23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

N BILL OF MATERIAL
PT COMPONENT DESCRIPTION NPD ITEM CODE QTY L
NO.

FABRICATION MATERIALS
PIPE
1 PIPE, ASTM A312 TP316/316L, DUAL CERT., BE, 6 PD0BY.PIPE.01 1.1 M
SEAMLESS, S-40S, ASME B36.19M.
FITTINGS
2 EQUAL TEE, ASME B16.9, ASTM A403 WP316/316L DUAL 6X6 PD0BY.TEE.02 2
CERT., BW, SEAMLESS, S-40S
3 SOCKOLET, MSS-SP-97, ASTM A182 F316/316L, DUAL 6X1 PD0BY.SOCKOLET.01 2
CERT., SW, 3000 LBS
G10 B11 267 4 SOCKOLET, MSS-SP-97, ASTM A182 F316/316L, DUAL 6X1/2 PD0BY.SOCKOLET.01 1 K
CERT., SW, 3000 LBS
12
STEM WEST 5 90 DEG ELBOW LR, ASME B16.9, ASTM A403 WP316/316L, 6 PD0BY.90ELBOWLR.01 1
SEE ISO
WD-78101-6"-FA0BY DUAL CERT., BW, SEAMLESS, S-40S
E 1080.293M 6 PIPE NIPPLE, 100MM LONG, BS 3799, ASTM A312 1 PD0BY.NIPPLE.03 1
F8 G10 B11
N 1127.459M TP316/316L DUAL CERT., PE X NPT(M), SEAMLESS, SCH
EL +101.037M 80S, ASME B36.19M.
7 PIPE NIPPLE, 100MM LONG, BS 3799, ASTM A312 1/2 PD0BY.NIPPLE.03 1
<2> 1 TP316/316L DUAL CERT., PE X NPT(M), SEAMLESS, SCH
80S, ASME B36.19M.

314
FLANGES
8 WELDNECK FLANGE, ASME B16.5, ASTM A182 F316/316L, 6 PD0BY.FLANGE.02 3
DUAL CERT., RF, 150#, S-40S J
ERECTION MATERIALS
6"NPD

FITTINGS
9 PLUG HEX HEAD, ASME B16.11, NPT(M) END, ASTM A182 1 OPLHAB2TMA12XXX 1
GRADE F316/316L DUAL CERT, 3000 LBS
GASKETS
10 GASKET NON METALIC FLAT, ASME B16.21, 150#, RF, 6 PD0BY.GAS.02 3
78
SEE ISO 2 15 PT PEGGED GRAPHITE W/316SS INSERT, ASME B16.5
14
WD-77216-6"-PD0BY-TIC 6X6"NPD 130 BOLTS
STEM WEST
E 1080.293M 11 STUD BOLT W/2 HEAVY HEX NUTS, ASME B18.2.2, ASTM 3/4 PD0BY.BOLT.01 24
N 1127.602M
<1 A193 B8 CLASS 2 / A194 GR.8 (PTFE COATED). - 100
EL +100.450M >
1 mm Length
I
4 VALVES / IN-LINE ITEMS
143 6X1/2"NPD
12 GATE VALVE, API 600, BB, OS &Y, ASTM A351 CF8M, 6 PD0BY.GATE.02 1
TRIM 316SS+STELLITE,150#, FLEXIBLE WEDGE, FLGD, RF
29 7 47
3 HANDWHEEL OPERATOR
13 GATE VALVE, API 602, BB, OS&Y, ASTM A182 1 PD0BYGATRFTE 1
102 F316/316L, DUAL CERT., TRIM 316SS+STELLITE, 800#,
SOLID WEDGE, NPT(F), HANDWHEEL OPERATOR
14 GATE VALVE, API 602, BB, OS&Y, ASTM A182 1/2 PD0BYGATRFTE 1
102 F316/316L, DUAL CERT., TRIM 316SS+STELLITE, 800#,
SOLID WEDGE, NPT(F), HANDWHEEL OPERATOR
INSTRUMENTS
15 PRESSURE TRANSMITTER 1/2 78-PT-130 1 H
PIPE SUPPORTS
16 PIPE SUPPORT 6 DG-C-6" 1
17 PIPE SUPPORT 6 DV-A1-4"-210-6"-S 1

39
9

106
STEM WEST
102 77-G1-WD77139
SEE ISO
WD-77139-6"-PD0BY-TIC
E 1080.293M
F8
N 1126.475M
65 6 29 EL +100.682M
3

F
9

232
13 3
STEM WEST 6X1"NPD

6"NPD 2
6X6"NPD
EL +100.450M
SEE ISO
WD-77252-1"-PD0BY-TIC
3 E 1080.293M
6X1"NPD N 1126.174M
EL +100.571M E
30
1

SEE ISO
WD-77131-6"-PD0BY-TIC SHT 2
DISCLAIMER: THIS DOCUMENT IS THE PROPERTY OF ADNOC GAS PROCESSING AND CONTAINS CONFIDENTIAL AND PROPRITARY INFORMATION, THAT CANNOT BE COPIED OR

E 1080.293M
REPRODUCED OR LENT, IN WHOLE OR IN PART, FOR ANY PURPOSE OTHER THAN THAT FOR WHICH IT IS SUPPLIED, WITHOUT THE EXPRESSED AUTHORITY OF

N 1125.795M
106 S16
EL +100.771M
DG-C-6"
GUIDE GAP = 0 mm CUT PIPE LENGTH
F8 G10 B11
(N-S) RESTRAINT
(E-W) RESTRAINT PIECE LENGTH NPD REMARKS PIECE LENGTH NPD REMARKS
<3 NO (MM) (IN) NO (MM) (IN)
> 5 D
37 1 318
9 <1> 698 6" <2> 82 6"
<3> 309 6"

6"NPD
S17
DV-A1-4"-210-6"-S

0 07.05.24 AS-BUILT BKP HN SD


PS-77131-PD0BY-001 A1B 10.01.23 RE-ISSUED FOR CONSTRUCTION BKP HN SD
REV. DATE DESCRIPTION DRN. CHKD. APPVD. C

ADNOC Gas Processing ADNOC


EPC CONTRACTOR ENGG. CONSULTANT:
ADNOC GAS PROCESSING,P.O.BOX 665,ABUDHABI,UAE.

