCT Sec) Cable332
Time Delay = 0.04 s 10 m AL
.3 .3
3-1/C 120
TR1-ERTGSS-7
13.8/0.474 kV
5000 A, 0.0886 s 7 %Z Dyn1
2250 kVA
.1 .1
∆ 0.118 s
18-1/C 400
.05 .05 8m AL
Cable139
.03 .03
3200 A
CB-ERTG7-QF1
RLY_ERTG7-H07 - G - LG
RLY-ERTG 07-K03 - G - LG

3200 A
LVBUS-ERTG7-0.46KV
.01 .01 0.46 kV
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 10 Bus-13.8kV ERTG-7 (Nom. kV=13.8, Plot Ref. kV=13.8) ETAP Star 22.5.0N

Project: PROTECTION STUDY Date: 06-03-2024


Location: PUERTO BOLIVAR - ECUADOR Fault: Ground
Contract: ABB
Amps X 100 LVBUS-ERTG7-0.46KV (Nom. kV=0.46, Plot Ref. kV=0.474)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
LVBUS-ERTG7-0.22KV LVBUS-ERTG7-0.46KV

500 TR2-ERTGSS-7 CB-ERTG7-QF1 500


FLA - AN 60 ABB Ekip Touch LSI (IEC)
ERTG7-0.46KV Sensor = 3200 Plug = 3200 Amps
300 300
FLA I1 = 0.943 (3018 Amps)
t1 = 3 t = k/I^2
I2 = 4.2 (13440 Amps)
t2 = 0.2 t = I^2T OUT
I3 = 10 (32000 Amps)
100 100

CB-ERTG7-QF3 TR2-ERTGSS-7
50 ABB Ekip Dip LSI (IEC) 50
4 %Z
Sensor = 1000 Plug = 1000 Amps
75 kVA Dyn1
30 I1 = 0.62*In (620 Amps) 30
t1 = 12 t = k/I^2 0.46/0.227 kV
I2 = 10*In (10000 Amps)
t2 = 0.1s (I^x)t = OUT

10 10
CB-PILLAR_BOX 18-1/C 400
ABB PR331/P (IEC-2008-X1) Cable222
8m AL Cable227
5 Frame = 1000 Plug = 1000 Amps 5 6 m CU 5 m CU
Seconds

Seconds
I1 = 0.5 (500 Amps) Cable139
1-4/C 35 1-4/C 120
3 t1 = 12 t1 = k/I^2 3
I2 = 5 (5000 Amps)
3200 A
CB-ERTG7-QF1 CB-220V-ERTG7-QF1 250 A
t2 = 0.7 (I^x)t = OUT 125 A
I3 = 10 (10000 Amps)
CB-ERTG7-QF6
1 1 LVBUS-ERTG7-0.46KV 3200 A
0.46 kV 0.22 kV LVBUS-ERTG7-0.22KV
CB-ERTG7-QF6
.5 ABB .5
XT4 250 TMA
.3 Size = 125 Amps .3 250 A
Thermal Trip = 83% (103.75 Amps) CB-ERTG7-QF2
Magnetic Trip = 6X (750 Amps) 1000 A
CB-220V-ERTG7-QF1 Open CB-ERTG7-QF3
1000 A
ABB 6-1/C 350
.1 XT4 250 TMA Cable211 - P .1
Size = 250 Amps 40 m CU
Thermal Trip = 75% (187.5 Amps) Cable211
Cable139 - P
.05 Magnetic Trip = 5X (1250 Amps) CB-220V-ERTG7-QF1 - 3P .05

.03 ERTG7-0.46KV CB-ERTG7-QF6 - 3P .03 ERTG7-0.46KV


LRC CB-ERTG7-QF3 - 3P
150 kVACB-PILLAR_BOX
1000 A
ERTG7-0.46KV2 CB-ERTG7-QF1 - 3P

LRC
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 100 LVBUS-ERTG7-0.46KV (Nom. kV=0.46, Plot Ref. kV=0.474) ERTG7-0.46KV2


ETAP Star 22.5.0N
450 kVA

Project: PROTECTION STUDY Date: 06-03-2024


Location: PUERTO BOLIVAR - ECUADOR Fault: Phase
Contract: ABB
Amps X 10 AIS-MAIN MV SWGR BUS-A (Nom. kV=13.8, Plot Ref. kV=13.8)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K

LV BUS-RR52 AIS-MAIN MV SWGR BUS-A


500 Cable164 500
TR-RR52 Bus-13.8kV RR-52 1250 A
Ampacity AIS-MAIN MV SWGR BUS-A
FLA - ONAN 65
300
RLY-RR52-K03 - P
300 13.8 kV
OC1
ABB 630 A
REF 611 HVCB_RSSL-1A_H06
100 CT Ratio 75:1 100 RLY_RSSL-1A_H06
IEC Extremely Inverse ±
CT42 R
Pickup = 0.592 (0.05 - 5 xCT Sec)
Time Dial = 1
600/5
50 50
3x = 10 s, 5x = 3.33 s, 8x = 1.27 s
30 Inst = 20 (1 - 40 xCT Sec) 30 Cable129
Time Delay = 0.05 s 720 m AL
3-1/C 240
600 A
10 RLY_RSSL-1A_H06 - P 10 LBS-RR52-K01
OC1
600 A 13.8 kV
ABB
5 5
REF 615
Seconds

Seconds
CT Ratio 600:5 Bus-13.8kV RR-52
3 Group 1 3
HVCB-RR52-K03
IEC Normal Inverse
Pickup = 0.34 (0.05 - 5 xCT Sec) 600 A
RLY-RR52-K03
Time Dial = 0.15 ±

TR-RR52 3x = 0.945 s, 5x = 0.642 s, 8x = 0.495 s CT12 R


1 1
Withstand
Inst = 6 (1 - 40 xCT Sec) 75/1
Time Delay = 0.2 s
Cable164
.5 .5
10 m AL
.3 .3 1-3/C 95
TR-RR52
5 %Z Dyn1
.1 CB-RR52-QF1 .1
850 kVA
ABB Ekip Dip LSI (IEC)
TR-RR52
13.8/0.494 kV
Sensor = 1000 Plug = 1000 Amps
Inrush
.05 I1 = 1*In (1000 Amps) Cable20 - P .05
t1 = 12 t = k/I^2
.03
I2 = 2.5*In (2500 Amps) .03 6 m AL
t2 = 0.2s (I^x)t = OUT RLY_RSSL-1A_H06 - 3P
Cable20
CB-RR52-QF1 - 3P
12-1/C 240
RLY-RR52-K03 - 3P

.01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
.01
1000 A
CB-RR52-QF1
Amps X 10 AIS-MAIN MV SWGR BUS-A (Nom. kV=13.8, Plot Ref. kV=13.8) ETAP Star 22.5.0N

LV BUS-RR52 0.48 kV

Project: PROTECTION STUDY Date: 06-03-2024


Location: PUERTO BOLIVAR - ECUADOR Fault: Phase 1000 A
Amps AIS-MAIN MV SWGR BUS-A (Nom. kV=13.8, Plot Ref. kV=13.8)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K

500 Cable164 Cable129 500


Ampacity Ampacity AIS-MAIN MV SWGR BUS-A 1250 A
300 300 13.8 kV

630 A
HVCB_RSSL-1A_H06
100 100
±
RLY_RSSL-1A_H06
CT42 R
600/5
50 50
RLY_RSSL-1A_H06 - G
30 OC1 30 Cable129
ABB 720 m AL
REF 615 3-1/C 240
CT Ratio 600:5
Group 1
600 A
10 IEC Very Inverse 10 LBS-RR52-K01
Pickup = 0.05 (0.01 - 5 xCT Sec)
600 A 13.8 kV
Time Dial = 1
5 3x = 6.75 s, 5x = 3.38 s, 8x = 1.93 s 5
Seconds

Seconds
Inst = 15 (1 - 40 xCT Sec) Bus-13.8kV RR-52
3 Time Delay = 0.04 s 3
HVCB-RR52-K03
600 A
RLY-RR52-K03
±
CT12 R
1 1
75/1
Cable164
.5 .5
10 m AL
RLY-RR52-K03 - G
.3 OC1 .3 1-3/C 95
ABB
TR-RR52
REF 611
CT Ratio 75:1 5 %Z Dyn1
.1
IEC Very Inverse .1
850 kVA
Pickup = 0.07 (0.01 - 5 xCT Sec) ∆ 0.103 s 13.8/0.494 kV
Time Dial = 1
.05
3x = 6.75 s, 5x = 3.38 s, 8x = 1.93 s .05
Inst = 20 (1 - 40 xCT Sec)
Time Delay = 0.04 s 6 m AL
.03 .03
RLY_RSSL-1A_H06 - G - LG Cable20
RLY-RR52-K03 - G - LG 12-1/C 240

.01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
.01
1000 A
CB-RR52-QF1
Amps AIS-MAIN MV SWGR BUS-A (Nom. kV=13.8, Plot Ref. kV=13.8) ETAP Star 22.5.0N

LV BUS-RR52 0.48 kV

Project: PROTECTION STUDY Date: 06-03-2024


Location: PUERTO BOLIVAR - ECUADOR Fault: Ground 1000 A
Amps X 10 RR52-RP2A (Nom. kV=0.48, Plot Ref. kV=0.494)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K

LUMP RR52B RR52-RP2A


500 FLA 500
LV BUS-RR52
300 300

CB-RR52-RP2A-QF4
ABB
1000 A
100
XT4 250 TMA
100
CB-RR52-QF1
Size = 250 Amps
Thermal Trip = 70% (175 Amps)
Magnetic Trip = 5X (1250 Amps)
50 50
1000 A LV BUS-RR52
30 30

0.48 kV
CB-RR52-QF1
630 A
10
ABB Ekip Dip LSI (IEC)
Sensor = 1000 Plug = 1000 Amps
10 CB-RR52-QF3
CB-RR52-RP2A-QF1
I1 = 1*In (1000 Amps)
ABB Ekip Dip LSI (IEC) t1 = 12 t = k/I^2
5 Sensor = 630 Plug = 630 Amps 5
I2 = 2.5*In (2500 Amps)
Seconds

Seconds
3
I1 = 0.8*In (504 Amps)
t1 = 36 t = k/I^2
t2 = 0.2s (I^x)t = OUT
3
21 m AL
I2 = 3*In (1890 Amps)
t2 = 0.1s (I^x)t = OUT
Cable19
3-1/C 400
1 1
CB-RR52-QF3
ABB Ekip Dip LSI (IEC)
630 A
.5 Sensor = 630 Plug = 630 Amps
I1 = 0.8*In (504 Amps)
.5
CB-RR52-RP2A-QF1
.3 t1 = 36 t = k/I^2 .3
I2 = 3*In (1890 Amps)
t2 = 0.1s (I^x)t = OUT
630 A RR52-RP2A
.1 .1
0.48 kV
.05 .05
250 A
.03 .03
CB-RR52-RP2A-QF4
LUMP RR52B CB-RR52-RP2A-QF1 - 3P CB-RR52-QF3 - 3P

LRC CB-RR52-QF1 - 3P
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 10 RR52-RP2A (Nom. kV=0.48, Plot Ref. kV=0.494) ETAP Star 22.5.0N LUMP RR52B
200 kVA
Project: PROTECTION STUDY Date: 06-03-2024
Location: PUERTO BOLIVAR - ECUADOR Fault: Phase
Contract: ABB
Amps X 10 Bus-13.8kV PUMP SS (Nom. kV=13.8, Plot Ref. kV=13.8)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K

Cable293 Bus-13.8kV PUMP SS


RLY-PUMP SS-K03 - P RLY_GRID I/C-1_H04
500 Ampacity Cable292 500
CT46
±

OC1 R
Ampacity ABB
1250/5
300 300
REF 611
CT Ratio 50:1
RLY_GRID I/C-1_H04 - P IEC Very Inverse 1250 A
HVCB_GRID I/C-1_H04
OC1 Pickup = 0.3 (0.05 - 5 xCT Sec)
100
Time Dial = 0.4 100
3x = 2.7 s, 5x = 1.35 s, 8x = 0.771 s
Inst = 8 (1 - 40 xCT Sec) 1250 A AIS-MAIN MV SWGR BUS-A
50
Time Delay = 0.03 s 50 13.8 kV

RLY_CSW+PUMPSS-A_H02 - P 630 A
30 30
OC1 HVCB_MSS+CSW+PSS-A_H02
ABB
REF 615
CT Ratio 200:5 RLY_CSW+PUMPSS-A_H02
Group 1
±

10 10 CT35 R
IEC Long Time Inverse 200/5
Pickup = 0.15 (0.05 - 5 xCT Sec)
TR-MSS BUILDING Time Dial = 0.1
5 5
Withstand 3x = 6 s, 5x = 3 s, 8x = 1.71 s

Seconds
Seconds

Cable292
Inst = 20 (1 - 40 xCT Sec) 20 m AL
3 3
Time Delay = 0.05 s 3-1/C 120
Cable293

TR-PUMP HOUSE SS 285 m AL


1
Withstand 1 3-1/C 120
RLY-MSS-K03 - P 600 A 600 A
600 A
OC1 LBS-MSS-K01
LBS-MSS-K02 LBS-PUMP SS-K01
.5 ABB .5
REF 611
.3 CT Ratio 50:1 .3 13.8 kV 13.8 kV
IEC Very Inverse
Pickup = 0.3 (0.05 - 5 xCT Sec)
Time Dial = 0.4 600 A
600 A Bus-13.8kV MSS Bus-13.8kV PUMP SS
3x = 2.7 s, 5x = 1.35 s, 8x = 0.771 s
Inst = 5 (1 - 40 xCT Sec) ∆ 0.15 s
.1 .1
600 A
Time Delay = 0.03 s HVCB-MSS-K03 HVCB-PUMP SS-K03
600 A
.05 TR-PUMP HOUSE SS .05
±
CT36 CT37
±

Inrush 50/1
R R
.03 .03 50/1
TR-MSS BUILDING RLY-MSS-K03
RLY_GRID I/C-1_H04 - 3P RLY-PUMP SS-K03
Inrush RLY_CSW+PUMPSS-A_H02 - 3P Cable331 Cable298
15 m AL 10 m AL
3-1/C 120 1-3/C 95
.01 .01
TR-MSS BUILDING TR-PUMP HOUSE SS
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
4 %Z Dyn1 13.8/0.46 kV
Amps X 10 Bus-13.8kV PUMP SS (Nom. kV=13.8, Plot Ref. kV=13.8) 315 kVA Dyn5 300 kVA
ETAP Star 22.5.0N
13.8/0.227 kV 4 %Z

Project: PROTECTION STUDY Date: 21-03-2024


Location: PUERTO BOLIVAR - ECUADOR
Contract: ABB
Document Tile Document No. Revision Date Page No.
RELAY COORDINATION &
ABB-TEC-CAL-035 V2 21-March-2024 28 of 85
PROTECTION STUDY

Annexure-3

13.8kV AIS Panel Main Substation Protection setting


table
13.8KV AIS MV SWITCHGEAR-1

FEEDER NAME Existing Switchgear-1 MSS+PUMP STS GRID INCOMER-1 REEFER LOOP 2 REEFER LOOP 1 ERTG-7 REEFER LOOP 3 DG 13.8KV MAIN BUS COUPLER

RELAY ID RLY_EXIST.SWGR-1_H01 RLY_CSW+MSS-A_H02 RLY_STS-A_H03 RLY_GRID I/C-1_H04 RLY_RSSL-2A_H05 RLY_RSSL-1A_H06 RLY_ERTG7-H07 RLY_RSSL-3A_H08 RLY_DG-A_H09 RLY_MAIN B/C_H11

CT RATIO 1250:5 A 200:5 A 600:5 A 1250:5 A 600:5 A 600:5 A 600:5 A 600:5 A 1250:5 A 1250:5 A

RELAY PROTECTIONS 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N

RELAY MAKE ABB ABB ABB ABB ABB ABB ABB ABB ABB ABB
COMMON DETAILS
RELAY MODEL REF615 REF615 REF615 REF615 REF615 REF615 REF615 REF615 REF615 REF615

Pmax (KVA) 12000 2565 4515 30000 4704 4704 5200 4704 12500 30000

Imax (Iload) Amps 502.0584396 107.3149915 188.8994879 1255.146099 196.8069083 196.8069083 217.5586572 196.8069083 522.9775413 1255.146099

START VALUE in PU / AMPS 0.28 PU / 350A 0.15 PU / 30A 0.35 PU / 210A 0.68PU / 850A 0.34 PU / 204A 0.34 PU / 204A 0.4 PU / 240A 0.34 PU / 204A 0.44 PU / 550A 0.68PU / 850A

PHLPTOC (51) TIME DIAL 0.8 0.1 0.24 0.2 0.15 0.15 0.3 0.15 0.2 0.2

CURVE TYPE IEC-VI IEC-LTI IEC-VI IEC-VI IEC-NI IEC-NI IEC-VI IEC-NI IEC-LTI IEC-VI

START VALUE 6 PU / 7500A 20 PU /4000A 10 PU /6000A 5.5 PU /6875A 6 PU /3600A 6 PU /3600A 10 PU /6000A 6 PU /3600A 2 PU /2500A 5.5 PU /6875A
PHASE
PHHPTOC (50) CURVE TYPE IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT
SETTINGS
OPER.DELAY (SEC) 0.02 0.5 0.1 0.2 0.2 0.2 0.16 0.2 0.6 0.2

START VALUE 2 6 PU / 7500A 20 PU /4000A 16.67 PU /10000A 6.4 PU /8000A 18.33 PU / 11000A 18.33 PU / 11000A 18.33 PU / 10998A 18.33 PU / 11000A 2 PU /2500A 6.4 PU /8000A

PHIPTOC (50) CURVE TYPE IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT

OPER.DELAY (SEC) 0.02 0.5 0.02 0.02 0.04 0.04 0.02 0.04 0.6 0.02

START VALUE 0.04 PU / 21A 0.15 PU / 30A 0.05 PU / 30A 0.24 PU / 300A 0.05 PU / 30A 0.05 PU / 30A 0.09 PU / 54A 0.05 PU / 30A 0.04 PU / 50A 0.24 PU / 300A

EFLPTOC (51N) TIME DIAL 0.3 1 1 0.35 1 1 0.6 1 1 0.35

CURVE TYPE IEC-NI IEC-VI IEC-VI IEC-VI IEC-VI IEC-VI IEC-VI IEC-VI IEC-NI IEC-VI

START VALUE 0.2PU / 102A 20 PU / 4000A 6.67 PU / 4000A 10 PU / 12500A 15 PU / 9000A 15 PU / 9000A 12.5 PU / 7500A 15 PU / 9000A 0.2PU / 250A 10 PU / 12500A
GROUND
EFHPTOC (50N) CURVE TYPE IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT
SETTINGS
OPER.DELAY (SEC) 0.6 0.1 0.1 0.02 0.04 0.04 0.04 0.04 0.6 0.02

START VALUE 2 0.2PU / 102A 50 PU / 10000A 16.67 PU / 10000 10 PU / 12500A 15 PU / 9000A 15 PU / 9000A 12.5 PU / 7500A 15 PU / 9000A 0.2PU / 250A 10 PU / 12500A

EFIPTOC (50N) CURVE TYPE IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT

OPER.DELAY (SEC) 0.6 0.04 0.04 0.02 0.04 0.04 0.04 0.04 0.6 0.02

13.8KV AIS MV SWITCHGEAR-2

FEEDER NAME DG GRID INCOMER-2 MSS+PUMP ERTG-8 REEFER LOOP 1 REEFER LOOP 2 REEFER LOOP 3 STS Existing Switchgear-2 13.8KV MAIN BUS COUPLER

RELAY ID RLY_DG-B_H02 RLY_GRID I/C-2_H03 RLY_CSW+MSS-B_H04 RLY_ERTG8-H05 RLY_RSSL-1B_H06 RLY_RSSL-2B_H07 RLY_RSSL-3B_H08 RLY_STS-B_H09 RLY_EXIST.SWGR-2_H10 RLY_MAIN B/C_H01

CTR 1250:5 A 1250:5 A 200:5 A 600:5 A 600:5 A 600:5 A 600:5 A 600:5 A 1250:5 A NA

RELAY PROTECTIONS 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N NA

RELAY MAKE ABB ABB ABB ABB ABB ABB ABB ABB ABB NA
COMMON DETAILS
RELAY MODEL REF615 REF615 REF615 REF615 REF615 REF615 REF615 REF615 REF615 NA

Pmax (KVA) 12500 30000 2565 5200 4704 4704 4704 4515 12000 NA

Imax (Iload) Amps 522.9775413 1255.146099 107.3149915 217.5586572 196.8069083 196.8069083 196.8069083 188.8994879 502.0584396 NA

