Refrigerant Line Sizing Table
Refrigerant Line Sizing Table
115 SIZING
Skills REFRIGERANT
Workshop SUCTION LINES
If the full-rated capacity of refrigeration equipment is to be
PROUDLY SPONSORED BY achieved, careful attention must be given to the proper sizing
of suction, liquid and discharge lines.
Excessive pressure drop leads to reduced system capacity,
while insufficient vapour velocity causes compressor lubrication
problems. When a condensing unit is used on a particular
Skills summary
n What?
installation, the discharge line does not present a problem,
as this is already sized and piped into the unit. The suction
and liquid lines, however, must always be correctly sized, as
A guide to the correct sizing of excessive pressure drop in either of these lines will impose a
suction lines in a refrigeration system.
severe penalty on the operating capacity of the compressor.
n Who?
Relevant for anyone involved in the design, This skills workshop provides methods of sizing the suction
selection, installation, operation, maintenance
and assessment of refrigeration systems. line, with an example.
PULLOUT
DETERMINING Elbows
THE TUBING SIZE 90° std 0.4 0.5 0.6 0.8 1 1.2 1.5 1.8 2.3 2.7 3
Tables 2 and 3 of suction line sizes for 90° long radius 0.3 0.3 0.4 0.5 0.7 0.8 1 1.2 1.5 1.8 2
refrigerants R134a and R22 enable line size to
45° std 0.2 0.2 0.3 0.4 0.5 0.6 0.8 1 1.2 1.4 1.6
be selected according to the suction temperature,
equivalent length and the evaporator capacity 180° std 0.7 0.8 1.0 1.2 1.7 1.9 2.5 3 3.7 4.6 5.2
by direct reference. The sizes selected will result
in a pressure drop of approximately 1 kelvin only. Tees
Note:
While use of R22, an HCFC refrigerant, is being phased Branch flow 0.8 0.9 1.2 1.5 2.1 2.4 3 3.7 4.6 5.5 6.4
out, Table 2.4 and its accompanying example calculation
still provide a good illustration of the pipe‑sizing process. Str thr flow 1:1 0.3 0.3 0.4 0.5 0.7 0.8 1 1.2 1.5 1.8 2
Under Australia’s commitment to the Montreal Protocol, Str thr flow 1:4 (red) 0.4 0.4 0.6 0.7 0.9 1.1 1.4 1.7 2.1 2.4 2.7
imports of R22 have essentially ceased, though annual imports
of small amounts will be allowed until 2030 for servicing Str thr flow 1:2 (red) 0.4 0.5 0.6 0.8 1 1.2 1.5 1.8 2.3 2.7 3
of long‑lived existing equipment and use of existing stocks
and re‑use of recycled R22 will also be permitted. (Reproduced with permission of Heatcraft Australia.)
10 1.19 2.72 5.13 8.76 13.6 27.4 47.8 75.7 156 277
20 0.81 1.86 3.50 5.98 9.26 18.7 32.7 51.7 107 189
10°C 30 0.65 1.49 2.80 4.79 7.41 15.0 26.1 41.4 85.7 152
15.34 40 0.55 1.27 2.39 4.09 6.32 12.8 22.3 35.3 73.2 129
50 0.49 1.12 2.12 3.61 5.59 11.3 19.7 31.2 64.7 114
60 0.44 1.02 1.91 3.27 5.06 10.2 17.8 28.3 58.5 104
10 0.99 2.29 4.29 7.33 11.34 23.0 40.1 63.5 132 232
20 0.68 1.56 2.93 5.00 7.74 15.7 27.4 43.4 89.8 158
5°C 30 0.54 1.25 2.35 4.00 6.20 12.6 21.9 34.7 71.9 127
13.45 40 0.46 1.07 2.00 3.42 5.29 10.7 18.7 29.6 61.4 108
50 0.41 0.94 1.77 3.02 4.68 9.50 16.6 26.2 54.3 95.7
60 0.37 0.85 1.60 2.73 4.23 8.59 15.0 23.7 49.1 866.6
10 0.82 1.88 3.56 6.09 9.42 19.2 33.3 52.9 110 194
20 0.56 1.29 2.43 4.16 6.43 13.1 22.8 36.1 74.8 132
0°C 30 0.45 1.03 1.94 3.33 5.15 10.5 18.2 28.9 59.9 106
11.74 40 0.38 0.88 1.66 2.84 4.39 8.95 15.5 24.7 51.1 90.3
50 0.34 0.78 1.47 2.51 3.89 7.92 13.8 21.8 45.2 79.9
60 0.31 0.70 1.33 2.27 3.52 7.16 12.4 19.7 40.9 72.3
10 0.67 1.55 2.93 5.01 7.76 15.8 27.6 43.6 90.5 160
20 0.46 1.06 2.00 3.42 5.30 10.8 18.8 29.8 61.8 109
−5°C 30 0.37 0.85 1.60 2.74 4.24 8.62 15.1 23.8 49.5 87.5
10.47 40 0.31 0.73 1.37 2.34 3.62 7.36 12.9 20.3 42.2 74.7
50 0.28 0.64 1.21 2.07 3.20 6.51 11.4 18.0 37.4 66.1
60 0.25 0.58 1.09 1.87 2.90 5.89 10.3 16.3 33.8 59.8
10 0.55 1.27 2.39 4.08 6.33 12.9 22.5 35.6 74.13 131
20 0.37 0.86 1.63 2.79 4.32 8.80 15.4 24.3 50.6 89.6