B
Arabian Industries LLC

REFERENCES: PROJECT
NOTES :
1. ALL DIMENSIONS ARE IN "MM", UNLESS OTHER WISE SPECIFIED
P&ID LINE NUMBER
POTABLE WATER SYSTEM UPGRADE
2. ALL ELEVATION / CO-ORDINATES ARE IN "M", UNLESS OTHERWISE SPECIFIED
3. NORTH ARROW DIRECTION SHOWS CALLED TRUE NORTH
4. PRIOR TO FABRICATION, THE CONTRACTOR SHALL CHECK THE FINISHED DIMENSIONS
OF FOUNDATIONS AND OF STRUCTURES AND OF EQUIPMENT AGAINST PIPING DRAWINGS
P&ID NO.
WD-77131-6"-PD0BY-TIC
IN TRAIN 1&2 AT RUWAIS
5. NPS<=2" DIMENSIONS AND ROUTING SHALL BE FIELD ADJUSTED 07-AD-0012
6. FOR LINE LIST REFER PROJECT DOC. 0500760-SCH-00-LA-1653 ADNOC Gas Processing Proj.No. PLANT LOCATION PLANT
PIPING GA NO.
7. THERMAL INSULATION COATING (TIC) SHALL BE PROVIDED FOR STAINLESS STEEL PIPING. 0500760 RUWAIS NGL TRAIN 1 & 2
8. FOR PIPE SUPPORT STANDARD REFER PROJECT DOC - 0500760-07-LA-2516, FOR PIPE SUPPORT 77-LD-0001
DESIGN OPERATING NDE INSULATION SCHEDULE REFER PROJECT DOC - 0500760-SCH-07-LA-2502 STRESS CN NO. SHEET REV.
LINE LINE TEST PRESS. PAINT A
CLASS SERVICE
TEST TYPE (Barg) PWHT
CODE GENERAL NOTES :
TEMP. (°C) PRESS. (Barg) TEMP. (°C) PRESS. (Barg) MPT/LPT RT TYPE THK 0500760-RT-07-LA-2505
PD0BY WD 70.00 6.00 40.00 5.45 HYDRO 9.00 5% 5% NO NOTE-7 2 MM SYSTEM-21
1. CONSTRUCTION CONTRACTOR SHALL VERIFY THE DIMENSION AND PIPING ELEVATION WITH
RESPECT TO ACTUAL SITE CONDITION PRIOR TO FABARICATION/INSTALLATION. WPS NO. WD-77131-6"-PD0BY-TIC 1 OF 6 0
2. FOR PAINTING REQUIREMENTS REFER COMPANY SPECIFICATION DGS-6600-010.
UNIT NO. AREA. EXTRACTED DATE : EXTRACTED BY :
LEGEND: FLOOR OPENING Unit 77 07 2024-05-07 17:43:15 sp3duser04
SHOP WELD FIELD WELD SOCKETWELD THREADED HEAT TRACED PIPE
23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

N 4
EL +105.683M BILL OF MATERIAL

SEE ISO PT COMPONENT DESCRIPTION NPD ITEM CODE QTY L


WD-77226-2"-PD0BY-TIC NO.
E 1081.475M
N 1125.917M FABRICATION MATERIALS
EL +105.312M PIPE
1 PIPE, ASTM A312 TP316/316L, DUAL CERT., BE, 6 PD0BY.PIPE.01 4.6 M
SEAMLESS, S-40S, ASME B36.19M.
FITTINGS

<6> 1
2 WELDOLET, MSS SP97, ASTM A182 F316/316L, DUAL 6X2 PD0BY.WELDOLET.01 1
CERT., BW, S-40S
3 SOCKOLET, MSS-SP-97, ASTM A182 F316/316L, DUAL 6X1 PD0BY.SOCKOLET.01 2
CERT., SW, 3000 LBS
21

371
122 93 4 90 DEG ELBOW LR, ASME B16.9, ASTM A403 WP316/316L, 6 PD0BY.90ELBOWLR.01 3 K
DUAL CERT., BW, SEAMLESS, S-40S
S10
24 S9 FLANGES
01 R-S-6"
GG-B2-6" 5 WELDNECK FLANGE, ASME B16.5, ASTM A182 F316/316L, 6 PD0BY.FLANGE.02 1
GUIDE GAP = 0 mm DUAL CERT., RF, 150#, S-40S
3 ERECTION MATERIALS
2 6X1"NPD
6X2"NPD GASKETS
6 GASKET NON METALIC FLAT, ASME B16.21, 150#, RF, 6 PD0BY.GAS.02 1
EL +105.312M
PEGGED GRAPHITE W/316SS INSERT, ASME B16.5
PS-77131-PD0BY-002 BOLTS
106
7 STUD BOLT W/2 HEAVY HEX NUTS, ASME B18.2.2, ASTM 3/4 PD0BY.BOLT.01 8
SEE ISO A193 B8 CLASS 2 / A194 GR.8 (PTFE COATED). - 100

