Performer ®
scroll compressors
Single 20 to 110 kW
50 - 60 Hz
http://holodko.ru/
CONTENTS
http://holodko.ru/
CONTENTS
INSTALLATION ................................................................................................................................................................................................................................................... 28
Compressor handling ............................................................................................................................................................................................................................ 28
Mounting .......................................................................................................................................................................................................................................................................... 28
Removing connections shipping plugs ........................................................................................................................................................ 29
System cleanliness ....................................................................................................................................................................................................................................... 29
Tubing ..................................................................................................................................................................................................................................................................................... 29
Filters driers ................................................................................................................................................................................................................................................................. 30
Brazing and soldering ........................................................................................................................................................................................................................... 30
Copper to copper connections .......................................................................................................................................................................... 30
Dissimilar metals connection ................................................................................................................................................................................. 30
Compressor connection ..................................................................................................................................................................................................... 30
System pressure test ................................................................................................................................................................................................................................ 31
Leak detection ....................................................................................................................................................................................................................................................... 31
Vacuum pump-down and moisture removal ................................................................................................................................... 32
Refrigerant charging ............................................................................................................................................................................................................................... 32
Commissioning ................................................................................................................................................................................................................................................... 32
Oil level checking and top-up ............................................................................................................................................................................................ 32
Oil level check ........................................................................................................................................................................................................................................... 32
Oil top-up ........................................................................................................................................................................................................................................................... 32
ACCESSORIES ....................................................................................................................................................................................................................................................... 33
Connectors and valves ........................................................................................................................................................................................................................ 33
Lubricants ........................................................................................................................................................................................................................................................................ 33
Crankcase heaters ......................................................................................................................................................................................................................................... 34
Discharge temperature protection ......................................................................................................................................................................... 35
Compressor acoustic hood ....................................................................................................................................................................................................... 35
http://holodko.ru/
PERFORMER® SCROLL COMPRESSION PRINCIPLE
Third orbit:
DISCHARGE
http://holodko.ru/
COMPRESSOR MODEL DESIGNATION
Nomenclature
Family, lubricant
& refrigerant
SM: Scroll, mineral oil,
for R22 Version
SY: Scroll, POE lubricant,
for R22
Motor protection
SZ: Scroll, POE lubricant,
type Description Applies to
for R407C - R134a
▼ ▼ ▼
Internal S 084 - 090
overload V V: brazed 100 - 110 - 120
Nominal capacity protector 148 - 161
in thousand Btu/h
at 60 Hz, R22, C C: brazed
ARI conditions
Internal S 115 - 125
thermostat 160 - 175 - 185
R R: rotolock
UL index
Connection details
SM/SZ 084 - 090 - 100 SM/SZ 115 - 125 - 160
MODEL SY/SZ 240 - 300 SY/SZ 380
110 - 120 - 148 - 161 170 - 185
MA AA AA
Version V R C
MB AB AB
Suction and discharge
brazed rotolock brazed rotolock brazed brazed
connection
Oil sight glass threaded threaded threaded threaded threaded threaded
Oil equalization connection 3/8’’ flare 3/8’’ flare 3/8’’ flare 1/2’’ flare 1/2’’ flare 1/2’’ flare
Oil drain connection - 1/4’’ NPT 1/4’’ NPT 1/4’’ NPT 1/4’’ NPT 1/4’’ NPT
Low pressure gauge port
1/4’’ flare 1/4’’ flare 1/4’’ flare 1/4’’ flare 1/4’’ flare 1/4’’ flare
(schrader)
http://holodko.ru/
TECHNICAL SPECIFICATIONS
50-Hz data
Nominal Nominal cooling Power A max Efficiency Sound Swept Displace- Oil Net
Model Cap. 60 Hz capacity input COP E.E.R. power volume ment charge weight
TR W Btu/h kW A W/W Btu/h /W dB(A) cm3/rev m3/h dm3 kg
SM084 7 20400 69 600 6.12 17 3.33 11.4 70 114.5 19.92 3.3 72
SM090 7.5 21800 74 400 6.54 17 3.33 11.4 70 120.5 20.97 3.3 72
SM100 8 23100 79 000 6.96 19 3.33 11.3 70 127.2 22.13 3.3 72
SM110 9 25900 88 600 7.82 20 3.32 11.3 75 144.2 25.09 3.3 80