START VALUE in PU / AMPS 0.44 PU / 550A 0.68PU / 850A 0.15 PU / 30A 0.4 PU / 240A 0.34 PU / 204A 0.34 PU / 204A 0.34 PU / 204A 0.35 PU / 210A 0.28 PU / 350A NA

PHLPTOC (51) TIME DIAL 0.2 0.2 0.1 0.3 0.15 0.15 0.15 0.24 0.8 NA

CURVE TYPE IEC-LTI IEC-VI IEC-LTI IEC-VI IEC-NI IEC-NI IEC-NI IEC-VI IEC-VI NA

START VALUE 2 PU /2500A 5.5 PU /6875A 20 PU /4000A 10 PU /6000A 6 PU /3600A 6 PU /3600A 6 PU /3600A 10 PU /6000A 6 PU / 7500A NA
PHASE
PHHPTOC (50) CURVE TYPE IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT NA
SETTINGS
OPER.DELAY (SEC) 0.6 0.2 0.5 0.16 0.2 0.2 0.2 0.1 0.02 NA

START VALUE 2 2 PU /2500A 6.4 PU /8000A 20 PU /4000A 18.33 PU / 10998A 18.33 PU / 11000A 18.33 PU / 11000A 18.33 PU / 11000A 16.67 PU /10000A 6 PU / 7500A NA

PHIPTOC (50) CURVE TYPE IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT NA

OPER.DELAY (SEC) 0.6 0.02 0.5 0.02 0.04 0.04 0.04 0.02 0.02 NA

START VALUE 0.04 PU / 50A 0.24 PU / 300A 0.15 PU / 30A 0.09 PU / 54A 0.05 PU / 30A 0.05 PU / 30A 0.05 PU / 30A 0.05 PU / 30A 0.04 PU / 21A NA

EFLPTOC (51N) TIME DIAL 1 0.35 1 0.6 1 1 1 1 0.3 NA

CURVE TYPE IEC-NI IEC-VI IEC-VI IEC-VI IEC-VI IEC-VI IEC-VI IEC-VI IEC-NI NA

START VALUE 0.2PU / 250A 10 PU / 12500A 20 PU / 4000A 12.5 PU / 7500A 15 PU / 9000A 15 PU / 9000A 15 PU / 9000A 6.67 PU / 4000A 0.2PU / 102A NA
GROUND
EFHPTOC (50N) CURVE TYPE IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT NA
SETTINGS
OPER.DELAY (SEC) 0.6 0.02 0.1 0.04 0.04 0.04 0.04 0.1 0.6 NA

START VALUE 2 0.2PU / 250A 10 PU / 12500A 50 PU / 10000A 12.5 PU / 7500A 15 PU / 9000A 15 PU / 9000A 15 PU / 9000A 16.67 PU / 10000 0.2PU / 102A NA

EFIPTOC (50N) CURVE TYPE IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT NA

OPER.DELAY (SEC) 0.6 0.02 0.04 0.04 0.04 0.04 0.04 0.04 0.6 NA
Document Tile Document No. Revision Date Page No.
RELAY COORDINATION &
ABB-TEC-CAL-035 V2 21-March-2024 30 of 85
PROTECTION STUDY

Annexure-4

13.8kV Reefer Substation Protection setting table


13.8KV REEFER SUBSTATION LOOP-1

FEEDER NAME REEFER LOOP 1 REEFER LOOP 1 REEFER LOOP 1 REEFER LOOP 1 REEFER LOOP 1 REEFER LOOP 1 REEFER LOOP 1 REEFER LOOP 1 REEFER LOOP 1
RSS 11 RSS 07 RSS 10 RSS 06 RSS 09 RSS 05 RSS 01 RSS 02 RSS 03

RELAY ID RLY-RSS11-K03 RLY-RSS07-K03 RLY-RSS10-K03 RLY-RSS06-K03 RLY-RSS09-K03 RLY-RSS05-K03 RLY-RSS01-K03 RLY-RSS02-K03 RLY-RSS03-K03

CT RATIO 75:1 A 75:1 A 75:1 A 75:1 A 75:1 A 75:1 A 75:1 A 75:1 A 75:1 A

RELAY PROTECTIONS 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N

RELAY MAKE ABB ABB ABB ABB ABB ABB ABB ABB ABB
COMMON DETAILS
RELAY MODEL REJ601 REJ601 REJ601 REJ601 REJ601 REJ601 REJ601 REJ601 REJ601

Pmax (KVA) 850 850 850 850 850 850 850 850 850

Imax (Iload) Amps 35.6 35.6 35.6 35.6 35.6 35.6 35.6 35.6 35.6

START VALUE in PU / AMPS 0.592 PU / 44.4A 0.592 PU / 44.4A 0.592 PU / 44.4A 0.592 PU / 44.4A 0.592 PU / 44.4A 0.592 PU / 44.4A 0.592 PU / 44.4A 0.592 PU / 44.4A 0.592 PU / 44.4A

PHLPTOC (51) TIME DIAL 1 1 1 1 1 1 1 1 1

CURVE TYPE IEC-EI IEC-EI IEC-EI IEC-EI IEC-EI IEC-EI IEC-EI IEC-EI IEC-EI
PHASE
SETTINGS
START VALUE 20 PU /1500A 20 PU /1500A 20 PU /1500A 20 PU /1500A 20 PU /1500A 20 PU /1500A 20 PU /1500A 20 PU /1500A 20 PU /1500A

PHHPTOC (50) CURVE TYPE IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT

OPER.DELAY (SEC) 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05

START VALUE 0.07 PU / 5.25A 0.07 PU / 5.25A 0.07 PU / 5.25A 0.07 PU / 5.25A 0.07 PU / 5.25A 0.07 PU / 5.25A 0.07 PU / 5.25A 0.07 PU / 5.25A 0.07 PU / 5.25A

EFLPTOC (51N) TIME DIAL 1 1 1 1 1 1 1 1 1

CURVE TYPE IEC-VI IEC-VI IEC-VI IEC-VI IEC-VI IEC-VI IEC-VI IEC-VI IEC-VI
GROUND
SETTINGS
START VALUE 20 PU / 1500A 20 PU / 1500A 20 PU / 1500A 20 PU / 1500A 20 PU / 1500A 20 PU / 1500A 20 PU / 1500A 20 PU / 1500A 20 PU / 1500A

EFHPTOC (50N) CURVE TYPE IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT

OPER.DELAY (SEC) 0.04 0.04 0.04 0.04 0.04 0.04 0.04 0.04 0.04

13.8KV REEFER SUBSTATION LOOP-2

FEEDER NAME REEFER LOOP 2 REEFER LOOP 2 REEFER LOOP 2 REEFER LOOP 2 REEFER LOOP 2 REEFER LOOP 2 REEFER LOOP 2 REEFER LOOP 2 REEFER LOOP 2
RSS 12 (EXISTING PMT) RSS 08 (EXISTING PMT) RSS 04 (EXISTING PMT) RSS 20 RSS 16 RSS 13 RSS 14 RSS 15 RSS 19 (EXISTING PMT)

RELAY ID NA NA NA RLY-RSS20-K03 RLY-RSS16-K03 RLY-RSS13-K03 RLY-RSS14-K03 RLY-RSS15-K03 NA

CTR NA NA NA 75:1 A 75:1 A 75:1 A 75:1 A 75:1 A NA

RELAY PROTECTIONS NA NA NA 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N NA

RELAY MAKE NA NA NA ABB ABB ABB ABB ABB NA


COMMON DETAILS
RELAY MODEL NA NA NA REJ601 REJ601 REJ601 REJ601 REJ601 NA

Pmax (KVA) NA NA NA 850 850 850 850 850 NA

Imax (Iload) Amps NA NA NA 35.6 35.6 35.6 35.6 35.6 NA

START VALUE in PU / AMPS NA NA NA 0.592 PU / 44.4A 0.592 PU / 44.4A 0.592 PU / 44.4A 0.592 PU / 44.4A 0.592 PU / 44.4A NA

PHLPTOC (51) TIME DIAL NA NA NA 1 1 1 1 1 NA

CURVE TYPE NA NA NA IEC-EI IEC-EI IEC-EI IEC-EI IEC-EI NA


PHASE
SETTINGS
START VALUE NA NA NA 20 PU /1500A 20 PU /1500A 20 PU /1500A 20 PU /1500A 20 PU /1500A NA

PHHPTOC (50) CURVE TYPE NA NA NA IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT NA

OPER.DELAY (SEC) NA NA NA 0.05 0.05 0.05 0.05 0.05 NA

START VALUE NA NA NA 0.07 PU / 5.25A 0.07 PU / 5.25A 0.07 PU / 5.25A 0.07 PU / 5.25A 0.07 PU / 5.25A NA

EFLPTOC (51N) TIME DIAL NA NA NA 1 1 1 1 1 NA

CURVE TYPE NA NA NA IEC-VI IEC-VI IEC-VI IEC-VI IEC-VI NA


GROUND
SETTINGS
START VALUE NA NA NA 20 PU / 1500A 20 PU / 1500A 20 PU / 1500A 20 PU / 1500A 20 PU / 1500A NA

EFHPTOC (50N) CURVE TYPE NA NA NA IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT NA

OPER.DELAY (SEC) NA NA NA 0.04 0.04 0.04 0.04 0.04 NA

13.8KV REEFER SUBSTATION LOOP-3

FEEDER NAME REEFER LOOP 3 REEFER LOOP 3 REEFER LOOP 3 REEFER LOOP 3 REEFER LOOP 3 REEFER LOOP 3 REEFER LOOP 3 REEFER LOOP 3
RSS 21 RSS 17 RSS 22 RSS 18 RSS 23 (EXISTING PMT) RSS 26 RSS 25 RSS 24

RELAY ID RLY-RSS21-K03 RLY-RSS17-K03 RLY-RSS22-K03 RLY-RSS18-K03 NA RLY-RSS26-K03 RLY-RSS25-K03 RLY-RSS24-K03

CTR 75:1 A 75:1 A 75:1 A 75:1 A NA 75:1 A 75:1 A 75:1 A

RELAY PROTECTIONS 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N NA 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N

RELAY MAKE ABB ABB ABB ABB NA ABB ABB ABB


COMMON DETAILS
RELAY MODEL REJ601 REJ601 REJ601 REJ601 NA REJ601 REJ601 REJ601

Pmax (KVA) 850 850 850 850 NA 850 850 850

Imax (Iload) Amps 35.6 35.6 35.6 35.6 NA 35.6 35.6 35.6

START VALUE in PU / AMPS 0.592 PU / 44.4A 0.592 PU / 44.4A 0.592 PU / 44.4A 0.592 PU / 44.4A NA 0.592 PU / 44.4A 0.592 PU / 44.4A 0.592 PU / 44.4A

PHLPTOC (51) TIME DIAL 1 1 1 1 NA 1 1 1

CURVE TYPE IEC-EI IEC-EI IEC-EI IEC-EI NA IEC-EI IEC-EI IEC-EI


PHASE
SETTINGS
START VALUE 20 PU /1500A 20 PU /1500A 20 PU /1500A 20 PU /1500A NA 20 PU /1500A 20 PU /1500A 20 PU /1500A

PHHPTOC (50) CURVE TYPE IEC-DT IEC-DT IEC-DT IEC-DT NA IEC-DT IEC-DT IEC-DT

OPER.DELAY (SEC) 0.05 0.05 0.05 0.05 NA 0.05 0.05 0.05

START VALUE 0.07 PU / 5.25A 0.07 PU / 5.25A 0.07 PU / 5.25A 0.07 PU / 5.25A NA 0.07 PU / 5.25A 0.07 PU / 5.25A 0.07 PU / 5.25A

EFLPTOC (51N) TIME DIAL 1 1 1 1 NA 1 1 1

CURVE TYPE IEC-VI IEC-VI IEC-VI IEC-VI NA IEC-VI IEC-VI IEC-VI


GROUND
SETTINGS
START VALUE 20 PU / 1500A 20 PU / 1500A 20 PU / 1500A 20 PU / 1500A NA 20 PU / 1500A 20 PU / 1500A 20 PU / 1500A

EFHPTOC (50N) CURVE TYPE IEC-DT IEC-DT IEC-DT IEC-DT NA IEC-DT IEC-DT IEC-DT

OPER.DELAY (SEC) 0.04 0.04 0.04 0.04 NA 0.04 0.04 0.04


Document Tile Document No. Revision Date Page No.
RELAY COORDINATION &
ABB-TEC-CAL-035 V2 21-March-2024 32 of 85
PROTECTION STUDY

Annexure-5

13.8kV STS Substation Protection setting table


 PROTECTION SETTINGS FOR 13.8KV STS SUBSTATION : OUTGOING TO STS CRANE FEEDER
PD Range Proposed Settings
Full load /
Sr. Reated Reated Protection Protection device
Feeder tag Load Description Panel CT PT rated current NEMA Code Time Remark
No KVA kV device Make Type Time setting
Amps Pick-up setting Charact
Parameter Unit Step range (sec) / Default setting Pick-up
range (sec) / eristic
TMS range
TMS
1 13.8kV Outgoing Crane K01
STS Substation : Crane Feeder 100 1 13.8 13 ABB REF 615 50P Three-phase non-directional overcurrent protection - Instantaneous stage PHIPTOC Group Settings
2 feeder K02
STS Crane-1 K04
STS Crane-2 5P10 Start Value 1.0…..40.00 xIn 0.01 - 1.00 1.25
K05
STS Crane-3 K06
STS Crane-4 K08 Start Value Multiplier 0.8…..10.0 - 0.1 - 1.0 1.0
STS Crane-5
STS Crane-6 Operate delay time - ms 10 20….200000 20 400
50P Three-phase non-directional overcurrent protection - Instantaneous stage PHIPTOC Non group Settings

1 = on
Operation - - - 1 = on 1 = on
5 = off

1 = 1 out of 3
Number of start phases 2 = 2 out of 3 - - - 1 = 1 out of 3 1 = 1 out of 3
3 = 3 out of 3

Reset delay time - ms 1 0….60000 20 20

51P-1 Three phase non-directional overcurrent protection - Low Stage PHLPTOC Group Settings
Start Value 0.05…..5.00 xIn 0.01 - 0.05 0.460
Start Value Multiplier 0.8…..10.0 0.1 - 1.0 1.0
Time Multiplier - 0.01 0.05….15.00 1.00 0.50
Operate delay time - ms 10 40…..200000 40 -
1 = ANSI Ext. inv.
2 = ANSI Very inv.
3 = ANSI Norm. inv.
4 = ANSI Mod.inv.
5 = ANSI Def. Time
6 = L.T.E. inv.
7 = L.T.V. inv.
8 = L.T. inv.
9 = IEC Norm. inv.
Curve Type 15 = IEC Def. Time 9 = IEC Norm. inv.
10 = IEC Very inv.
11 = IEC inv.
12 = IEC Ext. inv.
13 = IEC S.T. inv.
14 = IEC L.T. inv.
15 = IEC Def.Time.
17 = Programmable
18 = RI type
19 = RD type.

1 = immediate
Type of reset curve 2 = Def time reset 1 = immediate 1 = immediate
3 = Inverse reset
51P-1 Three phase non-directional overcurrent protection - Low Stage PHLPTOC Non group Settings
1 = on
Operation - - - 1 = on 1 = on
5 = off
1 = 1 out of 3
Number of start phases 2 = 2 out of 3 - - - 1 = 1 out of 3 1 = 1 out of 3
3 = 3 out of 3

Minimum Operate time - ms 1 20…60000 20 20

Reset delay time - ms 1 0…60000 20 20

1= RMS
Measurement mode 2= DFT 2 = DFT 2 = DFT
3 = Peak-to-Peak

50N Non-directional earth fault protection - Instantaneous stage EFIPTOC - Short Time : IEC Definite Time Group Settings
Start Value 0.1…..40.00 xIn 0.01 - 0.10 0.20
Start Value Multiplier 0.8…..10.0 0.1 - 1.0 1.0
Operate delay time - ms 10 40….200000 20 400.00
50N Non-directional earth fault protection - Instantaneous stage EFIPTOC Non group Settings

1 = on
Operation - - - 1 = on 1 = on
5 = off

Reset delay time - ms 1 0….60000 20 20

1= Measured Io
Io signal selection 1= Measured Io
2 = Calculated Io
PD Range Proposed Settings
Full load /
Sr. Reated Reated Protection Protection device
Feeder tag Load Description Panel CT PT rated current NEMA Code Time Remark
No KVA kV device Make Type Time setting
Amps Pick-up setting Charact
Parameter Unit Step range (sec) / Default setting Pick-up
range (sec) / eristic
TMS range
TMS

51N-1 Non-directional earth fault protection - Low Stage EFLPTOC Group Settings
Start Value 0.010…..5.000 xIn 0.005 - 0.010 0.040
Start Value Multiplier 0.8…..10.0 0.1 - 1.0 1.00
Time Multiplier - 0.01 0.05….15.00 1.00 0.20
Operate delay time - ms 10 40…..200000 40 -
1 = ANSI Ext. inv.
2 = ANSI Very inv.
3 = ANSI Norm. inv.
4 = ANSI Mod.inv.
5 = ANSI Def. Time
6 = L.T.E. inv.
7 = L.T.V. inv.
8 = L.T. inv.
9 = IEC Norm. inv.
Curve Type 15 = IEC Def. Time 9 = IEC Norm. inv.
10 = IEC Very inv.
11 = IEC inv.
12 = IEC Ext. inv.
13 = IEC S.T. inv.
14 = IEC L.T. inv.
15 = IEC Def.Time.
17 = Programmable
18 = RI type
19 = RD type.

1 = immediate
Type of reset curve 2 = Def time reset 1 = immediate 1 = immediate
3 = Inverse reset

51N-1 Non-directional earth fault protection - Low Stage EFLPTOC Non group Settings
1 = on
Operation - - - 1 = on 1 = on
5 = off

Minimum Operate time - ms 1 20…60000 20 20

Reset delay time - ms 1 0…60000 20 20


1= RMS
Measurement mode 2= DFT 2 = DFT 2 = DFT
3 = Peak-to-Peak
 PROTECTION SETTINGS FOR 13.8KV STS SUBSTATION : OUTGOING TO STS TRANSFORMER FEEDER
PD Range Proposed Settings
Full load /
Sr. Reated Reated Protection Protection device
Feeder tag Load Description Panel CT PT rated current NEMA Code Time Remark
No KVA kV device Make Type Time setting
Amps Pick-up setting Charact
Parameter Unit Step range (sec) / Default setting Pick-up
range (sec) / eristic
TMS range
TMS
1 STS Substation : 315 KVA
13.8kV Out going feeder K09 50 1 13.8 13 ABB REF 615 50P Three-phase non-directional overcurrent protection - Instantaneous stage PHIPTOC Group Settings
2 Distribution Transformer Feeder

5P10 Start Value 1.0…..40.00 xIn 0.01 - 1.00 2.37

Start Value Multiplier 0.8…..10.0 - 0.1 - 1.0 1.0

Operate delay time - ms 10 20….200000 20 400


50P Three-phase non-directional overcurrent protection - Instantaneous stage PHIPTOC Non group Settings

1 = on
Operation - - - 1 = on 1 = on
5 = off

1 = 1 out of 3
Number of start phases 2 = 2 out of 3 - - - 1 = 1 out of 3 1 = 1 out of 3
3 = 3 out of 3

Reset delay time - ms 1 0….60000 20 20

51P-1 Three phase non-directional overcurrent protection - Low Stage PHLPTOC Group Settings
Start Value 0.05…..5.00 xIn 0.01 - 0.05 0.290
Start Value Multiplier 0.8…..10.0 0.1 - 1.0 1.0
Time Multiplier - 0.01 0.05….15.00 1.00 2.00
Operate delay time - ms 10 40…..200000 40 -
1 = ANSI Ext. inv.
2 = ANSI Very inv.
3 = ANSI Norm. inv.
4 = ANSI Mod.inv.
5 = ANSI Def. Time
6 = L.T.E. inv.
7 = L.T.V. inv.
8 = L.T. inv.
9 = IEC Norm. inv.
Curve Type 15 = IEC Def. Time 12 = IEC Ext. inv.
10 = IEC Very inv.
11 = IEC inv.
12 = IEC Ext. inv.
13 = IEC S.T. inv.
14 = IEC L.T. inv.
15 = IEC Def.Time.
17 = Programmable
18 = RI type
19 = RD type.

