SIL MANUAL

SAFETY
INSTRUMENTED
SYSTEMS
DIGITAL PREVIEW

Plant Engineering and Maintenance


according to
IEC 61508 and IEC 61511

▪ Safety Integrity Levels


▪ Reliability and Probability of Failure on Demand
▪ Redundant System Architectures
▪ Risk Reduction
▪ Safety Requirements Specification
▪ IEC 61508 and IEC 61511 compendiums

5th Edition
SAFETY INSTRUMENTED SYSTEMS

Manual for Plant Engineering and Maintenance

With reference to IEC61508 Ed. 2.0 “Functional safety of electrical/


electronic/programmable electronic safety-related systems” and
IEC61511 Ed. 2.0 “Functional safety - Safety instrumented systems for the
process industry sector”.

5th Edition

Authors
Basilio Abbamonte
Software Development and Quality Assurance Manager, GM International. (Retired)

Glisente Landrini
Former President and Managing Director, GM International.

Chapters 7; 8; 10
Tino Vande Capelle
Director Functional Safety Services, GM International.
FS Senior Expert and Trainer (TÜV Rheinland, # 0109/05, SIS).

www.gminternational.com

1
ISBN: 978-88-942087-0-2
ISBN-A: 10.978.88942087 / 02
SIAE: 2017000345

Copyright: © 2025 G.M. International s.r.l.

All rights reserved. No part of this publication may be reproduced, stored in a retrieval
system or trasmitted in any form or by any means, mechanical, electronic, photocopying,
recording or otherwise without the prior written permission of GM International.
For information please contact:
G.M. International s.r.l., Via G. Mameli 53-55, 20852 Villasanta (MB), Italy

Printed in Italy, March 2025


2
Introduction

GM International designs, manufactures and sells SIL2 and SIL 3 certified Intrinsically Safe
Interfaces for use in Hazardous Locations, Safety Relays and Power Supplies that are
intended to prevent accidents before they occur, thus reducing risk and enhancing safety
in a very wide variety of applications.

This manual is a practical aid for the analysis, installation and maintenance of safety
instrumented systems and associated components and will hopefully serve as a guide for
understanding and implementing procedures into practical applications.

It represents an effort to share the results achieved in many years of research and
experience in the field, with anyone willing to approach Safety Related Systems.

This manual is not intended for safety reliability specialists, but for the thousands of
professionals employed in process industries who work with safety instrumented systems
and who are expected to follow the appropriate industry standards.

Aren’t the standards alone enough? The answer depends upon the knowledge and
experience of the individual and the company.

The growing demand for experts in a critical sector like functional safety, underlies the
urgency of a greater awareness and comprehension of all subjects presented herein.

Glisente Landrini
Former President of GM International

3
Index

Index

Authors........................................................................................................................... 1
Introduction...................................................................................................................3
Index...............................................................................................................................5
Chapter 1 Presentation of IEC 61508, IEC 61511 and other safety related
standards..................................................................................................11
1.1 Scope of IEC 61508...............................................................................................................................14
1.1.1 Safety.................................................................................................................................................15
1.1.2 IEC 61508: Brief description.........................................................................................................16
1.2 Other Safety-related standars............................................................................................................18
1.2.1 HSE - PES..........................................................................................................................................19
1.2.2 DIN (V) 19250...................................................................................................................................19
1.2.3 AIChE - CCPS...................................................................................................................................19
1.2.4 ISA-SP84.01 - 1996..........................................................................................................................19
1.2.5 API RTP 556....................................................................................................................................20
1.2.6 NFPA 85............................................................................................................................................20
1.2.7 IEC 61511 – 2004 (ANSI/ISA-84.00.01-2004)............................................................................21
1.2.8 API RP 14C.........................................................................................................................................21
1.2.9 Risk of relevant accidents, in EEC Standards..........................................................................21

Chapter 2 Prevention and mitigation layers for hazardous events.................. 23


2.1 Plants and processes in their environmental context.................................................................25
2.2 Process Control System......................................................................................................................27
2.3 Alarm system..........................................................................................................................................28
2.4 Emergency Shutdown system...........................................................................................................29
2.5 Physical protection and release devices........................................................................................30
2.6 Physical protections and containment systems.............................................................................31
2.7 Physical protections and dispersion systems................................................................................32
2.8 Physical protections and Fire & Gas neutralizing systems........................................................32
2.9 Internal emergency plan (evacuation procedures)......................................................................34
2.10 External emergency plan (evacuation procedures).....................................................................34
2.11 Considerations on protection levels................................................................................................35

Chapter 3 Basic concepts for a better comprehension of safety standards....37


3.1 Reliability and Unreliability................................................................................................................. 37
3.1.1 Reliability.......................................................................................................................................... 37
3.1.2 Unreliability......................................................................................................................................40

5
Index

3.2 Availability and unavailability..............................................................................................................41


3.2.1 Ambiguity of the term “availability”...........................................................................................43
3.2.2 Achievable Availability..................................................................................................................46
3.2.3 Operational Availability.................................................................................................................46
3.3 MTTF, MTTR, MTBF and their relations........................................................................................... 47
3.4 Failure Rate.............................................................................................................................................49
3.4.1 Components with constant failure rate.....................................................................................51
3.4.2 Failure rate Categories.................................................................................................................52
3.4.3 Dependent, or common cause, failures...................................................................................54
3.4.4 Common cause failures and Beta factor..................................................................................54
3.5 Safety analysis for SIL level selection: Modeling methods........................................................54
3.5.1 Reliability block diagrams............................................................................................................55
3.5.2 Fault tree analysis..........................................................................................................................56
3.5.3 Markov diagrams............................................................................................................................60

Chapter 4 Consequence Analysis of relevant accidents involving chemical


substances...............................................................................................73
4.1 Analysis of risks from the release of chemical substances....................................................... 73
4.2 Flammability effects.............................................................................................................................78
4.2.1 Pool fire.............................................................................................................................................78
4.2.2 Jet fire...............................................................................................................................................79
4.2.3 Flash fire...........................................................................................................................................80
4.2.4 Fireball / BLEVE...............................................................................................................................81
4.2.5 Explosion effects............................................................................................................................82
4.3 Toxic hazard: Dispersion modeling..................................................................................................85

Chapter 5 Safety Instrumented Systems (SIS)..................................................... 89


5.1 Introduction............................................................................................................................................89
5.2 Safety requirements.............................................................................................................................90
5.3 Average Probability of Failure on Demand (PFDavg), Safety Integrity Levels (SIL).............93
5.4 System architectures.........................................................................................................................100
5.4.1 Introduction...................................................................................................................................100
5.4.2 Common cause factor (β) and PFDavg for redundant architectures.............................. 103
5.4.3 1oo1 system architecture............................................................................................................ 105
5.4.4 1oo2 architecture........................................................................................................................... 112
5.4.5 2oo3 system architecture........................................................................................................... 118
5.4.6 Comparison between system architectures......................................................................... 122
5.5 Summary of simplified equations................................................................................................... 124
5.5.1 Influence of time interval and duration of periodic tests, on PFDavg, for redundant
equal components....................................................................................................................... 125
5.5.2 Application exercises using simplified equations................................................................ 125
5.6 Use of valves in Safety Instrumented Systems........................................................................... 127
5.6.1 Bypass examples and possibilities of on-line periodic proof testing for SIS shutdown
valves, or other field devices used in 1oo1 system architecture...................................... 127
5.6.2 Partial Stroking Test (PST) for valves....................................................................................... 128
5.6.3 Advantages and risks in the use of Partial Stroking Tests................................................. 129

6
Index

5.6.4 Technologies to help PST.......................................................................................................... 129


5.6.5 Full Stroke Test of valves (FST)................................................................................................. 130
5.7 SIS Conceptual Design 6 .................................................................................................................. 130
5.7.1 Conceptual Design Requirements........................................................................................... 132
5.8 Conceptual Design and SIL Level................................................................................................... 133

Chapter 6 IEC 61508: Fundamental concepts....................................................135


6.1 Overall safety lifecycle...................................................................................................................... 135
6.2 Safety Integrity Levels....................................................................................................................... 136
6.3 Part “1”: General requirements........................................................................................................ 138
6.3.1 Scope.............................................................................................................................................. 138
6.3.2 Compliance.................................................................................................................................... 139
6.3.3 Documentation (Clause 5)......................................................................................................... 139
6.3.4 Management of Functional Safety (Clause 6)....................................................................... 140
6.3.5 Overall Safety Lifecycle Requirements (Clause 7)............................................................... 142
6.3.6 HSE Findings................................................................................................................................. 143
6.3.7 The concept of safety lifecycle in IEC 61508........................................................................ 144
6.3.8 Functional Safety Assessment (Clause 8)...............................................................................147
6.3.9 Example documentation structure Annex A (Informative)................................................. 148
6.4 Part “2”: Requirements for electrical/electronic/programmable electronic safety-related
systems................................................................................................................................................ 150
6.4.1 Scope.............................................................................................................................................. 150
6.4.2 Terminology changes and architectural constrains in 61508:2010 Ed. 2...................... 153
6.4.3 Control of Failure during Operation Annex A (Normative)................................................ 158
6.4.4 Avoidance of Systematic Failures during different phases of the Lifecycle Annex B
(Normative)..................................................................................................................................... 158
6.4.5 Diagnostic Coverage and Safe Failure Fraction Annex C (Normative).......................... 159
6.4.6 Safety manual for compliant items Annex D (Normative).................................................. 160
6.4.7 Special architecture requirements for integrated circuits (ICs) with on-chip redundancy
Annex E (Normative).................................................................................................................... 160
6.4.8 Techniques and measures for ASICs – avoidance of systematic failures Annex F
(Informative).................................................................................................................................... 161
6.5 Part “3”: Software requirements...................................................................................................... 161
6.5.1 Scope............................................................................................................................................... 161
6.5.2 Additional requirements for management of safety-related software (Clause 6)....... 162
6.5.3 Software Safety Lifecycles (Clause 7)..................................................................................... 163
6.5.4 Software Safety Requirements Specification (Clause 7.2)................................................. 164
6.5.5 Validation plan for software aspects of system safety (Clause 7.3)................................ 165
6.5.6 Software design and development (Clause 7.4).................................................................. 165
6.5.7 Programmable electronics integration - hardware and software (Clause 7.5)............. 166
6.5.8 Software safety validation (Clause 7.7)................................................................................... 167
6.5.9 Software operation and modification procedures (Clause 7.6 and 7.8)......................... 167
6.5.10 Software verification (Clause 7.9)............................................................................................. 168
6.5.11 Software Functional Safety Assessment (Clause 8)............................................................ 169
6.5.12 Guide to the selection of techniques and measures Annex A (Normative).................. 169
6.5.13 Detailed tables Annex B (Informative).................................................................................... 170
6.5.14 Properties for software systematic capability Annex C (Informative)............................. 170