SM115 9.5 28000 95 600 8.31 25 3.37 11.5 76 155.0 26.97 3.8 80
SM120 10 30100 102 800 8.96 29 3.36 11.5 75 166.6 28.99 3.3 80
R22 SINGLE
SM125 10 30100 102 800 8.93 25 3.37 11.5 76 166.6 28.99 3.8 80
SM148 12 36100 123 100 10.80 32 3.34 11.4 79 199.0 34.60 3.6 86
SM160 13 39100 133 500 11.60 29 3.37 11.5 79.5 216.6 37.69 4.0 94
SM161 13 39000 133 200 11.59 32 3.37 11.5 79.5 216.6 37.69 3.6 86
SM175 14 42000 143 400 12.46 35 3.37 11.5 80 233.0 40.54 6.2 103
SM185 15 45500 155 300 13.62 35 3.34 11.4 80 249.9 43.48 6.2 103
SY240 20 61200 208 700 18.20 50 3.36 11.5 82 347.8 60.50 8.0 160
SY300 25 78200 267 000 22.83 69 3.43 11.7 82 437.5 76.10 8.0 160
SY380 30 92000 313 900 26.82 72 3.43 11.7 85 531.2 92.40 8.4 163
Rating conditions
SM/SY compressors SZ compressors
Refrigerant R22 R407C
Frequency 50 Hz 50 Hz
Standard rating conditions ARI standard conditions -
Evaporating temperature 7.2 °C 7.2 °C (dew point)
Condensing temperature 54.4 °C 54.4 °C (dew point)
Sub-cooling 8.3 K 8.3 K
Superheat 11.1 K 11.1 K
http://holodko.ru/
TECHNICAL SPECIFICATIONS
60-Hz data
Nominal Nominal cooling Power A max Efficiency Sound Swept Displace- Oil Net
Model Cap. 60 Hz capacity input COP E.E.R. power volume ment charge weight
TR W Btu/h kW A W/W Btu/h /W dB(A) cm3/rev m3/h dm3 kg
SM084 7 24600 84 000 7.38 17 3.34 11.4 75 114.5 24.05 3.3 72
SM090 7.5 26400 90 000 7.82 17 3.37 11.5 75 120.5 25.31 3.3 72
SM100 8 27500 94 000 8.14 19 3.38 11.5 75 127.2 26.71 3.3 72
SM110 9 31600 107 800 9.35 20 3.38 11.5 78 144.2 30.28 3.3 80
SM115 9.5 33700 115 200 10.08 25 3.35 11.4 79 155.0 32.55 3.8 80
SM120 10 36700 125 300 10.80 29 3.40 11.6 78 166.6 34.99 3.3 80
R22 SINGLE
SM125 10 37000 126 400 10.99 25 3.37 11.5 79 166.6 34.99 3.8 80
SM148 12 43800 149 500 13.01 32 3.37 11.5 83 199.0 41.80 3.6 86
SM160 13 47700 163 000 14.22 29 3.36 11.5 84 216.6 45.49 4.0 94
SM161 13 47600 162 600 14.07 32 3.39 11.5 84 216.6 45.49 3.6 86
SM175 14 51100 174 300 15.27 35 3.34 11.4 82.5 233.0 48.93 6.2 103
SM185 15 54300 185 400 16.22 35 3.35 11.4 82.5 249.9 52.48 6.2 103
SY240 20 74100 252 700 22.10 50 3.35 11.4 84.7 347.8 73.00 8.0 160
SY300 25 94500 322 500 27.50 69 3.43 11.7 85.9 437.5 91.90 8.0 160
SY380 30 110000 375 300 33.54 72 3.28 11.7 88.0 531.2 111.60 8.4 163
SZ125 10 34900 119 200 10.89 25 3.21 10.9 81 166.6 34.99 3.8 80
SZ148 12 42600 145 400 13.35 32 3.19 10.9 85 199.0 41.80 3.6 86
SZ160 13 45500 155 400 14.08 29 3.23 11.0 85 216.6 45.49 4.0 94
SZ161 13 46000 156 900 14.32 32 3.21 10.9 85 216.6 45.49 3.6 86
SZ175 14 48700 166 200 15.28 35 3.19 10.9 84 233.0 48.93 6.2 103
SZ185 15 51800 176 800 16.43 35 3.15 10.7 84 249.9 52.48 6.2 103
SZ240 20 71100 242 800 22.70 50 3.14 10.7 87 347.8 73.00 8.0 160
SZ300 25 87900 300 000 27.49 69 3.20 10.9 87.5 437.5 91.90 8.0 160
SZ380 30 108500 368 500 33.40 72 3.25 11.0 89.5 531.2 111.60 8.4 163
TR = Ton of Refrigeration
COP = Coefficient Of Performance
EER = Energy Efficiency Ratio
Rating conditions
SM/SY compressors SZ compressors
Refrigerant R22 R407C
Frequency 60 Hz 60 Hz
Standard rating conditions ARI standard conditions -
Evaporating temperature 7.2 °C 7.2 °C (dew point)
Condensing temperature 54.4 °C 54.4 °C (dew point)
Sub-cooling 8.3 K 8.3 K
Superheat 11.1 K 11.1 K
http://holodko.ru/
OPERATING ENVELOPES
Application envelopes The figures below show the opera- be interpolated. The operating limits
ting envelopes for SM / SY compres- serve to define the envelope within
at dew temperatures sors with refrigerant R22 and for SZ which reliable operations of the com-
compressors with refrigerants R407C, pressor are guaranteed:
R134a, R404A and R507A. The dischar- ● Maximum discharge gas tempera-
ge temperature depends on the com- ture: +135°C
bination of evaporating temperature, ● Maximum ambient temperature:
condensing temperature and suction +63°C (for SM / SZ 084 to 185), + 52°C
gas superheat. Because of this depen- (for SY / SZ 240 to 380)
dence, discharge temperature limits
● A suction superheat below 5 K is not
are indicated by a double line. The
solid line represents the limit should recommended due to the risk of li-
the superheat be 11.1 K or less. The quid floodback
● Maximum superheat of 30 K
dashed line, on the other hand, pro-
vides the limit when the superheat is ● Minimum and maximum evapora-
SM 084 to SM 185
70
SY 240 to SY 380 65
Condensing temp. limits
R22 60
Cond. temp. (°C)
55
50 S.H. = 30 K
SUPERHEAT
S.H. = 11.1 K
45
40
35
30
-25 -20 -15 -10 -5 0 5 10 15 20
Evap. temp. (°C)
SZ 084 to SZ 185
75
R134a 70
Condensing temp. limits
65
S.H. = 11.1 K
60
Cond. temp. (°C)
S.H. = 30 K
55
SUPERHEAT
50
45
40
35
30
-20 -15 -10 -5 0 5 10 15 20
Evap. temp. (°C)
http://holodko.ru/
OPERATING ENVELOPES
SZ 240 - 300
75
R134a 70
Condensing temp. limits
65
S.H. = 11.1 K
60
50
45
40
35
30
-20 -15 -10 -5 0 5 10 15 20
Evap. temp. (°C)
SZ 084 to SZ 185
75
R404A / R507A 70
Condensing temp. limits
65
60
Cond. temp. (°C)
S.H. = 30 K
55
SUPERHEAT
50
S.H. = 11.1 K
45
40
35
30
-25 -20 -15 -10 -5 0 5 10 15
Evap. temp. (°C)
55
S.H. = 30 K
SUPERHEAT
50
S.H. = 11.1 K
45
40
35
30
-25 -20 -15 -10 -5 0 5 10 15 20
Evap. temp. (°C)
55
S.H. = 11.1 K S.H. = 30 K
SUPERHEAT
50
45
40
35
30
-25 -20 -15 -10 -5 0 5 10 15 20
Evap. temp. (°C)
http://holodko.ru/
OPERATING ENVELOPES
Application envelopes at Refrigerant R407C is a zeotropic mix- For a given cycle, the MEAN point
ture, which causes a temperature glide temperatures are typically about 2° to
mean temperatures in both the evaporator and condenser. 3°C lower than DEW point tempera-
When discussing evaporating and tures. In these Selection and Applica-
condensing temperatures therefore, it tion Guidelines, Danfoss Commercial
is important to indicate whether these Compressors displays temperatures as
are DEW point values or MEAN point DEW point values.
values. In the figure below, the dashed The performance tables for R407C (see
lines reflect constant temperature and p. 6-7) are also based on DEW point
do not correspond with the constant values.
pressure lines.
Dew temperature
and pressure (log)
mean temperature
for R407C
Mean Dew
Mean
The following operating diagrams
show the difference between mean Dew
enthalpy
and dew temperature application en-
velopes.
60
Cond. temp. (°C)
55
S.H. = 30 K
SUPERHEAT
50
S.H. = 11.1 K
45
40
35
30
-25 -20 -15 -10 -5 0 5 10 15 20
Evap. temp. (°C)
Example for SZ 084 to 185
60
Cond. temp. (°C)
55
S.H. = 30 K
SUPERHEAT
50
S.H. = 11.1 K
45
40
35
30
-25 -20 -15 -10 -5 0 5 10 15 20
Evap. temp. (°C)
Example for SZ 084 to 185
10
http://holodko.ru/
PIPING CONNECTIONS
① ➁
Oil drain The oil drain connection allows oil to Oil fill
be removed from the sump for chan- connection
ging, testing, etc. The fitting contains and
an extension tube into the oil sump to gauge port
more effectively remove the oil. The
connection is composed of a female
1/4" NPT fitting.
11
http://holodko.ru/
ELECTRICAL CONNECTIONS AND WIRING
Motor voltage Performer® scroll compressors are 60 Hz, motor code 6 for 50 Hz and
available in five different motor vol- motor code 4 and 7 for both 50 and
tages. Motor voltage code 3 and 9 for 60 Hz.
Motor voltage
code 4 Motor voltage
with thermostat code 4
protector and with PTC and
Motor voltage internal overload electronic module Motor voltage Motor voltage Motor voltage
code 3 (S 084 - S 185) (S 240 - S 380) code 6 code 7 code 9
Nominal voltage - 380-400V - 3 - 50 Hz 400V - 3 - 60 Hz 230V - 3 - 50 Hz 500V - 3 - 50Hz -
50 Hz
Voltage range - 340-440V 360 - 440 V 207 - 253V 450 - 550V -
50 Hz
Nominal voltage 200-230V - 3 - 60 Hz 460V - 3 - 60 Hz 460V - 3 - 60Hz - 575V - 3 - 60 Hz 380 - 3 - 60 Hz
60 Hz
Voltage range 180 - 253 V 414 - 506V 414 - 506V - 517 - 632V 342 - 418 V
60Hz
Electrical connections Electrical power is connected to the ning torque is 3 Nm. Use a 1/4’’ ring
compressor terminals by Ø 4.8 mm terminal on the power leads.
