HEAT DISSIPATION DATA FOR TRANSFORMER RADIATORS

5 2 0 mm W I D E

Cooling WATTS DISSIPATED PER SECTION FOR OIL EXCESS


Center surface TEMPERATURE OF Weight Oil Per
distance Per 35°C 40°C 45°C 50°C 55°C 60°C per section
L1 section section in
ONA ONA ONA ONA ONA ONA ONA ONA ONA
Mm m2 ONAN ONAF ONAN kg Liters
F N F N F N F N F
500 0.58 176 297 224 379 278 470 332 561 395 668 456 771 5.55 1.93
600 0.70 203 343 251 424 304 514 355 600 415 702 465 786 6.55 2.22
700 0.84 231 390 280 473 333 563 387 654 450 761 510 862 7.55 2.52
800 0.96 259 437 308 521 361 611 415 701 478 808 520 879 8.55 2.82
900 1.08 288 486 328 554 378 639 426 720 500 845 532 900 9.55 3.12
1000 1.20 316 533 364 615 411 695 462 781 522 883 548 927 10.55 3.42
1100 1.32 342 577 391 661 444 751 498 842 561 949 626 1058 11.55 3.70
1200 1.45 364 614 422 713 477 807 537 908 606 1025 673 1138 12.55 3.99
1300 1.56 391 660 452 764 511 864 572 967 646 1092 719 1216 13.55 4.28
1400 1.68 414 699 479 810 540 913 608 1028 684 1156 760 1285 14.55 4.55
1500 1.80 434 733 507 857 570 964 621 1049 723 1222 801 1354 15.55 4.83
1600 1.93 459 775 532 899 600 1014 673 1137 759 1283 840 1420 16.55 5.11
1700 2.05 479 809 557 941 628 1062 706 1193 792 1339 880 1488 17.55 5.40
1800 2.16 502 847 582 984 656 1109 734 1240 829 1402 915 1547 18.55 5.68
1900 2.30 523 883 610 1031 684 1156 766 1295 862 1457 953 1611 19.55 5.98
2000 2.41 545 920 631 1066 709 1199 795 1344 896 1515 987 1669 20.55 6.26
2100 2.53 563 950 654 1105 736 1244 825 1394 921 1557 1024 1731 21.55 6.54
2200 2.64 582 982 678 1146 762 1288 851 1438 959 1621 1057 1787 22.55 6.82
2300 2.77 603 1018 702 1186 786 1329 881 1489 991 1675 1091 1844 23.55 7.10
2400 2.90 628 1060 724 1224 814 1376 907 1533 1017 1719 1127 1905 24.55 7.39
2500 3.01 645 1089 744 1257 837 1415 936 1582 1046 1768 1156 1954 25.55 7.67
2600 3.13 666 1124 764 1291 816 1380 963 1627 1069 1807 1190 2012 26.55 7.95
2700 3.25 682 1151 786 1328 886 1498 990 1673 1105 1868 1223 2067 27.55 8.25
2800 3.38 704 1188 807 1364 911 1540 1021 1725 1135 1919 1256 2123 28.55 8.53
2900 3.49 721 1217 829 1401 933 1577 1044 1764 1163 1966 1286 2174 29.55 8.81
3000 3.62 744 1256 851 1438 988 1670 1082 1829 1193 2017 1355 2290 30.55 9.09

CORRECTION FACTOR
Vertical distance in mm between 0 100 200 300 400 500 600 800 1000
Core center line and radiator center line.
Correction Factor K1 0.80 0.850 0.890 0.925 0.950 0.975 1.00 1.05 1.10

Horizontal distance between radiators : 575 600 625 650 675 700
Correction Factor K2 0.888 0.916 0.953 0.977 0.989 1.00

No. of sections per radiator : 3 4-5 6-8 9-11 12-14 15-17 18-20 21-24 25-28
Correction Factor K3 1.11 1.06 1.02 1.0 0.95 0.90 0.84 0.82 0.80