429
WD-77140-1"-PD0BY-TIC mm Length J
E 1081.475M VALVES / IN-LINE ITEMS
N 1123.394M
8 GATE VALVE, API 600, BB, OS &Y, ASTM A351 CF8M, 6 PD0BY.GATE.02 1
EL +105.790M
TRIM 316SS+STELLITE,150#, FLEXIBLE WEDGE, FLGD, RF
HANDWHEEL OPERATOR
4
PIPE SUPPORTS
9 PIPE SUPPORT 6 GG-B2-6" 1
1 10 PIPE SUPPORT 6 R-S-6" 1
82 >
4 11 <5
EL +104.883M

SEE ISO
6"N WD-77131-6"-PD0BY-TIC SHT 3
PD E 1081.475M
N 1118.703M
EL +105.683M

H
<4> 1
3626

106

SEE ISO
WD-77250-1"-PD0BY-TIC
3 E 1080.293M
6X1"NPD N 1125.689M
EL +101.257M E
216
DISCLAIMER: THIS DOCUMENT IS THE PROPERTY OF ADNOC GAS PROCESSING AND CONTAINS CONFIDENTIAL AND PROPRITARY INFORMATION, THAT CANNOT BE COPIED OR

EL +101.257M
REPRODUCED OR LENT, IN WHOLE OR IN PART, FOR ANY PURPOSE OTHER THAN THAT FOR WHICH IT IS SUPPLIED, WITHOUT THE EXPRESSED AUTHORITY OF

6"NPD

CUT PIPE LENGTH

PIECE LENGTH NPD REMARKS PIECE LENGTH NPD REMARKS


NO (MM) (IN) NO (MM) (IN)
267 F5 G6 B7 D
<4> 3525 6" <5> 725 6"
<6> 343 6"

SEE ISO
WD-77131-6"-PD0BY-TIC SHT 1
E 1080.293M
N 1125.795M 8
EL +100.771M STEM WEST
0 07.05.24 AS-BUILT BKP HN SD
A1B 10.01.23 RE-ISSUED FOR CONSTRUCTION BKP HN SD
REV. DATE DESCRIPTION DRN. CHKD. APPVD. C

ADNOC Gas Processing ADNOC


EPC CONTRACTOR ENGG. CONSULTANT:
ADNOC GAS PROCESSING,P.O.BOX 665,ABUDHABI,UAE.

B
Arabian Industries LLC

REFERENCES: PROJECT
NOTES :
1. ALL DIMENSIONS ARE IN "MM", UNLESS OTHER WISE SPECIFIED
P&ID LINE NUMBER
POTABLE WATER SYSTEM UPGRADE
2. ALL ELEVATION / CO-ORDINATES ARE IN "M", UNLESS OTHERWISE SPECIFIED
3. NORTH ARROW DIRECTION SHOWS CALLED TRUE NORTH
4. PRIOR TO FABRICATION, THE CONTRACTOR SHALL CHECK THE FINISHED DIMENSIONS
OF FOUNDATIONS AND OF STRUCTURES AND OF EQUIPMENT AGAINST PIPING DRAWINGS
P&ID NO.
WD-77131-6"-PD0BY-TIC
IN TRAIN 1&2 AT RUWAIS
5. NPS<=2" DIMENSIONS AND ROUTING SHALL BE FIELD ADJUSTED 07-AD-0012
6. FOR LINE LIST REFER PROJECT DOC. 0500760-SCH-00-LA-1653 ADNOC Gas Processing Proj.No. PLANT LOCATION PLANT
PIPING GA NO.
7. THERMAL INSULATION COATING (TIC) SHALL BE PROVIDED FOR STAINLESS STEEL PIPING. 0500760 RUWAIS NGL TRAIN 1 & 2
8. FOR PIPE SUPPORT STANDARD REFER PROJECT DOC - 0500760-07-LA-2516, FOR PIPE SUPPORT 77-LD-0001
DESIGN OPERATING NDE INSULATION SCHEDULE REFER PROJECT DOC - 0500760-SCH-07-LA-2502 STRESS CN NO. SHEET REV.
LINE LINE TEST PRESS. PAINT A
CLASS SERVICE
TEST TYPE (Barg) PWHT
CODE GENERAL NOTES :
TEMP. (°C) PRESS. (Barg) TEMP. (°C) PRESS. (Barg) MPT/LPT RT TYPE THK 0500760-RT-07-LA-2505
PD0BY WD 70.00 6.00 40.00 5.45 HYDRO 9.00 5% 5% NO NOTE-7 2 MM SYSTEM-21
1. CONSTRUCTION CONTRACTOR SHALL VERIFY THE DIMENSION AND PIPING ELEVATION WITH
RESPECT TO ACTUAL SITE CONDITION PRIOR TO FABARICATION/INSTALLATION. WPS NO. WD-77131-6"-PD0BY-TIC 2 OF 6 0
2. FOR PAINTING REQUIREMENTS REFER COMPANY SPECIFICATION DGS-6600-010.
UNIT NO. AREA. EXTRACTED DATE : EXTRACTED BY :
LEGEND: FLOOR OPENING Unit 77 07 2024-05-07 17:43:15 sp3duser04
SHOP WELD FIELD WELD SOCKETWELD THREADED HEAT TRACED PIPE
23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