(3/16”) screws. The maximum tighte-
ø 29 mm knockout
Terminal box wiring for The terminal box is provided with supply and 3 knockouts for the safety
SM / SZ 115 - 125 - 160 - 2 double knockouts for the power control circuit.
161 (motor code 3) -
175 - 185 Discharge gas thermostat kit Discharge gas pipe
(optional)
Cover
holding
screw (x2)
Torque:
2.2 N.m.
Belt type
cranckase
heater
(optional)
1/4” spade
Terminal box connector
12
http://holodko.ru/
ELECTRICAL CONNECTIONS AND WIRING
The 2 power supply, double knockouts The 3 other knockouts are as follows:
accommodate the following diameters: Ø 20.5 mm / Ø 0.81”
Ø 44 mm / Ø 1”3/4 hole (for a 1”1/4 Ø 22 mm / Ø 7/8” (for a 1/2” conduit)
conduit) and Ø 34mm / Ø 1”3/8 Ø 16.5 mm / Ø 0.65”
hole (for a 1” conduit), The protection rating of the terminal
Ø 32.1 mm / Ø 1.26” hole and box is IP54 when correctly sized IP54
Ø 25.4 mm / Ø 1” hole. rated cable glands are used.
Connect the internal safety thermostat
with 1/4” female spade connectors.
Terminal box wiring for The terminal box is provided with 4 The 4 others knockouts are as follows:
SY / SZ 240 – 300 – 380 double knockouts for the power sup- Ø 20.5 mm / Ø 0.81”
ply and 4 knockouts for the safety Ø 20.5 mm / Ø 0.81”
control circuit. The 4 power supply Ø 50 mm / Ø 1” 31/32
double knockouts accommodate the Ø 25.2 mm / Ø 0.99”
following diameters:
The protection rating of the terminal
Ø 22 mm / Ø 7/8” hole box is IP54 when correctly sized IP54-
and Ø 16.5 mm / Ø 0.65” knockout rated cable glands are used.
Ø 22 mm / Ø 7/8” hole
IP ratings according to IEC 529.
and Ø 16.5 mm / 0.65” knockout
Ø 43.7 mm / Ø 1”23/32 hole
and Ø 34.5 mm / 1”23/64 knockout
Ø 40.5 mm / Ø 1.59” hole
and Ø 32.2 mm / 1.27” knockout
Belt type
cranckase
heater
M1, M2
Control circuit
Power supply
Power supply
13
http://holodko.ru/
ELECTRICAL CONNECTIONS AND WIRING
Suggested wiring
diagrams logic
Compressor models SM / SZ 084 – 090 – 100 – 110 – 120 – 148 - 161
Q1 Q1
F1 F1 F1 F1
KM KM
KA KS KA KS
KM KA KA KA KA
F2 F2
A1 A1
T1 T2 T1 T2
A3 A3
KS BP
180 s HP 180 s
A2 T3 A2 T3
BP TH HP
KS
TH
KS M
M
DGT DGT
KM KA LLSV KS KM KA KS
85 52 019 - A
Wiring diagram with pump-down cycle Wiring diagram without pump-down cycle
Suggested wiring
diagrams logic
Compressor models SM / SZ 115 – 125 – 160 – 175 – 185
Q1 Q1
F1 F1 F1 F1
KM KM
KM KA KA KA KS
KA KA KA KS
F2 F2
T1 T2 T1 T2
A1
A3
180s HP T3 T3
A1 BP
KS
A2
A3
180s
BP TH HP
M A2 M
DGT
KS DGT TH 1 2
KS
1 2
KM KA LLSV KS KM KA KS
Wiring diagram with pump-down cycle Wiring diagram without pump-down cycle
A1 A2 A1 A3
TH 160 s
TH
T T
A2 KA
~
14
http://holodko.ru/
ELECTRICAL CONNECTIONS AND WIRING
Suggested wiring
diagrams logic
Compressor models SY / SZ 240 - 300 - 380
A1 A1
A3 A3
A2 A2
Wiring diagram with pump-down cycle Wiring diagram without pump-down cycle
Danfoss MCI The inrush current for the Performer® detrimental effects of high starting tor-
scroll compressors with motor code que surges and costly demand char-
soft-start controller 4 (400V / 3 / 50Hz or 460V / 3 / 60Hz) ges from the resultant current spike.
can be reduced using the Danfoss di- Upon starting, the controller gradually
gitally-controlled MCI compressor soft increases the voltage supplied to the
starter. MCI soft starters are designed motor until full-line voltage has been
to reduce the starting and stopping reached. All settings, such as ramp-up
current of 3-phase AC motors; MCI soft time and initial torque, are preset at
starters can reduce the in-rush current the factory and do not require modi-
by up to 40%, thereby eliminating the fication.
15
http://holodko.ru/
ELECTRICAL CONNECTIONS AND WIRING
MCI with By means of the built-in auxiliary con- no-load condition it can be selected
bypass contactor tact (23-24) the bypass function is easily on the basis of the thermal current
achieved, see wiring diagram below. (AC-1).
No heat is generated from the MCI. (13-14 contact not applicable with
As the contactor always switches in MCI 25C)
Input controlled When the control voltage is applied to adjustments. When the control voltage
soft start A1 - A2, the MCI soft starter will start is switched OFF, the motor will switch
the motor, according to the settings off instantaneously.
of the ramp-up time and initial torque
16
http://holodko.ru/
SYSTEM DESIGN RECOMMENDATIONS
Refrigerant charge limit Performer® scroll compressors incor- however be required to ensure ade-
porate internal safety devices such as quate protection of the compressor.
and compressor motor temperature protection, rever- Depending on the system configura-
protection se rotation protection and a dischar- tion and application, one or several
ge gas check valve. Additional safety of the following methods should be
devices or system components may considered.
Crankcase heater When the compressor is idle, the oil recommended on all stand-alone com-
temperature in the sump of the com- pressors and split systems. In addition,
pressor must be maintained at no any system containing a refrigerant
lower than 10 K above the saturation charge in excess of the maximum re-
temperature of the refrigerant on the commended system charge for com-
low-pressure side. This requirement pressors requires a crankcase heater. A
ensures that the liquid refrigerant is crankcase heater is also required on all
not accumulating in the sump. A crank- reversible cycle applications.
case heater is only effective if capable
of sustaining this level of temperature Notes:
difference. Tests must be conducted to Belt-type crankcase heater accessories
ensure that the appropriate oil tempe- are available from Danfoss (see page
rature is maintained under all ambient 34). The heater must be energized for
conditions (temperature and wind). a minimum of 12 hours before initial
However, below –5°C ambient tem- start-up (compressor service valves
perature and a wind speed of above opened) and must remain energized
5 m/sec, we recommend that the whenever the compressor is off.
heaters be thermally insulated in order Provide separate electrical supply for
to limit the surrounding energy losses. the heaters so that they remain ener-
Since the total system charge may gized even when the machine is out of
be undefined, a crankcase heater is service (eg. seasonal shutdown).
Liquid line solenoid valve An LLSV may be used to isolate the The quantity of refrigerant on the low-
(LLSV) liquid charge on the condenser side, pressure side of the system can be fur-
thereby preventing against charge ther reduced by using a pump-down
transfer or excessive migration to the cycle in association with the LLSV.
compressor during off-cycles.