1 = immediate
Type of reset curve 2 = Def time reset 1 = immediate 1 = immediate
3 = Inverse reset
51P-1 Three phase non-directional overcurrent protection - Low Stage PHLPTOC Non group Settings
1 = on
Operation - - - 1 = on 1 = on
5 = off
1 = 1 out of 3
Number of start phases 2 = 2 out of 3 - - - 1 = 1 out of 3 1 = 1 out of 3
3 = 3 out of 3

Minimum Operate time - ms 1 20…60000 20 20

Reset delay time - ms 1 0…60000 20 20

1= RMS
Measurement mode 2= DFT 2 = DFT 2 = DFT
3 = Peak-to-Peak

50N Non-directional earth fault protection - Instantaneous stage EFIPTOC - Short Time : IEC Definite Time Group Settings
Start Value 0.1…..40.00 xIn 0.01 - 0.10 0.26
Start Value Multiplier 0.8…..10.0 0.1 - 1.0 1.0
Operate delay time - ms 10 40….200000 20 400.00
50N Non-directional earth fault protection - Instantaneous stage EFIPTOC

1 = on
Operation - - - 1 = on 1 = on
5 = off

Reset delay time - ms 1 0….60000 20 20

1= Measured Io
Io signal selection 1= Measured Io
2 = Calculated Io
PD Range Proposed Settings
Full load /
Sr. Reated Reated Protection Protection device
Feeder tag Load Description Panel CT PT rated current NEMA Code Time Remark
No KVA kV device Make Type Time setting
Amps Pick-up setting Charact
Parameter Unit Step range (sec) / Default setting Pick-up
range (sec) / eristic
TMS range
TMS

51N-1 Non-directional earth fault protection - Low Stage EFLPTOC Group Settings
Start Value 0.010…..5.000 xIn 0.005 - 0.010 0.030
Start Value Multiplier 0.8…..10.0 0.1 - 1.0 1.00
Time Multiplier - 0.01 0.05….15.00 1.00 0.30
Operate delay time - ms 10 40…..200000 40 -
1 = ANSI Ext. inv.
2 = ANSI Very inv.
3 = ANSI Norm. inv.
4 = ANSI Mod.inv.
5 = ANSI Def. Time
6 = L.T.E. inv.
7 = L.T.V. inv.
8 = L.T. inv.
9 = IEC Norm. inv.
Curve Type 15 = IEC Def. Time 9 = IEC Norm. inv.
10 = IEC Very inv.
11 = IEC inv.
12 = IEC Ext. inv.
13 = IEC S.T. inv.
14 = IEC L.T. inv.
15 = IEC Def.Time.
17 = Programmable
18 = RI type
19 = RD type.

1 = immediate
Type of reset curve 2 = Def time reset 1 = immediate 1 = immediate
3 = Inverse reset

51N-1 Non-directional earth fault protection - Low Stage EFLPTOC Non group Settings
1 = on
Operation - - - 1 = on 1 = on
5 = off

Minimum Operate time - ms 1 20…60000 20 20

Reset delay time - ms 1 0…60000 20 20


1= RMS
Measurement mode 2= DFT 2 = DFT 2 = DFT
3 = Peak-to-Peak

25 Synchronism and energizing check SECRSYN Group Settings


-1 = Off
1 = Both dead
2 = Live L, Dead B
3 = Dead L, Live B
Live dead mode - 1 = Both Dead
4 = Dead Bus, L Any
5 = Dead L, Bus Any Disable
6 = One Live, Dead
7 = Not Both Live
Difference voltage 0.01……0.50 xUn 0.01 - 0.05
Difference frequency 0.001…..0.100 xFn 0.001 - 0.001
Difference angle 5……90 deg 1 - 5
25 Synchronism and energizing check SECRSYN Non Group Settings
1 = on
Operation 1 = on 5=off
5 = off
1 = Off
Synchro check mode 2 = Synchronous 3 = Asynchronous
3 = Asynchronous
Dead line value 0.1……0.8 xUn 0.1 0.2
Live line value 0.2……1.0 xUn 0.1 0.8
Dead bus value 0.1…….0.8 xUn 0.1 0.2
Live bus value 0.2…..1.0 xUn 0.1 0.5
Max energizing V 0.50……1.15 xUn 0.01 1.05
Disable
1 = Continuous
Control mode 1 = Continuous
2 = Command
Close pulse ms 10 200…..60000 200
Phase shift -180……180 deg 1 0
Minimum syn time - ms 10 0……60000 0
Maximum syn time - ms 10 100…..6000000 2000
Energizing time - ms 10 100…..60000 100
Closing time of CB - ms 10 40…..250 60
0 = False
Voltage source switch 0 = False
1 = True
PD Range Proposed Settings
Full load /
Sr. Reated Reated Protection Protection device
Feeder tag Load Description Panel CT PT rated current NEMA Code Time Remark
No KVA kV device Make Type Time setting
Amps Pick-up setting Charact
Parameter Unit Step range (sec) / Default setting Pick-up
range (sec) / eristic
TMS range
TMS

27 Three-phase undervoltage protection PHPTUV Group settings


Start value 0.05…..1.20 xUn 0.01 - 0.90 0.80
Time multiplier - 0.01 0.05……15.00 1.00 -
Operate delay time - ms 60…..300000 60 5000
5 = ANSI Def. Time
15 = IEC Def. Time
Operating curve type 21 = Inv. Curve A 15 = IEC Def. Time 15 = IEC Def. Time
22 = Inv. Curve B
23 = Programmable
1 = Immediate
Type of reset Curve 2 = Def time reset 1 = Immediate 1 = Immediate
'-1 = DT Lin decr rst
27 Three-phase undervoltage protection PHPTUV 'Non group settings
1= on
Operation - 1 = on 5=off
5 = off
1 = 1 out of 3
Num of start phases 2 = 2 out of 3 - 1 = 1 out of 3
3 = 3 out of 3
Minimum operate time - ms 1 60……60000 60
Reset delay time - ms 1 0…..60000 20
Curve parameter A 0.005…200.000 1.000
Curve parameter B 0.50…100.00 1.00
Curve parameter C 0.0…1.0 0.0
Curve parameter D 0.000…60.000 0.000
Curve parameter E 0.000…3.000 1.000
Curve Sat Relative 0.0…3.0 0.1 2.0
Voltage block value 0.05……1.00 xUn 0.01 - 0.20
0 = False
Enable block value - 1 = True
1 = True
1 = phase-to-earth
Voltage selection - 2 = phase-to-phase
2 = phase-to-phase
Relative hysteresis 1.0…5.0 % 0.1 - 4.0

59 Three phase overvoltage protection PHPTOV Group Settings


pickup value 0.05……1.60 xVn 0.01 1.10 1.15
Time multiplier 0.05……15.00 0.05 1.00 1.00
Trip delay time ms 10 40……..300000 40 3000
5= ANSI DT
15= IEC DT
17= Inv. Curve A
Operating curve type 5= ANSI DT 15= IEC DT
18= Inv. Curve B
19= Inv. Curve C
20= Programmable
1= Immediate
Type of reset curve 2= Def. time reset 1 = Immediate 1 = Immediate
-1 = DT Lin decr rst
59 Three-phase overvoltage protection PHPTUV 'Non group settings
1= enable
Operation - 1 = enable 1 = enable
5 = disable
1 = 1 out of 3
Num of pickup phases 2 = 2 out of 3 - 1 = 1 out of 3 1 = 1 out of 3
3 = 3 out of 3
Minimum operate time - ms 1 60……60000 60 -
Reset delay time - ms 1 0…..60000 20 20
Curve parameter A 0.005…200.000 1.000 -
Curve parameter B 0.50…100.00 1.00 -
Curve parameter C 0.0…1.0 0.0 -
Curve parameter D 0.000…60.000 0.000 -
Curve parameter E 0.000…3.000 1.000 -
Curve Sat Relative 0.0…3.0 0.1 2.0 -
Voltage block value 0.05……1.00 xUn 0.01 - 0.20 -
0 = False
Enable block value - 1 = True 0 = False
1 = True
1 = phase-to-earth
Voltage selection - 2 = phase-to-phase 2 = phase-to-phase
2 = phase-to-phase
Relative hysteresis 1.0…5.0 % 0.1 - 4.0 4.0
Document Tile Document No. Revision Date Page No.
RELAY COORDINATION &
ABB-TEC-CAL-035 V2 21-March-2024 38 of 85
PROTECTION STUDY

Annexure-6

13.8kV ERTG, MSS & CSW Substation Protection


setting table
13.8KV ERTG SUBSTATIONS MSS SUBSTATION CSW SUBSTATION

FEEDER NAME ERTG FEEDER-03 ERTG FEEDER-05 ERTG FEEDER-07 ERTG FEEDER-08 MAIN SUBSTATION CSW SUBSTATION

RELAY ID RLY-ERTG 03-K03 RLY-ERTG 05-K03 RLY-ERTG 07-K03 RLY-ERTG 08-K03 RLY-MSS-K03 RLY-CSW-K03

CT RATIO 150:1 A 150:1 A 150:1 A 150:1 A 50:1 A 150:1 A

RELAY PROTECTIONS 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N

RELAY MAKE ABB ABB ABB ABB ABB ABB


COMMON DETAILS
RELAY MODEL REJ601 REJ601 REJ601 REJ601 REJ601 REJ601

Pmax (KVA) 2250 2250 2250 2250 315 2250

Imax (Iload) Amps 94.1 94.1 94.1 94.1 13.2 94.1

START VALUE in PU / AMPS 0.692 PU / 103.8A 0.692 PU / 103.8A 0.692 PU / 103.8A 0.692 PU / 103.8A 0.3 PU / 15A 0.693 PU / 104A

PHLPTOC (51) TIME DIAL 0.4 0.4 0.4 0.4 1 1

CURVE TYPE IEC-EI IEC-EI IEC-EI IEC-EI IEC-LTI IEC-LTI


PHASE
SETTINGS
START VALUE 10 PU /1500A 10 PU /1500A 10 PU /1500A 10 PU /1500A 2.12 PU /106A 5.52 PU /828A

PHHPTOC (50) CURVE TYPE IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT

OPER.DELAY (SEC) 0.03 0.03 0.03 0.03 0.4 0.4

START VALUE 0.08 PU / 12A 0.08 PU / 12A 0.08 PU / 12A 0.08 PU / 12A 0.026 PU / 1.3A 0.063 PU / 9.45A

EFLPTOC (51N) TIME DIAL 0.4 0.4 0.4 0.4 1 1

CURVE TYPE IEC-VI IEC-VI IEC-VI IEC-VI IEC-NI IEC-NI

START VALUE 10 PU / 1500A 10 PU / 1500A 10 PU / 1500A 10 PU / 1500A 0.14PU / 7A 0.314PU / 47.1A


GROUND
EFHPTOC (50N) CURVE TYPE IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT
SETTINGS
OPER.DELAY (SEC) 0.04 0.04 0.04 0.04 0.4 0.4

START VALUE 10 PU / 1500A 10 PU / 1500A 10 PU / 1500A 10 PU / 1500A 0.14PU / 7A 0.314PU / 47.1A

EFIPTOC (50N) CURVE TYPE IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT

OPER.DELAY (SEC) 0.04 0.04 0.04 0.04 0.4 0.4


Document Tile Document No. Revision Date Page No.
RELAY COORDINATION &
ABB-TEC-CAL-035 V2 21-March-2024 40 of 85
PROTECTION STUDY

Annexure-7

13.8kV DG Switchgear Protection setting table


13.8KV DG SWITCHGEAR-2

FEEDER NAME DG INCOMER-1 DG INCOMER-2 DG INCOMER-3 DG INCOMER-4 DG INCOMER-5 DG OUTGOING-1 DG OUTGOING-2

RELAY ID RLY_DG1_H01 RLY_DG1_H02 RLY_DG1_H03 RLY_DG1_H04 RLY_DG1_H05 RLY_DG SWGR2_H07 RLY_DG SWGR2_H08

CT RATIO 150:5 A 150:5 A 150:5 A 150:5 A 150:5 A 1250:5 A 1250:5 A

RELAY PROTECTIONS 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N 50-51 / 50-51N

RELAY MAKE ABB ABB ABB ABB ABB ABB ABB


COMMON DETAILS
RELAY MODEL REF615 REF615 REF615 REF615 REF615 REF615 REF615

Pmax (KVA) 2500 2500 2500 2500 2500 12500 12500

Imax (Iload) Amps 104.6 104.6 104.6 104.6 104.6 523.0 523.0

START VALUE in PU / AMPS 0.7 PU / 105A 0.7 PU / 105A 0.7 PU / 105A 0.7 PU / 105A 0.7 PU / 105A 0.44 PU / 550A 0.44 PU / 550A

PHLPTOC (51) TIME DIAL 1 1 1 1 1 0.4 0.4

CURVE TYPE IEC-NI IEC-NI IEC-NI IEC-NI IEC-NI IEC-LTI IEC-LTI


PHASE
SETTINGS
START VALUE 5.9 PU /885A 5.9 PU /885A 5.9 PU /885A 5.9 PU /885A 5.9 PU /885A 2 PU /2500A 2 PU /2500A

PHHPTOC (50) CURVE TYPE IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT

OPER.DELAY (SEC) 0.4 0.4 0.4 0.4 0.4 0.8 0.8

START VALUE 0.07 PU / 10.5A 0.07 PU / 10.5A 0.07 PU / 10.5A 0.07 PU / 10.5A 0.07 PU / 10.5A 0.07 PU / 87.5A 0.07 PU / 87.5A

EFLPTOC (51N) TIME DIAL 1 1 1 1 1 1 1

CURVE TYPE IEC-NI IEC-NI IEC-NI IEC-NI IEC-NI IEC-NI IEC-NI


GROUND
SETTINGS
START VALUE 0.21PU / 31.5A 0.21PU / 31.5A 0.21PU / 31.5A 0.21PU / 31.5A 0.21PU / 31.5A 0.21PU / 262.5A 0.21PU / 262.5A

EFHPTOC (50N) CURVE TYPE IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT IEC-DT

OPER.DELAY (SEC) 0.4 0.4 0.4 0.4 0.4 0.8 0.8


Document Tile Document No. Revision Date Page No.
RELAY COORDINATION &
ABB-TEC-CAL-035 V2 21-March-2024 42 of 85
PROTECTION STUDY

Annexure-8

69kV Grid Incomer – Pass Module Protection setting


table
69KV GRID INCOMER

FEEDER NAME PASS MODULE PASS MODULE

RELAY ID RLY_69KV GRID_MAIN RLY_69KV GRID_BACKUP

CT RATIO 600:5 A 400:5 A

RELAY PROTECTIONS 50-51 / 50-51N 50-51 / 50-51N

RELAY MAKE ABB ABB


COMMON DETAILS
RELAY MODEL RET630 REF620

Pmax (KVA) 30000 30000

Imax (Iload) Amps 1255.1 1255.1

START VALUE in PU / AMPS 0.333 PU / 200A 0.425 PU / 170A

PHLPTOC (51) TIME DIAL 0.52 0.3

CURVE TYPE IEC-VI IEC-VI


PHASE
SETTINGS
START VALUE 6.333 PU /3800A 7.5 PU /3000A

PHHPTOC (50) CURVE TYPE IEC-DT IEC-DT

OPER.DELAY (SEC) 0.02 0.02

START VALUE 0.167 PU / 100A 0.155 PU / 62A

EFLPTOC (51N) TIME DIAL 0.56 0.35

CURVE TYPE IEC-VI IEC-VI


GROUND
SETTINGS
START VALUE 4PU / 2400A 5PU / 2000A

EFHPTOC (50N) CURVE TYPE IEC-DT IEC-DT

OPER.DELAY (SEC) 0.02 0.02


Document Tile Document No. Revision Date Page No.
RELAY COORDINATION &
ABB-TEC-CAL-035 V2 21-March-2024 44 of 85
PROTECTION STUDY

Annexure-9

LV system Protection Setting table


220V MAIN LV SWITCHGEAR - STS SS
LVCB-LVSST
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band Ixt Pickup Trip (Amps)
Phase 0.88 880 t1 12 2.5 2500 t2 0.2 OFF - -
1 CB-STS-QF1 Power Supply Incomer ABB XT7S EKIP-LSI 1000 801.2 0.220
Ground - - - - - - - - - - -

220V MAIN LV SWITCHGEAR - STS SS


STS 220V LV PANEL LVCB-TMA/TMD
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-STS-QF2 FIRE WATER PUMP ABB XT4N TMA 250 178.7 - 79% 197.5 5 1250 0.220

2 CB-STS-QF3 Building Installation Panel ABB XT1-C TMD 160 52.5 - 70% 112 Fixed Fixed 0.220

3 CB-STS-QF4 High Mast Lightning DB-10 ABB XT1-C TMD 160 NA - 70% 112 Fixed Fixed 0.220

4 CB-STS-QF5 High Mast Lightning DB-11 ABB XT1-C TMD 160 NA - 70% 112 Fixed Fixed 0.220

5 CB-STS-QF6 High Mast Lightning DB-12 ABB XT1-C TMD 160 NA - 70% 112 Fixed Fixed 0.220

6 CB-STS-QF7 Spare ABB XT1-C TMD 160 NA - 70% 112 Fixed Fixed 0.220

7 CB-STS-QF8 Spare ABB XT1-C TMD 160 NA - 70% 112 Fixed Fixed 0.220

8 CB-STS-QF9 Spare ABB XT1-C TMD 160 NA - 70% 112 Fixed Fixed 0.220

9 CB-STS-QF10 Spare ABB XT1-C TMD 160 NA - 70% 112 Fixed Fixed 0.220

10 CB-STS-QF11 48V DC Charger ABB XT1-C TMD 160 NA - 70% 112 Fixed Fixed 0.220

11 CB-STS-QF12 Spare ABB S202-M-B40 TMF 40 NA - Fixed Fixed Fixed Fixed 0.220

12 CB-STS-QF13 Spare ABB S202-M-B40 TMF 40 NA - Fixed Fixed Fixed Fixed 0.220

13 CB-STS-QF14 Spare ABB S202-M-B40 TMF 32 NA - Fixed Fixed Fixed Fixed 0.220

14 CB-STS-QF15 Spare ABB S202-M-B40 TMF 16 NA - Fixed Fixed Fixed Fixed 0.220

15 CB-STS-QF16 Spare ABB S202-M-B40 TMF 16 NA - Fixed Fixed Fixed Fixed 0.220

16 CB-STS-QF17 Spare ABB S202-M-B40 TMF 20 NA - Fixed Fixed Fixed Fixed 0.220

17 CB-STS-QF18 Spare ABB S202-M-B40 TMF 10 NA - Fixed Fixed Fixed Fixed 0.220

18 CB-STS-QF19 Spare ABB S202-M-B40 TMF 32 NA - Fixed Fixed Fixed Fixed 0.220

19 CB-STS-QF20 Spare ABB S202-M-B40 TMF 16 NA - Fixed Fixed Fixed Fixed 0.220

20 CB-STS-QF21 Spare ABB S202-M-B40 TMF 20 NA - Fixed Fixed Fixed Fixed 0.220

21 CB-STS-QF22 Spare ABB S202-M-B40 TMF 10 NA - Fixed Fixed Fixed Fixed 0.220
460V LV PANEL - ERTG SS-3
LVCB-LVSST
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function x Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band I t Pickup Trip (Amps)
Phase 0.943 3017.6 t1 3 3.4 10880 t2 0.2 OUT - -
1 CB-ERTG3-QF1 Power Supply Incomer ABB E4.2N Ekip-LSI Touch 3200 2741 0.460
Ground - - - - - - - - - - -
Phase 0.62 620 t1 3 1.5 1500 t2 0.05 OUT 3 3000
2 CB-ERTG3-QF2 To ERTG Piller Box-1 ABB XT6H Ekip-LSI Dip 1000 564.8 0.460
Ground - - - - - - - - - - -
Phase 0.62 620 t1 3 1.5 1500 t2 0.05 OUT 3 3000
3 CB-ERTG3-QF3 To ERTG Piller Box-2 ABB XT6H Ekip-LSI Dip 1000 564.8 0.460
Ground - - - - - - - - - - -
Phase 0.62 620 t1 3 1.5 1500 t2 0.05 OUT 3 3000
4 CB-ERTG3-QF4 To ERTG Piller Box-3 ABB XT6H Ekip-LSI Dip 1000 564.8 0.460
Ground - - - - - - - - - - -
Phase 0.62 620 t1 3 1.5 1500 t2 0.05 OUT 3 3000
5 CB-ERTG3-QF5 To ERTG Piller Box-4 ABB XT6H Ekip-LSI Dip 1000 564.8 0.460
Ground - - - - - - - - - - -
Phase 0.62 620 t1 3 1.5 1500 t2 0.05 OUT 3 3000
6 CB-ERTG3-QF6 To ERTG Piller Box-5 ABB XT6H Ekip-LSI Dip 1000 564.8 0.460
Ground - - - - - - - - - - -