N SEE ISO
WD-77131-6"-PD0BY-TIC SHT 2
BILL OF MATERIAL
E 1081.475M
PT COMPONENT DESCRIPTION NPD ITEM CODE QTY L
N 1118.703M
NO.
EL +105.683M

SEE ISO FABRICATION MATERIALS


WD-77188-1"-PD0BY-TIC PIPE
E 1081.475M 1 PIPE, ASTM A312 TP316/316L, DUAL CERT., BE, 6 PD0BY.PIPE.01 35.2 M
N 1117.028M
SEAMLESS, S-40S, ASME B36.19M.
EL +105.790M
FITTINGS
6"N 2 2 SOCKOLET, MSS-SP-97, ASTM A182 F316/316L, DUAL 6X1 PD0BY.SOCKOLET.01 3
61 PD S4
99 6X1"NPD CERT., SW, 3000 LBS
R-S-6"
3 90 DEG ELBOW LR, ASME B16.9, ASTM A403 WP316/316L, 6 PD0BY.90ELBOWLR.01 2
DUAL CERT., BW, SEAMLESS, S-40S
63
66 ERECTION MATERIALS K
PIPE SUPPORTS
PS-77131-PD0BY-003 4 PIPE SUPPORT 6 R-S-6" 5
106
5 PIPE SUPPORT 6 GG-B2-6" 3
S5
GG-B2-6"
GUIDE GAP = 0 mm
SEE ISO
WD-U77001-1"-PD0BY-TIC
2 E 1081.475M
6X1"NPD N 1111.179M
EL +105.790M

58
49
PS-77131-PD0BY-004 J

106
37
7

S4
R-S-6"

S4
64 R-S-6" I
00

PS-77131-PD0BY-005
S5
GG-B2-6"
GUIDE GAP = 0 mm
H
64
04
PS-77131-PD0BY-006
20
09
7

S4
R-S-6"
G

S4
64 R-S-6"
04

<7
>
1
3

PS-77131-PD0BY-007
F
S5
GG-B2-6"
GUIDE GAP = 0 mm

SEE ISO

787
WD-77189-1"-PD0BY-TIC
E 1081.475M
N 1091.189M
EL +104.896M

E
EL +104.896M

2
6X1"NPD
DISCLAIMER: THIS DOCUMENT IS THE PROPERTY OF ADNOC GAS PROCESSING AND CONTAINS CONFIDENTIAL AND PROPRITARY INFORMATION, THAT CANNOT BE COPIED OR
REPRODUCED OR LENT, IN WHOLE OR IN PART, FOR ANY PURPOSE OTHER THAN THAT FOR WHICH IT IS SUPPLIED, WITHOUT THE EXPRESSED AUTHORITY OF

CUT PIPE LENGTH

<8> 1
106

609
PIECE LENGTH NPD REMARKS PIECE LENGTH NPD REMARKS
SEE ISO
NO (MM) (IN) NO (MM) (IN)
3 WD-77131-6"-PD0BY-TIC SHT 4
E 1081.475M D
EL +104.287M <7> 34256 6" <8> 939 6"
N 1090.854M
6"N
PD EL +104.287M

228
0 07.05.24 AS-BUILT BKP HN SD
A1B 10.01.23 RE-ISSUED FOR CONSTRUCTION BKP HN SD
REV. DATE DESCRIPTION DRN. CHKD. APPVD. C

ADNOC Gas Processing ADNOC


EPC CONTRACTOR ENGG. CONSULTANT:
ADNOC GAS PROCESSING,P.O.BOX 665,ABUDHABI,UAE.

B
Arabian Industries LLC

REFERENCES: PROJECT
NOTES :
1. ALL DIMENSIONS ARE IN "MM", UNLESS OTHER WISE SPECIFIED
P&ID LINE NUMBER
POTABLE WATER SYSTEM UPGRADE
2. ALL ELEVATION / CO-ORDINATES ARE IN "M", UNLESS OTHERWISE SPECIFIED
3. NORTH ARROW DIRECTION SHOWS CALLED TRUE NORTH
4. PRIOR TO FABRICATION, THE CONTRACTOR SHALL CHECK THE FINISHED DIMENSIONS
OF FOUNDATIONS AND OF STRUCTURES AND OF EQUIPMENT AGAINST PIPING DRAWINGS
P&ID NO.
WD-77131-6"-PD0BY-TIC
IN TRAIN 1&2 AT RUWAIS
5. NPS<=2" DIMENSIONS AND ROUTING SHALL BE FIELD ADJUSTED 07-AD-0012
6. FOR LINE LIST REFER PROJECT DOC. 0500760-SCH-00-LA-1653 ADNOC Gas Processing Proj.No. PLANT LOCATION PLANT
PIPING GA NO.
7. THERMAL INSULATION COATING (TIC) SHALL BE PROVIDED FOR STAINLESS STEEL PIPING. 0500760 RUWAIS NGL TRAIN 1 & 2
8. FOR PIPE SUPPORT STANDARD REFER PROJECT DOC - 0500760-07-LA-2516, FOR PIPE SUPPORT 77-LD-0001
DESIGN OPERATING NDE INSULATION SCHEDULE REFER PROJECT DOC - 0500760-SCH-07-LA-2502 STRESS CN NO. SHEET REV.
LINE LINE TEST PRESS. PAINT A
CLASS SERVICE
TEST TYPE (Barg) PWHT
CODE GENERAL NOTES :
TEMP. (°C) PRESS. (Barg) TEMP. (°C) PRESS. (Barg) MPT/LPT RT TYPE THK 0500760-RT-07-LA-2505
PD0BY WD 70.00 6.00 40.00 5.45 HYDRO 9.00 5% 5% NO NOTE-7 2 MM SYSTEM-21
1. CONSTRUCTION CONTRACTOR SHALL VERIFY THE DIMENSION AND PIPING ELEVATION WITH
RESPECT TO ACTUAL SITE CONDITION PRIOR TO FABARICATION/INSTALLATION. WPS NO. WD-77131-6"-PD0BY-TIC 3 OF 6 0
2. FOR PAINTING REQUIREMENTS REFER COMPANY SPECIFICATION DGS-6600-010.
UNIT NO. AREA. EXTRACTED DATE : EXTRACTED BY :
LEGEND: FLOOR OPENING Unit 77 07 2024-05-07 17:43:15 sp3duser04
SHOP WELD FIELD WELD SOCKETWELD THREADED HEAT TRACED PIPE
23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