7
Index

6.5.15 Safety manual for compliant items - additional requirements for software elements
Annex D (Normative)................................................................................................................... 170
6.5.16 Relationships between IEC 61508-2 and IEC 61508-3 Annex E (Informative)............. 170
6.5.17 Techniques for achieving non-interference between software elements on a single
computer Annex F (Informative).................................................................................................171
6.5.18 Guidance for tailoring lifecycles associated with data driven systems Annex G
(Informative).....................................................................................................................................171
6.6 Part “4”: Definitions and abbreviations...........................................................................................171
6.6.1 Scope................................................................................................................................................171
6.7 Part “5”: Examples of methods for the determination of safety integrity levels...................171
6.7.1 Scope................................................................................................................................................171
6.7.2 Risk Reduction - General concepts......................................................................................... 172
6.7.3 HAZOP report example...............................................................................................................174
6.7.4 Risk and safety integrity: general concepts Annex A (Informative)................................ 175
6.7.5 Selection of methods for determining safety integrity level requirements - Annex B
(Informative) and ALARP tolerable risk concepts - Annex C (Informative).................... 176
6.7.6 Tolerable Risk decisions based on financial considerations............................................ 178
6.7.7 Quantitative method for SIL determination............................................................................ 181
6.7.8 Determination of safety integrity levels - A quantitative method Annex D (Informative).
184
6.7.9 Determination of safety integrity levels - Risk graph methods Annex E (Informative).187
6.7.10 Semi-quantitative method using layer of protection analysis (LOPA) Annex F
(Informative)................................................................................................................................... 187
6.7.11 Determination of safety integrity levels - A qualitative method - hazardous event
severity matrix Annex F (Informative)....................................................................................... 191
6.8 Part “6”: Guidelines on the application of IEC 61508-2 and IEC 61508-3............................. 191
6.8.1 Application of IEC 61508-2 and of IEC 61508-3 Annex A (Informative).......................... 191
6.8.2 Example of technique for evaluating probabilities of hardware failure Annex B
(Informative).................................................................................................................................... 191
6.8.3 Calculation of diagnostic coverage and safe failure fraction - worked example Annex C
(Informative)................................................................................................................................... 192
6.8.4 A methodology for quantifying the effect of hardware-related common cause failures
in E/E/PE systems Annex D (Informative)............................................................................... 195
6.8.5 Example applications of software safety integrity tables of IEC 61508-3 Annex E
(Informative)................................................................................................................................... 195
6.9 Part 7: Overview of techniques and measures........................................................................... 195
6.9.1 Overview of techniques and measures for E/E/PE safety-related systems: control of
random hardware failures (see IEC 61508-2) Annex A (Informative).............................. 195
6.9.2 Overview of techniques and measures for E/E/PE safety related systems: avoidance of
systematic failures (see IEC 61508-2 and IEC 61508-3) Annex B (Informative)........... 195
6.9.3 Overview of techniques and measures for achieving software safety integrity (see IEC
61508-3) Annex C (Informative)................................................................................................ 196
6.9.4 A probabilistic approach to determining software safety integrity for pre-developed
software Annex D (Informative)................................................................................................ 196
6.9.5 Overview of techniques and measures for design of ASICs Annex E (Informative)... 196
6.9.6 Definitions of properties of software lifecycle phases Annex F (Informative).............. 196
6.9.7 Guidance for the development of safety-related object oriented software Annex G

8
Index

(Informative)................................................................................................................................... 196
6.10 Conclusion to parts 5-6-7 of IEC61508 Edition 2....................................................................... 197

Chapter 7 IEC 61511 Ed 2.0: Functional safety - Safety Instrumented Systems


for process industry sector..................................................................199
7.1 Introduction.......................................................................................................................................... 199
7.2 History...................................................................................................................................................200
7.3 General overview of IEC61511 Ed. 2.0...........................................................................................200
7.4 IEC61511 Ed. 2.0 - part 1 Overview................................................................................................. 203
7.4.1 Lifecycle phases overview........................................................................................................205
7.4.2 The remaining clauses not directly referenced in the lifecycle phases........................ 217
7.5 Executive summary of the edition 2.0 changes.......................................................................... 219
7.6 References........................................................................................................................................... 223

Chapter 8 IEC61511 Ed. 2.0 - SIS Safety Requirement Specification (SRS)....225


8.1 Introduction......................................................................................................................................... 225
8.2 Content of the SRS............................................................................................................................ 226
8.2.1 General Requirements (61511-1, clause 10.2)........................................................................ 227
8.2.2 SIS Safety Requirements (61511-1, clause 10.3).................................................................... 227
8.2.3 Application Program Safety Requirements (61511-1, clause 10.3.5)................................ 249

Chapter 9 Functional safety manual................................................................... 253


9.1 Requirements...................................................................................................................................... 253
9.2 What’s new in IEC 61508 Edition 2................................................................................................ 255
9.3 Systematic SIL Capability................................................................................................................. 255
9.4 Safety manual for compliant items................................................................................................ 256
9.5 Examples.............................................................................................................................................. 257

Chapter 10 Functional safety Management in Safety Instrumented Systems


(SIS).......................................................................................................269
10.1 Disclaimer............................................................................................................................................ 269
10.2 Introduction......................................................................................................................................... 269
10.3 Objective of Functional Safety Management (FSM) (Clause 5.1)........................................... 269
10.3.1 FSM Objectives............................................................................................................................ 269
10.3.2 Systematic Failures..................................................................................................................... 270
10.3.3 FSM as a Quality Mechanism................................................................................................... 270
10.3.4 Mandatory FSM Procedures..................................................................................................... 270
10.3.5 Lifecycle Integration................................................................................................................... 270
10.3.6 Common Misconceptions.......................................................................................................... 271
10.4 Requirements for Management Activities (Clause 5.2)............................................................. 271
10.4.1 Policy and Strategy (Clause 5.2.1)............................................................................................ 271
10.4.2 Organization and Resources (Clause 5.2.2).......................................................................... 271
10.4.3 Competency Management (Clause 5.2.2.2).........................................................................273
10.4.4 Risk Evaluation and Management (Clause 5.2.3)................................................................274

9
Index

10.4.5 Safety Planning (Clause 5.2.4)..................................................................................................274


10.4.6 Implementation and Monitoring (Clause 5.2.5)................................................................... 275
10.4.7 Functional Safety Assessments and Audits (Clause 5.2.6).............................................. 275
10.4.8 Functional Safety Audits and Revisions (Clause 5.2.6.2)...................................................277
10.4.9 SIS Configuration Management (Clause 5.2.7).................................................................... 278
10.5 Conclusions......................................................................................................................................... 279

Index of Figures....................................................................................................... 283


Index of Tables......................................................................................................... 287
Reference..................................................................................................................289
Denial of responsibility............................................................................................291

10
Chapter 1 | Presentation of IEC 61508, IEC 61511 and other safety related standards

Chapter 1 Presentation of IEC 61508, IEC 61511 and


other safety related standards

Safety-related systems serve the function of protecting equipment and industrial


processes where danger may occur in case of failure. These systems are not part of the
process control system since their purpose is to bring the plant to a safe state in case of
malfunctioning. Until a few years ago, these systems, for example ESD (Emergency Shut-
Down), were being designed in compliance with the respective standards in force in the
different countries, with no reference to a general normative.
This condition has changed with IEC 61508 and IEC 61511 which also introduce the
following benefits for the final user:
• A more technical and scientific method in formulating requirements and specifications
in the designing process.
• A more accurate definition of risk.
• A more valid designing of safety-related systems.
• An easier and wider demonstration of safety-related system’s effectiveness.
• A far more cost-effective implementation of safety-related systems.
• An easier evaluation and effectiveness of maintenance operations.

The number of manufacturers of equipment complying with this standard is expected to


grow. Information provided by the manufacturers allows the integration of their products
into safety-related systems.

IEC 61508 is an international standard for the “functional safety” of electrical, electronic,
and programmable electronics equipment. At present, in Europe, EN 61508 has been
issued but not yet acknowledged as European Directive. This standard started in the mid
1980s when the International Electrotechnical Committee Advisory Committee of Safety
(IEC ACOS) set up a task force to consider standardization issues raised by the use of a
programmable electronic system (PES).Work began within IEC SC65A/Working Group 10
on a standard for PES used in safety-related systems. The group merged with Working
Group 9 where a standard on software safety was in progress. The combined group
treated safety as a system issue. IEC 61508 Brief history:
• 1985: Task Group set up to assess viability of developing a generic standard on PES’s.
• Two working groups collaborate of developments of IEC standard that was to
become IEC 61508 (draft IEC1508).
• 1998-2000: The parts of IEC 61508 (1-2-3-4-5-6-7) Edition 1 were published.
• 2005: PD IEC TR 61508-0 was published.
• “ENs” adopted in same year as the IEC publication dates.
• 2003: Revision of IEC 61508 /Edition 1 started.
• 2010: IEC 61508 / Edition 2 was published in April.

11
Chapter 1 | Presentation of IEC 61508, IEC 61511 and other safety related standards

IEC 61508 (Functional Safety of electrical, electronic & programmable electronic safety-
related systems) is divided into eight parts covering all safety lifecycle activities - concept
- specifications - design - implementation - operation maintenance & modification.
Parts 1, 2, 3 are required for compliance (normative), the others are supporting information
(informative) which provide further guidance information.

• Part 1 General requirements. (Normative)


• Part 2 Requirements for electrical/electronic/programmable
electronic safety-related systems. (Normative)
• Part 3 Software requirements. (Normative)
• Part 4 Definitions and abbreviations. (Informative)
• Part 5 Examples of methods for the determination of safety
integrity levels. (Informative)
• Part 6 Guidelines on the application of Parts 2 and 3. (Informative)
• Part 7 Overview of techniques and measures. (Informative)

Edition 2 has been approved in April 2010. The relationship between technical
requirements presented in parts 1, 2 and 3 and the supporting information in parts 4
through 7 is shown in Figure 1, in the following page.

Although the standard has been criticized for the “extensive” documentation requirements
and use of unproven “statistical” techniques, it represents a great step forward in many
industries.

The standard focuses attention on risk-based safety-related systems design, which should
result in far more cost-effective implementations. It also requires the attention to details
that is vital to any safe system design. Because of these features and the large degree of
international acceptance for a single set of documents, many consider the standard to be
major advance for the technical world.

The experience of GM International on SIL 2 and SIL 3 hardware and software design,
has shown how the suggested techniques in the standard are indeed a valid guidance for
reducing “dangerous undetected failures” which is the correct path towards increasing
safety integrity levels for any safety-related system.

12
Chapter 1 | Presentation of IEC 61508, IEC 61511 and other safety related standards

Technical Requirements
Part 1 Part 1

Development of the overall Example of methods for


safety requirements ( con- determination of safety
cept, scope, definition, integrity level
hazard and risk analysis )
7.1 to 7.5
Other requirements
Part 1

Allocation of the safety


requirements to the E/E/PE
safety-related systems Part 4
7.6 Definitions and
abbreviations
Part 1

Specification of the system


requirements for the E/E/PE
safety related systems Part 1

7.10 Documentation Clause 5


Part 6
Guidelines for the
and Annex A
application of
Parts 2 and 3

Part 2 Part 3
Realisation phase Realisation phase
for E/E/PE safety for safety-related
-related systems software
Part 1
Part 7
Overview of Management of
techniques and
measures functional safety
Part 1 Clause 6
Installation, commissioning
and safety validation of E/E/PE
safety-related systems Part 1
7.13 - 7.14 Functional safety
assessment
Part 1
Clause 8
Operation, maintenance,
modification and retrofit,
decommisioning or disposal of
E/E/PE safety-related systems
7.15 - 7.17

Figure 1, IEC 61508 requirements

13
Chapter 1 | Presentation of IEC 61508, IEC 61511 and other safety related standards

1.1 Scope of IEC 61508


Safety can be primary, functional or derived. Primary safety deals with risks, such as
electric discharges generated by an electric equipment. Functional safety depends on
the measures of risk reduction adopted in the system or equipment under control (EUC).
Derived safety deals with the indirect consequences of an EUC, which does not perform
as expected, for example providing a drug with a wrong recipe which might kill instead
of healing. The standard specifically refers to functional safety, however its principles can
also be generally applied to other aspects of safety.

IEC 61508 is one of the main publications, on safety matters, of IEC (International
Electrotechnical Commission) and involves many industries and applications, such as, for
example, the PED directive (Pressured Equipment Directive) and protection method “b”
for non-electrical equipment of ATEX (mechanic), as well as EN 50495 (Safety devices
required for safe functioning of equipment with respect to explosion risks), in which, for the
first time in ATEX standard, functional Safety Integrity Levels (SIL) are used as a protection
system.

The main purpose of IEC 61508 is to provide the basis for the preparation of specific
safety standards for plant and industrial sectors. A second scope of the standard is to help
the development of safety-related systems E/E/PE (Electrical/Electronic/Programmable
Electronic) where specific standards do not exist. Starting from 2002, two new specific
standards directly referring to IEC 61508 were introduced: IEC 61511 for process control
industries and IEC/EN 62061, EN ISO 13849-1 Safety of Machinery.

IEC 61508 covers safety-related systems when one or more of such systems incorporate
electrical/electronic/programmable electronic devices. These devices can include anything
from electrical relays and switches to Programmable Logic Controllers (PLCs) and all the
way up to complicated computer-driven overall safety systems. The standard specifically
covers possible hazards created when failures of safety functions performed by E/E/PE
safety-related systems occur. The overall program to insure that a safety-related E/E/PE
system brings about a safe state, when called upon to do so, is defined as “functional
safety”.