460V LV PANEL - ERTG SS-5


LVCB-LVSST
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function x Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band I t Pickup Trip (Amps)
Phase 0.943 3017.6 t1 3 3.4 10880 t2 0.2 OUT - -
1 CB-ERTG5-QF1 Power Supply Incomer ABB E4.2N Ekip-LSI Touch 3200 2741 0.460
Ground - - - - - - - - - - -
Phase 0.62 620 t1 3 1.5 1500 t2 0.05 OUT 3 3000
2 CB-ERTG5-QF2 To ERTG Piller Box-1 ABB XT6H Ekip-LSI Dip 1000 564.8 0.460
Ground - - - - - - - - - - -
Phase 0.62 620 t1 3 1.5 1500 t2 0.05 OUT 3 3000
3 CB-ERTG5-QF3 To ERTG Piller Box-2 ABB XT6H Ekip-LSI Dip 1000 564.8 0.460
Ground - - - - - - - - - - -
Phase 0.62 620 t1 3 1.5 1500 t2 0.05 OUT 3 3000
4 CB-ERTG5-QF4 To ERTG Piller Box-3 ABB XT6H Ekip-LSI Dip 1000 564.8 0.460
Ground - - - - - - - - - - -
Phase 0.62 620 t1 3 1.5 1500 t2 0.05 OUT 3 3000
5 CB-ERTG5-QF5 To ERTG Piller Box-4 ABB XT6H Ekip-LSI Dip 1000 564.8 0.460
Ground - - - - - - - - - - -
Phase 0.62 620 t1 3 1.5 1500 t2 0.05 OUT 3 3000
6 CB-ERTG5-QF6 To ERTG Piller Box-5 ABB XT6H Ekip-LSI Dip 1000 564.8 0.460
Ground - - - - - - - - - - -

460V LV PANEL - ERTG SS-7


LVCB-LVSST
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band Ix t Pickup Trip (Amps)
Phase 0.943 3017.6 t1 3 3.4 10880 t2 0.2 OUT - -
1 CB-ERTG7-QF1 Power Supply Incomer ABB E4.2N Ekip-LSI Touch 3200 2741 0.460
Ground - - - - - - - - - - -
Phase 0.62 620 t1 3 1.5 1500 t2 0.05 OUT 3 3000
2 CB-ERTG7-QF2 To ERTG Piller Box-1 ABB XT6S Ekip-LSI Dip 1000 564.8 0.460
Ground - - - - - - - - - - -
Phase 0.62 620 t1 3 1.5 1500 t2 0.05 OUT 3 3000
3 CB-ERTG7-QF3 To ERTG Piller Box-2 ABB XT6S Ekip-LSI Dip 1000 564.8 0.460
Ground - - - - - - - - - - -
Phase 0.62 620 t1 3 1.5 1500 t2 0.05 OUT 3 3000
4 CB-ERTG7-QF4 To ERTG Piller Box-3 ABB XT6S Ekip-LSI Dip 1000 564.8 0.460
Ground - - - - - - - - - - -
Phase 0.62 620 t1 3 1.5 1500 t2 0.05 OUT 3 3000
5 CB-ERTG7-QF5 To ERTG Piller Box-4 ABB XT6S Ekip-LSI Dip 1000 564.8 0.460
Ground - - - - - - - - - - -

460V LV PANEL - ERTG SS-8


LVCB-LVSST
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band Ix t Pickup Trip (Amps)
Phase 0.943 3017.6 t1 3 3.4 10880 t2 0.2 OUT - -
1 CB-ERTG8-QF1 Power Supply Incomer ABB E4.2N Ekip-LSI Touch 3200 2741 0.460
Ground - - - - - - - - - - -
Phase 0.62 620 t1 3 1.5 1500 t2 0.05 OUT 3 3000
2 CB-ERTG8-QF2 To ERTG Piller Box-1 ABB XT6S Ekip-LSI Dip 1000 564.8 0.460
Ground - - - - - - - - - - -
Phase 0.62 620 t1 3 1.5 1500 t2 0.05 OUT 3 3000
3 CB-ERTG8-QF3 To ERTG Piller Box-2 ABB XT6S Ekip-LSI Dip 1000 564.8 0.460
Ground - - - - - - - - - - -
Phase 0.62 620 t1 3 1.5 1500 t2 0.05 OUT 3 3000
4 CB-ERTG8-QF4 To ERTG Piller Box-3 ABB XT6S Ekip-LSI Dip 1000 564.8 0.460
Ground - - - - - - - - - - -
Phase 0.62 620 t1 3 1.5 1500 t2 0.05 OUT 3 3000
5 CB-ERTG8-QF5 To ERTG Piller Box-4 ABB XT6S Ekip-LSI Dip 1000 564.8 0.460
Ground - - - - - - - - - - -

460V ERTG LVCB_ TMA/TMD


Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-ERTG3-QF7 ERTG-3_75 KVA Auxiliary Transformer ABB XT4H TMA 160 94 Phase 70% 112 5 800 0.460

2 CB-ERTG5-QF7 ERTG-5_75 KVA Auxiliary Transformer ABB XT4H TMA 160 94 Phase 70% 112 5 800 0.460

3 CB-ERTG7-QF6 ERTG-7_75 KVA Auxiliary Transformer ABB XT4S TMA 125 94 Phase 83% 104 6 750 0.460

4 CB-ERTG8-QF6 ERTG-8_75 KVA Auxiliary Transformer ABB XT4S TMA 125 94 Phase 83% 104 6 750 0.460
220V LV PANEL - ERTG SS-3
LVCB-LV_TMA/TMD
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-220V-ERTG3-QF1 Incomer to 220LV SWBD_ ERTG 3 Auxiliary Transformer ABB XT4N TMA 250 190.8 - 84% 210 5 1250 0.220

2 CB-220V-ERTG3-QF2 Spare ABB XT1-C TMD 160 NA - 70% 112 Fixed Fixed 0.220

3 CB-220V-ERTG3-QF3 Spare ABB XT1-C TMD 160 NA - 70% 112 Fixed Fixed 0.220

4 CB-220V-ERTG3-QF4 Building Installation Panel ABB XT1-B TMD 160 NA - 70% 112 Fixed Fixed 0.220

5 CB-220V-ERTG3-QF5 HMLDB ABB XT1-B TMD 160 NA - 70% 112 Fixed Fixed 0.220

6 CB-220V-ERTG3-QF6 HMLDB ABB XT1-B TMD 160 NA - 70% 112 Fixed Fixed 0.220

7 CB-220V-ERTG3-QF7 Spare ABB XT1-B TMD 160 NA - 70% 112 Fixed Fixed 0.220

8 CB-220V-ERTG3-QF8 Spare ABB XT1-B TMD 160 NA - 70% 112 Fixed Fixed 0.220

9 CB-220V-ERTG3-QF9 1KVA 48VDC CHARGER ABB XT1-B TMD 160 NA - 70% 112 Fixed Fixed 0.220

10 CB-220V-ERTG3-QA1 Spare ABB S203-M-B20 TMF 20 NA - Fixed Fixed Fixed Fixed 0.220

11 CB-220V-ERTG3-QA2 Spare ABB S203-M-B20 TMF 20 NA - Fixed Fixed Fixed Fixed 0.220

12 CB-220V-ERTG3-QA3 Spare ABB S202-M-C20 TMF 20 NA - Fixed Fixed Fixed Fixed 0.220

13 CB-220V-ERTG3-QA4 Spare ABB S202-M-C20 TMF 20 NA - Fixed Fixed Fixed Fixed 0.220

14 CB-220V-ERTG3-QA5 Spare ABB S202-M-C16 TMF 16 NA - Fixed Fixed Fixed Fixed 0.220

15 CB-220V-ERTG3-QA6 Spare ABB S202-M-C16 TMF 16 NA - Fixed Fixed Fixed Fixed 0.220

16 CB-220V-ERTG3-QA7 Small Mast Lightning Circuit ABB S202-M-C16 TMF 16 NA - Fixed Fixed Fixed Fixed 0.220

17 CB-220V-ERTG3-QA8 Spare ABB S202-M-C10 TMF 10 NA - Fixed Fixed Fixed Fixed 0.220

18 CB-220V-ERTG3-QA9 Spare ABB S202-M-C40 TMF 40 NA - Fixed Fixed Fixed Fixed 0.220

18 CB-220V-ERTG3-QA10 Spare ABB S202-M-C40 TMF 40 NA - Fixed Fixed Fixed Fixed 0.220

19 CB-220V-ERTG3-QA11 Spare ABB S202-M-C32 TMF 32 NA - Fixed Fixed Fixed Fixed 0.220

20 CB-220V-ERTG3-QA12 Spare ABB S202-M-C32 TMF 32 NA - Fixed Fixed Fixed Fixed 0.220

220V LV PANEL - ERTG SS-5


LVCB-LV_TMA/TMD
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-220V-ERTG5-QF1 Incomer to 220LV SWBD_ ERTG 5 Auxiliary Transformer ABB XT4N TMA 250 190.8 - 84% 210 5 1250 0.220

2 CB-220V-ERTG5-QF2 Spare ABB XT1-C TMD 160 NA - 70% 112 Fixed Fixed 0.220

3 CB-220V-ERTG5-QF3 Spare ABB XT1-C TMD 160 NA - 70% 112 Fixed Fixed 0.220

4 CB-220V-ERTG5-QF4 Building Installation Panel ABB XT1-B TMD 160 NA - 70% 112 Fixed Fixed 0.220

5 CB-220V-ERTG5-QF5 HMLDB ABB XT1-B TMD 160 NA - 70% 112 Fixed Fixed 0.220

6 CB-220V-ERTG5-QF6 HMLDB ABB XT1-B TMD 160 NA - 70% 112 Fixed Fixed 0.220

7 CB-220V-ERTG5-QF7 Spare ABB XT1-B TMD 160 NA - 70% 112 Fixed Fixed 0.220

8 CB-220V-ERTG5-QF8 Spare ABB XT1-B TMD 160 NA - 70% 112 Fixed Fixed 0.220

9 CB-220V-ERTG5-QF9 1KVA 48VDC CHARGER ABB XT1-B TMD 160 NA - 70% 112 Fixed Fixed 0.220

10 CB-220V-ERTG5-QA1 Spare ABB S203-M-B20 TMF 20 NA - Fixed Fixed Fixed Fixed 0.220

11 CB-220V-ERTG5-QA2 Spare ABB S203-M-B20 TMF 20 NA - Fixed Fixed Fixed Fixed 0.220

12 CB-220V-ERTG5-QA3 Spare ABB S202-M-C20 TMF 20 NA - Fixed Fixed Fixed Fixed 0.220

13 CB-220V-ERTG5-QA4 Spare ABB S202-M-C20 TMF 20 NA - Fixed Fixed Fixed Fixed 0.220

14 CB-220V-ERTG5-QA5 Spare ABB S202-M-C16 TMF 16 NA - Fixed Fixed Fixed Fixed 0.220

15 CB-220V-ERTG5-QA6 Spare ABB S202-M-C16 TMF 16 NA - Fixed Fixed Fixed Fixed 0.220

16 CB-220V-ERTG5-QA7 Small Mast Lightning Circuit ABB S202-M-C16 TMF 16 NA - Fixed Fixed Fixed Fixed 0.220

17 CB-220V-ERTG5-QA8 Spare ABB S202-M-C10 TMF 10 NA - Fixed Fixed Fixed Fixed 0.220

18 CB-220V-ERTG5-QA9 Spare ABB S202-M-C40 TMF 40 NA - Fixed Fixed Fixed Fixed 0.220

18 CB-220V-ERTG5-QA10 Spare ABB S202-M-C40 TMF 40 NA - Fixed Fixed Fixed Fixed 0.220

19 CB-220V-ERTG5-QA11 Spare ABB S202-M-C32 TMF 32 NA - Fixed Fixed Fixed Fixed 0.220

20 CB-220V-ERTG5-QA12 Spare ABB S202-M-C32 TMF 32 NA - Fixed Fixed Fixed Fixed 0.220
220V LV PANEL - ERTG SS-7
LVCB-LV_TMA/TMD
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-220V-ERTG7-QF1 Incomer to 220LV SWBD_ ERTG 8 Auxiliary Transformer ABB XT4N TMA 250 190.8 - 84% 210 5 1250 0.220

2 CB-220V-ERTG7-QF2 Spare ABB XT1-C TMD 160 NA - 70% 112 Fixed Fixed 0.220

3 CB-220V-ERTG7-QF3 Spare ABB XT1-C TMD 160 NA - 70% 112 Fixed Fixed 0.220

4 CB-220V-ERTG7-QF4 Building Installation Panel ABB XT1-B TMD 160 NA - 70% 112 Fixed Fixed 0.220

5 CB-220V-ERTG7-QF5 HMLDB ABB XT1-B TMD 160 NA - 70% 112 Fixed Fixed 0.220

6 CB-220V-ERTG7-QF6 HMLDB ABB XT1-B TMD 160 NA - 70% 112 Fixed Fixed 0.220

7 CB-220V-ERTG7-QF7 Spare ABB XT1-B TMD 160 NA - 70% 112 Fixed Fixed 0.220

8 CB-220V-ERTG7-QF8 Spare ABB XT1-B TMD 160 NA - 70% 112 Fixed Fixed 0.220

9 CB-220V-ERTG7-QF9 1KVA 48VDC CHARGER ABB XT1-B TMD 160 NA - 70% 112 Fixed Fixed 0.220

10 CB-220V-ERTG8-QA1 Spare ABB S203-M-B20 TMF 20 NA - Fixed Fixed Fixed Fixed 0.220

11 CB-220V-ERTG8-QA2 Spare ABB S203-M-B20 TMF 20 NA - Fixed Fixed Fixed Fixed 0.220

12 CB-220V-ERTG8-QA3 Spare ABB S202-M-C20 TMF 20 NA - Fixed Fixed Fixed Fixed 0.220

13 CB-220V-ERTG8-QA4 Spare ABB S202-M-C20 TMF 20 NA - Fixed Fixed Fixed Fixed 0.220

14 CB-220V-ERTG8-QA5 Spare ABB S202-M-C16 TMF 16 NA - Fixed Fixed Fixed Fixed 0.220

15 CB-220V-ERTG8-QA6 Spare ABB S202-M-C16 TMF 16 NA - Fixed Fixed Fixed Fixed 0.220

16 CB-220V-ERTG8-QA7 Small Mast Lightning Circuit ABB S202-M-C16 TMF 16 NA - Fixed Fixed Fixed Fixed 0.220

17 CB-220V-ERTG8-QA8 Spare ABB S202-M-C10 TMF 10 NA - Fixed Fixed Fixed Fixed 0.220

18 CB-220V-ERTG8-QA9 Spare ABB S202-M-C40 TMF 40 NA - Fixed Fixed Fixed Fixed 0.220

18 CB-220V-ERTG8-QA10 Spare ABB S202-M-C40 TMF 40 NA - Fixed Fixed Fixed Fixed 0.220

19 CB-220V-ERTG8-QA11 Spare ABB S202-M-C32 TMF 32 NA - Fixed Fixed Fixed Fixed 0.220

20 CB-220V-ERTG8-QA12 Spare ABB S202-M-C32 TMF 32 NA - Fixed Fixed Fixed Fixed 0.220

220V LV PANEL - ERTG SS-8


LVCB-LV_TMA/TMD
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-220V-ERTG8-QF1 Incomer to 220LV SWBD_ ERTG 8 Auxiliary Transformer ABB XT4N TMA 250 190.8 - 84% 210 5 1250 0.220

2 CB-220V-ERTG8-QF2 Spare ABB XT1-C TMD 160 NA - 70% 112 Fixed Fixed 0.220

3 CB-220V-ERTG8-QF3 Spare ABB XT1-C TMD 160 NA - 70% 112 Fixed Fixed 0.220

4 CB-220V-ERTG8-QF4 Building Installation Panel ABB XT1-B TMD 160 NA - 70% 112 Fixed Fixed 0.220

5 CB-220V-ERTG8-QF5 HMLDB ABB XT1-B TMD 160 NA - 70% 112 Fixed Fixed 0.220

6 CB-220V-ERTG8-QF6 HMLDB ABB XT1-B TMD 160 NA - 70% 112 Fixed Fixed 0.220

7 CB-220V-ERTG8-QF7 Spare ABB XT1-B TMD 160 NA - 70% 112 Fixed Fixed 0.220

8 CB-220V-ERTG8-QF8 Spare ABB XT1-B TMD 160 NA - 70% 112 Fixed Fixed 0.220

9 CB-220V-ERTG8-QF9 1KVA 48VDC CHARGER ABB XT1-B TMD 160 NA - 70% 112 Fixed Fixed 0.220

10 CB-220V-ERTG8-QA1 Spare ABB S203-M-B20 TMF 20 NA - Fixed Fixed Fixed Fixed 0.220

11 CB-220V-ERTG8-QA2 Spare ABB S203-M-B20 TMF 20 NA - Fixed Fixed Fixed Fixed 0.220

12 CB-220V-ERTG8-QA3 Spare ABB S202-M-C20 TMF 20 NA - Fixed Fixed Fixed Fixed 0.220

13 CB-220V-ERTG8-QA4 Spare ABB S202-M-C20 TMF 20 NA - Fixed Fixed Fixed Fixed 0.220

14 CB-220V-ERTG8-QA5 Spare ABB S202-M-C16 TMF 16 NA - Fixed Fixed Fixed Fixed 0.220

15 CB-220V-ERTG8-QA6 Spare ABB S202-M-C16 TMF 16 NA - Fixed Fixed Fixed Fixed 0.220

16 CB-220V-ERTG8-QA7 Small Mast Lightning Circuit ABB S202-M-C16 TMF 16 NA - Fixed Fixed Fixed Fixed 0.220

17 CB-220V-ERTG8-QA8 Spare ABB S202-M-C10 TMF 10 NA - Fixed Fixed Fixed Fixed 0.220

18 CB-220V-ERTG8-QA9 Spare ABB S202-M-C40 TMF 40 NA - Fixed Fixed Fixed Fixed 0.220

18 CB-220V-ERTG8-QA10 Spare ABB S202-M-C40 TMF 40 NA - Fixed Fixed Fixed Fixed 0.220

19 CB-220V-ERTG8-QA11 Spare ABB S202-M-C32 TMF 32 NA - Fixed Fixed Fixed Fixed 0.220

20 CB-220V-ERTG8-QA12 Spare ABB S202-M-C32 TMF 32 NA - Fixed Fixed Fixed Fixed 0.220
220V MAIN LV SWITCHGEAR - MSS SS
LVCB-LVSST
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band Ixt Pickup Trip (Amps)
Phase 0.88 880 t1 9 2.5 2500 t2 0.2 OFF - -
1 CB-MSS-QF1 Power Supply Incomer ABB XT7S EKIP-LSI 1000 801.2 0.220
Ground - - - - - - - - - - -

220V MAIN LV SWITCHGEAR - MSS SS


MSS 220V LV PANEL LVCB-TMA/TMD
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-MSS-QF32 SS Lighting & Small Power ABB XT4N TMA 250 NA - 70% 175 5 1250 0.220

480V MAIN LV SWITCHGEAR - CSW SS


LVCB-LVSST
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band Ixt Pickup Trip (Amps)
Phase 1 2500 t1 3 2.8 7000 t2 0.2 OUT - -
1 CB-CSW_0.48KV-QF1 Power Supply Incomer@480V LV Panel ABB E4.2N Ekip-LSI Touch 2500 2337 0.480
Ground - - - - - - - - - - -
Phase 0.7 700 t1 12 2.5 2500 t2 0.1 - 4.5 4500
2 CB-CSW_0.48KV-QF2 Cooling Compressor-1 ABB XT6H Ekip-LS/I Dip 1000 NA 0.480
Ground - - - - - - - - - - -
Phase 0.7 700 t1 12 2.5 2500 t2 0.1 - 4.5 4500
3 CB-CSW_0.48KV-QF3 Cooling Compressor-2 ABB XT6H Ekip-LS/I Dip 1000 NA 0.480
Ground - - - - - - - - - - -
Phase 0.7 700 t1 12 2.5 2500 t2 0.1 - 4.5 4500
4 CB-CSW_0.48KV-QF4 Cooling Compressor-3 ABB XT6H Ekip-LS/I Dip 1000 NA 0.480
Ground - - - - - - - - - - -
Phase 0.7 700 t1 12 2.5 2500 t2 0.1 - 4.5 4500
5 CB-CSW_0.48KV-QF5 Spare ABB XT6H Ekip-LS/I Dip 1000 NA 0.480
Ground - - - - - - - - - - -
Phase 0.7 280 t1 12 2.5 1000 t2 0.1 - 4.5 1800
6 CB-CSW_0.48KV-QF6 Spare ABB XT5H Ekip-LS/I Dip 400 NA 0.480
Ground - - - - - - - - - - -