N BILL OF MATERIAL
PT COMPONENT DESCRIPTION NPD ITEM CODE QTY L
NO.

FABRICATION MATERIALS
FITTINGS
1 SOCKOLET, MSS-SP-97, ASTM A182 F316/316L, DUAL 6X1 PD0BY.SOCKOLET.01 4
CERT., SW, 3000 LBS
ERECTION MATERIALS
SEE ISO PIPE SUPPORTS
WD-77131-6"-PD0BY-TIC SHT 3 2 PIPE SUPPORT 6 SC-A-150-300-6"-S 1
E 1081.475M
3 PIPE SUPPORT 6 CC-A-6-700 1
N 1090.854M
EL +104.287M 4 PIPE SUPPORT 6 GH-2-6" 1
5 PIPE SUPPORT 6 R-S-6" 6 K
S3 6 PIPE SUPPORT 6 GG-B2-6" 3
CC-A-6-700 7 PIPE SUPPORT 6 AW-B-6"-S 1
6"N
PD

11
59

S2
SC-A-150-300-6"-S S5
R-S-6"
PS-77131-PD0BY-008
44 SEE ISO
S4 99 J
WD-77221-1"-PD0BY-TIC
GH-2-6" 1 E 1081.475M
GUIDE GAP = 0 mm 6X1"NPD N 1081.027M
98 EL +104.393M
26

S6
GG-B2-6"
GUIDE GAP = 0 mm
PS-77131-PD0BY-009
106

22
32
I

PS-77131-PD0BY-010 1
6X1"NPD

SEE ISO
82 WD-77194-1"-PD0BY-TIC
27
E 1081.475M
N 1072.800M
S5 EL +104.393M
R-S-6"

106
PS-77131-PD0BY-011 H
40 1
5
6X1"NPD

64
0
106 S7
S5 AW-B-6"-S
R-S-6"
SEE ISO 61
65
WD-77141-1"-PD0BY-TIC
E 1081.475M
N 1072.160M G
EL +104.393M
S5
R-S-6"

S6
S5
GG-B2-6"
R-S-6"
PS-77131-PD0BY-012 64
00

22
16
6
S5 F
R-S-6"

64
PS-77131-PD0BY-013 00
1
6X1"NPD SEE ISO
WD-77195-1"-PD0BY-TIC
E 1081.475M
N 1049.995M
EL +104.393M
PS-77131-PD0BY-014
S6 SEE ISO
WD-77131-6"-PD0BY-TIC SHT 5
GG-B2-6" E
6"N 106 E 1081.475M
GUIDE GAP = 0 mm PD N 1048.395M
EL +104.287M
DISCLAIMER: THIS DOCUMENT IS THE PROPERTY OF ADNOC GAS PROCESSING AND CONTAINS CONFIDENTIAL AND PROPRITARY INFORMATION, THAT CANNOT BE COPIED OR
REPRODUCED OR LENT, IN WHOLE OR IN PART, FOR ANY PURPOSE OTHER THAN THAT FOR WHICH IT IS SUPPLIED, WITHOUT THE EXPRESSED AUTHORITY OF

CUT PIPE LENGTH

PIECE LENGTH NPD REMARKS PIECE LENGTH NPD REMARKS


NO (MM) (IN) NO (MM) (IN)
D

0 07.05.24 AS-BUILT BKP HN SD


A1B 10.01.23 RE-ISSUED FOR CONSTRUCTION BKP HN SD
REV. DATE DESCRIPTION DRN. CHKD. APPVD. C

ADNOC Gas Processing ADNOC


EPC CONTRACTOR ENGG. CONSULTANT:
ADNOC GAS PROCESSING,P.O.BOX 665,ABUDHABI,UAE.