IEC 61508 does not cover safety issues like electric shock, hazardous falls, long-term
exposure to a toxic substance, etc.; these issues are covered by other standards like ATEX
or similar. IEC 61508 also does not cover low safety E/E/PE systems where a single E/E/
PE system is capable of providing the necessary risk reduction and the required safety
integrity level of the E/E/PE system is less than SIL 1.
IEC 61508 is concerned with the E/E/PE safety-related systems whose failure could affect
the safety of persons and/or the environment. However, it is recognized that the methods
of IEC 61508 also may be applied to business loss and asset protection cases.

14
DIGITAL PREVIEW
If you want to request the full hard copy or to read the online full
version scan the QR-code on the last page of this document.

280
Chapter 2 | Prevention and mitigation layers for hazardous events

Chapter 2 Prevention and mitigation layers for


hazardous events

Accidents rarely have a single cause and are usually a combination of improbable events
that people initially assumed as independent and unlikely to happen at the same time. A
tragic example is the one occurred to a pesticide plant in Bhopal (India). It was December
3, 1984 and the unexpected leakage of more than 40 tons of methyl isocyanate (MIC)
immediately killed almost 4000 people and caused illnesses and death to many thousands
more.

Figure 3, Bhopal Disaster. 1976 Union Carbide plant: 20 thousand deaths and almost 200
thousand injured

Although operative procedures prescribed the tank to be refrigerated at a temperature


below 5°C, the alarm was set at 11°C. At that time, the refrigerating system was switched
off due to bad economic conditions and the material was stored at the temperature
of 20°C. The alarm set was therefore moved from 11°C to 20°C (first cause). The plant
was in shutdown for maintenance. A worker was tasked to wash some clogged pipes
and filters. Blind flanges were not installed as required by the procedures in case of
cleaning of the pipes (second cause) and water leaked past the valves into the tank
containing MIC. Temperature and pressure gauges indicated abnormal conditions but
were ignored, because thought to be inaccurate (third cause). A vent scrubber, which
could have neutralized the MIC release into the atmosphere, was not working because it
was presumed not to be necessary while production was suspended (fourth cause). But
the vent scrubber would not have been able to handle that size of dangerous release
anyway (fifth cause). The flare tower, although insufficient for the task (sixth cause), could
have burned off part of the material, but it was out of service for maintenance (seventh
cause). The material could have been vented to nearby tanks, but the gauges erroneously
showed them as partially filled (eight cause). A water curtain was available to neutralize a
release in the atmosphere, but the MIC was vented from a stack that was 33 meters above

23
Chapter 2 | Prevention and mitigation layers for hazardous events

the ground level, too high to be reached by the water curtain. Workers became aware
of the MIC release because of the irritation to their eyes and throats. Their complaints
to the management, at that time, were ignored. Workers panicked and fled ignoring the
availability of 4 buses that were intended for emergency evacuation of the employees. The
plant supervisor could not find his oxygen mask and broke a leg while trying to climb over
the boundary fence. When the plant manager was later informed of the accident he did not
believe the fact, by stating that the gas release could not be from his plant, nothing could
ever happen to the plant, especially a MIC release, because the plant was not in operation.

Investigations of several industrial accidents proved that many of them happen


during an interruption of production while an operator was trying to maintain or
restart production. In each case, the company’s safety procedures were violated or
jeopardized.

The best and most redundant safety layers can be defeated by poor or conflicting
management practices. If all prevention layers are effective (e.g. strong and solid), failures
cannot spread from one to another. In reality, these layers are not strong and solid, but more
like Swiss cheese. The holes are caused by flaws in management, design specifications,
engineering, operations, procedures, improperly performed maintenance, and other errors.
Not only there are holes in each layer, but these holes are constantly moving, increasing,
ad decreasing, as well as appearing and disappearing. It is clear that if these “holes” line up
properly, a failure can propagate through all layers causing a hazardous event. Supposing
these holes are not present, the SIL levels (PFDavg) of each layer can be multiplied. This
means that three SIL 1 layers could lead to SIL 3. Unfortunately this is just theory, due to the
imperfections mentioned above. However, increasing the level of the three layers (SIL 2 and
SIL 3), makes the achieving of a SIL 3 global level much more probable.

Other Mech SIS Alarm DCS


s

PROCESS
Risks
Level of Inherent
tolerable risk in the
risk process
Figure 4, Risk reduction with several prevention layers

24
Chapter 2 | Prevention and mitigation layers for hazardous events

As already seen, risk is a function of the probability (or frequency) of a hazardous event
and of its severity (or consequence). In an industrial plant the various layers are planned
to reduce one or the other. Prevention layers are used to reduce the probability of the
hazardous event, while mitigation layers are implemented to reduce the damaging
consequences of an already happened hazardous event. In an industrial plant, there are
usually four prevention and four mitigation layers. In this chapter ten layers are specified (5
for prevention + 5 for mitigation). This is not relevant if not for a better comprehension and
identification of the functions of the different layers.

Figure 5, Prevention and mitigation layers of the hazardous event

2.1 Plants and processes in their environmental context


Industrial plants and processes must always be designed taking safety issues into
consideration. This is why HAZOP (Hazard and Operability studies) or other safety reviews,
such as fault tree analysis and various checklists, what-if, etc., should always be performed.
Trevor Kletz 1 points out that: “time is usually better spent looking for all the sources of
hazard, than in quantifying with even greater precision those we have already found”.
In the NASA space program almost 35% of actual in-flight malfunctions had not been
identified during the analysis. The main requirement of an industrial process is to be safe,
not forgetting the rule that “what is not there cannot be damaged”, which means that it is
important to make the process as simple as possible. Safe processes and systems may be
more expensive, but offer greater advantages to the final user throughout the life of the
plant. Risk reduction may result in a simplification and therefore in a reduction of costs.

25
Chapter 2 | Prevention and mitigation layers for hazardous events

For example, the problem of children remaining trapped and suffocated while playing in
refrigerators has lead the industry to the use of magnetic latches, which, a part from being
much safer, are simpler and less expensive.

Figure 6, Refinery

Layer 1 takes into consideration all processes, plants and activities which may generate
hazardous situations. All these represent the environmental context to which each safety
matter refers to.

Arguments which are taken in to evaluation are:


• Area’s classification
• Stocking plants
• Production plants
• Storage plants
• Hot fluid plants
• Cold fluid plants
• Electric plants
• Auxiliary fluid plants.
• Organizational structure of the layer.

Teams of expert engineers working on this layer are:


• Team Leader
• Project Engineer
• Quality Assurance Engineer
• Machinery Engineer
• Mechanical Engineer

1. Trevor Kletz, D. Sc., F. Eng., member of HSE and process safety consultant, has published more than one hundred papers and
nine books on loss of prevention and process safety.

26
DIGITAL PREVIEW
If you want to request the full hard copy or to read the online full
version scan the QR-code on the last page of this document.

280
Chapter 3 | Basic concepts for a better comprehension of safety standards

Chapter 3 Basic concepts for a better


comprehension of safety standards

Some fundamental concepts for understanding safety related argumentations are


presented here to ease the comprehension of Part 6 of IEC 61508, which concerns
guidelines on the application of Part 2 and 3.
Some of these concepts are used in the previous Parts of IEC 61508 and for this reason,
they are here recalled.
This chapter is not a complete and exhaustive presentation of all the treated subjects,
but rather a manual, to “refresh” some specific arguments, or basic equations for the
calculation of MTBF, PFDavg, SFF, SIL levels, etc.
Other subjects like HAZOP, FMEDA, etc., are presented at Chapter 5.

3.1 Reliability and Unreliability


3.1.1 Reliability
Reliability is a measure of success and is defined by engineers as:
“The probability that a component part, equipment, or system will satisfactorily perform
its intended function when required to do so, under given circumstances, such as design
limits, environmental conditions, limitations as to operating time, and frequency and
thoroughness of maintenance for a specified period of time”.

This definition includes four important aspects:


• The device’s “intended function” must be known.
• “When the device is required to function” must be judged.
• “Satisfactory performance” must be determined.
• “Specified design limits” must be known.

All four aspects must be addressed when defining a situation to be a success or a failure.

The first aspect concerns the clear definition of what the device is asked to do, and
nothing else.
The second aspect concerns the requested operability: when it will be requested to do so,
not in another moment or in any moment but “on demand”.
The third aspect deals with the evaluation of what the device has to do with good
performances, in order to honor the demand in an acceptable way.
The forth aspect regards operability conditions in which the device works,
e.g. design limits, temperature limits, etc.

37
Chapter 3 | Basic concepts for a better comprehension of safety standards

The four aspects together define the terms in which reliability is evaluated.
Reliability is valid for those conditions and not for others.
If conditions change, reliability can change too.
Mathematically, reliability (R) is:
“The probability that a device will be successful in the time interval from time 0 to time t”.

Reliability

1
0,76

Operating time
0
t TTF Time

Failure time

Figure 13, Reliability Figure of a device

Reliability equals the probability that TTF, failure time, is greater than t, operating time
interval. The graph in Figure 13 shows device reliability as a function of time. Increasing the
time interval from 0 to TTF (estimated failure time, or TTF -Time To Fail, where the device is
estimated to fail with probability close to 100%) reliability changes from 1 to 0.
At time t probability will be 76%; in other words, operability without failure from 0 to t is
0.76. Calculating reliabilities for a time t greater than TTF has no meaning.

Example
A newly manufactured and successfully tested washing machine operates properly
when put into service at time t = 0 (success = 1).
Since the machine will eventually fail, the probability of success for an infinite time
interval is zero. Thus, all reliability functions start at a unitary probability and decrease
to a probability of zero (failure).

Note 1
Reliability is a function of operating time. A statement such as “System reliability is 0.95” is
meaningless because the time interval is unknown. The statement “Reliability equals 0.98
for a mission time of 10,000 hrs” instead, makes perfect sense.

38
Chapter 3 | Basic concepts for a better comprehension of safety standards

Note 2
The reliability function graph indicated in Figure 13 is just a simple example. Reliability
functions considered in this manual assume an exponential decay of failure probability,
similar to those indicated below Figure 14, where the concept of TTF, as defined limit
value, is not applicable because mathematically a reliability equal to zero is never reached.
This family of curves represents the reliability function characterized by a constant failure
rate.

1,00

0,90

0,80

0,70

0,60

0,50

0,40

0,30

0,20

0,10

0,00
Time
Figure 14, Device Reliability Function with exponential decay

These curves are represented mathematically by the general equation:

R(t) = e-λt

and have different values of λ (failure rate). They are defined at constant failure rate
because the ratio between the calculated values at equal time intervals is constant:

R(t + δ)
= f(δ)
R(t)

The ratio between two values of the function (the rate) depends on the time difference
delta and not on the time in which the values are calculated.
In other words, being δ the value of the ratio, or rate, the time is constant.
This is better defined by the following equation:

e-λ(t+δ)
= e-λδ
e-λt
in which the ratio does not depend on the time but on the value of interval δ.

39
Chapter 3 | Basic concepts for a better comprehension of safety standards

Note
It is useful to remind that representing the function of this family in a graph with logarithmic
scale for values and linear scale for time, the functions will be straight.
Reliability is an important measure for those devices which are not repairable, like
airplanes. Washing machines or industrial control systems are repairable and MTTF (Mean
time to failure) is more likely to be used instead.

3.1.2 Unreliability
Unreliability is the measure of failure; it is defined as “the probability that a device will fail
in the time interval from 0 to t”.

Unreliability U(t) = 1 – Reliability (t)

It starts with probability zero and increases up to probability one.

Example
A controller has a reliability of 0,99 for a mission of 10,000 hrs.
What is its unreliability for the same mission time?
Unreliability = 1 – 0,99 = 0,01

A property of exponential reliability curves is the constant failure rate for values of λ << 1.
Mathematically, unreliability is defined as:

U(t) = 1 - R(t) = 1 - e-λt

Applying Mc Laurin’s expansion equation, unreliability can also be expressed by the


following:

∞ -(λt)n λ λ2 λ3
U(t) = 1 - ∑ = 1 - 1 - t + t2 + t3 + ...
0 n! 1! 2! 3!

To be noticed that terms beyond λ2 are very small, and therefore the equation can be
approximated to the easier:

U(t) = 1 - 1 + λt = λt

This can save calculation time, however remember that approximation degrades with
higher values of failure rates and interval times. Further considerations can be made on
the mean time to failure (MTTF). Supposing a number of n devices to be analyzed with
known failure rates λ and a population of n units, after time t, the number of failed units is
nF:
nF = n x λ x t

40
DIGITAL PREVIEW
If you want to request the full hard copy or to read the online full
version scan the QR-code on the last page of this document.