220V MAIN LV SWITCHGEAR - CSW SS


LVCB-LVSST
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band Ixt Pickup Trip (Amps)
Phase 0.7 700 t1 15 2.6 2600 t2 0.2 OFF - -
1 CB-CSW_0.22KV-QF1 Power Supply Incomer@220V LV Panel ABB XT7S Ekip-LSI Touch 1000 635.8 0.220
Ground - - - - - - - - - - -

220V MAIN LV SWITCHGEAR - CSW SS

CSW 220V LV PANEL LVCB-TMA/TMD

THERMAL SETTING MAGNETIC SETTING


Load Current
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps)
Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)

1 CB-CSW_0.22KV-QF2 CSW Building DB-1 ABB XT4N TMA 250 NA - 70% 175 5 1250 0.220

2 CB-CSW_0.22KV-QF3 CSW Building DB-2 ABB XT4N TMA 250 NA - 70% 175 5 1250 0.220

3 CB-CSW_0.22KV-QF4 CSW Building DB-3 ABB XT4N TMA 250 NA - 70% 175 5 1250 0.220

4 CB-CSW_0.22KV-QF5 Spare ABB XT4N TMA 250 NA - 70% 175 5 1250 0.220

5 CB-CSW_0.22KV-QF6 Spare ABB XT4N TMA 250 NA - 70% 175 5 1250 0.220

6 CB-CSW_0.22KV-QF7 Spare ABB XT2N TMD 160 NA - 70% 112 Fixed Fixed 0.220
LV REEFER SUBSTSTION 01 - REEFER LOOP 1
480V MAIN REEFER PANEL TYPE-1
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band Ix t Pickup Trip (Amps)
Phase 1 1000 t1 12 3.5 3500 t2 0.2 - - -
1 CB-RSS01-QF1 480V Main Reefer Panel Incomer-RSS01 ABB XT6N Ekip Dip-LS/I 1000 994 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS01-QF3 480V Main Reefer Panel Incomer-RP2A ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
3 CB-RSS01-QF4 480V Main Reefer Panel Incomer-RP2B ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 01 - REEFER LOOP 1


480V RP2A & RP2B PANEL REEFER SS
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function x Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band I t Pickup Trip (Amps)
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
1 CB-RSS01-RP2A-QF1 480V RP2A Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS01-RP2B-QF1 480V RP2B Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 01 - REEFER LOOP 1


480V MAIN REEFER PANEL TYPE-1
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS01-QF2 480V Capacitor Bank Incomer-RSS01 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS01-QF5 2067-GANG ROA PANEL-RSS01 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS01-QF6 2X7-GANG ROA PANEL-RSS01 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS01-QF7 1X7-GANG ROA PANEL-RSS01 - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS01-QF8 RSS01Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS01-QF9 RSS01Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS01-QF10 RSS01Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS01-QF11 RSS01Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS01-QF12 RSS01Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS01-QF13 RSS01Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 01 - REEFER LOOP 1


480V RP2A PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS01-RP2A-QF2 480V Capacitor Bank Incomer-RSS01-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS01-RP2A-QF3 2X7-GANG ROA PANEL-RSS01-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS01-RP2A-QF4 2X7-GANG ROA PANEL-RSS01-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS01-RP2A-QF5 1X7-GANG ROA PANEL-RSS01 -RP2A - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS01-RP2A-QF6 RSS01 -RP2A Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS01-RP2A-QF7 RSS01 -RP2A Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS01-RP2A-QF8 RSS01 -RP2A Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS01-RP2A-QF9 RSS01 -RP2A Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS01-RP2A-QF10 RSS01 -RP2A Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS01-RP2A-QF11 RSS01 -RP2A Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 01 - REEFER LOOP 1


480V RP2B PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS01-RP2B-QF2 480V Capacitor Bank Incomer-RSS01-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS01-RP2B-QF3 2X7-GANG ROA PANEL-RSS01-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS01-RP2B-QF4 2X7-GANG ROA PANEL-RSS01-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS01-RP2B-QF5 1X7-GANG ROA PANEL-RSS01 -RP2B - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS01-RP2B-QF6 RSS01 -RP2B Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS01-RP2B-QF7 RSS01 -RP2B Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS01-RP2B-QF8 RSS01 -RP2B Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS01-RP2B-QF9 RSS01 -RP2B Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS01-RP2B-QF10 RSS01 -RP2B Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS01-RP2B-QF11 RSS01 -RP2B Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480
LV REEFER SUBSTSTION 02 - REEFER LOOP 1
480V MAIN REEFER PANEL TYPE-1
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band Ix t Pickup Trip (Amps)
Phase 1 1000 t1 12 3.5 3500 t2 0.2 - - -
1 CB-RSS02-QF1 480V Main Reefer Panel Incomer-RSS02 ABB XT6N Ekip Dip-LS/I 1000 994 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS02-QF3 480V Main Reefer Panel Incomer-RP2A ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
3 CB-RSS02-QF4 480V Main Reefer Panel Incomer-RP2B ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 02 - REEFER LOOP 1


480V RP2A & RP2B PANEL REEFER SS
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function x Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band I t Pickup Trip (Amps)
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
1 CB-RSS02-RP2A-QF1 480V RP2A Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS02-RP2B-QF1 480V RP2B Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 02 - REEFER LOOP 1


480V MAIN REEFER PANEL TYPE-1
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS02-QF2 480V Capacitor Bank Incomer-RSS02 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS02-QF5 2067-GANG ROA PANEL-RSS02 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS02-QF6 2X7-GANG ROA PANEL-RSS02 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS02-QF7 1X7-GANG ROA PANEL-RSS02 - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS02-QF8 RSS02Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS02-QF9 RSS02Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS02-QF10 RSS02Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS02-QF11 RSS02Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS02-QF12 RSS02Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS02-QF13 RSS02Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 02 - REEFER LOOP 1


480V RP2A PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS02-RP2A-QF2 480V Capacitor Bank Incomer-RSS02-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS02-RP2A-QF3 2X7-GANG ROA PANEL-RSS02-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS02-RP2A-QF4 2X7-GANG ROA PANEL-RSS02-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS02-RP2A-QF5 1X7-GANG ROA PANEL-RSS02 -RP2A - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS02-RP2A-QF6 RSS02 -RP2A Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS02-RP2A-QF7 RSS02 -RP2A Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS02-RP2A-QF8 RSS02 -RP2A Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS02-RP2A-QF9 RSS02 -RP2A Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS02-RP2A-QF10 RSS02 -RP2A Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS02-RP2A-QF11 RSS02 -RP2A Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 02 - REEFER LOOP 1


480V RP2B PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS02-RP2B-QF2 480V Capacitor Bank Incomer-RSS02-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS02-RP2B-QF3 2X7-GANG ROA PANEL-RSS02-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS02-RP2B-QF4 2X7-GANG ROA PANEL-RSS02-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS02-RP2B-QF5 1X7-GANG ROA PANEL-RSS02 -RP2B - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS02-RP2B-QF6 RSS02 -RP2B Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS02-RP2B-QF7 RSS02 -RP2B Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS02-RP2B-QF8 RSS02 -RP2B Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS02-RP2B-QF9 RSS02 -RP2B Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS02-RP2B-QF10 RSS02 -RP2B Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS02-RP2B-QF11 RSS02 -RP2B Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480
LV REEFER SUBSTSTION 03 - REEFER LOOP 1
480V MAIN REEFER PANEL TYPE-1
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band Ix t Pickup Trip (Amps)
Phase 1 1000 t1 12 3.5 3500 t2 0.2 - - -
1 CB-RSS03-QF1 480V Main Reefer Panel Incomer-RSS02 ABB XT6N Ekip Dip-LS/I 1000 994 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS03-QF3 480V Main Reefer Panel Incomer-RP2A ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
3 CB-RSS03-QF4 480V Main Reefer Panel Incomer-RP2B ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 03 - REEFER LOOP 1


480V RP2A & RP2B PANEL REEFER SS
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function x Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band I t Pickup Trip (Amps)
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
1 CB-RSS03-RP2A-QF1 480V RP2A Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS03-RP2B-QF1 480V RP2B Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 03 - REEFER LOOP 1


480V MAIN REEFER PANEL TYPE-1
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS03-QF2 480V Capacitor Bank Incomer-RSS03 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS03-QF5 2067-GANG ROA PANEL-RSS03 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS03-QF6 2X7-GANG ROA PANEL-RSS03 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS03-QF7 1X7-GANG ROA PANEL-RSS03 - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS03-QF8 RSS03Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS03-QF9 RSS03Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS03-QF10 RSS03Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS03-QF11 RSS03Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS03-QF12 RSS03Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS03-QF13 RSS03Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 03 - REEFER LOOP 1


480V RP2A PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS03-RP2A-QF2 480V Capacitor Bank Incomer-RSS03-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS03-RP2A-QF3 2X7-GANG ROA PANEL-RSS03-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS03-RP2A-QF4 2X7-GANG ROA PANEL-RSS03-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS03-RP2A-QF5 1X7-GANG ROA PANEL-RSS03 -RP2A - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS03-RP2A-QF6 RSS03 -RP2A Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS03-RP2A-QF7 RSS03 -RP2A Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS03-RP2A-QF8 RSS03 -RP2A Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS03-RP2A-QF9 RSS03 -RP2A Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS03-RP2A-QF10 RSS03 -RP2A Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS03-RP2A-QF11 RSS03 -RP2A Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 03 - REEFER LOOP 1


480V RP2B PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS03-RP2B-QF2 480V Capacitor Bank Incomer-RSS03-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS03-RP2B-QF3 2X7-GANG ROA PANEL-RSS03-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS03-RP2B-QF4 2X7-GANG ROA PANEL-RSS03-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS03-RP2B-QF5 1X7-GANG ROA PANEL-RSS03 -RP2B - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS03-RP2B-QF6 RSS03 -RP2B Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS03-RP2B-QF7 RSS03 -RP2B Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS03-RP2B-QF8 RSS03 -RP2B Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS03-RP2B-QF9 RSS03 -RP2B Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS03-RP2B-QF10 RSS03 -RP2B Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS03-RP2B-QF11 RSS03 -RP2B Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480
LV REEFER SUBSTSTION 04 - REEFER LOOP 2
480V MAIN REEFER PANEL TYPE-1
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band Ix t Pickup Trip (Amps)
Phase 0.88 880 t1 12 3.5 3500 t2 0.2 - - -
1 CB-RSS04-QF1 480V Main Reefer Panel Incomer-RSS04 ABB XT6N Ekip Dip-LS/I 1000 782 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS04-QF3 480V Main Reefer Panel Incomer-RP2A ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 04 - REEFER LOOP 2


480V RP2A PANEL REEFER SS
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function x Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band I t Pickup Trip (Amps)
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
1 CB-RSS04-RP2A-QF1 480V RP2A Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 04 - REEFER LOOP 2


480V MAIN REEFER PANEL TYPE-1
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS04-QF2 480V Capacitor Bank Incomer-RSS04 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS04-QF5 2X7-GANG ROA PANEL-RSS04 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS04-QF6 2X7-GANG ROA PANEL-RSS04 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS04-QF7 1X7-GANG ROA PANEL-RSS04 - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS04-QF8 RSS04 Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS04-QF9 RSS04 Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS04-QF10 RSS04 Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS04-QF11 RSS04 Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS04-QF12 RSS04 Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS04-QF13 RSS04 Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 04 - REEFER LOOP 2


480V RP2A PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS04-RP2A-QF2 480V Capacitor Bank Incomer-RSS04-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS04-RP2A-QF3 2X7-GANG ROA PANEL-RSS04-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS04-RP2A-QF4 2X7-GANG ROA PANEL-RSS04-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS04-RP2A-QF5 1X7-GANG ROA PANEL-RSS04 -RP2A - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS04-RP2A-QF6 RSS04 -RP2A Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS04-RP2A-QF7 RSS04 -RP2A Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS04-RP2A-QF8 RSS04 -RP2A Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS04-RP2A-QF9 RSS04 -RP2A Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS04-RP2A-QF10 RSS04 -RP2A Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS04-RP2A-QF11 RSS04 -RP2A Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480
LV REEFER SUBSTSTION 05 - REEFER LOOP 1
480V MAIN REEFER PANEL TYPE-1
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band Ix t Pickup Trip (Amps)
Phase 1 1000 t1 12 3.5 3500 t2 0.2 - - -
1 CB-RSS05-QF1 480V Main Reefer Panel Incomer-RSS05 ABB XT6N Ekip Dip-LS/I 1000 994 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS05-QF3 480V Main Reefer Panel Incomer-RP2A ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
3 CB-RSS05-QF4 480V Main Reefer Panel Incomer-RP2B ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 05 - REEFER LOOP 1


480V RP2A & RP2B PANEL REEFER SS
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function x Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band I t Pickup Trip (Amps)
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
1 CB-RSS05-RP2A-QF1 480V RP2A Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS05-RP2B-QF1 480V RP2B Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 05 - REEFER LOOP 1


480V MAIN REEFER PANEL TYPE-1
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS05-QF2 480V Capacitor Bank Incomer-RSS05 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS05-QF5 2067-GANG ROA PANEL-RSS05 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS05-QF6 2X7-GANG ROA PANEL-RSS05 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS05-QF7 1X7-GANG ROA PANEL-RSS05 - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS05-QF8 RSS05Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS05-QF9 RSS05Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS05-QF10 RSS05Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS05-QF11 RSS05Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS05-QF12 RSS05Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS05-QF13 RSS05Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 05 - REEFER LOOP 1


480V RP2A PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS05-RP2A-QF2 480V Capacitor Bank Incomer-RSS05-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS05-RP2A-QF3 2X7-GANG ROA PANEL-RSS05-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS05-RP2A-QF4 2X7-GANG ROA PANEL-RSS05-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS05-RP2A-QF5 1X7-GANG ROA PANEL-RSS05 -RP2A - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS05-RP2A-QF6 RSS05 -RP2A Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS05-RP2A-QF7 RSS05 -RP2A Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS05-RP2A-QF8 RSS05 -RP2A Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS05-RP2A-QF9 RSS05 -RP2A Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS05-RP2A-QF10 RSS05 -RP2A Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS05-RP2A-QF11 RSS05 -RP2A Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 05 - REEFER LOOP 1


480V RP2B PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS05-RP2B-QF2 480V Capacitor Bank Incomer-RSS05-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS05-RP2B-QF3 2X7-GANG ROA PANEL-RSS05-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS05-RP2B-QF4 2X7-GANG ROA PANEL-RSS05-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS05-RP2B-QF5 1X7-GANG ROA PANEL-RSS05 -RP2B - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS05-RP2B-QF6 RSS05 -RP2B Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS05-RP2B-QF7 RSS05 -RP2B Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS05-RP2B-QF8 RSS05 -RP2B Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS05-RP2B-QF9 RSS05 -RP2B Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS05-RP2B-QF10 RSS05 -RP2B Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS05-RP2B-QF11 RSS05 -RP2B Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480
LV REEFER SUBSTSTION 06 - REEFER LOOP 1
480V MAIN REEFER PANEL TYPE-1
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band Ix t Pickup Trip (Amps)
Phase 1 1000 t1 12 3.5 3500 t2 0.2 - - -
1 CB-RSS06-QF1 480V Main Reefer Panel Incomer-RSS06 ABB XT6N Ekip Dip-LS/I 1000 994 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS06-QF3 480V Main Reefer Panel Incomer-RP2A ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
3 CB-RSS06-QF4 480V Main Reefer Panel Incomer-RP2B ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 06 - REEFER LOOP 1


480V RP2A & RP2B PANEL REEFER SS
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function x Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band I t Pickup Trip (Amps)
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
1 CB-RSS06-RP2A-QF1 480V RP2A Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS06-RP2B-QF1 480V RP2B Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 06 - REEFER LOOP 1


480V MAIN REEFER PANEL TYPE-1
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS06-QF2 480V Capacitor Bank Incomer-RSS06 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS06-QF5 2067-GANG ROA PANEL-RSS06 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS06-QF6 2X7-GANG ROA PANEL-RSS06 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS06-QF7 1X7-GANG ROA PANEL-RSS06 - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS06-QF8 RSS06 Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS06-QF9 RSS06 Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS06-QF10 RSS06 Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS06-QF11 RSS06 Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS06-QF12 RSS06 Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS06-QF13 RSS06 Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 06 - REEFER LOOP 1


480V RP2A PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS06-RP2A-QF2 480V Capacitor Bank Incomer-RSS06-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS06-RP2A-QF3 2X7-GANG ROA PANEL-RSS06-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS06-RP2A-QF4 2X7-GANG ROA PANEL-RSS06-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS06-RP2A-QF5 1X7-GANG ROA PANEL-RSS06 -RP2A - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS06-RP2A-QF6 RSS06 -RP2A Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS06-RP2A-QF7 RSS06 -RP2A Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS06-RP2A-QF8 RSS06 -RP2A Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS06-RP2A-QF9 RSS06 -RP2A Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS06-RP2A-QF10 RSS06 -RP2A Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS06-RP2A-QF11 RSS06 -RP2A Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 06 - REEFER LOOP 1


480V RP2B PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS06-RP2B-QF2 480V Capacitor Bank Incomer-RSS06-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS06-RP2B-QF3 2X7-GANG ROA PANEL-RSS06-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS06-RP2B-QF4 2X7-GANG ROA PANEL-RSS06-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS06-RP2B-QF5 1X7-GANG ROA PANEL-RSS06 -RP2B - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS06-RP2B-QF6 RSS06 -RP2B Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS06-RP2B-QF7 RSS06 -RP2B Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS06-RP2B-QF8 RSS06 -RP2B Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS06-RP2B-QF9 RSS06 -RP2B Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS06-RP2B-QF10 RSS06 -RP2B Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS06-RP2B-QF11 RSS06 -RP2B Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480
LV REEFER SUBSTSTION 07 - REEFER LOOP 1
480V MAIN REEFER PANEL TYPE-1
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band Ix t Pickup Trip (Amps)
Phase 1 1000 t1 12 3.5 3500 t2 0.2 - - -
1 CB-RSS07-QF1 480V Main Reefer Panel Incomer-RSS07 ABB XT6N Ekip Dip-LS/I 1000 994 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS07-QF3 480V Main Reefer Panel Incomer-RP2A ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
3 CB-RSS07-QF4 480V Main Reefer Panel Incomer-RP2B ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 07 - REEFER LOOP 1


480V RP2A & RP2B PANEL REEFER SS
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function x Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band I t Pickup Trip (Amps)
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
1 CB-RSS07-RP2A-QF1 480V RP2A Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS07-RP2B-QF1 480V RP2B Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 07 - REEFER LOOP 1


480V MAIN REEFER PANEL TYPE-1
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS07-QF2 480V Capacitor Bank Incomer-RSS07 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS07-QF5 2X7-GANG ROA PANEL-RSS07 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS07-QF6 2X7-GANG ROA PANEL-RSS07 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS07-QF7 1X7-GANG ROA PANEL-RSS07 - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS07-QF8 RSS07 Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS07-QF9 RSS07 Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS07-QF10 RSS07 Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS07-QF11 RSS07 Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS07-QF12 RSS07 Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS07-QF13 RSS07 Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 07 - REEFER LOOP 1


480V RP2A PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS07-RP2A-QF2 480V Capacitor Bank Incomer-RSS07-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS07-RP2A-QF3 2X7-GANG ROA PANEL-RSS07-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS07-RP2A-QF4 2X7-GANG ROA PANEL-RSS07-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS07-RP2A-QF5 1X7-GANG ROA PANEL-RSS07 -RP2A - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS07-RP2A-QF6 RSS07 -RP2A Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS07-RP2A-QF7 RSS07 -RP2A Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS07-RP2A-QF8 RSS07 -RP2A Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS07-RP2A-QF9 RSS07 -RP2A Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS07-RP2A-QF10 RSS07 -RP2A Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS07-RP2A-QF11 RSS07 -RP2A Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 07 - REEFER LOOP 1


480V RP2B PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS07-RP2B-QF2 480V Capacitor Bank Incomer-RSS07-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS07-RP2B-QF3 2X7-GANG ROA PANEL-RSS07-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS07-RP2B-QF4 2X7-GANG ROA PANEL-RSS07-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS07-RP2B-QF5 1X7-GANG ROA PANEL-RSS07 -RP2B - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS07-RP2B-QF6 RSS07 -RP2B Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS07-RP2B-QF7 RSS07 -RP2B Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS07-RP2B-QF8 RSS07 -RP2B Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS07-RP2B-QF9 RSS07 -RP2B Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS07-RP2B-QF10 RSS07 -RP2B Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS07-RP2B-QF11 RSS07 -RP2B Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480
LV REEFER SUBSTSTION 08 - REEFER LOOP 2
480V MAIN REEFER PANEL TYPE-1
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band Ix t Pickup Trip (Amps)
Phase 0.88 880 t1 12 3.5 3500 t2 0.2 - - -
1 CB-RSS08-QF1 480V Main Reefer Panel Incomer-RSS08 ABB XT6N Ekip Dip-LS/I 1000 782 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS08-QF3 480V Main Reefer Panel Incomer-RP2A ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 08 - REEFER LOOP 2


