Presentation

Premium automation platform


InterBus-S bus

Presentation
The InterBus-S bus is a serial link type fieldbus for sensors and actuators which conforms to the requirements of an industrial environment.

Premium

IP 65 Momentum I/O Installation remote bus module

ATV-66

$ 24 V Installation remote bus module

Bus terminal module $ 24 V IP 65 Momentum I/O

Momentum
The topology of the InterBus-S bus is designed as a ring system with master/slave central access procedure. It is subdivided into three parts : / The remote bus 1 (bus devices use RS 485 point-to-point connection). / The installation remote bus 2 (remote bus tap link via a bus terminal module). Its technology is particularly suitable for IP 65 dust and damp proof systems. / The local bus with TTL technology is particularly suitable for buses within a control cabinet. Each bus subscriber comprises a transmitter and a receiver. The InterBus-S system is like a data ring and has the structure of a shift register distributed on the bus. With its registers, each module constitutes a component of this shift register ring. The InterBus-S master circulates the data in series on this ring.

Characteristics : page 43602/4 43602_Ver4.00-EN.fm/2

References : page 43602/5


Schneider Electric

Description, connectable devices

Premium automation platform


InterBus-S bus

Description
Premium PLCs are connected to the InterBus-S bus via the TSX IBY 100 InterBus-S bus module. The TSX IBX 100 communication coprocessor can be used to connect a PCX 57 coprocessor integrated in a PC compatible to the InterBus-S bus. The front panel on the TSX IBY 100 module comprises : 1 1 A display block with 6 indicator lamps (on the card for the TSX IBX 100) 2 A 9-way female RS 232 SUB-D connector : CMD Tool software support (configuration software) 2 3 3 A 9-way female RS 232 SUB-D connector : InterBus-S link (this connector integrates an additional power supply for the fibre optic link)

Connectable devices
The TSX IBY 100 or TSX IBX 100 module acts as the master on the InterBus-S bus : other Schneider Electric devices (slaves) which can be connected on the bus are : / ATV variable speed drives / XBT-BB operator terminals / Telefast IP20 I/O interfaces / Momentum I/O / AS-i/InterBus-S gateway / Any third-party device conforming to InterBus-S standard profiles

Characteristics : page 43602/4


Schneider Electric

References : page 43602/5 43602_Ver4.00-EN.fm/3

Characteristics, software configuration

Premium automation platform


InterBus-S bus

Characteristics of the bus supported by TSX IBY 100 modules or TSX IBX 100 coprocessors
Type of bus Structure Type Physical interface Industrial bus RS 485 RS 485 with $ 24 V in cable TTL Combined interface (vertically mounted signal and $ 24 V power supply) Remote bus Installation remote bus Local bus InterBus loop

Method of access Transmission Mode Data rate Medium

Master/Slave NRZ 500 kbps - Twisted pair - Fibre optic - Wave guide rail - Infra-red - Rotating collector Special cable for : - Sensor and I/O module 24V power supply - data transmission Special cable 2 x 1.5 mm2

Physical configuration Length of a segment Maximum length of cable between : 400 m maxi - Bus terminal module and 1st module : 1.5 m - 2 modules : 1,5 m Bus terminal module and last module : 10 m 8 200 max. in the loop - Bus terminal module and 1st interface : 20 m - 2 modules : 10 m Bus terminal module and last module : 100 m 1 loop per bus term. module 63

- Module and the 1st bus - Bus terminal module terminal module : 400 m and 1st module : 50 m - 2 bus term. modules : 400 m - 2 modules : 50 m Module and last station on the remote bus : 12.8 km The bus terminal module and last module : 50 m Total current of connected modules : 4.5 A max.

Number of tap links Number of bus terminal modules Number of slaves Number of I/O InterBus-S services

16 max. 254 max. 512 max. 3872 I/3872 Q max. (4096 I/O in total)

Implicit exchange of process data : 242 %IW and 242 %QW - Pre-processing - Logical addressing - Segmentation

Software configuration
The InterBus-S bus can be configured in 3 modes : / Auto mode : This mode does not require the use of any special configuration software (I/O images are copied to %IW, %QW implicitly). It facilitates the wiring check. / Mode PL7  IBY mode : This mode is used to define and load the configuration to the module (explicit assignment of %IW, %QW). The CMD Tool software (1) is required in order to generate the configuration text file / CMD  IBY mode : Reserved for configurations > 8 K words, and requires the use of the CMD Tool software. PMS message handling (usable on PCP devices) is managed via standard OFs (Read-var, Write-var, etc). The catalogue file which enables Schneider Electric devices to be integrated in the CMD Tool software is available on our Web site : / Address : www.schneiderautomation.com / File for downloading : Schneider device catalog for CMD G4

(1) Contact your Phnix Contact vendor.

References : page 43602/5 43602_Ver4.00-EN.fm/4


Schneider Electric

References

Premium automation platform


InterBus-S bus

References
Interbus-S bus modules Description No. of modules per PLC/PC InterBus-S module for Premium PLC 0 on TSX 57-10 1 on TSX/PCX 57-20 2 on TSX/PCX 57-30 2 on TSX 57-40 Communication Services profile Master/Slave 0.5 M bps Reference (1) Weight kg 0.320

- cyclical variable TSX IBY 100 exchanges - PMS messaging - bus operating modes managemt

TSX IBY 100

InterBus-S coprocessor for PCX coprocessor

0 on TSX 57-10 1 on TSX/PCX 2 on TSX/PCX 2 on TSX 57-40

Master/Slave 0.5 Mbps

- cyclical variable TSX IBX 100 exchanges - PMS messaging - bus operating modes managemt

0.280

Converter software Description Use Symbol converter software Used to convert CMD symbols into PL7 symbols

Reference TLX LIBS CNVE

Weight kg

TSX IBX 100

Bus connection elements Description Use Momentum communication module Momentum I/O base units on InterBus-S bus

Length

Reference (1) 170 INT 110 00

Weight kg

170 INT 110 00

Remote bus cables

100 m

TSX IBS CA 100

400 m

TSX IBS CA 400

Installation remote bus cables

Preformed cables for linking 2 communication modules

0.110 m

170 MCI 007 00

1m

170 MCI 100 00

Connecting cable

TSX IB/ to PC connection (with CMD Tool software)

3m

990 NAA 263 20

9-way Remote bus cables SUB-D connectors (sold in lots of 2)

170 XTS 009 00

0.045

(1) Product supplied with multilingual Quick Reference Guide : English and French.