280
Chapter 4 | Consequence Analysis of relevant accidents involving chemical substances

Chapter 4 Consequence Analysis of relevant


accidents involving chemical substances

4.1 Analysis of risks from the release of chemical


substances
Before conducting a consequence analysis of any hazardous event it is necessary to
consider consequences which could derive from the release of chemical substances.

Figure 33 shows an event tree diagram for the release of hazardous chemicals, for a gas
release and for a liquid/liquefied gas release.

If the release of a chemical substance occurs, consequences may result directly from the
release event, as for example in BLEVE/Fireball1, or physical explosions.

It is also possible to have only a release of chemical substances in the atmosphere, which
may later cause damages depending on their chemical/physical properties.
Two possible consequences, coincident with the initial release event, are physical
explosions and/or the BLEVEs with the resulting fireballs.

1. BLEVE: Boiling Liquid Expanding Vapor Explosion (see Section 4.2.4).

73
Chapter 4 | Consequence Analysis of relevant accidents involving chemical substances

Loss of
Initiating event Release type Outcome
containment type

Physical explosion Physical explosion

BLEVE/Fireball BLEVE/Fireball
No release /
No release - no no consequence
Loss of control impact

Gas release
(see Figure 34)
Gas
Chemical release
Liquid Liquid release
(Liquefied Gas) (see Figure 35)

Figure 33, Event tree diagram for simplified loss of chemical containment

A pressure vessel, stimulated beyond its nominal designed pressure, can undergo a
catastrophic failure creating a physical explosion.
Such event is euphemistically called by the media as an “energy release”.
If released substances as the result of a physical explosion are flammable, a fireball may
also occur.

If the accident involves a flammable liquid spill, followed by ignition, with the resulting fire
of the whole tank, a BLEVE/Fireball may occur.
If the loss of containment event does not cause a fire or an immediate explosion, the
chemical substances contained in the process will be spread into the atmosphere.

74
Chapter 4 | Consequence Analysis of relevant accidents involving chemical substances

Vapor Liquid
Release Immediate cloud rainout Explosion Toxic
Outcome
type ignition forms and and occurs chemical
ignites ignition

Jet Fire
Yes

Yes Vapor cloud


explosion
Gas release Yes

No Flash Fire

No

Yes Pool Fire

No Yes Toxic
exposure
No

No No
consequences

Figure 34, Event tree for gas release

The effects of this kind of release may be involved in a variety of effects depending on:
• Release conditions
• Thermodynamic conditions
• Release nature (liquid, gas, liquefied gas)

Consequences strongly depend on the conditions mentioned above and could have a
large impact depending on possible incident outcomes.

If released substances are high pressure gas or liquids that instantly flash into a gas upon
release, a jet fire ignition will occur if the gas is immediately ignited. In the absence of
immediate ignition, a large vapor cloud may form. Delayed ignition of the vapor cloud may
cause an explosion (VCE, Vapor Cloud Explosion) with the resulting blast overpressure and
shock wave.

75
Chapter 4 | Consequence Analysis of relevant accidents involving chemical substances

Depending on the characteristics of the released material and the surrounding


environment, a vapor cloud may not result in an explosion after ignition.
In this case the cloud could burn in a slower laminar fashion, causing a flash fire which has
a strong thermal effect, but does not cause a blast wave.

Differences between these two combustion modalities depend on the complex


phenomenon of flame propagation velocity, which requires a specific modeling to predict
with any accuracy.
Even if any ignition does not happen, the non-ignited toxic cloud of gas will spread and
disperse, with risks for workers and nearby residents.
Non-ignited gas releases, and in some cases the combustion products of the ignited
release, can have a detrimental effect on the surrounding environment.

Possible incident outcomes, as the result of a liquid or liquefied gas discharge, mostly
depend on the behavior of the liquid upon release:
1) Immediate vaporization of liquid.
2) Rapid vaporization of the liquid with substantial formation of a liquid pool.
3) Slow or negligible vaporization with significant liquid pooling.

In case 1) the event tree shown in Figure 33 will unfold.


In cases 2) and 3) the event tree shown in Figure 34 better represents the possible
outcomes of the release.

Figure 35 shows that the outcomes from a liquid release, with vapor cloud formation, are
largely similar to the ones resulting from a release with direct formation of a vapor cloud.
The cloud formation can result from either rapid vaporization or slow evaporation of a
pool. In the case where a pool of liquid is formed and ignited, a pool fire will result.
If the pool is not ignited, evaporation of the liquid may lead to a harmful exposure hazard
downwind, if the material is toxic. Moreover, this can also contaminate groundwater even
if is not ignited.
In both the vapor and liquid release cases, a potential exists that released substances will
be carried away from the source of the release as an aerosol or as a gas cloud, which will
then cool, collect, and rain out of the atmosphere to collect in a pool.
The hazards associated with such condensation pool are essentially the same as the
hazards from the direct spill of a liquid, except that they are a quite long distance from
the release source.
Due to this, a secondary containment, will most likely, not help mitigating their
consequences.

76
DIGITAL PREVIEW
If you want to request the full hard copy or to read the online full
version scan the QR-code on the last page of this document.

280
Chapter 5 | Safety Instrumented Systems (SIS)

Chapter 5 Safety Instrumented Systems (SIS)

5.1 Introduction
Safety Instrumented Systems (SIS) are frequently used to reduce process hazards in
production plants. For each potentially dangerous process, a design is done to detect the
situation and automatically take action to prevent or mitigate the hazardous event.
Each function is called Safety Instrumented Function (SIF).
For each SIF, the required Risk Reduction Factor (RRF) is determined.
A number of SIFs, associated with a particular process, are typically implemented within a
single SIS.

Programmable Electronic Controller


Logic Solver

Inputs Outputs

Sensor
PT

Sensor
PT Process

Figure 41, Example of a small SIS

A simple SIS is shown in Figure 41 together with a logic solver in a safety instrumented
function.
SIS have many implemented safety functions, one for each potentially dangerous
condition, in a single logic solver, which collects and analyzes data information from

89
Chapter 5 | Safety Instrumented Systems (SIS)

sensors to determine if a dangerous condition occurs, and consequently to start a


shutdown sequence to bring the process to a safe state. Typically, these control systems
are called “safety-related systems”. A potentially dangerous condition is called “demand”.

The majority of SIS are based on the “de-energize to trip” concept, meaning that, in normal
working conditions, input and output are energized and the programmed action to prevent
or mitigate the dangerous event consists in the opening of a connection by de-energizing
an electric circuit. This action is called “trip”.

A SIS is composed of process connections, sensors, logic solver, and final elements.
Sensors may be temperature/pressure measurement devices, flame detectors, toxic gas
detectors, emergency switches or many other devices.
Final elements range from simple solenoid valves to large control valves with their
associated actuators.

One type of logic solver is a programmable logic controller (PEC) which consists of input
circuitry, a logic solver and output circuitry.
The logic solver is implemented using a microprocessor and software. Different types of
input output circuitry exist to interface analog or discrete sensors or final elements.
Particular SIS are:
• ESD: Emergency Safety Shutdown system
• BMS: Burner Management System
• F&G: Fire and Gas system

A SIS includes instrumentation and/or controls installed to prevent or mitigate hazardous


conditions, or to bring the process to a safe state, in presence of a safety demand. This
can happen if specific process conditions are violated, e.g. pressure, level, temperature
alarms. SIS are used for any kind of process in which hazard and risk analysis require their
use. SIS availability depends on:
• Failure rate and failure mode of components or sub-systems
• Component architectures (1oo1, 1oo2D, 2oo2, 2oo3, etc)
• Voting circuits
• Diagnostic coverage
• Periodic testing frequency

5.2 Safety requirements


SIS functional safety requirements specify:
• logics and actions that a SIS has to comply with;
• process actions a SIS has to perform;
• process conditions to initiate such actions, including manual shutdown, power supply
failure, etc.;
• requested SIL level and required performance to achieve it.

90
Chapter 5 | Safety Instrumented Systems (SIS)

IEC 61511 standard specifies requirements that shall be sufficient to design the SIS and
shall include the following:
• A description of all necessary SIFs to achieve required functional safety.
• Requirements to identify and take account of common cause failures.
• A definition of the safe state of the process for each identified SIF.
• A definition of any individually safe process state which, when occurring concurrently,
creates a separate hazard (e.g. overload of emergency storage, multiple relief to flare
system).
• The assumed sources of demand and demand rate of each SIF.
• Requirements for proof-test intervals.
• Response time requirements for the SIF to bring the process to a safe state.
• The SIL and mode of operation (demand/continuous) for each SIF.
• A description of process measurements and their trip point.
• A description of process output actions and the criteria for successful operation (e.g.
requirements for tight shut-off valves).
• The functional relationship between process input and output, including logic,
mathematical functions, and any required permissions.
• Requirements for manual shutdown.
• Requirements relating to energize or de-energize to trip.
• Requirements for resetting the SIF after a shutdown.
• Maximum allowable spurious trip rate.
• Failure modes and desired response of the SIF.
• Any specific requirements related to the procedures for starting up and restarting the
SIF.
• All interfaces between the SIS and any other system, including BPCS and operators.
• A description of the modes of operation of the plant and identification of the SIFs
required for operating within each mode.
• Application software safety requirements.
• Requirements for overrides / inhibits / bypasses including how they will be cleared.
• The specification of any action necessary to achieve or maintain a safe state in the
event of fault(s) being detected in the SIF.
• The mean time to repair which is feasible for the SIF.
• Identification of the dangerous combinations of output states of the SIS that need to
be avoided.
• Identification of the extremes of all environmental conditions which are likely to be
encountered by the SIS.
• Identification of normal and abnormal modes for both the plant as a whole (e.g. plant
startup) and individual plant operational procedures.
• Definition of requirements for any safety instrumented function necessary to survive
a major accident event (e.g. the time required for a valve to remain operational in the
event of a fire).

The standard provides requirements for the specification of the application software safety
requirements.

91
Chapter 5 | Safety Instrumented Systems (SIS)

It is essential for the application software specifications to be consistent with the safety
requirements listed below:
• An application software safety requirements specification shall be developed.
• The input to the specification of the software safety requirements for each SIS
subsystem shall include:
-specified safety requirements of the SIF;
-requirements resulting from the SIS architecture;
-any requirements of safety planning.
• The specification of the requirements for application software safety shall be
sufficiently detailed to allow the design and implementation to achieve the required
safety integrity and to allow an assessment of the functional safety to be carried out.
• The application software developer shall review the information in the specification to
ensure that the requirements are unambiguous, consistent and understandable.
• The specified requirements for software safety should be expressed and structured
in such a way that they are clear, verifiable, testable, modifiable and traceable.
• The application software safety requirements specification shall provide information
allowing proper equipment selection.

92
DIGITAL PREVIEW
If you want to request the full hard copy or to read the online full
version scan the QR-code on the last page of this document.

280
Chapter 6 | IEC 61508: Fundamental concepts

Chapter 6 IEC 61508: Fundamental concepts

6.1 Overall safety lifecycle


The standard is based on two fundamental concepts:
• safety lifecycles;
• safety integrity levels (SIL).

A safety lifecycle is defined as an engineering process that includes all the necessary
steps to achieve the required functional safety.
The basic philosophy behind the safety lifecycle is to develop and document a safety plan,
execute it and document its execution (showing that the plan has been met) and continue
to follow it all the way to decommissioning with appropriate documentation throughout the
life of the system.
Changes during the process must similarly follow the pattern of planning, execution,
validation, and documentation.

The safety lifecycle referred to in IEC 61508 is shown in Figure 54.

135
Chapter 6 | IEC 61508: Fundamental concepts

1 Concept

2 Overall scope definition

Hazard and risk


3 analysis

Overall safety
4 requirements

Overall safety
5 requirements allocation

9 E/E/PE system safety


Overall planning requirements allocation
11 Other risk
6 Overall 7 Overall 8 Overall reduction measures
operation and safety installation and
maintenance
planning
validation
planning
commissioning
planning
10 E/E/PE
safety-related systems
Specification and
Realisation

Realisation
(see E/E/PE system
safety lifecycle)

Overall installation and


12 commissioning

Overall safety
13 validation
Back to appropriate
overall safety lifecycle
phase

Overall operation, Overall modification


14 maintenance and repair 15 and retrofit

Decommissioning or
16 disposal

Figure 54, Overall safety lifecycle according to IEC 61508

6.2 Safety Integrity Levels


A Safety Integrity Level (SIL) is defined as a relative level of risk reduction provided by a
safety function. IEC 61508 defines four SIL levels.
SIL 1 has the lowest level of risk reduction while SIL 4, the highest.
Table 1 shows SIL levels for each demand mode low and high demand (or continuous)
modes of operation.