−10°C 30 0.30 0.69 1.31 2.23 3.46 7.04 12.3 19.5 40.5 71.7
8.76 40 0.26 0.59 1.11 1.90 2.95 6.01 10.5 16.6 34.6 61.2
50 0.23 0.52 0.99 1.68 2.61 5.32 9.29 14.7 30.6 54.1
60 0.20 0.47 0.89 1.52 2.36 4.81 8.40 13.3 27.7 49.0
70 0.06 0.26 0.65 1.30 2.23 3.48 5.11 6.76 9.19 12.1 15.5 19.40 40.6 72.2
Minimum capacity for oil return 0.50 0.90 1.57 2.19 3.26 4.32 5.78 7.20 9.08 11.0 22.5 38.2
10 0.12 0.51 1.29 2.57 4.41 6.94 10.2 13.5 18.2 24.0 30.8 38.8 81.4 145
20 0.08 0.35 0.88 1.75 3.01 4.74 6.93 9.19 12.4 16.4 21.0 26.5 55.6 98.7
30 0.07 0.28 0.70 1.40 2.41 3.79 5.55 7.36 9.95 13.1 16.8 21.2 44.5 79.0
−25°C 40 0.06 0.24 0.60 1.20 2.06 3.24 4.73 6.28 8.50 11.2 14.4 18.1 38.0 67.4
50 0.05 0.21 0.53 1.06 1.82 2.86 4.19 5.55 7.51 9.91 12.7 16.0 33.6 59.7
(9.09)
60 0.05 0.19 0.48 0.96 1.65 2.59 3.79 5.02 6.80 8.97 11.5 14.5 30.4 54.0
70 0.04 0.17 0.44 0.88 1.51 2.38 3.48 4.62 6.24 8.24 10.6 13.3 27.9 49.6
80 0.04 0.16 0.41 0.82 1.41 2.21 3.23 4.29 5.80 7.65 9.80 12.4 25.9 46.1
Minimum capacity for oil return 0.42 0.76 1.32 1.88 2.75 3.65 4.85 6.09 7.75 9.42 19.1 32.5
10 0.06 0.26 0.67 1.33 2.31 3.61 5.30 6.96 9.46 12.5 16.0 20.1 42.5 75.9
20 0.04 0.18 0.46 0.91 1.58 2.47 3.62 4.75 6.46 8.50 10.1 13.8 29.0 51.8
30 0.03 0.14 0.37 0.73 1.26 1.97 2.90 3.80 5.17 6.80 8.76 11.0 23.2 41.8
−40°C 40 0.03 0.12 0.31 0.62 1.08 1.69 2.47 3.25 4.41 5.81 7.48 9.38 19.8 35.4
50 0.03 0.11 0.28 0.55 0.95 1.49 2.19 2.87 3.90 5.14 6.61 8.29 17.5 31.3
(5.485)
60 0.02 0.10 0.25 0.50 0.86 1.35 1.98 2.60 3.53 4.65 5.98 7.50 15.7 28.3
70 0.02 0.09 0.23 0.46 0.79 1.24 1.82 2.39 3.24 4.27 5.50 6.89 14.6 26.0
80 0.02 0.08 0.21 0.42 0.74 1.15 1.69 2.22 3.01 3.97 5.11 6.41 13.5 24.2
Minimum capacity for oil return 0.32 0.56 1.04 1.44 2.10 2.78 3.75 4.71 6.08 7.39 14.4 25.0
For other condensing temperatures, multiply carrying capacity values by the Example:
following correction factors: Suction line needs to be sized for an ‘Apex Cold Stores’ freezer, with the condensing unit 12 metres from the evaporator.
The condensing unit’s refrigerating capacity is approximately 8700 watts at −35°C suction. There are eight bends, and one
angle valve (crankcase pressure regulator) and one globe valve.
Condensing temperature
1. An estimate must be made as to the probable line size to permit equivalent lengths to be made. Reference to Table 3
27°C 32°C 38°C 43°C 49°C 54°C for R22 refrigerant with capacity of 8700 watts at −40°C shows size would be 35mm tube (given that 38mm pipe,
which more closely matches 8700, is not commonly available in refrigerant grade).
1.11 1.07 1.03 0.92 0.86 0.80
2. Working with 35mm tube, the equivalent lengths (as listed in Table 2.2 are):
Minimum capacities for oil return up vertical risers based on 8K superheat (a) 1 globe valve (manual shut‑off ) = 12.0 metres EDITION
05
and 32°C liquid temperature. Increase or reduce table values by 2 per cent for (b) 1 angle valve (CPR) = 4.6 metres AUSTRALIA
GERATION
N REFRI TIONING
AND AIR-C
ONDI
NATIONAL
RESOURCE
5K more or less superheat. For other liquid temperatures, multiply table values (c) 8 x 90° bends = 8 x 1 = 8.0 metres
by the following factors: (d) straight tube = 12.0 metres
TO YOU
HT BY
UG
O
BR
CE 1920
GIVIN
SIN
G
RY
A
B
C T
K
TO US
THE I ND
02
Liquid temperature 3. Referring to Table 3 (30m equivalent length row in − 40°C section), This month’s
Skills Workshop has
it can be seen that, for evaporator capacity of 8700 W, the listed tubing been taken from
16°C 21°C 27°C 38°C 43°C 49°C 54°C size is 38.1mm. Australian Refrigeration
and Air-Conditioning
1.15 1.10 1.05 0.95 0.90 0.85 0.80 4. Cross‑checking in the 40m column, 7.48 kW capacity is a bit low. Volume 2,
by Graham Boyle, F.AIRAH.
(Reproduced with permission of Heatcraft Australia.) 5. Because 38.1mm is not a standard refrigeration pipe size, 41.3 is selected.