480V RP2A PANEL REEFER SS
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function x Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band I t Pickup Trip (Amps)
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
1 CB-RSS08-RP2A-QF1 480V RP2A Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 08 - REEFER LOOP 2


480V MAIN REEFER PANEL TYPE-1
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS08-QF2 480V Capacitor Bank Incomer-RSS08 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS08-QF5 2X7-GANG ROA PANEL-RSS08 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS08-QF6 2X7-GANG ROA PANEL-RSS08 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS08-QF7 1X7-GANG ROA PANEL-RSS08 - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS08-QF8 RSS08 Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS08-QF9 RSS08 Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS08-QF10 RSS08 Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS08-QF11 RSS08 Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS08-QF12 RSS08 Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS08-QF13 RSS08 Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 08 - REEFER LOOP 2


480V RP2A PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS08-RP2A-QF2 480V Capacitor Bank Incomer-RSS08-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS08-RP2A-QF3 2X7-GANG ROA PANEL-RSS08-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS08-RP2A-QF4 2X7-GANG ROA PANEL-RSS08-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS08-RP2A-QF5 1X7-GANG ROA PANEL-RSS08 -RP2A - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS08-RP2A-QF6 RSS08 -RP2A Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS08-RP2A-QF7 RSS08 -RP2A Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS08-RP2A-QF8 RSS08 -RP2A Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS08-RP2A-QF9 RSS08 -RP2A Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS08-RP2A-QF10 RSS08 -RP2A Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS08-RP2A-QF11 RSS08 -RP2A Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480
LV REEFER SUBSTSTION 09 - REEFER LOOP 1
480V MAIN REEFER PANEL TYPE-1
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band Ix t Pickup Trip (Amps)
Phase 1 1000 t1 12 3.5 3500 t2 0.2 - - -
1 CB-RSS09-QF1 480V Main Reefer Panel Incomer-RSS09 ABB XT6N Ekip Dip-LS/I 1000 994 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS09-QF3 480V Main Reefer Panel Incomer-RP2A ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
3 CB-RSS09-QF4 480V Main Reefer Panel Incomer-RP2B ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 09 - REEFER LOOP 1


480V RP2A & RP2B PANEL REEFER SS
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function x Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band I t Pickup Trip (Amps)
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
1 CB-RSS09-RP2A-QF1 480V RP2A Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS09-RP2B-QF1 480V RP2B Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 09 - REEFER LOOP 1


480V MAIN REEFER PANEL TYPE-1
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS09-QF2 480V Capacitor Bank Incomer-RSS09 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS09-QF5 2067-GANG ROA PANEL-RSS09 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS09-QF6 2X7-GANG ROA PANEL-RSS09 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS09-QF7 1X7-GANG ROA PANEL-RSS09 - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS09-QF8 RSS09Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS09-QF9 RSS09Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS09-QF10 RSS09Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS09-QF11 RSS09Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS09-QF12 RSS09Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS09-QF13 RSS09Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 09 - REEFER LOOP 1


480V RP2A PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS09-RP2A-QF2 480V Capacitor Bank Incomer-RSS09-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS09-RP2A-QF3 2X7-GANG ROA PANEL-RSS09-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS09-RP2A-QF4 2X7-GANG ROA PANEL-RSS09-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS09-RP2A-QF5 1X7-GANG ROA PANEL-RSS09 -RP2A - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS09-RP2A-QF6 RSS09 -RP2A Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS09-RP2A-QF7 RSS09 -RP2A Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS09-RP2A-QF8 RSS09 -RP2A Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS09-RP2A-QF9 RSS09 -RP2A Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS09-RP2A-QF10 RSS09 -RP2A Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS09-RP2A-QF11 RSS09 -RP2A Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 09 - REEFER LOOP 1


480V RP2B PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS09-RP2B-QF2 480V Capacitor Bank Incomer-RSS09-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS09-RP2B-QF3 2X7-GANG ROA PANEL-RSS09-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS09-RP2B-QF4 2X7-GANG ROA PANEL-RSS09-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS09-RP2B-QF5 1X7-GANG ROA PANEL-RSS09 -RP2B - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS09-RP2B-QF6 RSS09 -RP2B Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS09-RP2B-QF7 RSS09 -RP2B Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS09-RP2B-QF8 RSS09 -RP2B Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS09-RP2B-QF9 RSS09 -RP2B Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS09-RP2B-QF10 RSS09 -RP2B Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS09-RP2B-QF11 RSS09 -RP2B Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480
LV REEFER SUBSTSTION 10 - REEFER LOOP 1
480V MAIN REEFER PANEL TYPE-1
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band Ix t Pickup Trip (Amps)
Phase 1 1000 t1 12 3.5 3500 t2 0.2 - - -
1 CB-RSS10-QF1 480V Main Reefer Panel Incomer-RSS10 ABB XT6N Ekip Dip-LS/I 1000 994 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS10-QF3 480V Main Reefer Panel Incomer-RP2A ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
3 CB-RSS10-QF4 480V Main Reefer Panel Incomer-RP2B ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 10 - REEFER LOOP 1


480V RP2A & RP2B PANEL REEFER SS
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function x Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band I t Pickup Trip (Amps)
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
1 CB-RSS10-RP2A-QF1 480V RP2A Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS10-RP2B-QF1 480V RP2B Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 10 - REEFER LOOP 1


480V MAIN REEFER PANEL TYPE-1
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS10-QF2 480V Capacitor Bank Incomer-RSS10 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS10-QF5 2X7-GANG ROA PANEL-RSS10 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS10-QF6 2X7-GANG ROA PANEL-RSS10 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS10-QF7 1X7-GANG ROA PANEL-RSS10 - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS10-QF8 RSS10 Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS10-QF9 RSS10 Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS10-QF10 RSS10 Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS10-QF11 RSS10 Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS10-QF12 RSS10 Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS10-QF13 RSS10 Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 10 - REEFER LOOP 1


480V RP2A PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS10-RP2A-QF2 480V Capacitor Bank Incomer-RSS10-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS10-RP2A-QF3 2X7-GANG ROA PANEL-RSS10-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS10-RP2A-QF4 2X7-GANG ROA PANEL-RSS10-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS10-RP2A-QF5 1X7-GANG ROA PANEL-RSS10 -RP2A - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS10-RP2A-QF6 RSS10 -RP2A Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS10-RP2A-QF7 RSS10 -RP2A Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS10-RP2A-QF8 RSS10 -RP2A Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS10-RP2A-QF9 RSS10 -RP2A Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS10-RP2A-QF10 RSS10 -RP2A Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS10-RP2A-QF11 RSS10 -RP2A Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 10 - REEFER LOOP 1


480V RP2B PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS10-RP2B-QF2 480V Capacitor Bank Incomer-RSS10-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS10-RP2B-QF3 2X7-GANG ROA PANEL-RSS10-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS10-RP2B-QF4 2X7-GANG ROA PANEL-RSS10-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS10-RP2B-QF5 1X7-GANG ROA PANEL-RSS10 -RP2B - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS10-RP2B-QF6 RSS10 -RP2B Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS10-RP2B-QF7 RSS10 -RP2B Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS10-RP2B-QF8 RSS10 -RP2B Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS10-RP2B-QF9 RSS10 -RP2B Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS10-RP2B-QF10 RSS10 -RP2B Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS10-RP2B-QF11 RSS10 -RP2B Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480
LV REEFER SUBSTSTION 11 - REEFER LOOP 1
480V MAIN REEFER PANEL TYPE-1
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band Ix t Pickup Trip (Amps)
Phase 1 1000 t1 12 3.5 3500 t2 0.2 - - -
1 CB-RSS11-QF1 480V Main Reefer Panel Incomer-RSS11 ABB XT6N Ekip Dip-LS/I 1000 994 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS11-QF3 480V Main Reefer Panel Incomer-RP2A ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
3 CB-RSS11-QF4 480V Main Reefer Panel Incomer-RP2B ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 11 - REEFER LOOP 1


480V RP2A & RP2B PANEL REEFER SS
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function x Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band I t Pickup Trip (Amps)
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
1 CB-RSS11-RP2A-QF1 480V RP2A Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS11-RP2B-QF1 480V RP2B Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 11 - REEFER LOOP 1


480V MAIN REEFER PANEL TYPE-1
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS11-QF2 480V Capacitor Bank Incomer-RSS11 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS11-QF5 2X7-GANG ROA PANEL-RSS11 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS11-QF6 2X7-GANG ROA PANEL-RSS11 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS11-QF7 1X7-GANG ROA PANEL-RSS11 - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS11-QF8 RSS11 Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS11-QF9 RSS11 Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS11-QF10 RSS11 Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS11-QF11 RSS11 Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS11-QF12 RSS11 Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS11-QF13 RSS11 Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 11 - REEFER LOOP 1


480V RP2A PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS11-RP2A-QF2 480V Capacitor Bank Incomer-RSS11-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS11-RP2A-QF3 2X7-GANG ROA PANEL-RSS11-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS11-RP2A-QF4 2X7-GANG ROA PANEL-RSS11-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS11-RP2A-QF5 1X7-GANG ROA PANEL-RSS11 -RP2A - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS11-RP2A-QF6 RSS11 -RP2A Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS11-RP2A-QF7 RSS11 -RP2A Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS11-RP2A-QF8 RSS11 -RP2A Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS11-RP2A-QF9 RSS11 -RP2A Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS11-RP2A-QF10 RSS11 -RP2A Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS11-RP2A-QF11 RSS11 -RP2A Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 11 - REEFER LOOP 1


480V RP2B PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS11-RP2B-QF2 480V Capacitor Bank Incomer-RSS11-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS11-RP2B-QF3 2X7-GANG ROA PANEL-RSS11-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS11-RP2B-QF4 2X7-GANG ROA PANEL-RSS11-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS11-RP2B-QF5 1X7-GANG ROA PANEL-RSS11 -RP2B - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS11-RP2B-QF6 RSS11 -RP2B Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS11-RP2B-QF7 RSS11 -RP2B Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS11-RP2B-QF8 RSS11 -RP2B Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS11-RP2B-QF9 RSS11 -RP2B Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS11-RP2B-QF10 RSS11 -RP2B Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS11-RP2B-QF11 RSS11 -RP2B Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480
LV REEFER SUBSTSTION 12 - REEFER LOOP 2
480V MAIN REEFER PANEL TYPE-1
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band Ix t Pickup Trip (Amps)
Phase 0.88 880 t1 12 3.5 3500 t2 0.2 - - -
1 CB-RSS12-QF1 480V Main Reefer Panel Incomer-RSS12 ABB XT6N Ekip Dip-LS/I 1000 782 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS12-QF3 480V Main Reefer Panel Incomer-RP2A ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 12 - REEFER LOOP 2


480V RP2A PANEL REEFER SS
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function x Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band I t Pickup Trip (Amps)
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
1 CB-RSS12-RP2A-QF1 480V RP2A Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 12 - REEFER LOOP 2


480V MAIN REEFER PANEL TYPE-1
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS12-QF2 480V Capacitor Bank Incomer-RSS12 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS12-QF5 2X7-GANG ROA PANEL-RSS12 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS12-QF6 2X7-GANG ROA PANEL-RSS12 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS12-QF7 1X7-GANG ROA PANEL-RSS12 - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS12-QF8 RSS12 Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS12-QF9 RSS12 Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS12-QF10 RSS12 Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS12-QF11 RSS12 Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS12-QF12 RSS12 Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS12-QF13 RSS12 Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 12 - REEFER LOOP 2


480V RP2A PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS12-RP2A-QF2 480V Capacitor Bank Incomer-RSS12-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS12-RP2A-QF3 2X7-GANG ROA PANEL-RSS12-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS12-RP2A-QF4 2X7-GANG ROA PANEL-RSS12-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS12-RP2A-QF5 1X7-GANG ROA PANEL-RSS12 -RP2A - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS12-RP2A-QF6 RSS12 -RP2A Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS12-RP2A-QF7 RSS12 -RP2A Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS12-RP2A-QF8 RSS12 -RP2A Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS12-RP2A-QF9 RSS12 -RP2A Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS12-RP2A-QF10 RSS12 -RP2A Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS12-RP2A-QF11 RSS12 -RP2A Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480
LV REEFER SUBSTSTION 13 - REEFER LOOP 2
480V MAIN REEFER PANEL TYPE-1
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band Ix t Pickup Trip (Amps)
Phase 1 1000 t1 12 3.5 3500 t2 0.2 - - -
1 CB-RSS13-QF1 480V Main Reefer Panel Incomer-RSS13 ABB XT6N Ekip Dip-LS/I 1000 994 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS13-QF3 480V Main Reefer Panel Incomer-RP2A ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
3 CB-RSS13-QF4 480V Main Reefer Panel Incomer-RP2B ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 13 - REEFER LOOP 2


480V RP2A & RP2B PANEL REEFER SS
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function x Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band I t Pickup Trip (Amps)
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
1 CB-RSS13-RP2A-QF1 480V RP2A Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS13-RP2B-QF1 480V RP2B Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 13 - REEFER LOOP 2


480V MAIN REEFER PANEL TYPE-1
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS13-QF2 480V Capacitor Bank Incomer-RSS13 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS13-QF5 2067-GANG ROA PANEL-RSS13 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS13-QF6 2X7-GANG ROA PANEL-RSS13 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS13-QF7 1X7-GANG ROA PANEL-RSS13 - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS13-QF8 RSS13Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS13-QF9 RSS13Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS13-QF10 RSS13Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS13-QF11 RSS13Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS13-QF12 RSS13Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS13-QF13 RSS13Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 13 - REEFER LOOP 2


480V RP2A PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS13-RP2A-QF2 480V Capacitor Bank Incomer-RSS13-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS13-RP2A-QF3 2X7-GANG ROA PANEL-RSS13-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS13-RP2A-QF4 2X7-GANG ROA PANEL-RSS13-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS13-RP2A-QF5 1X7-GANG ROA PANEL-RSS13 -RP2A - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS13-RP2A-QF6 RSS13 -RP2A Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS13-RP2A-QF7 RSS13 -RP2A Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS13-RP2A-QF8 RSS13 -RP2A Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS13-RP2A-QF9 RSS13 -RP2A Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS13-RP2A-QF10 RSS13 -RP2A Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS13-RP2A-QF11 RSS13 -RP2A Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 13 - REEFER LOOP 2


480V RP2B PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS13-RP2B-QF2 480V Capacitor Bank Incomer-RSS13-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS13-RP2B-QF3 2X7-GANG ROA PANEL-RSS13-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS13-RP2B-QF4 2X7-GANG ROA PANEL-RSS13-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS13-RP2B-QF5 1X7-GANG ROA PANEL-RSS13 -RP2B - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS13-RP2B-QF6 RSS13 -RP2B Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS13-RP2B-QF7 RSS13 -RP2B Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS13-RP2B-QF8 RSS13 -RP2B Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS13-RP2B-QF9 RSS13 -RP2B Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS13-RP2B-QF10 RSS13 -RP2B Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS13-RP2B-QF11 RSS13 -RP2B Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480
LV REEFER SUBSTSTION 14 - REEFER LOOP 2
480V MAIN REEFER PANEL TYPE-1
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band Ix t Pickup Trip (Amps)
Phase 1 1000 t1 12 3.5 3500 t2 0.2 - - -
1 CB-RSS14-QF1 480V Main Reefer Panel Incomer-RSS14 ABB XT6N Ekip Dip-LS/I 1000 994 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS14-QF3 480V Main Reefer Panel Incomer-RP2A ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
3 CB-RSS14-QF4 480V Main Reefer Panel Incomer-RP2B ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 14 - REEFER LOOP 2


480V RP2A & RP2B PANEL REEFER SS
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function x Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band I t Pickup Trip (Amps)
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
1 CB-RSS14-RP2A-QF1 480V RP2A Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS14-RP2B-QF1 480V RP2B Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 14 - REEFER LOOP 2


480V MAIN REEFER PANEL TYPE-1
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS14-QF2 480V Capacitor Bank Incomer-RSS14 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS14-QF5 2067-GANG ROA PANEL-RSS14 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS14-QF6 2X7-GANG ROA PANEL-RSS14 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS14-QF7 1X7-GANG ROA PANEL-RSS14 - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS14-QF8 RSS14Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS14-QF9 RSS14Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS14-QF10 RSS14Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS14-QF11 RSS14Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS14-QF12 RSS14Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS14-QF13 RSS14Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 14 - REEFER LOOP 2


480V RP2A PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS14-RP2A-QF2 480V Capacitor Bank Incomer-RSS14-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS14-RP2A-QF3 2X7-GANG ROA PANEL-RSS14-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS14-RP2A-QF4 2X7-GANG ROA PANEL-RSS14-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS14-RP2A-QF5 1X7-GANG ROA PANEL-RSS14 -RP2A - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS14-RP2A-QF6 RSS14 -RP2A Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS14-RP2A-QF7 RSS14 -RP2A Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS14-RP2A-QF8 RSS14 -RP2A Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS14-RP2A-QF9 RSS14 -RP2A Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS14-RP2A-QF10 RSS14 -RP2A Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS14-RP2A-QF11 RSS14 -RP2A Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 14 - REEFER LOOP 2


480V RP2B PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS14-RP2B-QF2 480V Capacitor Bank Incomer-RSS14-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS14-RP2B-QF3 2X7-GANG ROA PANEL-RSS14-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS14-RP2B-QF4 2X7-GANG ROA PANEL-RSS14-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS14-RP2B-QF5 1X7-GANG ROA PANEL-RSS14 -RP2B - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS14-RP2B-QF6 RSS14 -RP2B Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS14-RP2B-QF7 RSS14 -RP2B Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS14-RP2B-QF8 RSS14 -RP2B Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS14-RP2B-QF9 RSS14 -RP2B Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS14-RP2B-QF10 RSS14 -RP2B Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS14-RP2B-QF11 RSS14 -RP2B Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480
LV REEFER SUBSTSTION 15 - REEFER LOOP 2
480V MAIN REEFER PANEL TYPE-1
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band Ix t Pickup Trip (Amps)
Phase 1 1000 t1 12 3.5 3500 t2 0.2 - - -
1 CB-RSS15-QF1 480V Main Reefer Panel Incomer-RSS15 ABB XT6N Ekip Dip-LS/I 1000 994 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS15-QF3 480V Main Reefer Panel Incomer-RP2A ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
3 CB-RSS15-QF4 480V Main Reefer Panel Incomer-RP2B ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 15 - REEFER LOOP 2


480V RP2A & RP2B PANEL REEFER SS
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function x Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band I t Pickup Trip (Amps)
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
1 CB-RSS15-RP2A-QF1 480V RP2A Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS15-RP2B-QF1 480V RP2B Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 15 - REEFER LOOP 2


480V MAIN REEFER PANEL TYPE-1
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS15-QF2 480V Capacitor Bank Incomer-RSS15 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS15-QF5 2067-GANG ROA PANEL-RSS15 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS15-QF6 2X7-GANG ROA PANEL-RSS15 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS15-QF7 1X7-GANG ROA PANEL-RSS15 - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS15-QF8 RSS15Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS15-QF9 RSS15Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS15-QF10 RSS15Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS15-QF11 RSS15Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS15-QF12 RSS15Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS15-QF13 RSS15Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 15 - REEFER LOOP 2


480V RP2A PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS15-RP2A-QF2 480V Capacitor Bank Incomer-RSS15-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS15-RP2A-QF3 2X7-GANG ROA PANEL-RSS15-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS15-RP2A-QF4 2X7-GANG ROA PANEL-RSS15-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS15-RP2A-QF5 1X7-GANG ROA PANEL-RSS15-RP2A - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS15-RP2A-QF6 RSS15 -RP2A Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS15-RP2A-QF7 RSS15 -RP2A Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS15-RP2A-QF8 RSS15 -RP2A Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS15-RP2A-QF9 RSS15 -RP2A Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS15-RP2A-QF10 RSS15 -RP2A Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS15-RP2A-QF11 RSS15 -RP2A Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 15 - REEFER LOOP 2


480V RP2B PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS15-RP2B-QF2 480V Capacitor Bank Incomer-RSS15-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS15-RP2B-QF3 2X7-GANG ROA PANEL-RSS15-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS15-RP2B-QF4 2X7-GANG ROA PANEL-RSS15-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS15-RP2B-QF5 1X7-GANG ROA PANEL-RSS15 -RP2B - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS15-RP2B-QF6 RSS15 -RP2B Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS15-RP2B-QF7 RSS15 -RP2B Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS15-RP2B-QF8 RSS15 -RP2B Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS15-RP2B-QF9 RSS15 -RP2B Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS15-RP2B-QF10 RSS15 -RP2B Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS15-RP2B-QF11 RSS15 -RP2B Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480
LV REEFER SUBSTSTION 16 - REEFER LOOP 2
480V MAIN REEFER PANEL TYPE-1
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band Ix t Pickup Trip (Amps)
Phase 1 1000 t1 12 3.5 3500 t2 0.2 - - -
1 CB-RSS16-QF1 480V Main Reefer Panel Incomer-RSS16 ABB XT6N Ekip Dip-LS/I 1000 994 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS16-QF3 480V Main Reefer Panel Incomer-RP2A ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
3 CB-RSS16-QF4 480V Main Reefer Panel Incomer-RP2B ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 16 - REEFER LOOP 2