136
Chapter 6 | IEC 61508: Fundamental concepts

PFH
PFDavg
Probability of
SIL Average probability RRF
dangerous failure per
Safety Integrity Level of failure on demand Risk Reduction Factor
hour (continuous or
per year (low demand
high demand mode of
mode)
operation)

SIL 4 ≥ 10-5 to < 10-4 ≥ 10-9 to < 10-8 ≤ 100000 to > 10000

SIL 3 ≥ 10-4 to < 10-3 ≥ 10-8 to < 10-7 ≤ 10000 to > 1000

SIL 2 ≥ 10-3 to < 10-2 ≥ 10-7 to < 10-6 ≤ 1000 to > 100

SIL 1 ≥ 10-2 to < 10-1 ≥ 10-6 to < 10-5 ≤ 100 to > 10

Table 1, Safety Integrity requirements relation between SIL, PFDavg, PFH and RFF

Operating modes (defined in Part 4 of the standard) are:

• Low demand mode:


where the safety function is only performed on demand, in order to transfer the EUC
into a specified safe state, and where the frequency of demands is no greater than
one per year;
• High demand mode:
where the safety function is only performed on demand, in order to transfer the EUC
into a specified safe state, and where the frequency of demands is greater than one
per year;
• Continuous mode:
where the safety function retains the EUC in a safe state as part of normal operation.

While continuous mode appears to be more stringent than demand mode, it should be
remembered that the units for the continuous mode are “per hour”.
Demand mode units assume a time interval of roughly one year per definition. Considering
the fact that there are about 10000 hours in a year (actually 8760), the two modes are
approximately the same in terms of safety matrix.

Basically speaking, functional safety is achieved by properly designing a Safety


Instrumented System (SIS) to carry out a Safety Instrumented Function (SIF) at a reliability
indicated by the Safety Integrity Level (SIL).
The concepts of risk and safety integrity are further discussed in Part 5 of the standard.

137
Chapter 6 | IEC 61508: Fundamental concepts

6.3 Part “1”: General requirements


6.3.1 Scope
IEC 61508 standard covers safety-related systems when one or more of such systems
incorporate electrical/electronic/programmable electronic devices. These include relay-
based systems, inherently safe solid-state logic based systems, and, perhaps most
importantly, programmable systems based on microcomputer technology.
The standard specifically covers possible hazards created when failures of the safety
functions, performed by E/E/PE safety-related systems, occur.
Functional safety is the overall program to ensure that a safety-related E/E/PE system
brings about a safe state when it is called upon to do so and is different from safety issues.
For example, IEC 61508 does not cover safety issues like electric shock, long-term
exposure to toxic substances, etc. that are covered by other standards.
IEC 61508 also does not cover low safety E/E/PE systems where a single E/E/PE system is
capable of providing the necessary risk reduction and the required safety integrity of the
E/E/PE system is less than safety integrity level 1, (e.g. the E/E/PE system is only reliable 90
% of the time or less).

IEC 61508 is concerned with the E/E/PE safety-related systems whose failures could affect
the safety of persons and/or the environment.
However, it is recognized that the methods of IEC 61508 may apply to business loss and
asset’s protection as well.
Human beings may be considered as part of safety-related system, although specific
human factor requirements are not treated in detail in the standard. The standard also
specifically avoids the concept of “fail safe” because of the high level of complexity
involved with the E/E/PE systems considered.

In regard to this, it is useful to mention an event occurred in Italy in 2002 in an industrial


plant highly protected with more than one safety-related systems, (SIL 3 level): in August
the plant was almost closed due to holidays, but having received an urgent material
request, a young plant manager, decided to set some process control in manual position,
in order to complete the production order with the help of just a few workers.
A vessel devoted to the purification of 14 tons of raw organically peroxide exploded,
resulting in the top cover blown away up to 50 meters in the air.
Eye witnesses have seen the fireball reach over 100 meters in height.
The vessel cover fell on an energy distribution cabinet nearby without consequences. The
hazardous event was not as bad as it could have been.
But, was it possible to stop this inexperienced manager to do such a risky work, forbidden
by all user manuals?

Not all accidents caused by human factors are sudden and unpredictable: the disaster in
Chernobyl in 1986 for example.

138
DIGITAL PREVIEW
If you want to request the full hard copy or to read the online full
version scan the QR-code on the last page of this document.

280
Chapter 7 | IEC 61511 Ed 2.0: Functional safety - Safety Instrumented Systems for process industry

Chapter 7 IEC 61511 Ed 2.0: Functional safety -


Safety Instrumented Systems for process
industry sector

This chapter presents a general overview of the “IEC 61511 – Functional safety – safety
instrumented system (SIS) for the process industry sector - Normative Part 1: Framework,
definitions, system, hardware and software requirements”, edition 2.0. The initial Edition
2.0 of IEC 61511-1 was released in February 2016 and amended in August 2017. The correct
consolidated version reference is IEC 61511-1:2016+AMD1:2017 CSV.
The standard has been renamed by international committees to suit their country-specific
preferences. For example, the second edition of IEC 61511 was approved in the USA by
the ISA84 committee without modification and published as ANSI/ISA-61511-1-2018 in July
2018.

Disclaimer: This text provides a general overview and explanation of the IEC 61511
standard. The information presented reflects the author's own interpretation and opinion
and is not intended to replace or supersede the actual content and requirements of the
IEC 61511 standard.
Every engineer is responsible for thoroughly analyzing their specific applications and
systems and should not rely solely on the general advice provided in this chapter. The
IEC 61511 standard remains the authoritative source, and users should refer directly to the
standard for the complete and official requirements.

7.1 Introduction
Safety Instrumented Systems (SISs) have long been integral to executing Safety
Instrumented Functions (SIFs) in the process industries. To ensure effective and reliable
performance, these systems must meet minimum standards and performance levels. The
IEC 61511 series provides comprehensive guidance for the application of SISs, addressing
their design, engineering, implementation, operation, maintenance, and decommissioning
within a structured safety life-cycle framework. Key concepts include the SIS safety
life-cycle and Safety Integrity Levels (SILs), ensuring consistency and compliance with
functional safety requirements.

The standard emphasizes the importance of Hazard and Risk Assessments (H&RA) to
derive SIS specifications and integrates the role of other safety systems only in terms of
SIS performance requirements. It applies broadly to electrical/electronic/programmable
electronic technologies and extends its principles to other logic solver technologies
and final elements. By adopting a systematic and rational approach, the IEC 61511 series
harmonizes process industry standards globally, promoting safety and economic efficiency.

199
Chapter 7 | IEC 61511 Ed 2.0: Functional safety - Safety Instrumented Systems for process industry

Although inherently safe process designs are preferred, the standard recognizes the
necessity of protective systems for addressing residual risks, encompassing various
technologies such as chemical, mechanical, and electronic. It also accommodates
jurisdictional regulations that take precedence, ensuring alignment with local safety
mandates. By fostering consistency in terminology, principles, and implementation, IEC
61511 aims to enhance safety and operational integrity across the process industries and is
recognized as a Good Engineering Practice guideline.

7.2 History
The first edition of IEC 61511 (Ed. 1.0) was released in 2003, building upon the principles
established in the ‘umbrella standard’ IEC 61508 (Ed. 1.0), which was introduced in 1998.
The release of IEC 61508 Ed. 2.0 in April 2010 brought significant updates that have
directly influenced the existing IEC 61511 standard and will continue to shape its future
revisions.

These two standards have distinct areas of focus. IEC 61508 primarily addresses
manufacturers, offering guidance on designing and building safety equipment,
instrumentation, and systems. In contrast, IEC 61511 is designed for end users, plant
operators, and project teams, focusing on the realization of Safety Instrumented Systems
(SIS) within the process industry. This includes sectors such as Oil & Gas, Chemical &
Petrochemicals, Food & Beverage, and Pharmaceutical applications.

The global adoption and acceptance of IEC 61511 vary, but in many countries—such as the
UK, Norway, and Belgium—it is increasingly recognized as a standard of good practice for
SIS implementation in the process industry. While IEC 61511 itself is not a legal requirement,
adherence to good engineering practices often is. As such, compliance with IEC 61511
serves as a practical and effective means of meeting these legal obligations.

7.3 General overview of IEC61511 Ed. 2.0


IEC 61511 Edition 2.0 is a performance-based standard that balances flexibility with
prescriptive elements to guide the design, implementation, and maintenance of Safety
Instrumented Systems (SIS). While the standard includes more prescriptive definitions and
extensively uses the term “SHALL” to outline requirements, it does not function as a rigid,
recipe-driven guide. Instead, it provides a framework rooted in two key concepts: the
safety lifecycle and Safety Integrity Levels (SIL).

The safety lifecycle is a systematic and rational engineering process designed to promote
good engineering practices throughout the design, engineering, and maintenance of
SIS, ensuring consistent and reliable performance. SIL serves as a metric to express the
expected reliability and performance of safety functions.

200
Chapter 7 | IEC 61511 Ed 2.0: Functional safety - Safety Instrumented Systems for process industry

IEC 61511 Edition 2.0 encompasses both technical and non-technical (management)
requirements, highlighting the importance of integrating organizational practices
with engineering principles to achieve functional safety. This dual focus supports a
comprehensive approach to safety and underscores the standard's role as a cornerstone
for best practices in SIS within the process industries. See Figure 80 (ref. IEC61511 Ed. 2.0
part 1).

Technical Requirements Support parts

Part 1

Development of the overall Part 1


safety requirements References
( concept, scope definition, Clause 2
hazard and
risk assessment)
Part 1
Clause 8
Definition and abbreviation
Part 1 Clause 3

Allocation of the safety


Part 1
requirements to the safety
intrumented functions and Conformance
deevelopment of the safety Clause 4
requirements specification
Clause 9 and 10 Part 1
Management and functional
safety
Clause 8
Design phase for Design phase for
safety instrumen- SIS Application
ted system programming Part 1
Clause 11 Clause 12
Safety life-cycle requirements
Clause 6

Part 1
Part 1
Verification
Factory acceptance testing, Clause 7
installation and commis-
sioning and safety valida-
Part 1
tion of safety instrumented
systems Information requirements
Clause 13, 14 and 15 Clause 19

Part 1 Part 2

Operation and mainte- Guideline for the applica-


nance, modification and tion of part 1
retrofit, decommissioning or
disposal of safety Part 3
instrumented system Guidance for the determina-
tion of the required safety
Clause 16, 17 and 18
integrty level

Figure 80, Overall framework of this standard

201
Chapter 7 | IEC 61511 Ed 2.0: Functional safety - Safety Instrumented Systems for process industry

In Edition 2.0 of IEC 61511, the standard remains divided into three parts, consistent with
the structure of IEC 61511 Edition 1.0:

Part 1 (IEC 61511-1:2016+AMD1:2017 CSV, August 2017) is normative and includes:


Framework, definitions, and requirements for systems, hardware, and software.
This part defines the compliance requirements outlined in Clauses 5 through 19. It
addresses project planning, management, documentation, and competency requirements,
as well as the technical requirements necessary to achieve safety throughout the safety
lifecycle.

Part 2 (IEC 61511-2, July 2016) is informative and provides: Guidelines for the application
of IEC 61511-1. This part offers guidance to help users read, interpret, and apply the
requirements described in Part 1.

Part 3 (IEC 61511-3, July 2016) is informative and provides: Guidance for determining the
required Safety Integrity Levels (SILs).This part offers general guidance on risk and SIL
determination. It includes:
Annex A: Risk and safety integrity – general guidance
Annexes B through I: Both quantitative and qualitative approaches to SIL selection, such
as event tree analysis, safety layer matrix methods, risk graphs, LOPA (Layer of Protection
Analysis), and risk matrices.
Annex J: (new since ed. 2.0) addressing multiple safety systems and the management of
systemic dependencies
Annex K: The ALARP principle (As Low As Reasonably Practicable).