Pump-down cycle A pump-down cycle represents one low pressure pump-down switch. This
of the most effective ways to protect step reduces the amount of charge on
against the off-cycle migration of li- the low side in order to prevent off-
quid refrigerant. Once the controls has cycle migration. Recommended set-
been satisfied, a solenoid valve closes tings of the low-pressure pump-down
on the condenser outlet. The compres- switch can be found in the table on
sor then pumps the majority of the sys- p. 22. For suggested wiring diagrams,
tem charge into the condenser and re- please see p. 14-15.
ceiver before the system stops on the
Suction accumulator A suction accumulator offers protec- off-cycle migration by providing addi-
tion against refrigerant floodback at tional internal free volume to the low
start-up, during operations or after side of the system. The accumulator
defrosting (heat pump). Sustained should not be sized for less than 50%
and repeated liquid slugging and of the total system charge. Tests must
floodback can seriously impair the be conducted to determine the actual
oil’s ability to lubricate. The suction refrigerant holding capacity needed
line accumulator also protects against for the application.
17
http://holodko.ru/
SYSTEM DESIGN RECOMMENDATIONS
Liquid receiver A liquid receiver is highly recommen- duced in order to safely store the re-
ded on split systems and remote con- frigerant charge during the off-cycles,
denser systems with a total refrigerant which greatly reduces the chance of
charge in excess of the recommended refrigerant migration back to the com-
maximum for the compressor. Becau- pressor.
se of the long refrigerant lines these On unitary or close-coupled systems,
systems have a relatively high system where the system refrigerant charge is
charge which is hard to define with ac- expected to be both correct and defi-
curacy. Further these types of systems nable the entire system charge may be
quite often tend to be overcharged in stored in the condenser during pump-
the field. By installing a liquid receiver, down if all components have been
a pump-down cycle can then be intro- properly sized.
Protection against flooded Flooded starts occur when a compres- from the evaporator into the compres-
starts and liquid floodback sor starts up with a large quantity of sor sump by gravity. If the system char-
liquid refrigerant in the compressor. ge exceeds the limit shown in the ta-
Liquid finds its way into a compressor ble, a crankcase heater must be used.
by means of off-cycle migration. Liquid
During operations, liquid floodback
floodback occurs when liquid refrige-
may be detected by measuring either
rant returns to a compressor while it is
the oil sump temperature, which
running. Excessive liquid refrigerant in
should be at least 10 K above the satu-
the compressor will cause oil dilution,
rated suction temperature, or the dis-
liquid washout of oil from the bearings,
charge gas temperature, which should
or loss of oil from the sump. The cran-
be at least 30 K above the saturated
kcase heater will not be effective if the
discharge temperature. If at any time
system design allows for uncontrolled
during operations, the oil sump tem-
floodback to the compressor during
perature drops to within 10 K or less
running or starting. Performer® scroll
above the saturated suction tempera-
compressors can tolerate occasional
ture, or should the discharge gas tem-
flooded starts as long as the system
perature be less than 30 K above the
charge does not exceed that given in
saturated discharge temperature, the
the table in the following section. Per-
lubricant will become excessively dilu-
former® scrolls can also handle inter-
ted and tests would have to be perfor-
mittent floodback, yet system design
med in order to select an appropriate
must be such that repeated and exces-
compressor protection method. Repe-
sive floodback is not possible.
titive liquid floodback testing must be
Off-cycle refrigerant migration occurs carried out under TXV threshold ope-
when the compressor is located at the rating conditions: a high pressure ratio
coldest part of the installation, when and minimum load, along with the
the system uses a bleed-type expan- measurement of both suction super-
sion device, or if liquid can migrate heat and discharge gas temperature.
Discharge gas temperature DGT protection is required if the high HP1 = 25 bar (g) (62°C)
protection (DGT) and low pressure switch settings do not Risk of operation beyond the applica-
protect the compressor against opera- tion envelope.
tions beyond its specific application DGT protection required.
envelope. Please refer to the examples
Example 2 (R22, SH = 11 K)
below, which illustrates where DGT
LP switch setting:
protection is required (Example 1) and
LP2 = 2.9 bar (g) (-7°C)
where it is not (Example 2).
HP switch setting:
Example 1 (R22, SH = 11 K) HP2 = 21 bar (g) (55°C)
LP switch setting: No risk of operation beyond the appli-
LP1 = 1.8 bar (g) (-17°C) cation envelope.
HP switch setting: No DGT protection required.
18
http://holodko.ru/
SYSTEM DESIGN RECOMMENDATIONS
70
65
60
HP1
Example 1
Cond. temp. (°C)
55 HP2
it Example 2
- lim
50
D GT
45
40
35
R22
LP1 LP2
30
-25 -20 -15 -10 -5 0 5 10 15 20
Evap. temp. (°C)
S 084 S 148
S 110 S 115 S 175 S 300
Compressor models S 090 S 160 S 240
S 120 S 125 S 185 S 380
S 100 S 161
Refrigerant charge limit (kg) 8.5 10 11 12.5 13.5 16 20
Cooling only systems REC Refrigerant migration & floodback test REQ Refrigerant migration & floodback test
with remote condensor REC Crankcase heater, because full system REQ Crankcase heater
and split system units charge is not definable (risk of overcharging) REC Liquid receiver
19
http://holodko.ru/
SYSTEM DESIGN RECOMMENDATIONS
Motor protection
Internal motor protection Compressor models SM / SZ 084 185 models. The table below shows
- 090 - 100 - 110 - 120 - 148 - 161 the protection method for the various
have been provided with an internal compressor models.
overload motor protection to prevent
Compressor models SY / SZ 240 - 300
against excessive current and tempe-
- 380 are delivered with a preinstalled
rature caused by overloading, low re-
motor protection module inside the
frigerant flow phase loss or incorrect
terminal box. This device provides for
motor rotation. The cutout current is
efficient and reliable protection against
the MCC value listed in the data sheets.
overheating and overloading as well as
While not compulsory, an additional
phase loss/reversal.The motor protec-
external overload protection is still ad-
tor comprises a control module and
visable for either alarm or manual re-
PTC sensors embedded in the motor
set. The protector is located in the star
winding. The close contact between
point of the motor and, should it be
thermistors and windings ensures a
activated, will cut out all three phases.
very low level of thermal inertia.The
It will be reset automatically.
motor temperature is being constantly
Compressor models SM / SZ 115 - measured by a (PTC) thermistor loop
125 - 160 - 175 - 185 have been pro- connected on S1-S2.
vided with a bimetallic single-pole, If any thermistor exceeds its response
single-throw thermostat located in temperature, its resistance increases
the motor windings. In the event of above the trip level (4,500 Ω) and the
motor overheating caused by low output relay then trips (i.e. contacts
refrigerant flow or improper motor M1-M2 are open). After cooling to
rotation, the thermostat will open. Be- below the response temperature (re-
cause the thermostat is an automatic sistance < 2,750 Ω), a 5 minute time
reset device, it must be wired within a delay is activated. After this delay has
lockout safety circuit with a manual re- elapsed, the relay is once again pulled
set to restart the unit. For overcurrent in (i.e. contacts M1-M2 closed). The
and phase loss protection, an exter- time delay may be cancelled by means
nal overload protector must be used of resetting the mains (L-N disconnect)
for the SM / SZ 115, 125, 160, 175 and for approx. 5 sec.