B
Arabian Industries LLC

REFERENCES: PROJECT
NOTES :
1. ALL DIMENSIONS ARE IN "MM", UNLESS OTHER WISE SPECIFIED
P&ID LINE NUMBER
POTABLE WATER SYSTEM UPGRADE
2. ALL ELEVATION / CO-ORDINATES ARE IN "M", UNLESS OTHERWISE SPECIFIED
3. NORTH ARROW DIRECTION SHOWS CALLED TRUE NORTH
4. PRIOR TO FABRICATION, THE CONTRACTOR SHALL CHECK THE FINISHED DIMENSIONS
OF FOUNDATIONS AND OF STRUCTURES AND OF EQUIPMENT AGAINST PIPING DRAWINGS
P&ID NO.
WD-77131-6"-PD0BY-TIC
IN TRAIN 1&2 AT RUWAIS
5. NPS<=2" DIMENSIONS AND ROUTING SHALL BE FIELD ADJUSTED 07-AD-0012
6. FOR LINE LIST REFER PROJECT DOC. 0500760-SCH-00-LA-1653 ADNOC Gas Processing Proj.No. PLANT LOCATION PLANT
PIPING GA NO.
7. THERMAL INSULATION COATING (TIC) SHALL BE PROVIDED FOR STAINLESS STEEL PIPING. 0500760 RUWAIS NGL TRAIN 1 & 2
8. FOR PIPE SUPPORT STANDARD REFER PROJECT DOC - 0500760-07-LA-2516, FOR PIPE SUPPORT 77-LD-0001
DESIGN OPERATING NDE INSULATION SCHEDULE REFER PROJECT DOC - 0500760-SCH-07-LA-2502 STRESS CN NO. SHEET REV.
LINE LINE TEST PRESS. PAINT A
CLASS SERVICE
TEST TYPE (Barg) PWHT
CODE GENERAL NOTES :
TEMP. (°C) PRESS. (Barg) TEMP. (°C) PRESS. (Barg) MPT/LPT RT TYPE THK 0500760-RT-07-LA-2505
PD0BY WD 70.00 6.00 40.00 5.45 HYDRO 9.00 5% 5% NO NOTE-7 2 MM SYSTEM-21
1. CONSTRUCTION CONTRACTOR SHALL VERIFY THE DIMENSION AND PIPING ELEVATION WITH
RESPECT TO ACTUAL SITE CONDITION PRIOR TO FABARICATION/INSTALLATION. WPS NO. WD-77131-6"-PD0BY-TIC 4 OF 6 0
2. FOR PAINTING REQUIREMENTS REFER COMPANY SPECIFICATION DGS-6600-010.
UNIT NO. AREA. EXTRACTED DATE : EXTRACTED BY :
LEGEND: FLOOR OPENING Unit 77 07 2024-05-07 17:43:15 sp3duser04
SHOP WELD FIELD WELD SOCKETWELD THREADED HEAT TRACED PIPE
23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

N BILL OF MATERIAL
PT COMPONENT DESCRIPTION NPD ITEM CODE QTY L
NO.

FABRICATION MATERIALS
FITTINGS
1 WELDOLET, MSS SP97, ASTM A182 F316/316L, DUAL 6X2 PD0BY.WELDOLET.01 4
CERT., BW, S-40S
2 SOCKOLET, MSS-SP-97, ASTM A182 F316/316L, DUAL 6X1 PD0BY.SOCKOLET.01 1
SEE ISO CERT., SW, 3000 LBS
WD-77131-6"-PD0BY-TIC SHT 4
E 1081.475M ERECTION MATERIALS
N 1048.395M PIPE SUPPORTS
EL +104.287M 3 PIPE SUPPORT 6 R-S-6" 5
S3 4 PIPE SUPPORT 6 GG-B2-6" 2 K
R-S-6"

6"N
32 PD
00

SEE ISO
WD-77199-2"-PD0BY-TIC
E 1081.475M
PS-77131-PD0BY-015 1 N 1041.136M
88 J
59 6X2"NPD EL +104.409M

S4
GG-B2-6"
GUIDE GAP = 0 mm

123 1
43 6X2"NPD
7 SEE ISO
WD-77190-2"-PD0BY-TIC
E 1081.475M
I
S3 N 1039.245M
R-S-6" EL +104.409M
18
91
PS-77131-PD0BY-016

123
SEE ISO
WD-77197-2"-PD0BY-TIC
1 E 1081.475M
6X2"NPD N 1034.866M
EL +104.409M

122
43 H
79

26
3

S3
R-S-6" SEE ISO
WD-77196-1"-PD0BY-TIC
2
E 1081.475M
PS-77131-PD0BY-017 6X1"NPD
N 1028.924M
EL +104.393M G
59
42
106
S4
GG-B2-6"
GUIDE GAP = 0 mm

41
7

S3
R-S-6" F

PS-77131-PD0BY-018 SEE ISO


60 1 WD-77219-2"-PD0BY-TIC
96 6X2"NPD E 1081.475M
N 1022.108M
68
16 EL +104.409M

SEE ISO
PS-77131-PD0BY-019 123 WD-77131-6"-PD0BY-TIC SHT 6
E 1081.475M
S3 N 1020.541M
EL +104.287M E
R-S-6"
6"N
PD
DISCLAIMER: THIS DOCUMENT IS THE PROPERTY OF ADNOC GAS PROCESSING AND CONTAINS CONFIDENTIAL AND PROPRITARY INFORMATION, THAT CANNOT BE COPIED OR
REPRODUCED OR LENT, IN WHOLE OR IN PART, FOR ANY PURPOSE OTHER THAN THAT FOR WHICH IT IS SUPPLIED, WITHOUT THE EXPRESSED AUTHORITY OF

CUT PIPE LENGTH

PIECE LENGTH NPD REMARKS PIECE LENGTH NPD REMARKS


NO (MM) (IN) NO (MM) (IN)
D

0 07.05.24 AS-BUILT BKP HN SD


A1B 10.01.23 RE-ISSUED FOR CONSTRUCTION BKP HN SD
REV. DATE DESCRIPTION DRN. CHKD. APPVD. C

ADNOC Gas Processing ADNOC


EPC CONTRACTOR ENGG. CONSULTANT:
ADNOC GAS PROCESSING,P.O.BOX 665,ABUDHABI,UAE.