480V RP2A & RP2B PANEL REEFER SS
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function x Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band I t Pickup Trip (Amps)
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
1 CB-RSS16-RP2A-QF1 480V RP2A Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS16-RP2B-QF1 480V RP2B Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 16 - REEFER LOOP 2


480V MAIN REEFER PANEL TYPE-1
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS16-QF2 480V Capacitor Bank Incomer-RSS16 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS16-QF5 2067-GANG ROA PANEL-RSS16 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS16-QF6 2X7-GANG ROA PANEL-RSS16 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS16-QF7 1X7-GANG ROA PANEL-RSS16 - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS16-QF8 RSS16Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS16-QF9 RSS16Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS16-QF10 RSS16Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS16-QF11 RSS16Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS16-QF12 RSS16Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS16-QF13 RSS16Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 16 - REEFER LOOP 2


480V RP2A PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS16-RP2A-QF2 480V Capacitor Bank Incomer-RSS16-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS16-RP2A-QF3 2X7-GANG ROA PANEL-RSS16-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS16-RP2A-QF4 2X7-GANG ROA PANEL-RSS16-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS16-RP2A-QF5 1X7-GANG ROA PANEL-RSS16 -RP2A - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS16-RP2A-QF6 RSS16 -RP2A Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS16-RP2A-QF7 RSS16 -RP2A Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS16-RP2A-QF8 RSS16 -RP2A Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS16-RP2A-QF9 RSS16 -RP2A Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS16-RP2A-QF10 RSS16 -RP2A Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS16-RP2A-QF11 RSS16 -RP2A Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 16 - REEFER LOOP 2


480V RP2B PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS16-RP2B-QF2 480V Capacitor Bank Incomer-RSS16-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS16-RP2B-QF3 2X7-GANG ROA PANEL-RSS16-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS16-RP2B-QF4 2X7-GANG ROA PANEL-RSS16-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS16-RP2B-QF5 1X7-GANG ROA PANEL-RSS16 -RP2B - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS16-RP2B-QF6 RSS16 -RP2B Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS16-RP2B-QF7 RSS16 -RP2B Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS16-RP2B-QF8 RSS16 -RP2B Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS16-RP2B-QF9 RSS16 -RP2B Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS16-RP2B-QF10 RSS16 -RP2B Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS16-RP2B-QF11 RSS16 -RP2B Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480
LV REEFER SUBSTSTION 17 - REEFER LOOP 3
480V MAIN REEFER PANEL TYPE-1
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band Ix t Pickup Trip (Amps)
Phase 1 1000 t1 12 3.5 3500 t2 0.2 - - -
1 CB-RSS17-QF1 480V Main Reefer Panel Incomer-RSS17 ABB XT6N Ekip Dip-LS/I 1000 994 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS17-QF3 480V Main Reefer Panel Incomer-RP2A ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
3 CB-RSS17-QF4 480V Main Reefer Panel Incomer-RP2B ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 17 - REEFER LOOP 3


480V RP2A & RP2B PANEL REEFER SS
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function x Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band I t Pickup Trip (Amps)
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
1 CB-RSS17-RP2A-QF1 480V RP2A Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS17-RP2B-QF1 480V RP2B Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 17 - REEFER LOOP 3


480V MAIN REEFER PANEL TYPE-1
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS17-QF2 480V Capacitor Bank Incomer-RSS17 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS17-QF5 2X7-GANG ROA PANEL-RSS17 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS17-QF6 2X7-GANG ROA PANEL-RSS17 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS17-QF7 1X7-GANG ROA PANEL-RSS17 - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS17-QF8 RSS17 Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS17-QF9 RSS17 Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS17-QF10 RSS17 Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS17-QF11 RSS17 Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS17-QF12 RSS17 Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS17-QF13 RSS17 Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 17 - REEFER LOOP 3


480V RP2A PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS17-RP2A-QF2 480V Capacitor Bank Incomer-RSS17-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS17-RP2A-QF3 2X7-GANG ROA PANEL-RSS17-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS17-RP2A-QF4 2X7-GANG ROA PANEL-RSS17-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS17-RP2A-QF5 1X7-GANG ROA PANEL-RSS17 -RP2A - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS17-RP2A-QF6 RSS17 -RP2A Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS17-RP2A-QF7 RSS17 -RP2A Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS17-RP2A-QF8 RSS17 -RP2A Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS17-RP2A-QF9 RSS17 -RP2A Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS17-RP2A-QF10 RSS17 -RP2A Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS17-RP2A-QF11 RSS17 -RP2A Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 17 - REEFER LOOP 3


480V RP2B PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS17-RP2B-QF2 480V Capacitor Bank Incomer-RSS17-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS17-RP2B-QF3 2X7-GANG ROA PANEL-RSS17-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS17-RP2B-QF4 2X7-GANG ROA PANEL-RSS17-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS17-RP2B-QF5 1X7-GANG ROA PANEL-RSS17 -RP2B - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS17-RP2B-QF6 RSS17 -RP2B Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS17-RP2B-QF7 RSS17 -RP2B Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS17-RP2B-QF8 RSS17 -RP2B Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS17-RP2B-QF9 RSS17 -RP2B Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS17-RP2B-QF10 RSS17 -RP2B Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS17-RP2B-QF11 RSS17 -RP2B Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480
LV REEFER SUBSTSTION 18 - REEFER LOOP 3
480V MAIN REEFER PANEL TYPE-1
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band Ix t Pickup Trip (Amps)
Phase 1 1000 t1 12 3.5 3500 t2 0.2 - - -
1 CB-RSS18-QF1 480V Main Reefer Panel Incomer-RSS18 ABB XT6N Ekip Dip-LS/I 1000 994 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS18-QF3 480V Main Reefer Panel Incomer-RP2A ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
3 CB-RSS18-QF4 480V Main Reefer Panel Incomer-RP2B ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 18 - REEFER LOOP 3


480V RP2A & RP2B PANEL REEFER SS
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function x Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band I t Pickup Trip (Amps)
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
1 CB-RSS18-RP2A-QF1 480V RP2A Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS18-RP2B-QF1 480V RP2B Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 18 - REEFER LOOP 3


480V MAIN REEFER PANEL TYPE-1
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS18-QF2 480V Capacitor Bank Incomer-RSS18 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS18-QF5 2X7-GANG ROA PANEL-RSS18 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS18-QF6 2X7-GANG ROA PANEL-RSS18 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS18-QF7 1X7-GANG ROA PANEL-RSS18 - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS18-QF8 RSS18 Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS18-QF9 RSS18 Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS18-QF10 RSS18 Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS18-QF11 RSS18 Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS18-QF12 RSS18 Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS18-QF13 RSS18 Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 18 - REEFER LOOP 3


480V RP2A PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS18-RP2A-QF2 480V Capacitor Bank Incomer-RSS18-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS18-RP2A-QF3 2X7-GANG ROA PANEL-RSS18-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS18-RP2A-QF4 2X7-GANG ROA PANEL-RSS18-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS18-RP2A-QF5 1X7-GANG ROA PANEL-RSS18 -RP2A - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS18-RP2A-QF6 RSS18 -RP2A Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS18-RP2A-QF7 RSS18 -RP2A Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS18-RP2A-QF8 RSS18 -RP2A Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS18-RP2A-QF9 RSS18 -RP2A Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS18-RP2A-QF10 RSS18 -RP2A Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS18-RP2A-QF11 RSS18 -RP2A Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 18 - REEFER LOOP 3


480V RP2B PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS18-RP2B-QF2 480V Capacitor Bank Incomer-RSS18-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS18-RP2B-QF3 2X7-GANG ROA PANEL-RSS18-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS18-RP2B-QF4 2X7-GANG ROA PANEL-RSS18-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS18-RP2B-QF5 1X7-GANG ROA PANEL-RSS18 -RP2B - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS18-RP2B-QF6 RSS18 -RP2B Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS18-RP2B-QF7 RSS18 -RP2B Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS18-RP2B-QF8 RSS18 -RP2B Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS18-RP2B-QF9 RSS18 -RP2B Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS18-RP2B-QF10 RSS18 -RP2B Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS18-RP2B-QF11 RSS18 -RP2B Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480
LV REEFER SUBSTSTION 19 - REEFER LOOP 2
480V MAIN REEFER PANEL TYPE-1
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band Ix t Pickup Trip (Amps)
Phase 1 1000 t1 12 3.5 3500 t2 0.2 - - -
1 CB-RSS19-QF1 480V Main Reefer Panel Incomer-RSS15 ABB XT6N Ekip Dip-LS/I 1000 994 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS19-QF3 480V Main Reefer Panel Incomer-RP2A ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
3 CB-RSS19-QF4 480V Main Reefer Panel Incomer-RP2B ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
4 CB-RSS19-QF5 480V Main Reefer Panel Incomer-RP2C ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 19 - REEFER LOOP 2


480V RP2A & RP2B PANEL REEFER SS
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function x Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band I t Pickup Trip (Amps)
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
1 CB-RSS19-RP2A-QF1 480V RP2A Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS19-RP2B-QF1 480V RP2B Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
3 CB-RSS19-RP2C-QF1 480V RP2C Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 19 - REEFER LOOP 2


480V MAIN REEFER PANEL TYPE-1
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS19-QF2 480V Capacitor Bank Incomer-RSS19 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS19-QF6 2067-GANG ROA PANEL-RSS19 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS19-QF7 2X7-GANG ROA PANEL-RSS19 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS19-QF8 1X7-GANG ROA PANEL-RSS19 - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS19-QF9 RSS19Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS19-QF10 RSS19Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS19-QF11 RSS19Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS19-QF12 RSS19Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS19-QF13 RSS19Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS19-QF14 RSS19Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 19 - REEFER LOOP 2


480V RP2A PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS19-RP2A-QF2 480V Capacitor Bank Incomer-RSS19-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS19-RP2A-QF3 2X7-GANG ROA PANEL-RSS19-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS19-RP2A-QF4 2X7-GANG ROA PANEL-RSS19-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS19-RP2A-QF5 1X7-GANG ROA PANEL-RSS19-RP2A - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS19-RP2A-QF6 RSS19 -RP2A Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS19-RP2A-QF7 RSS19 -RP2A Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS19-RP2A-QF8 RSS19 -RP2A Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS19-RP2A-QF9 RSS19 -RP2A Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS19-RP2A-QF10 RSS19 -RP2A Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS19-RP2A-QF11 RSS19 -RP2A Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 19 - REEFER LOOP 2


480V RP2B PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS19-RP2B-QF2 480V Capacitor Bank Incomer-RSS19-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS19-RP2B-QF3 2X7-GANG ROA PANEL-RSS19-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS19-RP2B-QF4 2X7-GANG ROA PANEL-RSS19-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS19-RP2B-QF5 1X7-GANG ROA PANEL-RSS19 -RP2B - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS19-RP2B-QF6 RSS19 -RP2B Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS19-RP2B-QF7 RSS19 -RP2B Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS19-RP2B-QF8 RSS19 -RP2B Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS19-RP2B-QF9 RSS19 -RP2B Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS19-RP2B-QF10 RSS19 -RP2B Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS19-RP2B-QF11 RSS19 -RP2B Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 19 - REEFER LOOP 2


480V RP2C PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS19-RP2C-QF2 480V Capacitor Bank Incomer-RSS19-RP2C ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS19-RP2C-QF3 2X7-GANG ROA PANEL-RSS19-RP2C ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS19-RP2C-QF4 2X7-GANG ROA PANEL-RSS19-RP2C ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS19-RP2C-QF5 1X7-GANG ROA PANEL-RSS19 -RP2C - Spare ABB XT1S TMA 100 - - - - - - 0.480
5 CB-RSS19-RP2C-QF6 RSS19 -RP2C Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS19-RP2C-QF7 RSS19 -RP2C Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS19-RP2C-QF8 RSS19 -RP2C Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS19-RP2C-QF9 RSS19 -RP2C Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS19-RP2C-QF10 RSS19 -RP2C Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS19-RP2C-QF11 RSS19 -RP2C Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480
LV REEFER SUBSTSTION 20 - REEFER LOOP 2
480V MAIN REEFER PANEL TYPE-1
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band Ix t Pickup Trip (Amps)
Phase 1 1000 t1 12 3.5 3500 t2 0.2 - - -
1 CB-RSS20-QF1 480V Main Reefer Panel Incomer-RSS20 ABB XT6N Ekip Dip-LS/I 1000 994 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS20-QF3 480V Main Reefer Panel Incomer-RP2A ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
3 CB-RSS20-QF4 480V Main Reefer Panel Incomer-RP2B ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 20 - REEFER LOOP 2


480V RP2A & RP2B PANEL REEFER SS
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function x Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band I t Pickup Trip (Amps)
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
1 CB-RSS20-RP2A-QF1 480V RP2A Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS20-RP2B-QF1 480V RP2B Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 20 - REEFER LOOP 2


480V MAIN REEFER PANEL TYPE-1
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS20-QF2 480V Capacitor Bank Incomer-RSS20 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS20-QF5 2067-GANG ROA PANEL-RSS20 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS20-QF6 2X7-GANG ROA PANEL-RSS20 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS20-QF7 1X7-GANG ROA PANEL-RSS20 - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS20-QF8 RSS20Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS20-QF9 RSS20Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS20-QF10 RSS20Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS20-QF11 RSS20Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS20-QF12 RSS20Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS20-QF13 RSS20Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 20 - REEFER LOOP 2


480V RP2A PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS20-RP2A-QF2 480V Capacitor Bank Incomer-RSS20-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS20-RP2A-QF3 2X7-GANG ROA PANEL-RSS20-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS20-RP2A-QF4 2X7-GANG ROA PANEL-RSS20-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS20-RP2A-QF5 1X7-GANG ROA PANEL-RSS20 -RP2A - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS20-RP2A-QF6 RSS20 -RP2A Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS20-RP2A-QF7 RSS20 -RP2A Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS20-RP2A-QF8 RSS20 -RP2A Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS20-RP2A-QF9 RSS20 -RP2A Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS20-RP2A-QF10 RSS20 -RP2A Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS20-RP2A-QF11 RSS20 -RP2A Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 20 - REEFER LOOP 2


480V RP2B PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS20-RP2B-QF2 480V Capacitor Bank Incomer-RSS20-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS20-RP2B-QF3 2X7-GANG ROA PANEL-RSS20-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS20-RP2B-QF4 2X7-GANG ROA PANEL-RSS20-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS20-RP2B-QF5 1X7-GANG ROA PANEL-RSS20 -RP2B - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS20-RP2B-QF6 RSS20 -RP2B Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS20-RP2B-QF7 RSS20 -RP2B Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS20-RP2B-QF8 RSS20 -RP2B Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS20-RP2B-QF9 RSS20 -RP2B Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS20-RP2B-QF10 RSS20 -RP2B Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS20-RP2B-QF11 RSS20 -RP2B Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480
LV REEFER SUBSTSTION 21 - REEFER LOOP 3
480V MAIN REEFER PANEL TYPE-1
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band Ix t Pickup Trip (Amps)
Phase 1 1000 t1 12 3.5 3500 t2 0.2 - - -
1 CB-RSS21-QF1 480V Main Reefer Panel Incomer-RSS21 ABB XT6N Ekip Dip-LS/I 1000 994 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS21-QF3 480V Main Reefer Panel Incomer-RP2A ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
3 CB-RSS21-QF4 480V Main Reefer Panel Incomer-RP2B ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 21 - REEFER LOOP 3


480V RP2A & RP2B PANEL REEFER SS
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function x Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band I t Pickup Trip (Amps)
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
1 CB-RSS21-RP2A-QF1 480V RP2A Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS21-RP2B-QF1 480V RP2B Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 21 - REEFER LOOP 3


480V MAIN REEFER PANEL TYPE-1
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS21-QF2 480V Capacitor Bank Incomer-RSS21 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS21-QF5 2X7-GANG ROA PANEL-RSS21 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS21-QF6 2X7-GANG ROA PANEL-RSS21 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS21-QF7 1X7-GANG ROA PANEL-RSS21 - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS21-QF8 RSS21 Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS21-QF9 RSS21 Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS21-QF10 RSS21 Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS21-QF11 RSS21 Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS21-QF12 RSS21 Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS21-QF13 RSS21 Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 21 - REEFER LOOP 3


480V RP2A PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS21-RP2A-QF2 480V Capacitor Bank Incomer-RSS21-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS21-RP2A-QF3 2X7-GANG ROA PANEL-RSS21-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS21-RP2A-QF4 2X7-GANG ROA PANEL-RSS21-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS21-RP2A-QF5 1X7-GANG ROA PANEL-RSS21 -RP2A - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS21-RP2A-QF6 RSS21 -RP2A Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS21-RP2A-QF7 RSS21 -RP2A Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS21-RP2A-QF8 RSS21 -RP2A Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS21-RP2A-QF9 RSS21 -RP2A Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS21-RP2A-QF10 RSS21 -RP2A Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS21-RP2A-QF11 RSS21 -RP2A Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 21 - REEFER LOOP 3


480V RP2B PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS21-RP2B-QF2 480V Capacitor Bank Incomer-RSS21-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS21-RP2B-QF3 2X7-GANG ROA PANEL-RSS21-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS21-RP2B-QF4 2X7-GANG ROA PANEL-RSS21-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS21-RP2B-QF5 1X7-GANG ROA PANEL-RSS21 -RP2B - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS21-RP2B-QF6 RSS21 -RP2B Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS21-RP2B-QF7 RSS21 -RP2B Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS21-RP2B-QF8 RSS21 -RP2B Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS21-RP2B-QF9 RSS21 -RP2B Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS21-RP2B-QF10 RSS21 -RP2B Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS21-RP2B-QF11 RSS21 -RP2B Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480
LV REEFER SUBSTSTION 22 - REEFER LOOP 3
480V MAIN REEFER PANEL TYPE-1
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band Ix t Pickup Trip (Amps)
Phase 1 1000 t1 12 3.5 3500 t2 0.2 - - -
1 CB-RSS22-QF1 480V Main Reefer Panel Incomer-RSS22 ABB XT6N Ekip Dip-LS/I 1000 994 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS22-QF3 480V Main Reefer Panel Incomer-RP2A ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
3 CB-RSS22-QF4 480V Main Reefer Panel Incomer-RP2B ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 22 - REEFER LOOP 3


480V RP2A & RP2B PANEL REEFER SS
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function x Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band I t Pickup Trip (Amps)
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
1 CB-RSS22-RP2A-QF1 480V RP2A Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS22-RP2B-QF1 480V RP2B Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 22 - REEFER LOOP 3


480V MAIN REEFER PANEL TYPE-1
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS22-QF2 480V Capacitor Bank Incomer-RSS22 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS22-QF5 2X7-GANG ROA PANEL-RSS22 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS22-QF6 2X7-GANG ROA PANEL-RSS22 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS22-QF7 1X7-GANG ROA PANEL-RSS22 - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS22-QF8 RSS22 Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS22-QF9 RSS22 Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS22-QF10 RSS22 Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS22-QF11 RSS22 Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS22-QF12 RSS22 Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS22-QF13 RSS22 Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 22 - REEFER LOOP 3


480V RP2A PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS22-RP2A-QF2 480V Capacitor Bank Incomer-RSS22-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS22-RP2A-QF3 2X7-GANG ROA PANEL-RSS22-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS22-RP2A-QF4 2X7-GANG ROA PANEL-RSS22-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS22-RP2A-QF5 1X7-GANG ROA PANEL-RSS22 -RP2A - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS22-RP2A-QF6 RSS22 -RP2A Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS22-RP2A-QF7 RSS22 -RP2A Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS22-RP2A-QF8 RSS22 -RP2A Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS22-RP2A-QF9 RSS22 -RP2A Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS22-RP2A-QF10 RSS22 -RP2A Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS22-RP2A-QF11 RSS22 -RP2A Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 22 - REEFER LOOP 3


480V RP2B PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS22-RP2B-QF2 480V Capacitor Bank Incomer-RSS22-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS22-RP2B-QF3 2X7-GANG ROA PANEL-RSS22-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS22-RP2B-QF4 2X7-GANG ROA PANEL-RSS22-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS22-RP2B-QF5 1X7-GANG ROA PANEL-RSS22 -RP2B - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS22-RP2B-QF6 RSS22 -RP2B Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS22-RP2B-QF7 RSS22 -RP2B Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS22-RP2B-QF8 RSS22 -RP2B Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS22-RP2B-QF9 RSS22 -RP2B Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS22-RP2B-QF10 RSS22 -RP2B Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS22-RP2B-QF11 RSS22 -RP2B Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480
LV REEFER SUBSTSTION 23 - REEFER LOOP 2
480V MAIN REEFER PANEL TYPE-1
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band Ix t Pickup Trip (Amps)
Phase 1 1000 t1 12 3.5 3500 t2 0.2 - - -
1 CB-RSS23-QF1 480V Main Reefer Panel Incomer-RSS15 ABB XT6N Ekip Dip-LS/I 1000 994 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS23-QF3 480V Main Reefer Panel Incomer-RP2A ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
3 CB-RSS23-QF4 480V Main Reefer Panel Incomer-RP2B ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
4 CB-RSS23-QF5 480V Main Reefer Panel Incomer-RP2C ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 23 - REEFER LOOP 2