External motor protection All safety devices must comply with the A circuit breaker, on the other hand,
requirements of the pertinent certifi- should be set at not more than 125%
cation authorities in the country where of the compressor rated load current.
the compressor will be used. The exter- The rated load current is the maximum
nal overload protector can be either a current expected during operations
thermal overload relay or a circuit brea- of the considered application; it can
ker. A thermal overload relay should be found either in the corresponding
be set to trip at not more than 140% data sheets or in the Danfoss Commer-
of the compressor-rated load current. cial Compressors selection program
20
http://holodko.ru/
SYSTEM DESIGN RECOMMENDATIONS
for all compressors. The tripping cur- tes at 110% of the Maximum Must-Trip
rent must never exceed the MMT va- current.
lue found in the data sheets; the MMT ● Locked rotor protection:
value appears as "A.Max" on the com- The protector must trip within 10 se-
pressor nameplate. conds upon starting at a locked rotor
Further requirements for the external current.
overload protector are: ● Single-phasing protection:
Phase sequence and reverse Use a phase meter to establish the occur, shut the compressor down and
rotation protection phase orders and connect line phases connect the phases to their proper ter-
L1, L2 and L3 to terminals T1, T2 and minals. If reverse rotation is not halted,
T3, respectively. The compressor will the compressor will cycle off on the in-
only operate properly in a single direc- ternal motor protection.
tion, and the motor is wound so that if
Compressor models SY / SZ 240 to
the connections are correct, the rota-
380 are delivered with an electronic
tion will also be correct.
module which provides protection
Compressor models SM / SZ 084 to against phase reversal and loss at
185 incorporate an internal reverse start-up. Apply the recommended
vent valve which will react in the pre- wiring diagrams from page 15. The
sence of reverse rotation and will al- circuit should be thoroughly checked
lows refrigerant to circulate through in order to determine the cause of the
a by-pass from the suction to the dis- phase problem before re-energizing
charge. Although reverse rotation is the control circuit.
not destructive, even over long periods The phase sequencing and phase loss
of time up to several days it should be monitoring functions are active during
corrected as soon as possible. Reverse a 5 sec. window 1 sec. after compressor
rotation will be obvious to the user as start-up (power on L1-L2-L3). Should
soon as power is turned on; the com- one of these parameters be incorrect,
pressor will not build up any pressure, the relay would lock out (contact M1-
the sound level will be abnormally M2 open). The lockout may be cancel-
high and power consumption will be led by resetting the power mains (dis-
minimal. If reverse rotation symptoms connect L-N) for approximately 5 sec.
Compressor
Start
Phase monitoring
Cycle rate limit The system must be designed in a way accessory is introduced); a number
that guarantees a minimum compres- higher than 12 reduces the service
sor running time of 2 minutes so as to life of the motor-compressor unit. If
provide for sufficient motor cooling necessary, place an anti-short-cycle
after start-up along with proper oil re- timer in the control circuit, connected
turn. Note that the oil return may vary as shown in the wiring diagram (p14-
since it depends upon system design. 15). A three-minute (180-sec) time out
There must be no more than 12 starts is recommended.
per hour (6 when a resistor soft-start
21
http://holodko.ru/
SYSTEM DESIGN RECOMMENDATIONS
Voltage unbalance The operating voltage limits are shown unbalance is 2%. Voltage unbalance
in the table on page 12.The voltage causes high amperage over one or
applied to the motor terminals must several phases, which in turn leads to
lie within these table limits during overheating and possible motor da-
both start-up and normal operations. mage. Voltage unbalance is given by
The maximum allowable voltage the formula:
High pressure A high-pressure (HP) safety switch is connected to the service valve gauge
required to shut down the compressor port, which must not be isolated.
should the discharge pressure exceed
the values shown in the table below. Note:
The high-pressure switch can be set Because power consumption of scroll
to lower values depending on the compressors is almost directly pro-
application and ambient conditions. portional to discharge pressure, the
The HP switch must either be placed in high-pressure control can be used to
a lockout circuit or consist of a manual indirectly limit the maximum current
reset device to prevent cycling around draw. A high-pressure control used in
the high-pressure limit. If a discharge this manner however can never repla-
valve is used, the HP switch must be ce an external overload protector.
Low pressure A low pressure (LP) safety switch must is given in the following table. For
be used. Deep vacuum operations of systems without pump-down, the LP
a scroll compressor can cause internal safety switch must either be a manual
electrical arcing and scroll instability. lockout device or an automatic switch
Performer® scroll compressors exhibit wired into an electrical lockout circuit.
high volumetric efficiency and may The LP switch tolerance must not al-
draw very low vacuum levels, which low for vacuum operations of the com-
could induce such a problem. The pressor. LP switch settings for pump-
minimum low-pressure safety switch down cycles with automatic reset are
(loss of charge safety switch) setting also listed in the table below:
Working pressure range high side bar (g) 10.9 - 27.7 10.5 - 29.1 6.7 - 20.2 12.7 - 32
Working pressure range low side bar (g) 1.4 - 6.9 1.1 - 6.4 0.6 - 3.9 2 - 7.3
Maximum high pressure safety switch setting bar (g) 28 29.5 20.5 32.5
Minimum low pressure safety switch setting * bar (g) 0.5 0.5 0.5 0.5
Minimum low pressure pump-down switch setting ** bar (g) 1.3 1.0 0.5 1.8
22
http://holodko.ru/
SYSTEM DESIGN RECOMMENDATIONS
Essential piping design Proper piping practices should be em- higher position than the compressor, a
ployed to ensure adequate oil return, suitably sized «U»-shaped trap close to
considerations even under minimum load conditions the compressor is necessary to prevent
with special consideration given to the oil leaving the compressor from drai-
size and slope of the tubing coming ning back to the discharge side of the
from the evaporator. Tubing returns compressor during off cycle. The up-
from the evaporator should be desi- per loop also helps avoid condensed
gned so as not to trap oil and to pre- liquid refrigerant from draining back
vent oil and refrigerant migration back to the compressor when stopped (see
to the compressor during off-cycles. fig. 2).
If the evaporator lies above the com- Piping should be designed with ade-
pressor, as is often the case in split or quate three-dimensional flexibility. It
remote condenser systems, the addi- should not be in contact with the sur-
tion of a pump-down cycle is stron- rounding structure, unless a proper
gly recommended. If a pump-down tubing mount has been installed. This
cycle were to be omitted, the suction protection proves necessary to avoid
line must have a loop at the evapora- excess vibration, which can ultimately
tor outlet to prevent refrigerant from result in connection or tube failure
draining into the compressor during due to fatigue or wear from abrasion.
off-cycles. Aside from tubing and connection da-
mage, excess vibration may be trans-
If the evaporator were situated below mitted to the surrounding structure
the compressor, the suction riser must and generate an unacceptable noise
be trapped so as to prevent liquid re- level within that structure as well (for
frigerant from collecting at the ther- more information on noise and vibra-
mal bulb location (see fig. 1). tion, see the section on: "Sound and
When the condenser is mounted at a vibration management" p.27).
