WATER SUPPLY LEGEND
HW
HW
HW
S2 S1 SYMBOL DESCRIPTION TYPE
S3
S1 Point for 3 Bowl sink unit all taps @ 1100mm Affl. N H
S2 Point for pot wash all taps @ 1100mm Affl. N H
S3 Point for Geyser (2no.'s) @ 1800mm Affl. N H
S4 Point for RO @ 1800mm Affl. N
PESTO FLASH
S5 Point for hand wash (2no.'s) @ 450mm Affl. N H
S4
S6 Point for sink (2no.'s) @ 450mm Affl. N RH
Air Curtain
S7 Point for cooking range (3no.'s) @ 450mm Affl. R
S8 Point for pepsi @ 1100mm Affl. R
S5
S9 Point for Ice-cuber @ 450mm Affl. R
HW
HW
S10 Point for WT sink @ 450mm Affl. N RH
HW
HW
S11 Point for idly steamer @ 450mm Affl. R
HW
S6
WATER SUPPLY LEGEND
DMB- 43"X2nos
SYMBOL DESCRIPTION
Angle valve Long Body Tap RO water
Angle valve Long Body Tap Hot water
Angle valve Long Body Tap Normal water
S8
S7
Gate valve
Water level indicator @ 1350mm
Air Curtain
S9
GAS DETECTOR
PANEL
Instant Gyser
25 LTR. GEYSER 2NOS.
M Digital water meter
Water tap of point
500 ltrs loft tank(1389x988x439)
main hole Dia 305
DMB- 43"X3nos
NOTE :
1. Applicable leed & fire rating as per tdg to be followed
2. All materials used to be class 'a', 1 hour fire rated as applicable
HW HW
3. RO tank to be hung above the ceiling with support of substructure.
HW
S6
HW
HW
S3 4. PPR- type 3 (3 layer pipes) of pn 6 grade to be use for water supply
HW
S11 S10 HW HW HW HW HW HW HW HW HW HW HW HW HW HW HW HW
S5
5. Insulation for hot water pipe(thermax,Maxima Fuelpac etc
6. All pipes should be installed freely from ceiling void area. Water Supply Piping from floor
is not allowed. Piping drops from ceiling inside BOH areas should be exposed on
walls/partitions. In FOH areas, piping drops from ceiling can be installed through niche in
walls with openable S.S. covers.
DMB- 43"X3nos
7. Upvc pipe to be used for drainage
8. Upvc pipe shall be solvent joint
9. 4MM thick torch sheild dr. fixit membrane to be used for water
10. proofing whether applicable
11. Leak testing should be done at the time of commissioning of line
REVISION RELEASED FOR: ARCHITECT/ INTERIOR DESIGN
S.NO. REMARKS DATE information tender construction as built
FC- 08 & 09 NOTE:
- DATE 2021 02 03 371, First Floor, Rangpuri ,Near
HYDERABAD AIRPORT 1. ALL DIMENSIONS ARE INCLUDING FINISHES
Celebration Garden,NH-8 , N.Delhi-37
2. DO NOT SCALE DRAWING.ONLY MENTIONED - - SCALE NTS
DIMENSIONS ARE TO BE CONSIDERED. Tel / Fax : +91 25062077-79
TITLE 3. ALL DIMENSIONS MUST BE CHECKED BEFORE - - - DRAWN BY GAURAV e-mail id : genarchpl@gmail.com
COMMENCING WORK ON SITE.
WATER SUPPLY LAYOUT 4. ANY DISCREPANCIES SHALL BE BROUGHT UNDER CONSULTANT
- - - CHD BY -
THE NOTICE OF
- ARCHITECTS PRIOR COMMENCEMENT OF WORK.
- - - DWG. NO. -