Electrical data Multi-turn actuators for open-close duty with DC motors of type range VK
Short-time duty S2 - 15 min 24 V DC

Multi-turn actuator Motor

Overcurrent AUMA
Nominal Nominal Max. Starting protection power class
Output speed Max. torque power1) Speed current2) current3) current device setting switchgear
Type [rpm] [Nm] Motor type PN [kW] [rpm] IN [A] Imax [A] IA [A] [A] Contactor
4 – 5.5 4.5 5–6 25 6 A2
VKX0063-4-0,02G 0.02 1,800
6 – 7.5 4.5 5–7 25 7 A2
7.5 – 11 6.0 9 –12 25 12 A2
SAEx 07.2 30 VKX0063-4-0,04G 0.04 1,600
10 – 15.5 6.0 10 – 13 25 13 A2
12.5 – 17 6.0 13 –15 40 15 A2
VKX0063-2-0,06G 0.06 2,700
17 – 23.5 6.0 14 – 16 40 16 A2
3.5 – 5.5 5.0 9 – 12 25 12 A2
VKX0063-4-0,03G 0.03 1,700
5 – 7.5 5.0 10 – 13 25 13 A2
60
6–8 6.0 10 – 11.5 40 11.5 A2
SAEx 07.6 VKX0063-2-0,07G 0.07 2,700
8 – 11 6.0 11 – 13 40 13 A2
12 – 17 6.5 13 – 15 40 15 A2
40 VKX0063-2-0,07G 0.07 2,700
16 – 23.5 6.5 14 – 16 40 16 A2

Notes on table
1) Nominal power PN Mechanical power output at motor shaft at run torque of multi-turn actuator (corresponds to approx. 35 % of
maximum torque).
2) Nominal current IN Current at run torque
3) Max. current Imax Current at maximum torque

Notes on installation and sizing


Motor data Motor data is approximate. Due to usual manufacturing tolerances, there may be deviations from the values
given.
Motor type The DC motors are designed as shunt motors.
Motor protection To protect against overheating, thermoswitches are embedded in the motor.

Actuators without integral actuator controls (AUMA NORM):


Thermoswitches have to be considered within the external controls (refer to terminal plan).
Note: Failure to connect thermoswitches shall void the warranty for the motor.
According to EN 60079-14, a thermal overcurrent protection device (e.g. motor protection switch)
must be installed for explosion-proof actuators in addition to the thermoswitches.
AC current DC current
250 V, 50 – 60 Hz 60 V 1.0 A
cos j = 1 2.5 A 42 V 1.2 A
cos j = 0.6 1.6 A 24 V 1.5 A

Actuators with AC integral actuator controls:


Thermal motor protection is already integrated.
Switchgear sizing For motor operation, reversing contactors (mechanically, electrically and electronically locked) can be used.

Actuators without integral actuator controls (AUMA NORM):


Switchgear are supplied by the customer. We recommend specification of switchgear suitable for their rated
operating currents in compliance with the assigned AUMA power class.

Switchgear assignment to AUMA power classes:


DC shunt motor, motor type VK:
AUMA Reversing contactor
power class Rated operating current acc. to EN 60947-4
Utilization category DC-3
A2 30 A

Actuators with ACExC integral controls:


Required switchgear in power class A2 are directly integrated in the ACExC actuator controls.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y008.125/003/en Issue 1.19 Page 1/1