HP
0.5%
>4 m/s HP
max. 4 m
LP
Condenser
U-trap
8 to 12 m/s
max. 4 m LP
0.5% Evaporator
>4m/s
fig 1 fig 2
23
http://holodko.ru/
SPECIFIC APPLICATION RECOMMENDATIONS
Low
ambient compressor
operations
Low ambient operations The Performer® scroll compressor re- rential. Care should be taken during
and minimum pressure quires a minimum pressure differential low ambient operations when heat
of 3 to 4 bar between the suction and removal from air-cooled condensers
differential discharge pressures to force the orbi- is greatest and head pressure con-
ting scroll-down against the oil film on trol may be required for low ambient
the thrust bearing. Anything less than temperature applications. Operation
this differential and the orbiting scroll under low pressure differential may
can lift up, causing a metal-to-metal be observed by a significant increase
contact. It is therefore necessary to in the sound power level generated by
maintain sufficient discharge pressure the compressor.
in order to ensure this pressure diffe-
Low ambient start-up Under cold ambient conditions (<0°C), allowed to operate under vacuum. The
upon start-up the pressure in the con- low-pressure control must be set in ac-
denser and, if present, the receiver may cordance with the table on page 22 in
be so low that a sufficient pressure dif- order to prevent this from happening.
ferential across the expansion device Low pressure differentials can also
cannot be developed to properly feed cause the expansion device to «hunt»
the evaporator. As a result, the com- erratically, which might cause surging
pressor may go into a deep vacuum, conditions within the evaporator, with
which can lead to compressor failure liquid spillover into the compressor.
due to internal arcing and instability This effect is most pronounced during
in the scroll members. Under no cir- low load conditions, which frequently
cumstances should the compressor be occur during low ambient conditions.
Head pressure control under Several possible solutions are availa- Note:
low ambient conditions ble to prevent the compressor from The minimum condensing pressure
drawing down to a vacuum upon start- must be set at the minimum saturated
up under low ambient conditions. In condensing temperature shown in the
air-cooled machines, cycling the fans application envelopes.
with a head pressure controller will en- Under very low ambient conditions,
sure that the fans remain off until the in which testing has revealed that the
condensing pressure has reached a sa- above procedures might not ensure
tisfactory level. In water-cooled units, satisfactory condensing and suction
the same can be performed using a pressures, the use of a liquid receiver
water regulator valve that is also ope- with condenser and receiver pressure
rated by head pressure, thereby en- regulators would be possible.
suring that the water valve does not For further information, please contact
open until the condensing pressure Danfoss Technical Support.
reaches a satisfactory level.
Crankcase heaters Crankcase heaters are strongly recom- tions. The crankcase heater will mi-
mended on all refrigerant systems nimize refrigerant migration caused
where the compressor is exposed to by the large temperature gradient
cold ambient temperatures, especially between the compressor and the re-
split and remote condenser installa- mainder of the system.
24
http://holodko.ru/
SPECIFIC APPLICATION RECOMMENDATIONS
Low load operations It is recommended that the unit be trol. This consideration is especially
tested and monitored at minimum important in manifolded units where
load and, if possible, during low am- low load conditions may require the
bient conditions as well. During con- frequent cycling of compressors. This
ditions of low load on the system, the can lead to liquid refrigerant entering
following considerations should be the compressor if the expansion valve
taken into account to ensure proper does not provide stable refrigerant su-
system operating characteristics. perheat control under varying loads.
● The superheat setting of the expan- ● Condenser fans should be cycled in
sion device should be sufficient to en- such a way that the minimum pressu-
sure proper superheat levels during re differential is maintained between
low loading periods. A minimum of the suction and discharge pressures.
5 K stable superheat is required. In ad- Variable-speed fans can also be used
dition, the refrigerant charge should to control the amount of heat to be re-
be sufficient to ensure proper sub- moved from the condenser.
cooling within the condenser so as to ● The compressors should be run for
avoid the risk of flashing in the liquid a minimum period in order to ensure
line before the expansion device. The that the oil has sufficient time to pro-
expansion device should be sized to perly return to the compressor sumps
ensure proper control of the refrige- and that the motor has sufficient time
rant flow into the evaporator. An over- to cool under conditions of lowest re-
sized valve may result in erratic con- frigerant mass flows.
Brazed plate Brazed plate heat exchange needs plate heat exchanger, no pump-down
very little internal volume to satisfy cycle is normally required. The suction
heat exchangers the set of heat transfer requirements. line running from the heat exchanger
Consequently, the heat exchanger of- to the compressor must be trapped
fers very little internal volume for the to avoid refrigerant migration to the
compressor to draw vapor from on the compressor.
suction side. The compressor can then When using a brazed plate heat ex-
quickly enter into a vacuum condition; changer as the condensing coil, a suffi-
it is therefore important that the ex- cient free volume for the discharge gas
pansion device be sized correctly and to accumulate is required in order to
that a sufficient pressure differential avoid excess pressure buildup. At least
across the expansion device be availa- 1 meter of discharge line is necessary
ble to ensure adequate refrigerant to generate this volume. To help re-
feed into the evaporator. This aspect duce the gas volume immediately af-
is of special concern when operating ter start-up even further, the supply of
the unit under low ambient and load cooling water to the heat exchanger
conditions. For further information on may be opened before the compres-
these conditions, please refer to the sor starts up so as to remove superheat
previous sections. and condense the incoming discharge
Due to the small volume of the brazed gas more quickly.
Reversible heat pump Transients are likely to occur in rever- specific tests for repetitive floodback
sible heat pump systems, i.e. a chan- are required to confirm whether or
systems geover cycle from cooling to heating, not a suction accumulator needs to be
defrost or low-load short cycles. These installed. A crankcase heater and dis-
transient modes of operation may charge gas thermostat are required for
lead to liquid refrigerant carryover reversible heat pump applications.
(or floodback) or excessively wet re- The following considerations cover
frigerant return conditions. As such, the most important issues in the realm
reversible cycle applications require of common applications. Each appli-
specific precautions for ensuring a cation design however should be tho-
long compressor life and satisfactory roughly tested to ensure acceptable
operating characteristics. Regardless operating characteristics.
of the refrigerant charge in the system,
25
http://holodko.ru/
SPECIFIC APPLICATION RECOMMENDATIONS
Crankcase heaters Crankcase heaters are mandatory on off-cycles due to the outdoor location
reversible cycle applications given the of most units and operations during
high probability of liquid migration low ambient conditions.
back to the compressor sump during
Discharge temperature Heat pumps frequently utilize high line to protect the compressor from
thermostat condensing temperatures in order to excessive temperatures. Operating
achieve a sufficient temperature rise the compressor at too high discharge
in the medium being heated. At the temperatures can result in mechanical
same time, they often require low eva- damage to the compressor as well as
porator pressures to obtain sufficient thermal degradation of the compres-
temperature differentials between the sor lubricating oil and a lack of suffi-
evaporator and the outside tempera- cient lubrication.
ture. This situation may result in high The discharge gas thermostat should
discharge temperature; as such, it is be set to shut down the compressor
mandatory that a discharge gas ther- in the event discharge gas rises above
mostat be installed on the discharge 135°C.
Discharge line The Performer® scroll compressor is port and the reversing valve or any
and reversing valve a high volumetric machine and, as other restriction. This gives sufficient
such, can rapidly build up pressure free volume for the discharge gas to
in the discharge line if gas in the line collect and to reduce the pressure
becomes obstructed even for a very peak during the time it takes for the
short period of time which situation valve to change position. At the same
may occur with slow-acting, reversing time, it is important that the selection
valves in heat pumps. Discharge pres- and sizing of the reversing or 4 way
sures exceeding the operating envelope valve ensure that the valve switches
may result in nuissance high pressure quickly enough to prevent against too
switch cutouts and place excess strain high discharge pressure and nuisance
on both the bearings and motor. high pressure cutouts.
To prevent such occurrences, it is Check with the valve manufacturer
important that a 1 meter minimum for optimal sizing and recommended
discharge line length be allowed mounting positions.
between the compressor discharge
Suction line accumulator The use of a suction line accumulator back to a defrost cycle or to normal
is strongly recommended in reversi- cooling operations.
ble-cycle applications as a result of the Sustained and repeated liquid slugging
possibility of a substantial quantity and floodback can seriously impair the
of liquid refrigerant remaining in the oil’s ability to lubricate the compressor
evaporator, which acts as a condenser bearings.This situation can be obser-
during the heating cycle. ved in wet climates where it is neces-
This liquid refrigerant can then return sary to frequently defrost the outdoor
to the compressor, either flooding the coil in an air source heat pump. In such
sump with refrigerant or as a dynamic cases a suction accumulator becomes
liquid slug when the cycle switches mandatory.