In general, the IEC61511 standard:


• Requires that a process hazard and risk analysis be performed.
• Mandates the allocation of safety functions to protection layers.
• Specifies that when tolerable risk cannot be achieved, additional protection layers
must be defined in the Safety Requirements Specification (SRS) for the Safety
Instrumented System (SIS).
• Outlines requirements for system architecture, hardware configuration, application
programming, and system integration.
• Defines techniques and numerical targets (SIL levels) to measure the performance of
the SIS.
• Requires the collection of Quality field data through operational and mechanical
integrity program activities to assess actual SIS performance.
• Implements a safety lifecycle, detailing activities and responsibilities essential for
functional safety management and compliance.
• Establishes requirements for testing, analysis, and documentation to verify
performance, as well as the need for functional safety assessments and audits, taking
competency and independence into account.

202
DIGITAL PREVIEW
If you want to request the full hard copy or to read the online full
version scan the QR-code on the last page of this document.

280
Chapter 8 | IEC61511 Ed. 2.0 - SIS Safety Requirement Specification (SRS)

Chapter 8 IEC61511 Ed. 2.0 - SIS Safety


Requirement Specification (SRS)

Important Note
This chapter presents a general overview of the SIS Safety Requirement Specification
(SRS) - Normative Part 1: Framework, definitions, system, hardware and application
programming requirements”, edition 2.0. This is based on the FDIS version (65A-61511-1-
Ed2-IS-FDIS-OE, 2015-06-17, FDIS=Final Draft International Standard). At the time of editing
this chapter the forecasted publication date of IEC61511 Ed. 2.0 – part1 is for 2016-02.
Please note that there may be additional or different changes to the final published version
of the IEC 61511 Ed 2.0.

8.1 Introduction
In 2003 the Health and Safety Executive (HSE) from the UK released the 2nd edition of a
study called ‘Out of control: Why control systems go wrong and how to prevent failure?’.
This was based on 34 international incidents, concluding that 44% of the causes were
related to specification issues. It is clear that when it comes to safety specification, there
should be no assumptions on how to build, operate or maintain it.

Despite having the IEC61511 Edition 1.0 out since 2004, observations from a Functional
Safety Competency Trainer point of view, it is clear that the majority of the participants
know what the purpose of a SRS should be, unfortunately the only thing most people have
in common is the title of the document “Safety Requirements Specifications or simply SRS”.
There is plenty of evidence that in general the Process Industry is struggling to meet the
SIS safety requirements (10.3 - IEC61511-1). One has to say that, although the content of the
SRS is explained in a bullet list, there is very little guidance of how to implement those,
therefore many projects are left with a serious gap on ‘what should have been described’
versus ‘what cut/copy paste’ many engineer manage to reproduce again.

The 61511 Ed. 2.0 part 1 has again a normative requirement to develop a SIS Safety
Requirements Specification (Phase 3, clause 10) with some additional (new) requirements
compared to edition 1.0 in clause 10 as one of the more important activities of the
safety life cycle. The SRS requirements should address the basic and functional design
specifications and should be prepared before starting design, installation and operation.
The aim is to have every single Safety Instrumented Function (SIF or safety loop) described
in such a way that anyone wherever and whenever need to understand the SIF; or
build-, maintain-, operate-, repair- and test- that SIF; will have a precise, clear, verifiable,
maintainable and feasible information available.

223
Chapter 8 | IEC61511 Ed. 2.0 - SIS Safety Requirement Specification (SRS)

8.2 Content of the SRS


The SIS SRS may be a single document or a collection of several documents including
procedures, drawings and corporate standard practices. The SRS should be the master
document. Referenced documents are subordinate to the SRS. Of course 1 single SRS
document is easier to maintain and control, multiple and various documents all linked
together can lead to more human – failures (systematic) failures, and this is exactly what
a good engineering practice standard like the IEC61511 is trying to avoid. However, all is
depending on the owner organization practices and standards.

The SIS SRS will be a key document that should be generated in Phase 3 (clause 10,
Safety requirements specification for the safety instrumented system) and preferably be
finished (although reality it never is) before starting at Phase 4 (clause 11, SIS design and
engineering & clause 12, SIS application program development).
There is also a recommendation from the IEC61511 standard to perform a Functional Safety
Assessment (FSA) known as ‘stage 1’ in the lifecycle assessment by an independent senior
competent person(s), in order to determine that the SRS document meets the functional
safety objectives.
These requirements may be developed by the Hazard and Risk Assessment (HRA) team
and/or the project team itself. Final validation of the SIS is carried out using this SRS
document. However, the SRS will need to be maintained and be available for those that
need it for the duration of a complete lifecycle of any project. It is not just valuable for the
design phase only, the SRS will remain a key document for the successful operation and
maintenance of the SIS system.

Inputs to the SRS are coming from the preceding life cycle phases:
• Phase 1 (clause 8, Process hazard and risk assessment)
• The hazard description
• The frequency of occurrence
• The consequence
• Phase 2 (clause 9, Allocation of safety functions to existing protection layers)
• This is typically done by Layer Of Protection Analysis (LOPA)

When the tolerable risk cannot be met, then additional protection layers will need to be
specified in the SRS for the SIS:
• Specifies requirements for system architecture, hardware configuration, application
program and system integration
• Specifies techniques and numerical targets (SIL levels) to measure the performance
of the SIS

Typical content of a SRS may contain things like:


• General Functional SIS Requirements that all SIFs have in common within the SIS, e.g.
user interface for the operator/maintenance personnel, etc.;
• Specific SIF Safety Functional Requirements, HOW it should work;

224
Chapter 8 | IEC61511 Ed. 2.0 - SIS Safety Requirement Specification (SRS)

• Specific SIF Safety Integrity Requirements, HOW well it should work;


• Specific SIF Safety Integrity Requirements, HOW well it should work and HOW long it
should work for;
• Application Program Safety Requirements
• Non-Functional SIS requirements, such as code and standard, application specific
standards, environmental conditions, client-plant-project specific guidelines, etc.

8.2.1 General Requirements (61511-1, clause 10.2)


There is no such thing as one ‘generic’ SRS that can be used for everyone and every
application in the process industry. The SRS will need to be customized to the client or
plant/project specific guidelines and specifications.

However, there are some general requirements that could be applicable for all, below are
some examples given:
• What type of process application (continuous or batch)?
• What type of general hazards and their potential to harm people, environment and
capital investment?
• What process or facilities are in the neighborhood?
• Which environmental conditions can influence the SIS equipment?
• Which standards, codes and local legislation are applicable?
• What type of utility supplies, e.g. net power, uninterrupted power supply (ups), diesel
generated power, instrument air compressor, etc.?
• What is the required Plant Life Time for the SIF?

8.2.2 SIS Safety Requirements (61511-1, clause 10.3)


Similar as the previous edition of the 61511 part 1, clause 10.3 contains in total 29
requirements as an itemized list. Those requirements SHALL be sufficient to design the
SIS and SHALL include the below description of the intent and approach applied during
the development of the SIS safety requirements as applicable. The word SHALL make
those individual requirements mandatory to consider for every project providing you claim
compliance to the IEC 61511 standard.
Below are some potential example(s) based upon personal interpretation and experiences
of such requirements

8.2.2.1 A description of all the Safety Instrumented Function


necessary to achieve the required functional safety
Following the demand on the Safety Instrumented Function (SIF), a detailed description of
the actions that are designed to interface with that SIF to prevent the hazardous condition.
Sometimes the SIF can be referred to as the IPF (Instrumented Protective Function) list of
all Safety Instrumented Function (SIF), Equipment Protective Functions (EPF) and Manual

225
Chapter 8 | IEC61511 Ed. 2.0 - SIS Safety Requirement Specification (SRS)

Protective Functions (MPF).


Example:
• Low level (LAL-103) in a LNG tank 100A causes the suction pump (P-101) to trip;
• LAHH-201 shall protect the LP Gas system from Hi Hi level of LP Gas Scrubber by
closing ESDV-203;
• High-high storage tank level (LAHH-901) closes tank inlet valve SDV-904;
• High reactor temperature (TAH-506) closes the two reactor feed valves XV-501A and
XV-501B;
• High column temperature (TAH-333) closes the re-boiler steam valve XV-301.
Describe the following:
• Process variables being measured and which devices used (typically a tag name);
• Process conditions under which SIF need to act (trip point or alarm);
• Logic of the SIF that needs to be executed;
• Final element or action that the SIF will result in (actuator(s), safe state, tag name).

8.2.2.2 A list of the plant input and output devices related to each SIF
which is clearly identified by the plant means of equipment
identification
This is typically done by a field I/O or tag list, but in relation to ‘how’ the SIF functionality
is built or connected to those tag names, a detailed SIF or a safety loop description
supported by a loop diagram is recommended.
Every single SIF can contain several devices or subsystems as the IEC61508 defines them.

Example of a simple 1oo1 SIF graphical represented in Figure 88.

Figure 87, Example of a simple 1oo1 SIF

8.2.2.3 Requirements to identify and take account of common cause


failures
The potential common causes that could affect fault tolerant / redundant architectures

226
DIGITAL PREVIEW
If you want to request the full hard copy or to read the online full
version scan the QR-code on the last page of this document.

280
Chapter 9 | Functional safety manual

Chapter 9 Functional safety manual

Manufacturers are required to provide a safety manual for each device, sensor, controller
or final element that is part of a safety-related system and for which it is necessary to prove
compatibility with IEC 61508 and IEC 61511.
The purpose of this short chapter is to provide a “checklist” of requirements for such
manual.

The main purpose of this document is to specify user responsibilities for installation and
operation, in order to maintain the designed safety level.
Many users consider it to be a pre-sales document, since they want to see if there are
serious limitations in the use of a product before purchasing it.

9.1 Requirements
IEC 61508 requires that manufacturers:
• Provide procedures required for a test to detect known “dangerous failures” as
identified by the failure rates analysis of the product. The procedures must include
a statement that results of such testing are recorded. Any tools required must be
identified. The expected skill level of those in charge of accomplishing the task must
be specified. Diagnostic coverage factor for the specified test must be stated.
• Provide procedures to repair or replace the product. These must include a statement
that all failures must be reported to the manufacturer.
Any tools required must be identified. The expected skill level of those accomplishing
the work must also be specified.
• Provide any necessary installation and site acceptance test procedures required in
order to achieve safety.
• If a product firmware upgrade is possible, procedures must be given and all needed
tools must be identified. The expected skill level of those carrying out the task must
be specified.
• The safety manual must contain estimated failure rates and an estimate of the beta
factor for use when redundant devices are designed into the safety instrumented
function.
• If there are any unknown product lifetime limits, these must be stated. Otherwise a
statement that there are no known wear-out mechanisms.
Note: Although not required, it may be advisable to make some statements about
product lifetime even if there are no known wear-out mechanisms.

251
Chapter 9 | Functional safety manual

All required parameter setting assumed for safety must be stated.


Any application limitations and environmental limits must be stated (or a reference pointing
to another document).
Worst case diagnostic test time must be stated for the claimed diagnostic test coverage.

IEC 61508-2, in section 7.4.7.3, specifies the following information which shall be available
for each safety-related subsystem:
• A functional specification of those functions and interfaces of the subsystem which
can be used by the safety functions.
• The estimated rates of failure (due to random hardware failures), in any modes which
could cause a dangerous failure of the E/E/PE safety-related system, which are
detected by the diagnostic tests.
• Any limits on the subsystem environment which could be observed in order to
maintain the validity of the estimated rates of failure due to random hardware failures.
• Any limit on the lifetime of the subsystem which should not be exceeded in order to
maintain the validity of the estimated rates of failure due to random hardware failure.
• Any periodic proof test / or maintenance required.
• Diagnostic coverage.
• Diagnostic test interval.
• Any additional information (for instance repair time) which is necessary to allow the
derivation of the mean time to restoration (MTTR) following detection of a fault by the
diagnostics.
• All information which is necessary to enable the derivation of the safe failure fraction
(SFF) of the subsystem as applied in the E/E/PE safety-related system.
• The hardware fault tolerance of the subsystem.
• Any limits on the application of the subsystem which should be observed in order to
avoid systematic failures.
• The highest safety integrity level (SIL) that can be claimed for a safety function which
uses the subsystem on the base of:
- Measure and techniques used to prevent systematic failures being introduced
during the design and implementation of the hardware and software of the
subsystem,
- Design features which make the subsystem tolerant against systematic failures.
Note: this is not required in the case of those subsystems which are considered to
have been proven in use.