B
Arabian Industries LLC

REFERENCES: PROJECT
NOTES :
1. ALL DIMENSIONS ARE IN "MM", UNLESS OTHER WISE SPECIFIED
P&ID LINE NUMBER
POTABLE WATER SYSTEM UPGRADE
2. ALL ELEVATION / CO-ORDINATES ARE IN "M", UNLESS OTHERWISE SPECIFIED
3. NORTH ARROW DIRECTION SHOWS CALLED TRUE NORTH
4. PRIOR TO FABRICATION, THE CONTRACTOR SHALL CHECK THE FINISHED DIMENSIONS
OF FOUNDATIONS AND OF STRUCTURES AND OF EQUIPMENT AGAINST PIPING DRAWINGS
P&ID NO.
WD-77131-6"-PD0BY-TIC
IN TRAIN 1&2 AT RUWAIS
5. NPS<=2" DIMENSIONS AND ROUTING SHALL BE FIELD ADJUSTED 07-AD-0012
6. FOR LINE LIST REFER PROJECT DOC. 0500760-SCH-00-LA-1653 ADNOC Gas Processing Proj.No. PLANT LOCATION PLANT
PIPING GA NO.
7. THERMAL INSULATION COATING (TIC) SHALL BE PROVIDED FOR STAINLESS STEEL PIPING. 0500760 RUWAIS NGL TRAIN 1 & 2
8. FOR PIPE SUPPORT STANDARD REFER PROJECT DOC - 0500760-07-LA-2516, FOR PIPE SUPPORT 77-LD-0001
DESIGN OPERATING NDE INSULATION SCHEDULE REFER PROJECT DOC - 0500760-SCH-07-LA-2502 STRESS CN NO. SHEET REV.
LINE LINE TEST PRESS. PAINT A
CLASS SERVICE
TEST TYPE (Barg) PWHT
CODE GENERAL NOTES :
TEMP. (°C) PRESS. (Barg) TEMP. (°C) PRESS. (Barg) MPT/LPT RT TYPE THK 0500760-RT-07-LA-2505
PD0BY WD 70.00 6.00 40.00 5.45 HYDRO 9.00 5% 5% NO NOTE-7 2 MM SYSTEM-21
1. CONSTRUCTION CONTRACTOR SHALL VERIFY THE DIMENSION AND PIPING ELEVATION WITH
RESPECT TO ACTUAL SITE CONDITION PRIOR TO FABARICATION/INSTALLATION. WPS NO. WD-77131-6"-PD0BY-TIC 5 OF 6 0
2. FOR PAINTING REQUIREMENTS REFER COMPANY SPECIFICATION DGS-6600-010.
UNIT NO. AREA. EXTRACTED DATE : EXTRACTED BY :
LEGEND: FLOOR OPENING Unit 77 07 2024-05-07 17:43:15 sp3duser04
SHOP WELD FIELD WELD SOCKETWELD THREADED HEAT TRACED PIPE
23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

N BILL OF MATERIAL
PT COMPONENT DESCRIPTION NPD ITEM CODE QTY L
NO.

FABRICATION MATERIALS
PIPE
1 PIPE, ASTM A312 TP316/316L, DUAL CERT., BE, 6 PD0BY.PIPE.01 87.3 M
SEAMLESS, S-40S, ASME B36.19M.
FITTINGS
2 WELDOLET, MSS SP97, ASTM A182 F316/316L, DUAL 6X2 PD0BY.WELDOLET.01 1
CERT., BW, S-40S
3 SOCKOLET, MSS-SP-97, ASTM A182 F316/316L, DUAL 6X1 PD0BY.SOCKOLET.01 3
CERT., SW, 3000 LBS
4 CAP, ASME B16.9, ASTM A403 WP316/316L, BE, 6 PD0BY.CAP.03 1 K
SEAMLESS, S-40S
5 PIPE NIPPLE, 100MM LONG, BS 3799, ASTM A312 1 PD0BY.NIPPLE.03 2
TP316/316L DUAL CERT., PE X NPT(M), SEAMLESS, SCH
80S, ASME B36.19M.
FLANGES
6 WELDNECK FLANGE, ASME B16.5, ASTM A182 F316/316L, 6 PD0BY.FLANGE.02 2
DUAL CERT., RF, 150#, S-40S
ERECTION MATERIALS
FITTINGS
SEE ISO 6"N 7 HOSE COUPLING 1 HOSE COUPLING 1
WD-77131-6"-PD0BY-TIC SHT 5 PD 62
57 70 GASKETS
E 1081.475M 87 J
8 GASKET NON METALIC FLAT, ASME B16.21, 150#, RF, 6 PD0BY.GAS.02 2
N 1020.541M
EL +104.287M PEGGED GRAPHITE W/316SS INSERT, ASME B16.5
PS-77131-PD0BY-020 BOLTS
9 STUD BOLT W/2 HEAVY HEX NUTS, ASME B18.2.2, ASTM 3/4 PD0BY.BOLT.01 16
A193 B8 CLASS 2 / A194 GR.8 (PTFE COATED). - 100
mm Length
VALVES / IN-LINE ITEMS
10 GATE VALVE, API 600, BB, OS &Y, ASTM A351 CF8M, 6 PD0BY.GATE.02 1
TRIM 316SS+STELLITE,150#, FLEXIBLE WEDGE, FLGD, RF
HANDWHEEL OPERATOR
SEE ISO 11 GATE VALVE, API 602, BB, OS&Y, ASTM A182 1 PD0BYGATRFTE 1
WD-77218-1"-PD0BY-TIC F316/316L, DUAL CERT., TRIM 316SS+STELLITE, 800#,
S13 E 1081.475M I
SOLID WEDGE, NPT(F), HANDWHEEL OPERATOR
GG-B2-6" N 1015.839M
GUIDE GAP = 0 mm EL +104.393M PIPE SUPPORTS
12 PIPE SUPPORT 6 R-S-6" 3
13 PIPE SUPPORT 6 GG-B2-6" 2
S12 3
R-S-6" 6X1"NPD 106