26
http://holodko.ru/
SOUND AND VIBRATION MANAGEMENT
Sound generation Typical sound and vibration in of the unit and structure.
Refrigeration and Air-Conditioning Gas pulsation:
in a refrigeration / systems encountered by design and This tends to travel through the coo-
air conditioning system service engineers may be broken ling medium, i.e. the refrigerant.
down into the following three source The following sections will focus on
categories. the causes and methods of mitigation
Sound radiation: for each of the above sources.
This generally takes an airborne path.
Mechanical vibrations:
These generally extend along the parts
Compressor sound For sound radiating from the compres- capable of transmitting sound/vibra-
radiation sor, the emission path is airborne and tion within the unit come into direct
the sound waves are traveling directly contact with any non-insulated parts
from the machine in all directions. on the walls of the unit.
The Performer® scroll compressor is Because of the Performer’s unique de-
designed to be quiet and the frequen- sign of a full-suction gas-cooled mo-
cy of the sound generated is pushed tor, compressor body insulation across
into the higher ranges, which not only its entire operating range is possible.
are easier to reduce but also do not Accoustic hoods are available from
generate the penetrating power of Danfoss Commercial Compressors as
lower-frequency sound. accessories. These hoods are quick
Use of sound-insulation materials on and easy to install and do not increase
the inside of unit panels is an effec- the overall size of the compressors to
tive means of substantially reducing a great extend. Refer to page 35 for
the sound being transmitted to the sound attenuation and code num-
outside. Ensure that no components bers.
Mechanical vibrations Vibration isolation constitutes the pri- the frame supporting the mounted
mary method for controlling structural compressor be of sufficient mass and
vibration. Performer® scroll compres- stiffness to help dampen any residual
sors are designed to produce minimal vibration potentially transmitted to
vibration during operations. The use the frame. For further information on
of rubber isolaters on the compressor mounting requirements, please refer
base plate or on the frame of a mani- to the section on mounting assembly.
folded unit is very effective in redu- The tubing should be designed so
cing vibration being transmitted from as to both reduce the transmission
the compressor(s) to the unit. Rubber of vibrations to other structures and
grommets are supplied with all Perfor- withstand vibration without incurring
mer® compressors. Once the supplied any damage. Tubing should also be
rubber grommets have been properly designed for three-dimensional flexi-
mounted, vibration transmitted from bility. For more information on piping
the compressor base plate to the unit design, please see the section entitled
are held to a strict minimum. In ad- "Essential piping design considera-
dition, it is extremely important that tions" p. 23.
Gas pulsation The Performer® scroll compressor has ted conditions and operating configu-
been designed and tested to ensure rations to ensure that minimum gas
that gas pulsation has been optimized pulsation is present. If an unaccep-
for the most commonly encountered table level is identified, a discharge
air conditioning pressure ratio. On muffler with the appropriate resonant
heat pump installations and other volume and mass should be installed.
installations where the pressure ratio This information can be obtained from
lies beyond the typical range, testing the component manufacturer.
should be conducted under all expec-
27
http://holodko.ru/
INSTALLATION
Compressor handling Each Performer® scroll compressor is lift rings on the compressor to lift the
delivered with two lift rings. Always entire installation, which may be too
use these rings when lifting the com- heavy for lifting in this manner.
pressor. A spreader bar rated for the Maintain the compressor in an upright
mass of the compressor is highly re- position during all handling maneu-
commended to ensure a better load vers.
distribution. Given that the center of Never apply force to the terminal box
gravity on the scroll is very high, the with the intention of moving the com-
use of one lifting lug will result in an pressor, as the force placed upon the
unstable load. The compressor mass is terminal box will cause extensive da-
too great for the single lug to handle, mage to both the box and the even-
and the risk is run that the lug could tual motor protection module compo-
separate from the compressor with ex-
tensive damage and possible personal
injury as a result.
The use of lifting hooks closed with a
clasp and certified to lift the weight of
the compressor is also highly recom-
mended (see the adjacent figure).
Always respect the appropriate rules
concerning lifting objects of the type
and weight of these compressors.
When the compressor is mounted as
part of an installation, never use the
Mounting All compressors come delivered with 21 Nm. The bolts and washers are sup-
four rubber mounting grommets and plied with the assembly kit.
metal sleeve liners that serve to isolate The required bolt size for the SY / SZ
the compressor from the base frame. 240 to 380 compressors is HM10. The
These grommets attenuate to a great minimum required flat washer out-
extent the transmission of compressor side diameter is 27 mm. Mounting
vibrations to the base frame. The rub- bolts must be tightened to a torque of
ber grommets must be compressed 40 Nm. These bolts and washers are
until contact between the flat washer not supplied with the compressor.
and the steel-mounting sleeve is esta-
blished. Note:
The required bolt size for the SM / SZ The large flat washer must be positio-
084 to 185 compressors is HM8. This ned in place before shipping the unit
bolt must be tightened to a torque of with the compressor installed.
Lock washer
Compressor
HM 8 Bolt base plate
Flat washer
28 mm
Steel mounting sleeve
Rubber grommet
Nut
28
http://holodko.ru/
INSTALLATION
36 mm
Steel mounting sleeve
Rubber grommet
Nut*
Removing connections Before the suction and discharge plugs fore connecting the compressor to the
are removed, the nitrogen holding installation in order to avoid moisture
shipping plugs charge must be released via the suc- from entering the compressor. When
tion schrader valve to avoid an oil mist the plugs are removed, it is essential
blowout. Remove the suction plug first to keep the compressor in an upright
and the discharge plug afterwards. The position so as to avoid oil spillage.
plugs shall be removed only just be-
System cleanliness The refrigerant compression system, requires that the oil be exposed to the
regardless of the type of compressor atmosphere just as little as possible.
used, will only provide high efficiency System contamination is one of main
and good reliability, along with a long factors affecting equipment reliabi-
operating life, if the system contains lity and compressor service life. It is
solely the refrigerant and oil it was important therefore to take system
designed for. Any other substances cleanliness into account when assem-
within the system will not improve bling a refrigeration system.
performance and, in most cases, will During the manufacturing process, cir-
be highly detrimental to system ope- cuit contamination may be caused by:
rations.
● Brazing and welding oxides,
The presence of non-condensable ● Filings and particles from the remo-
substances and system contaminants, val of burrs in pipe-work,
such as metal shavings, solder and
● Brazing flux,
flux, have a negative impact on com-
● Moisture and air.
pressor service life. Many of these con-
taminants are small enough to pass Consequently, when building equip-
through a mesh screen and can cause ment and assemblies, the following
considerable damage within a bearing precautions must be taken:
assembly. The use of highly-hygrosco- Never drill holes into the pipe-work af-
pic polyester oil in R407C compressors ter installation.
Tubing Only use clean and dehydratated refri- rant-grade fittings should be used and
geration-grade copper tubing. Tube- these must be of both a design and
cutting must be carried out so as not size to allow for a minimum pressure
to deform the tubing roundness and drop through the completed assem-
to ensure that no foreign debris re- bly. Follow the brazing instructions
mains within the tubing. Only refrige- next pages.