Any information which is required to identify the hardware and software configuration of
the subsystem in order to enable the configuration management hardware and software
of the secondary system, to allow the management of the E/E/PE safety-related system in
accordance with IEC 61508-1, 6.2.1.
Documentary evidence that the subsystem has been validated.

252
Chapter 9 | Functional safety manual

IEC 61511-1, in section 1.2.4.4.7, defines the following requirements which the safety manual
shall address:
• Use of diagnostics to perform safety functions.
• List of certified / verified safety libraries.
• Mandatory test and system shutdown logics.
• Use of watchdogs.
• Requirements for, and limitation of, tools and programming languages.
• Safety integrity level for which the device or system is suitable.

9.2 What’s new in IEC 61508 Edition 2


IEC 61508:2010 Ed. 2 has focused on new aspects related to safety, both adding new
requirements and expanding requirements already present in the previous edition.
In this chapter we will quickly discuss the following topics:
• Systematic SIL Capability (see 9.3),
• Safety Manual requirements (see 9.4).

9.3 Systematic SIL Capability


When dealing with the safety of modules, subsystems or systems, two major sources of
failure must be considered:
• random failures,
• systematic failures.

Random failures are those arising without an evident link to other external conditions and
have a nearly constant rate during the useful life of the equipment, when used according
to the design limits. They are typically hardware defects, usually defined by a Failure Rate
figure expressed in FIT (failures in 1 billion operating hours)
Systematic failures are those arising with an evident link to external conditions, so that,
when an operating condition is reproduced, their failure rate heavily increases.
Both can be hardware and/or software defects.

Techniques to avoid both random and systematic failures have been discussed in Edition 1;
this new Edition focuses on defining the Systematic Capability of a compliant item to:
• drastically limit systematic failures caused by hardware design, environmental stress
and operational failure;
• eliminate systematic failures during software development.

Methods to obtain such results depend on both a Quality Management System, oriented
to IEC 61508 requirements, and some specific design techniques used during product
development.

253
Chapter 10 Functional Safety Management in Safety
Instrumented Systems (SIS)

10.1 Disclaimer
This text is provided as a general overview and explanation of the IEC 61511 standard.
The information presented is the author interpretation and opinion and is not intended to
replace or supersede the actual content and requirements of the IEC 61511 standard. Every
engineer is responsible for thoroughly analysing their specific application and system and
should not rely solely on the general advice provided here. The IEC 61511 standard remains
the authoritative source, and users should refer directly to the standard for the complete
and official requirements.

10.2 Introduction
Functional Safety is a critical aspect of engineering and operations within industries that
rely on Safety Instrumented Systems (SIS) to mitigate risks. The successful implementation
of SIS is governed by rigorous standards such as IEC 61511, which provides a structured
approach to ensure the design, operation, and maintenance of these systems achieve
and maintain safety integrity levels (SIL). This chapter explores the key aspects of
functional safety management as outlined in Clause 5 of IEC 61511, focusing on essential
management activities, competency, risk evaluation, safety planning, implementation, and
monitoring, as well as Functional Safety Assessments. All clause references in this chapter
are based on the IEC/ISA 61511 second edition (2016/17-2018).

10.3 Objective of Functional Safety Management (FSM)


(Clause 5.1)
10.3.1 FSM Objectives
FSM aims to define, document, monitor, and assess requirements for technical and
managerial activities throughout the SIS lifecycle. For instance:

• During hazard analysis, FSM ensures that LOPA and HAZOP studies are reviewed by
qualified personnel.
• It oversees that risk reduction targets are clearly communicated and integrated into
the Safety Requirements Specification (SRS).
• Similarly, during operations, FSM tracks proof test intervals and field failure data,

269
Chapter 10 | Functional Safety Management in Safety Instrumented Systems (SIS)

ensuring that operational feedback informs maintenance strategies and mitigates


systematic failures effectively.

FSM specifies responsibilities across individuals, departments, and organizations, ensuring


that functional safety objectives are met effectively.

10.3.2 Systematic Failures


FSM specifically targets systematic failures, often caused by human errors, which cannot
be predicted using mathematical models. For example, in the oil and gas industry,
systematic failures might involve incorrect calibration of pressure sensors during routine
maintenance, leading to inaccurate readings and potential operational hazards. In the
chemical processing industry, programming errors in logic solvers could cause unintended
activation of safety mechanisms, disrupting production.

These examples underscore the need for tailored training, rigorous review protocols, and
structured validation processes to mitigate such risks effectively. Common issues include
errors during SIS configuration, insufficient testing of logic solvers, and miscalibration of
sensors. Mitigation strategies involve implementing:

• Rigorous change management protocols.


• Regular training programs for personnel.
• Detailed assessment and audits to identify potential vulnerabilities early.

This highlights the importance of quality assurance throughout the SIS lifecycle.

10.3.3 FSM as a Quality Mechanism


FSM is a dynamic and evolving system designed to maintain functional safety throughout
the SIS's operational life. It integrates monitoring tools like FSAs and audits to enhance
quality by identifying and rectifying errors early. FSM must be planned, the plan or
procedure may be in conjunction with organisation’s Quality Management System.

10.3.4 Mandatory FSM Procedures


Organizations making functional safety claims for products or services must have an FSM
system. Procedures should be established to demonstrate the adequacy and compliance
of these systems.

10.3.5 Lifecycle Integration


FSM encompasses all aspects of the lifecycle, including organization, risk evaluation,
safety planning, implementation, monitoring, and revision. A robust FSM framework

270
Chapter 10 | Functional Safety Management in Safety Instrumented Systems (SIS)

includes mechanisms for handling change, traceability, and competency evaluations.

10.3.6 Common Misconceptions


FSM is equally critical for all SIL levels, not just higher ones. It is not a static, checklist-
based process but a living system requiring continual updates and attention. Grandfather
clauses for existing systems still require ongoing FSM and performance monitoring.

Clause 5.1 emphasizes the importance of identifying management activities necessary to


achieve functional safety objectives. The management of functional safety encompasses
planning, resource allocation, organizational structure, and the establishment of
administrative systems that mitigate human errors—a significant contributor to SIS failures.
This section highlights the necessity of ensuring competent personnel are involved in all
phases of the SIS lifecycle. Key activities include:

• Planning and resource development.


• Defining organizational roles and responsibilities.
• Conducting Functional Safety Assessments and audits.
• Verification and validation activities, detailed further in Clauses 7 and 15, respectively.

10.4 Requirements for Management Activities (Clause 5.2)


10.4.1 Policy and Strategy (Clause 5.2.1)
Organizations must define a policy and strategy for achieving functional safety, including
methods for evaluating success and ensuring effective communication. These policies are
typically documented in corporate or site-specific SIS standards. The strategy outlines the
execution of functional safety activities and the evaluation methods employed to ensure
objectives are met. Effective communication mechanisms, including training programs and
competency tracking, are vital to disseminate responsibilities throughout the organization.

The strategy for functional safety should integrate with existing organizational frameworks
such as risk management policies or quality management systems. This ensures a
cohesive approach where functional safety objectives align with overarching corporate
goals. Moreover, this strategy should include the use of modern tools and software for
lifecycle management to enhance accuracy and efficiency.

10.4.2 Organization and Resources (Clause 5.2.2)


Clause 5.2.2 highlights the necessity of assigning roles and responsibilities for each
phase of the SIS lifecycle. Rather than assigning tasks to specific individuals, activities are
allocated to roles, ensuring continuity despite personnel changes.
For example:

271
Chapter 10 | Functional Safety Management in Safety Instrumented Systems (SIS)

• Planning for Layer of Protection Analysis (LOPA) may be assigned to a Process Safety
Management Coordinator.
• SIL verification tasks may fall under the remit of an SIS Subject Matter Expert (SME).

This allocation ensures clarity and accountability, often supported by Human Resources
systems that define job descriptions and competencies. Additionally, organizations must
establish a clear structure to oversee SIS lifecycle activities, potentially creating specialized
teams or roles dedicated solely to functional safety management.
A Responsibilities Matrix, as outlined in Annex C of ISA-TR84.00.04-2020, is a powerful
tool for ensuring accountability. For example, during the commissioning phase of the SIS
lifecycle, this matrix might define:

• Functional Safety Manager: Responsible for overall lifecycle compliance and


coordinating assessments.
• Process Engineer: Accountable for validating the safety requirements related to
process design.
• Control Systems Engineer: Consulted for ensuring correct SIS hardware and
software integration.
• Maintenance Technician: Responsible for executing pre-startup tests and ensuring
readiness of field devices.
• Operations Supervisor: Informed of operational procedures and trained to handle
the SIS interface.

This practical example highlights how responsibilities are clearly delineated to ensure
tasks are executed efficiently and without overlap, fostering accountability and operational
continuity. This matrix explicitly defines the roles and responsibilities across various
disciplines involved in functional safety management, such as engineering, operations, and
maintenance. It provides:

• Role Clarity: Clearly delineates who is responsible, accountable, consulted, and


informed (RACI) for each task in the SIS lifecycle.
• Competency Assurance: Links required competencies and training to each role to
ensure that personnel can effectively execute their responsibilities.
• Operational Continuity: Facilitates a smooth transition of responsibilities in case of
personnel changes, reducing risks associated with knowledge gaps.

Examples of roles typically included in such a matrix are:

• Functional Safety Manager


• Process Engineer
• Control Systems Engineer
• Maintenance Technician
• Operations Supervisor

272
DIGITAL PREVIEW
If you want to request the full hard copy or to read the online full
version scan the QR-code on the last page of this document.

280
Index of Figures

Index of Figures

Figure 1, IEC 61508 requirements.............................................................................................................................13


Figure 2, Legislation for risk of relevant hazardous events in the EEC and Italy....................................... 22
Figure 3, Bhopal Disaster. 1976 Union Carbide plant: 20 thousand deaths and almost 200
thousand injured..................................................................................................................................... 23
Figure 4, Risk reduction with several prevention layers................................................................................... 24
Figure 5, Prevention and mitigation layers of the hazardous event.............................................................. 25
Figure 6, Refinery........................................................................................................................................................ 26
Figure 7, Control room................................................................................................................................................27
Figure 8, Offshore platform...................................................................................................................................... 30
Figure 9, Release valves..............................................................................................................................................31
Figure 10, Hydrant cannon........................................................................................................................................ 32
Figure 11, Refinery tower flare.................................................................................................................................. 32
Figure 12, Optimal safety scale................................................................................................................................ 36
Figure 13, Reliability Figure of a device..................................................................................................................38
Figure 14, Device Reliability Function with exponential decay........................................................................ 39
Figure 15, Venn diagram of successful-unsuccessful operations of a device...............................................41
Figure 16, Venn diagram for successful and unsuccessful operation of a device..................................... 45
Figure 17, Schematic representation of MTTF, MTTR, MTBF............................................................................47
Figure 18, Venn Diagram: Reliability-Unreliability; Availability-Unreliability and relations
with MTTF and MTTR..............................................................................................................................48
Figure 19, Example of failure rate function of time (life) (bathtub curve)........................................................ 51
Figure 20, Failure rates subdivision in common and normal mode (Beta factor)....................................... 54
Figure 21, Example of reliability block diagrams................................................................................................. 55
Figure 22, Typical fault tree symbols......................................................................................................................57
Figure 23, Fault tree events for a power supply system (example 1)............................................................. 58
Figure 24, Fault tree events for a power supply system................................................................................... 59
Figure 25, Markov model for a system with two states and one transition
(single non-repairable component)..................................................................................................... 61
Figure 26, States probabilities for great number of cycles.............................................................................. 62
Figure 27, Markov model for a system with two states and two transitions................................................ 63
Figure 28, States probability for great number of cycles and for a single repairable device................. 64
Figure 29, Markov diagram for a system with 3 states and 5 transitions..................................................... 65
Figure 30, State probability for a great number of cycles................................................................................ 68

269
Index of Figures

Figure 31, Markov diagram for 1oo1 architecture..................................................................................................70