56
16

11
18
8

PS-77131-PD0BY-021

S12
R-S-6"

3
6X1"NPD
15
0
106
F
SEE ISO 106
WD-771001-1''-PD0BY-TIC
E 1081.475M
N 1004.650M 3 64 S13
37 3
EL +104.393M 6X1"NPD 7 GG-B2-6"
GUIDE GAP = 0 mm

5
PS-77131-PD0BY-022
11
STEM NORTH 101 26
<9 7
>
1
5 65 E
S12 23
4
7 R-S-6"

2
DISCLAIMER: THIS DOCUMENT IS THE PROPERTY OF ADNOC GAS PROCESSING AND CONTAINS CONFIDENTIAL AND PROPRITARY INFORMATION, THAT CANNOT BE COPIED OR

F6 G8 B9 6X2"NPD
REPRODUCED OR LENT, IN WHOLE OR IN PART, FOR ANY PURPOSE OTHER THAN THAT FOR WHICH IT IS SUPPLIED, WITHOUT THE EXPRESSED AUTHORITY OF

102
15
0
CUT PIPE LENGTH
21 10
STEM UP PIECE LENGTH NPD REMARKS PIECE LENGTH NPD REMARKS
SEE ISO 123 NO (MM) (IN) NO (MM) (IN)
F6 G8 B9
WD-77201-2"-PD0BY-TIC D
E 1081.475M <9> 86907 6" <10> 295 6"
N 1003.350M <1
0 >
EL +104.409M 1

0 07.05.24 AS-BUILT BKP HN SD


4 A1B 10.01.23 RE-ISSUED FOR CONSTRUCTION BKP HN SD
REV. DATE DESCRIPTION DRN. CHKD. APPVD. C

ADNOC Gas Processing ADNOC


EPC CONTRACTOR ENGG. CONSULTANT:
ADNOC GAS PROCESSING,P.O.BOX 665,ABUDHABI,UAE.

B
Arabian Industries LLC

REFERENCES: PROJECT
NOTES :
1. ALL DIMENSIONS ARE IN "MM", UNLESS OTHER WISE SPECIFIED
P&ID LINE NUMBER
POTABLE WATER SYSTEM UPGRADE
2. ALL ELEVATION / CO-ORDINATES ARE IN "M", UNLESS OTHERWISE SPECIFIED
3. NORTH ARROW DIRECTION SHOWS CALLED TRUE NORTH
4. PRIOR TO FABRICATION, THE CONTRACTOR SHALL CHECK THE FINISHED DIMENSIONS
OF FOUNDATIONS AND OF STRUCTURES AND OF EQUIPMENT AGAINST PIPING DRAWINGS
P&ID NO.
WD-77131-6"-PD0BY-TIC
IN TRAIN 1&2 AT RUWAIS
5. NPS<=2" DIMENSIONS AND ROUTING SHALL BE FIELD ADJUSTED 07-AD-0012
6. FOR LINE LIST REFER PROJECT DOC. 0500760-SCH-00-LA-1653 ADNOC Gas Processing Proj.No. PLANT LOCATION PLANT
PIPING GA NO.
7. THERMAL INSULATION COATING (TIC) SHALL BE PROVIDED FOR STAINLESS STEEL PIPING. 0500760 RUWAIS NGL TRAIN 1 & 2
8. FOR PIPE SUPPORT STANDARD REFER PROJECT DOC - 0500760-07-LA-2516, FOR PIPE SUPPORT 77-LD-0001
DESIGN OPERATING NDE INSULATION SCHEDULE REFER PROJECT DOC - 0500760-SCH-07-LA-2502 STRESS CN NO. SHEET REV.
LINE LINE TEST PRESS. PAINT A
CLASS SERVICE
TEST TYPE (Barg) PWHT
CODE GENERAL NOTES :
TEMP. (°C) PRESS. (Barg) TEMP. (°C) PRESS. (Barg) MPT/LPT RT TYPE THK 0500760-RT-07-LA-2505
PD0BY WD 70.00 6.00 40.00 5.45 HYDRO 9.00 5% 5% NO NOTE-7 2 MM SYSTEM-21
1. CONSTRUCTION CONTRACTOR SHALL VERIFY THE DIMENSION AND PIPING ELEVATION WITH
RESPECT TO ACTUAL SITE CONDITION PRIOR TO FABARICATION/INSTALLATION. WPS NO. WD-77131-6"-PD0BY-TIC 6 OF 6 0
2. FOR PAINTING REQUIREMENTS REFER COMPANY SPECIFICATION DGS-6600-010.
UNIT NO. AREA. EXTRACTED DATE : EXTRACTED BY :
LEGEND: FLOOR OPENING Unit 77 07 2024-05-07 17:43:15 sp3duser04
SHOP WELD FIELD WELD SOCKETWELD THREADED HEAT TRACED PIPE