ISO 5802:2001

a) Ideal pd distribution NOTE Also satisfactory for flow into fan inlets, but may be
unsatisfactory for flow into inlet boxes; may produce swirl in
boxes.

b) Goodpoint
Appendix B.2 ISO 5802- Retangular measure pd distribution

NOTE More than 75 % of pd readings greater than NOTE Less than 75 % of pd readings greater than
pdmax /10 (unsatisfactory for flow into fan inlets or inlet boxes). pdmax /10 (unsatisfactory for flow into fan inlets or inlet boxes).

c) Satisfactory pd distribution d) Unsatisfactory pd distribution

NOTE Less than 75 % of pd readings greater than NOTE Less than 75 % of pd readings greater than
pdmax /10 (unsatisfactory for flow into fan inlets or inlet boxes). pdmax /10 (unsatisfactory for flow into fan inlets or inlet boxes).

e) Unsatisfactory pd distribution f) Unsatisfactory pd distribution

Figure 9 — Typical dynamic pressure distributions encountered in dynamic pressure measurement planes
in fan system installations