29
http://holodko.ru/
INSTALLATION
Filter driers For new installations with SY / SZ com- mina are recommended. Also for new
pressors with polyolester oil, Danfoss installations with SM compressors
Commercial Compressors recom- with mineral oil the Danfoss DCL drier
mends using the Danfoss DML 100%- is recommended.
moleculair sieve, solid core filter drier. The drier is to be oversized rather than
Molecular sieve filter driers with loose undersized. When selecting a drier,
beads from third party suppliers shall always take into account its capacity
be avoided. For servicing of existing (water content capacity), the system
installations where acid formation is refrigeration capacity and the system
present the Danfoss DCL solid core refrigerant charge.
filter driers containing activated alu-
Copper to copper When brazing copper-to-copper con- silver or more with a melting tempera-
connections nections, the use of a copper/phos- ture of below 800°C is recommended.
phorus brazing alloy containing 5% No flux is required during brazing.
Dissimilar metals When manipulating dissimilar metals use of silver solder and anti-oxidant
connection such as copper and brass or steel, the flux is necessary.
30
http://holodko.ru/
INSTALLATION
into the joint, but not into the com- plugs shall be removed just before
pressor. brazing the compressor.
● Remove all remaining flux once the
Before eventual unbrazing
joint has been soldered with a wire the compressor or any system
brush or a wet cloth. Remaining flux component, the refrigerant charge
would cause corrosion of the tubing. must be removed from both the
Ensure that no flux is allowed high- and low-pressure sides. Failu-
to enter into the tubing or re to do so may result in serious per-
compressor. Flux is acidic and can sonal injury. Pressure gauges must
cause substantial damage to the in- be used to ensure all pressures are
ternal parts of the system and com- at atmospheric level.
pressor.
For more detailed information on the
The polyolester oil used in appropriate materials required for bra-
SY / SZ compressors is highly zing or soldering, please contact the
hygroscopic and will rapidly absorb product manufacturer or distributor.
moisture from the air. The compres- For specific applications not covered
sor must therefore not be left open herein, please contact Danfoss Com-
to the atmosphere for a long pe- mercial Compressors for further infor-
riod of time. The compressor fitting mation.
System pressure test Always use an inert gas such as nitro- or acetylene as these may form an in-
gen for pressure testing. Never use flammable mixture. Do not exceed the
other gasses such as oxygen, dry air following pressures:
Leak detection Leak detection must be carried out or acetylene as these may form an in-
using a mixture of nitrogen and refri- flammable mixture.
gerant or nitrogen and helium, as in- Pressurize the system on HP side first
dicated in the table below. Never use then Low side.
other gasses such as oxygen, dry air
Note 1: Leak detection with refrigerant may be forbidden in some countries. Check local
regulations.
Note 2: The use of leak detecting additives is not recommended as they may affect the
lubricant properties.
31
http://holodko.ru/
INSTALLATION
Vacuum pump-down and Moisture obstructs the proper functio- tion can also lead to copper plating.
ning of both the compressor and the All these phenomena may cause both
moisture removal refrigeration system. Air and moisture mechanical and electrical compres-
reduce service life and increase con- sor failures. The typical method for
densing pressure, which causes ab- avoiding such problems is a vacuum
normally high discharge temperatures pump-down executed with a vacuum
that are then capable of degrading the pump, thus creating a minimum va-
lubricating properties of the oil. The cuum of 500 microns (0.67 mbar).
risk of acid formation is also increased Please refer to Bulletin "Vaccum pump
by air and moisture, and this condi- down and dehydration procedure".
Refrigerant charging For the initial charge the compressor the filter drier. Then during commis-
must not run and eventual service val- sioning, when needed, a complement
ves must be closed. Charge refrigerant of charge can be done in liquid phase:
as close as possible to the nominal sys- slowly throttling liquid in on the low
tem charge before starting the com- pressure side as far away as possible
pressor. This initial charging operation from the compressor suction connec-
must be done in liquid phase as much tion. The refrigerant charge quantity
as possible away from the compressor: must be suitable for both summer and
the best location is on the liquid line winter operations.
between the condenser outlet and
Commissioning The system must be monitored after pressor sump temperature 10 K above
initial start-up for a minimum of 60 saturation temperature to show that
minutes to ensure proper operating there is no refrigerant migration ta-
characteristics such as: king place,
● Proper metering device operation ● Acceptable cycling rate of compres-
and desired super heat readings, sors, including duration of run times,
● Suction and discharge pressure are ● Current draw of individual compres-
Oil level check When the compressor is running un- minutes after the compressor stops,
der stabilised conditions the oil level the level must be between 1/4" and
must be visible in the sight glass. 3/4" of sight glass.
The presence of foam filling in the sight
glass undicates large concentration of When compressor is off the
refrigerant in the oil and / or presence level in the sight glass can be
of liquid returning to the compressor. influenced by the presence of refri-
The oil level can also be checked a few gerant in the oil.
Oil top-up Always use original Danfoss Commer- filling in instructions for Danfoss Com-
cial Compressors specified oil type mercial Compressors".
from new cans.
Top-up the oil while the compressor is Please note that the compres-
running. Use the Schrader connector sors SZ and SY use different
and a suitable pump or any other ac- viscosity POE oil, respectively 160SZ
cessible connector on the compressor and 320SZ.
suction line. See Bulletin "Lubricants,
32
http://holodko.ru/
ACCESSORIES
Lubricants SM / SY / SZ compressors use different For initial compressor oil charge refer
oil types as indicated below. to page 6-7. Please refer to "Lubricant,
Always use original Danfoss Commer- filling in instructions for Danfoss Com-
cial Compressors specified oil type mercial Compressors" for detailed oil
from new cans. specifications and top-up method.
code number
Compressor model Oil type Oil name
1 litre can 2 litre can 5 litre can
SM compressors Mineral 160P - 7754001 7754002
33
http://holodko.ru/
ACCESSORIES
Crankcase heaters The belt-type crankcase heater the compressor against off-cycle
accessories are designed to protect migration of refrigerant
Optimum location
area
h 1/2 h
1/3 h
34
http://holodko.ru/
ACCESSORIES
Discharge temperature The discharge gas temperature must The thermostat must be attached to
not exceed 135°C. the discharge line within 150 mm from
protection the compressor discharge port.
The discharge gas thermostat acces-
sory kit includes all components requi- Discharge thermostat kit code num-
red for installation, as shown below. ber: 7750009.
Thermostat
Discharge line
Insulation
Bracket
Compressor Compressor acoustic hoods have been porate soundproofing materials and
developed to meet specific extra-low offer excellent high and low frequency
acoustic hoods noise requirements. The covers incor- attenuation.
attenuation* Hood
Compressor model (at 50Hz) code
dB(A) number
35
http://holodko.ru/
ORDERING INFORMATION AND PACKAGING
Ordering information Performer® scroll compressors may The below tables lists the code num-
be ordered from Danfoss Commercial bers for industrial packs. For ordering
Compressors in either industrial packs single packs please replace the last
(Multiple packaging) or in single packs digit with an " I " .
(Individual packaging).
36
http://holodko.ru/
ORDERING INFORMATION AND PACKAGING
37
http://holodko.ru/
ORDERING INFORMATION AND PACKAGING
Packaging
Gross Static
Length Width Height
Compressor models Nbr* weight stacking
mm mm mm
kg pallets
38
http://holodko.ru/
http://holodko.ru/
Danfoss Commercial Compressors http://cc.danfoss.com
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also
applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks
in this material are property of the respective companies. Performer®, Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
FRCC.PC.003.A1.02 - March 2005 www.kraft.fr
http://holodko.ru/