480V RP2A & RP2B PANEL REEFER SS
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function x Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band I t Pickup Trip (Amps)
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
1 CB-RSS23-RP2A-QF1 480V RP2A Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS23-RP2B-QF1 480V RP2B Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
3 CB-RSS23-RP2C-QF1 480V RP2C Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 23 - REEFER LOOP 2


480V MAIN REEFER PANEL TYPE-1
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS23-QF2 480V Capacitor Bank Incomer-RSS23 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS23-QF6 2067-GANG ROA PANEL-RSS23 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS23-QF7 2X7-GANG ROA PANEL-RSS23 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS23-QF8 1X7-GANG ROA PANEL-RSS23 - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS23-QF9 RSS23Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS23-QF10 RSS23Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS23-QF11 RSS23Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS23-QF12 RSS23Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS23-QF13 RSS23Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS23-QF14 RSS23Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 23 - REEFER LOOP 2


480V RP2A PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS23-RP2A-QF2 480V Capacitor Bank Incomer-RSS23-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS23-RP2A-QF3 2X7-GANG ROA PANEL-RSS23-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS23-RP2A-QF4 2X7-GANG ROA PANEL-RSS23-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS23-RP2A-QF5 1X7-GANG ROA PANEL-RSS23-RP2A - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS23-RP2A-QF6 RSS23 -RP2A Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS23-RP2A-QF7 RSS23 -RP2A Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS23-RP2A-QF8 RSS23 -RP2A Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS23-RP2A-QF9 RSS23 -RP2A Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS23-RP2A-QF10 RSS23 -RP2A Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS23-RP2A-QF11 RSS23 -RP2A Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 23 - REEFER LOOP 2


480V RP2B PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS23-RP2B-QF2 480V Capacitor Bank Incomer-RSS23-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS23-RP2B-QF3 2X7-GANG ROA PANEL-RSS23-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS23-RP2B-QF4 2X7-GANG ROA PANEL-RSS23-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS23-RP2B-QF5 1X7-GANG ROA PANEL-RSS23 -RP2B - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS23-RP2B-QF6 RSS23 -RP2B Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS23-RP2B-QF7 RSS23 -RP2B Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS23-RP2B-QF8 RSS23 -RP2B Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS23-RP2B-QF9 RSS23 -RP2B Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS23-RP2B-QF10 RSS23 -RP2B Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS23-RP2B-QF11 RSS23 -RP2B Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 23 - REEFER LOOP 2


480V RP2C PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS23-RP2C-QF2 480V Capacitor Bank Incomer-RSS23-RP2C ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS23-RP2C-QF3 2X7-GANG ROA PANEL-RSS23-RP2C ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS23-RP2C-QF4 2X7-GANG ROA PANEL-RSS23-RP2C ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS23-RP2C-QF5 1X7-GANG ROA PANEL-RSS23 -RP2C - Spare ABB XT1S TMA 100 - - - - - - 0.480
LV REEFER SUBSTSTION 24 - REEFER LOOP 3
480V MAIN REEFER PANEL TYPE-1
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band Ix t Pickup Trip (Amps)
Phase 1 1000 t1 12 3.5 3500 t2 0.2 - - -
1 CB-RSS24-QF1 480V Main Reefer Panel Incomer-RSS24 ABB XT6N Ekip Dip-LS/I 1000 994 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS24-QF3 480V Main Reefer Panel Incomer-RP2A ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
3 CB-RSS24-QF4 480V Main Reefer Panel Incomer-RP2B ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 24 - REEFER LOOP 3


480V RP2A & RP2B PANEL REEFER SS
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function x Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band I t Pickup Trip (Amps)
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
1 CB-RSS24-RP2A-QF1 480V RP2A Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS24-RP2B-QF1 480V RP2B Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 24 - REEFER LOOP 3


480V MAIN REEFER PANEL TYPE-1
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS24-QF2 480V Capacitor Bank Incomer-RSS24 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS24-QF5 2X7-GANG ROA PANEL-RSS24 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS24-QF6 2X7-GANG ROA PANEL-RSS24 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS24-QF7 1X7-GANG ROA PANEL-RSS24 - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS24-QF8 RSS24 Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS24-QF9 RSS24 Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS24-QF10 RSS24 Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS24-QF11 RSS24 Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS24-QF12 RSS24 Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS24-QF13 RSS24 Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 24 - REEFER LOOP 3


480V RP2A PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS24-RP2A-QF2 480V Capacitor Bank Incomer-RSS24-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS24-RP2A-QF3 2X7-GANG ROA PANEL-RSS24-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS24-RP2A-QF4 2X7-GANG ROA PANEL-RSS24-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS24-RP2A-QF5 1X7-GANG ROA PANEL-RSS24 -RP2A - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS24-RP2A-QF6 RSS24 -RP2A Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS24-RP2A-QF7 RSS24 -RP2A Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS24-RP2A-QF8 RSS24 -RP2A Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS24-RP2A-QF9 RSS24 -RP2A Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS24-RP2A-QF10 RSS24 -RP2A Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS24-RP2A-QF11 RSS24 -RP2A Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 24 - REEFER LOOP 3


480V RP2B PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS24-RP2B-QF2 480V Capacitor Bank Incomer-RSS24-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS24-RP2B-QF3 2X7-GANG ROA PANEL-RSS24-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS24-RP2B-QF4 2X7-GANG ROA PANEL-RSS24-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS24-RP2B-QF5 1X7-GANG ROA PANEL-RSS24 -RP2B - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS24-RP2B-QF6 RSS24 -RP2B Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS24-RP2B-QF7 RSS24 -RP2B Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS24-RP2B-QF8 RSS24 -RP2B Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS24-RP2B-QF9 RSS24 -RP2B Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS24-RP2B-QF10 RSS24 -RP2B Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS24-RP2B-QF11 RSS24 -RP2B Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480
5 CB-RSS23-RP2C-QF6 RSS23 -RP2C Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS23-RP2C-QF7 RSS23 -RP2C Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS23-RP2C-QF8 RSS23 -RP2C Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS23-RP2C-QF9 RSS23 -RP2C Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS23-RP2C-QF10 RSS23 -RP2C Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS23-RP2C-QF11 RSS23 -RP2C Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480
LV REEFER SUBSTSTION 25 - REEFER LOOP 3
480V MAIN REEFER PANEL TYPE-1
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band Ix t Pickup Trip (Amps)
Phase 1 1000 t1 12 3.5 3500 t2 0.2 - - -
1 CB-RSS25-QF1 480V Main Reefer Panel Incomer-RSS25 ABB XT6N Ekip Dip-LS/I 1000 994 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS25-QF3 480V Main Reefer Panel Incomer-RP2A ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
3 CB-RSS25-QF4 480V Main Reefer Panel Incomer-RP2B ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 25 - REEFER LOOP 3


480V RP2A & RP2B PANEL REEFER SS
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function x Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band I t Pickup Trip (Amps)
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
1 CB-RSS25-RP2A-QF1 480V RP2A Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS25-RP2B-QF1 480V RP2B Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 25 - REEFER LOOP 3


480V MAIN REEFER PANEL TYPE-1
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS25-QF2 480V Capacitor Bank Incomer-RSS25 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS25-QF5 2X7-GANG ROA PANEL-RSS25 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS25-QF6 2X7-GANG ROA PANEL-RSS25 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS25-QF7 1X7-GANG ROA PANEL-RSS25 - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS25-QF8 RSS25 Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS25-QF9 RSS25 Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS25-QF10 RSS25 Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS25-QF11 RSS25 Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS25-QF12 RSS25 Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS25-QF13 RSS25 Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 25 - REEFER LOOP 3


480V RP2A PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS25-RP2A-QF2 480V Capacitor Bank Incomer-RSS25-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS25-RP2A-QF3 2X7-GANG ROA PANEL-RSS25-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS25-RP2A-QF4 2X7-GANG ROA PANEL-RSS25-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS25-RP2A-QF5 1X7-GANG ROA PANEL-RSS25 -RP2A - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS25-RP2A-QF6 RSS25 -RP2A Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS25-RP2A-QF7 RSS25 -RP2A Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS25-RP2A-QF8 RSS25 -RP2A Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS25-RP2A-QF9 RSS25 -RP2A Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS25-RP2A-QF10 RSS25 -RP2A Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS25-RP2A-QF11 RSS25 -RP2A Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 25 - REEFER LOOP 3


480V RP2B PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS25-RP2B-QF2 480V Capacitor Bank Incomer-RSS25-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS25-RP2B-QF3 2X7-GANG ROA PANEL-RSS25-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS25-RP2B-QF4 2X7-GANG ROA PANEL-RSS25-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS25-RP2B-QF5 1X7-GANG ROA PANEL-RSS25 -RP2B - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS25-RP2B-QF6 RSS25 -RP2B Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS25-RP2B-QF7 RSS25 -RP2B Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS25-RP2B-QF8 RSS25 -RP2B Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS25-RP2B-QF9 RSS25 -RP2B Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS25-RP2B-QF10 RSS25 -RP2B Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS25-RP2B-QF11 RSS25 -RP2B Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480
LV REEFER SUBSTSTION 26 - REEFER LOOP 3
480V MAIN REEFER PANEL TYPE-1
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band Ix t Pickup Trip (Amps)
Phase 1 1000 t1 12 3.5 3500 t2 0.2 - - -
1 CB-RSS26-QF1 480V Main Reefer Panel Incomer-RSS26 ABB XT6N Ekip Dip-LS/I 1000 994 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS26-QF3 480V Main Reefer Panel Incomer-RP2A ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
3 CB-RSS26-QF4 480V Main Reefer Panel Incomer-RP2B ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 26 - REEFER LOOP 3


480V RP2A & RP2B PANEL REEFER SS
Load Current Long-Time Short-Time Instantaeous
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function x Base kV
(Amps) Pickup Setting Trip (Amps) Band Label Band Pickup Setting Trip (Amps) Band Label Band I t Pickup Trip (Amps)
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
1 CB-RSS26-RP2A-QF1 480V RP2A Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -
Phase 0.8 504 t1 36 3 1890 t2 0.1 - - -
2 CB-RSS26-RP2B-QF1 480V RP2B Panel Incomer ABB XT5N Ekip Dip-LS/I 630 391 0.480
Ground - - - - - - - - - - -

LV REEFER SUBSTSTION 26 - REEFER LOOP 3


480V MAIN REEFER PANEL TYPE-1
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS26-QF2 480V Capacitor Bank Incomer-RSS26 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS26-QF5 2X7-GANG ROA PANEL-RSS26 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS26-QF6 2X7-GANG ROA PANEL-RSS26 ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS26-QF7 1X7-GANG ROA PANEL-RSS26 - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS26-QF8 RSS26 Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS26-QF9 RSS26 Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS26-QF10 RSS26 Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS26-QF11 RSS26 Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS26-QF12 RSS26 Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS26-QF13 RSS26 Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 26 - REEFER LOOP 3


480V RP2A PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS26-RP2A-QF2 480V Capacitor Bank Incomer-RSS26-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS26-RP2A-QF3 2X7-GANG ROA PANEL-RSS26-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS26-RP2A-QF4 2X7-GANG ROA PANEL-RSS26-RP2A ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS26-RP2A-QF5 1X7-GANG ROA PANEL-RSS26 -RP2A - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS26-RP2A-QF6 RSS26 -RP2A Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS26-RP2A-QF7 RSS26 -RP2A Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS26-RP2A-QF8 RSS26 -RP2A Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS26-RP2A-QF9 RSS26 -RP2A Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS26-RP2A-QF10 RSS26 -RP2A Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS26-RP2A-QF11 RSS26 -RP2A Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

LV REEFER SUBSTSTION 26 - REEFER LOOP 3


480V RP2B PANEL REEFER SS
Load Current THERMAL SETTING MAGNETIC SETTING
S,NO LVCB ID Consumer Designation Manufacturer Relay Model Trip Device Model Amps (In) Function Base kV
(Amps) Pickup Setting Trip (Amps) Pickup Setting Trip (Amps)
1 CB-RSS26-RP2B-QF2 480V Capacitor Bank Incomer-RSS26-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

2 CB-RSS26-RP2B-QF3 2X7-GANG ROA PANEL-RSS26-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

3 CB-RSS26-RP2B-QF4 2X7-GANG ROA PANEL-RSS26-RP2B ABB XT4S TMA 250 150.37 - 70% 175 5 1250 0.480

4 CB-RSS26-RP2B-QF5 1X7-GANG ROA PANEL-RSS26 -RP2B - Spare ABB XT1S TMA 100 - - - - - - 0.480

5 CB-RSS26-RP2B-QF6 RSS26 -RP2B Capacitor Bank - C1 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

6 CB-RSS26-RP2B-QF7 RSS26 -RP2B Capacitor Bank - C2 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

7 CB-RSS26-RP2B-QF8 RSS26 -RP2B Capacitor Bank - C3 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

8 CB-RSS26-RP2B-QF9 RSS26 -RP2B Capacitor Bank - C4 ABB XT1H 160 TMD 50 30 - 70% 35 Fixed Fixed 0.480

9 CB-RSS26-RP2B-QF10 RSS26 -RP2B Capacitor Bank - C5 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480

10 CB-RSS26-RP2B-QF11 RSS26 -RP2B Capacitor Bank - C6 ABB XT1H 160 TMD 50 15 - 70% 35 Fixed Fixed 0.480
Document Tile Document No. Revision Date Page No.
RELAY COORDINATION &
ABB-TEC-CAL-035 V2 21-March-2024 78 of 85
PROTECTION STUDY

Annexure-10

Overall Single Line Diagram for MV System


THIS DOCUMENT/DRAWING IS THE PROPERTY OF PAABB VER. DATE DESCRIPTION DRA. REV. APP. PROJECT: CONTENT: DATE: PAGE:
AND PARTS THEREOF MUST NOT BE REPRODUCED OR V0 11.01.2021 FOR APPROVAL MI SRL MG OCTOBER/2021 1/1
COPIED WITHOUT PAABB WRITTEN PERMISSION, AND
THE CONTENTS THEREOF MUST NOT BE IMPARTED TO A
V1 12.04.2021 FOR APPROVAL MI SRL MG PUERTO BOLÍVAR PORT EXPANSION OVERALL SINGLE LINE DIAGRAM FOR SCALE:
NTS
DRAWING
SIZE: A0
VERSION:

V3
V2 15.07.2021 CHANGE OF LAYOUT FROM THE CUSTOMER RT SRL MG
THIRD PARTY NOR BE USED FOR ANY UNAUTHORIZED
PURPOSE. V3 12.10.2021 CABLE SIZE AND VA RATINGS UPDATED RT SRL MG EPC - PHASE 1 MV SYSTEM DRAWING NO:
ABB-TEC-DGR-003
Document Tile Document No. Revision Date Page No.
RELAY COORDINATION &
ABB-TEC-CAL-035 V2 21-March-2024 80 of 85
PROTECTION STUDY

Annexure-11

Overall Single Line Diagram for LV System


THIS DOCUMENT/DRAWING IS THE PROPERTY VER. DATE DESCRIPTION DRA. REV. APP. PROJECT: CONTENT: DATE: PAGE:
OF PAABB AND PARTS THEREOF MUST NOT BE V0 11.01.2021 FOR APPROVAL MI PP MG JULY/2021 1/5
REPRODUCED OR COPIED WITHOUT PAABB V1 15.04.2021 FOR APPROVAL MI PP MG PUERTO BOLÍVAR PORT SINGLE LINE DIAGRAM - SCALE: DRAWING VERSION:
WRITTEN PERMISSION, AND THE CONTENTS NTS SIZE: A3
THEREOF MUST NOT BE IMPARTED TO A
THIRD PARTY NOR BE USED FOR ANY
UNAUTHORIZED PURPOSE.
V2 15.07.2021 CHANGE OF LAYOUT FROM THE CUSTOMER RT PP MG
EXPANSION EPC - PHASE 1 LV DISTRIBUTION
MAIN SUBSTATION
DRAWING NO:
ABB-TEC-DGR-004
V2
THIS DOCUMENT/DRAWING IS THE PROPERTY VER. DATE DESCRIPTION DRA. REV. APP. PROJECT: CONTENT: DATE: PAGE:
OF PAABB AND PARTS THEREOF MUST NOT BE V0 11.01.2021 FOR APPROVAL MI PP MG JULY/2021 2/5
REPRODUCED OR COPIED WITHOUT PAABB V1 15.04.2021 FOR APPROVAL MI PP MG PUERTO BOLÍVAR PORT SINGLE LINE DIAGRAM - SCALE: DRAWING VERSION:
WRITTEN PERMISSION, AND THE CONTENTS NTS SIZE: A3
THEREOF MUST NOT BE IMPARTED TO A
THIRD PARTY NOR BE USED FOR ANY
UNAUTHORIZED PURPOSE.
V2 15.07.2021 CHANGE OF LAYOUT FROM THE CUSTOMER RT PP MG
EXPANSION EPC - PHASE 1 LV DISTRIBUTION
REEFER SUBSTATION (TYPICAL)
DRAWING NO:
ABB-TEC-DGR-004
V2
THIS DOCUMENT/DRAWING IS THE PROPERTY VER. DATE DESCRIPTION DRA. REV. APP. PROJECT: CONTENT: DATE: PAGE:
OF PAABB AND PARTS THEREOF MUST NOT BE V0 11.01.2021 FOR APPROVAL MI PP MG JULY/2021 3/5
REPRODUCED OR COPIED WITHOUT PAABB V1 15.04.2021 FOR APPROVAL MI PP MG PUERTO BOLÍVAR PORT SINGLE LINE DIAGRAM - SCALE: DRAWING VERSION:
WRITTEN PERMISSION, AND THE CONTENTS NTS SIZE: A3
THEREOF MUST NOT BE IMPARTED TO A
THIRD PARTY NOR BE USED FOR ANY
UNAUTHORIZED PURPOSE.
V2 15.07.2021 CHANGE OF LAYOUT FROM THE CUSTOMER RT PP MG
EXPANSION EPC - PHASE 1 LV DISTRIBUTION
ERTG SUBSTATION (TYPICAL)
DRAWING NO:
ABB-TEC-DGR-004
V2
THIS DOCUMENT/DRAWING IS THE PROPERTY VER. DATE DESCRIPTION DRA. REV. APP. PROJECT: CONTENT: DATE: PAGE:
OF PAABB AND PARTS THEREOF MUST NOT BE V0 11.01.2021 FOR APPROVAL MI PP MG JULY/2021 4/5
REPRODUCED OR COPIED WITHOUT PAABB V1 15.04.2021 FOR APPROVAL MI PP MG PUERTO BOLÍVAR PORT SINGLE LINE DIAGRAM - SCALE: DRAWING VERSION:
WRITTEN PERMISSION, AND THE CONTENTS NTS SIZE: A3
THEREOF MUST NOT BE IMPARTED TO A
THIRD PARTY NOR BE USED FOR ANY
UNAUTHORIZED PURPOSE.
V2 15.07.2021 CHANGE OF LAYOUT FROM THE CUSTOMER RT PP MG
EXPANSION EPC - PHASE 1 LV DISTRIBUTION
STS SUBSTATION
DRAWING NO:
ABB-TEC-DGR-004
V2
THIS DOCUMENT/DRAWING IS THE PROPERTY VER. DATE DESCRIPTION DRA. REV. APP. PROJECT: CONTENT: DATE: PAGE:
OF PAABB AND PARTS THEREOF MUST NOT BE V0 11.01.2021 FOR APPROVAL MI PP MG JULY/2021 5/5
REPRODUCED OR COPIED WITHOUT PAABB V1 15.04.2021 FOR APPROVAL MI PP MG PUERTO BOLÍVAR PORT SINGLE LINE DIAGRAM - SCALE: DRAWING VERSION:
WRITTEN PERMISSION, AND THE CONTENTS NTS SIZE: A3
THEREOF MUST NOT BE IMPARTED TO A
THIRD PARTY NOR BE USED FOR ANY
UNAUTHORIZED PURPOSE.
V2 15.07.2021 CHANGE OF LAYOUT FROM THE CUSTOMER RT PP MG
EXPANSION EPC - PHASE 1 LV DISTRIBUTION
CSW SUBSTATION
DRAWING NO:
ABB-TEC-DGR-004
V2