Task:
A constant torque drive system has to be dimensioned with 1LA motor a
SINAMICS G120 drive.
Explanation:
Line data
400 V, 50 Hz
Motor
Temperature rise class F/105K
Ambient temperature: 40 °C (motor and drive)
Installation altitude: max. 1000 m
MLoad = 60 Nm in an adjusting range from 800 rpm to 2500 rpm
Mmax = 115 Nm for to ≤ 60 s
The required max. load speed of 2500 rpm is close to the possible speed of 2600
rpm (4-pole Motor) with 87 Hz-characteristics at constant flux. So in the motor
wizard in screen „basic data 1“ “87 Hz” has to be selected as motor frequency.
87 Hz can only be selected, if the line is in range of 380 to 415 V or 660 or 690 V.
Because then it is possible to connect the coil in delta connection, e.g. at 50 Hz
with 230 V and at 87 Hz with 400 V. For “87 Hz” the 4-pole motors of 1LA7 and
1LA5 are possible.
At a forced cooled motor the allowable torque from 50Hz will be reduced
because the cooling effect is lower. A self-cooled motor will be selected. In this
task, the motor cooling method has no influence on the result from.
Result: