G

LEGEND
F
LAYER 1 SERVICE MECHANICAL
PENUMATIC TUBE SYSTEM
E CHILLER WATER PIPES
T ER PIPE COLD WATER AND SANITARY
W A Y AIR COND DUCTING
T I C D ITRA
A L SERVICE ELECTRICAL
D E UME CO SAN ELECTRICAL TRUNKING, TEL/IT TRUNKING, ELV TRUNKING
PN TUB AN
D
FFIT
SO
TER AS LAYER 2 SERVICE MECHANICAL
C AM A G AIR COND DUCTING
BE E D WS L PG FIRE FIGHTING PIPE
L L IPE
I
CH P T ING LPG GAS PIPE
IGHE
HOT WATER PIPES
B F
E IP
FIR P G AS LAYER 3 SERVICE MECHANICAL
R A L ES MEDICAL GAS PIPE LINES
T E C
DI LIN A/C GRILLS OUTLET, SPRINKLERS, DETECTOR, LIGHT FITTING
A A E
G T PWES M IPE
K I N O
H PI P
R UN
L T I NG
ICA T
R UC
C T D D V EL NOTE:-
EL
E
C ON G LE
AIR E ILIN 1. Ceiling space height requirement to engineer's detail.
V EC Otherwise ceiling space shall be not less than 900 mm
BO
Min 900mm (Refer Note 1)

A 2. Location of riser compartments and toilets beside AHU rooms


1 1 m m shall be avoided. Where this is necessary the Mechanical
R 30 0
YE E Engineer shall be consulted for approval
LA A NC SING
R
L EA ROS
C RC
2 FO
E R2 LUKISAN TIPIKAL PERKHIDMATAN SISTEM MEKANIKAL
LAY
DAN ELEKTRIK DALAM RUANG SILING DI KORIDOR
3

R 3
YE
LA A B C D E F G
4

ELECTRICAL
TRUNKING
TELEFON/IT
BEAM SOFFIT
TRUNKING
ELV TRUNKING
1 CHILLED
WATER PIPES
PNEUMATIC
TUBE SYSTEM
FIRE FIGHTING
PIPE
LAYER 1
HOT WATER COLD
2
MIN 900mm

AIR COND PIPES WATER


AIR COND DUCTING MEDICAL GAS AND
DUCTING PIPES LPG PIPES SANITARY
PIPE
LAYER 2

3 CLEARANCE 300mm ABOVE CEILING LEVEL


FOR CROSSING

LAYER 3 CEILING LEVEL

4
ELECTRICAL SERVICE (1/3) MECHANICAL SERVICE (2/3)