Figure 32, Markov diagram for 1oo2 architecture.................................................................................................71
Figure 33, Event tree diagram for simplified loss of chemical containment.................................................74
Figure 34, Event tree for gas release......................................................................................................................75
Figure 35, Event tree for liquid release..................................................................................................................77
Figure 36, Example of Pool fire................................................................................................................................79
Figure 37, Example of Jet fire................................................................................................................................... 80
Figure 38, Example of Flash fire............................................................................................................................... 81
Figure 39, Example of fireball.................................................................................................................................. 82
Figure 40, Example of a vapor cloud explosion (BLEVE)...................................................................................84
Figure 41, Example of a small SIS............................................................................................................................ 89
Figure 42, PFD and PFDavg at different T-proof intervals (1oo1 architecture)............................................. 94
Figure 43, PFDavg distribution within the SIF.......................................................................................................97
Figure 44, Schematic diagrams of some system architectures...................................................................... 99
Figure 45, 1oo1 system architecture......................................................................................................................104
Figure 46, 1oo2 system architecture......................................................................................................................112
Figure 47, Components application in 1oo2 system architecture...................................................................116
Figure 48, 2oo3 system architecture and voting circuit.................................................................................... 118
Figure 49, Example of 2oo3 (a) architecture and voting circuit (b).................................................................121
Figure 50, P&I diagram with online bypass valve for periodic proof testing.............................................. 127
Figure 51, Proposed safety instrumented functions (SIFs)................................................................................ 131
Figure 52, Proposed conceptual SIS design...................................................................................................... 133
Figure 53, Block Diagram for Pilot Gas Shutdown SIF..................................................................................... 133
Figure 54, Overall safety lifecycle according to IEC 61508............................................................................ 136
Figure 55, Management of Functional Safety according to IEC61508-1, Clause 6.................................... 141
Figure 56, Close loop view of the safety lifecycles........................................................................................... 142
Figure 57, Results of system failure cause study: HSE “Out of Control”...................................................... 142
Figure 58, Origin of safety lifecycles..................................................................................................................... 144
Figure 59, First portion of the overall safety lifecycles..................................................................................... 145
Figure 60, Realization activities in the overall safety lifecycles..................................................................... 145
Figure 61, E/E/PES safety lifecycle in realization phase (Part 2)..................................................................... 146
Figure 62, Operation and Maintenance phases of the overall safety lifecycle......................................... 146
Figure 63, Relation between Parts 2 and 3 of IEC 61508................................................................................ 153
Figure 64, Terminology: System, Subsystem, Element..................................................................................... 154
Figure 65, Synthesis of elements to achieve the required systematic capability
(IEC 61508-2 Clause 7.4.3)...................................................................................................................156
Figure 66, Synthesis of elements to achieve the required systematic capability
(IEC 61508-2 Clause 7.4.3)...................................................................................................................156
Figure 67, Systematic Safety Integrity / Systematic Capability IEC 61508 Edition 2................................. 157

270
Index of Figures

Figure 67, Systematic Safety Integrity / Systematic Capability IEC 61508 Edition 2................................. 157
Figure 68, Architecture for data communication...............................................................................................158
Figure 69, Safety lifecycle of software in realization phase............................................................................ 163
Figure 70, Software safety integrity and the development lifecycle (V-Model)......................................... 164
Figure 71, Basic concept of risk reduction........................................................................................................... 172
Figure 72, General concepts of risk reduction, according to IEC 61508..................................................... 176
Figure 73, Risk and ALARP zone............................................................................................................................ 178
Figure 74, Example of safety integrity level calculation...................................................................................182
Figure 75, Risk graph: general scheme................................................................................................................ 184
Figure 76, Risk graph: example (illustrates general principles only).............................................................185
Figure 77, Sample Process for LOPA Example....................................................................................................189
Figure 78, Event tree for LOPA example..............................................................................................................189
Figure 79, Example of FMEDA analysis................................................................................................................ 193
Figure 80, Overall framework of this standard...................................................................................................201
Figure 81, SIS safety lifecycle phases and FSA stages....................................................................................204
Figure 82, Relationship of system, SIS hardware and SIS application program....................................... 207
Figure 83, Application program safety life cycle and its relationship to the SIS safety life
cycle (ref. IEC61511 Ed. 2.0 part 1)......................................................................................................208
Figure 84, Application program V-Model..............................................................................................................211
Figure 85, Relation between Verification and Assessment............................................................................ 214
Figure 86, Relationship between IEC61511 and IEC61508............................................................................... 217
Figure 87, Example of a simple 1oo1 SIF..............................................................................................................226
Figure 88, Example of PFD and PFDavg variation in case T-proof test is carried out once a year with
70% effectiveness.................................................................................................................................230
Figure 89, Functional diagram of a SIL 3 Repeater Power Supply HART from GM International......... 231
Figure 90, Failure Rate Table and the potential PFDavg................................................................................ 233
Figure 91, Example of a testing procedure at T-proof..................................................................................... 234
Figure 92, GM International PSS1250 Power Supply, example of application..........................................239
Figure 93, GM International Smart relay D5294S typical application.........................................................240
Figure 94, GM International D5094S Relay, example of application............................................................ 241
Figure 95, MTTR, Mean Time To Restoration..................................................................................................... 244

271
Index of Tables

Index of Tables

Table 1, Safety Integrity requirements relation between SIL, PFDavg, PFH and RFF................................ 93
Table 2, Simplified equations for PFDavg calculation....................................................................................... 94
Table 3, 1oo1 system architecture and TI of 1 year.............................................................................................. 95
Table 4, 1oo1 system architecture and TI of 1 year except for valve............................................................... 96
Table 5, PFDavg “weighing” for 1oo1 system architecture................................................................................97
Table 6, 1oo1 system architecture and T-proof test interval optimization..................................................... 96
Table 7, The impact of redundancy........................................................................................................................100
Table 8, PFDavg formulae considering Beta Factor..........................................................................................103
Table 9, 1oo2 system architecture and TI = 1 year.............................................................................................. 114
Table 10, 1oo2 SIF changes for TI = 1, 3, 5 and 10 years....................................................................................115
Table 11, 1oo2 system architecture for Valve only............................................................................................... 117
Table 12, 2oo3 system architecture and TI of 1 year.........................................................................................120
Table 13, Comparison between system architectures......................................................................................122
Table 14, TI = 1 yr, TD = 0.0009 yr........................................................................................................................... 123
Table 15, TI = 3 yrs, TD = 0.0009 yr....................................................................................................................... 123
Table 16, TI = 5 yrs, TD = 0.0009 yr....................................................................................................................... 123
Table 17, TI = 10 yrs, TD = 0.0009 yr...................................................................................................................... 123
Table 18, SIS design guidelines based on SIL...................................................................................................... 131
Table 19, Conceptual design summary................................................................................................................. 132
Table 20, Failure Rate Data (Failures per year).................................................................................................. 134
Table 21, Assessment independence level, as a function of consequences............................................. 147
Table 22, Assessment independence level for E/E/PE and software lifecycle activities......................... 147
Table 23, Documentation examples...................................................................................................................... 149
Table 24, SFF (Safe Failure Fraction) for A type components........................................................................152
Table 25, SFF (Safe Failure Fraction) for B type components........................................................................152
Table 26, Architectural Constrains: Route 2H.....................................................................................................155
Table 27, Risk reduction factor, as a function of SIL levels and Availability................................................. 174
Table 28, Table 28, Example of typical HAZOP report..................................................................................... 174
Table 29, Hazardous events classification.......................................................................................................... 183
Table 30, Interpretation of the classes of risk..................................................................................................... 183
Table 31, Data raegarding the example in Figure 77.........................................................................................186
Table 32, Sample LOPA Example...........................................................................................................................190

273
Index of Tables

Table 33, Safety integrity requirements: PFDavg and PFH............................................................................205


Table 34, Minimum HFT requirements according to SIL.................................................................................209
Table 35, List of the SIS sensors, calibration & operation range, accuracy, alarm and trip point.........236
Table 36, Functional relationship of the inputs and outputs (I/O) for the SIFs.......................................... 237

274
Reference

Reference

• IEC 61508, IEC 61511 Standard


• “Control System Safety Evaluation & Reliability” 2nd edition
William M. Goble. ISA (ISBN 978-1-55617-996-9)
• “Use and Development of Qualitative Reliability and Safety Analysis in New Product
Design” William M. Goble. EXIDA
• “Safety Instrumented Systems: Design, Analysis, and Justification”
Paul Gruhn and Harry L. Cheddie, ISA (ISBN: 978-1-55617-956-3).
• “Safety Integrity Level Selection - Systematic Methods Including Layer of Protection
Analysis” Edward M. Marszal, P.E., Dr. Eric W. Scharpf, MIPENZ, ISA (ISBN 978-1-55617-
777-4)
• “What Went Wrong?: Case Histories of Process Plant Disasters”,
Trevor A. Kletz, Gulf Publishing, 1998
• “Still Going Wrong!: Case Histories of Process Plant Disasters and How They Could
Have Been Avoided” Trevor A. Kletz, Elsevier 2003
• “SFPE Handbook of Fire Protection Engineering”
NFPA, Philip J. Di Nenno, Society of Fire Protection Engineers
• “What is a PFDavg?” Julia V. Bukowski, Jan Rouvroye and William M. Goble
• “Gestione Integrata della Sicurezza” Angelo Papagno, ASI ESTESA
• “Valve Ranking and Partial Stroke”
G. Ramachandran. ISA Technical Conference, Long Beach CA , 2004
• “Determining the Required Safety Integrity Level for your Process”
Lawrence Beckman, ISA Transactions 1998
• “Easily Assess Complex Safety Loops”
Lawrence Beckman, Chemical Engineering Progress, March 2001
• “Analisi di rischio ed affidabilità dei sistemi di allarme e blocco”
Fabrizio Gambetti, Conferenza Snam Progetti.
• "Establishing Preventative Safety and Maintenance Strategies by Risk Based
Management – The Tools of the Trade", Tilman Rasche, Ken Wolly Minerals Industry
Health and Safety Centre, Australia, 2000
• “Maintainability & Maintenance Management”
Joseph D. Patton, Jr., ISA 2005 (ISBN 9781556179440)
• "API/CMA Recommended Practice 752 - Management of Hazards Associated with
Location of Process Plant Buildings" SCSRA Risk Resources, April 1995
• “Guidelines for Evaluating Process Plant Buildings for External Explosions and Fires”
Center for Chemical Process Safety, ISBN 9780816906468
• “Out of Control, Why control systems go wrong and how to prevent failure.”
HSE (HSG238) 2003.

275
Reference

• “Reliability Assessments of Repairable Systems”


K G L Simpson and M Kelly (Silvertech Safety Consultancy Ltd.)
• “Guidelines for Safe and Reliable Instrumented Protective Systems” (2007)
CCPS
• “IEC61508 Ed. 2.0 Functional Safety of electrical/electronic/programmable electronic
safety-related systems”, parts 1-7 (2010)
IEC
• “IEC61511 Ed. 2.0 Functional Safety: Safety Instrumented Systems for the Process
Industry sector”, parts 1-3 – (CDV version 65A/691/CDV – 2014)
IEC
• “Changes /What is it with IEC61511?”
Norwegian University of Science and Technology NTNU 2012, Mary Ann Lundteigen
• “IEC61511-1 Ed. 2, Initial Reflections on an Evolving Standard”
TÜV Rheinland International Symposium 2012, Dirk Hablawetz – BASF SE
• “IEC61511-1 Ed. 2, When and what”
TÜV Rheinland International Symposium 2014, Heidi Fuglum and Cato Bratt – ABB
Norway

276
Reference

Denial of responsibility

Information presented in this publication is for the general education of the reader.
Because the authors do not have control over the use of the information by the readers,
the authors disclaim any and all liability of any kind arising out of such use.
The reader is expected to exercise sound professional judgment in using any of the
information presented in a particular application.
Additionally, the authors have investigated or considered the effect of any patents on the
ability of the reader to use any of the information in a particular application. The reader is
responsible for reviewing any possible patents that may affect any particular use of the
information presented.
Any references to commercial products in the work are cited as examples only. Any
referenced trademarks or tradenames, belong to the respective owner of the mark or
name.

Examples are provided as simple illustrations of the topics discussed and, as such, are not
intended as a guide to manage plant safety. The readers should use and apply only the
guidance provided in the standards pertaining to their applications.

The reproduction by any means, partial or total, of the book and its content is prohibited
without making a clear reference to the original source.

277
IEC 61508 Ed.2 and IEC 61511 Ed.2 are certainly the leading standards in terms
of safety related equipment: The knowledge of their requirements and the ability
to fulfil them are essential to both manufacturers and customers.

This manual is updated according to the latest edition of both standards and
includes a new chapter about Safety Requirements Specification.