Professional Documents
Culture Documents
ELECTRICAL SYSTEM
UNIT-I
ELECTRIC MOTORS
COMPRESSED AIR SYSTEM
HVAC AND REFRIGERATION SYSTEM
UNIT-II
UNIT-III
DG SET SYSTEMS
ENERGY EFFICIENT TECHNOLOGIES IN ELECTRICAL SYSTEMS
ENERGY EFFICIENCY IN
ELECTRICAL UTILITIES
UNIT I
CHAPTER I
ELECTRICAL SYSTEM
UNIT I
Introduction
Classification
Electrical Systems may be classified by:
type of current (direct and
alternating)
plant location (overhead and cable)
layout (circular and radial)
normal operating mode (open and
closed)
ELECTRICAL SYSTEM
UNIT I
ELECTRICAL SYSTEM
UNIT I
Important
Equipment
ELECTRICAL SYSTEM
UNIT I
ELECTRICAL SYSTEM
Load Factor
Diversity Factor
Utilisation Factor
Maximum Demand
Maximum Demand is measured during a prefixed time duration of either 15
minutes or 30 minutes and then multiplied by either four or two respectively to
give kVAH per hour i.e. KVA. Thus, at the end of each time cycle, the timer is
reset and fresh measurement starts.
UNIT I
ELECTRICAL SYSTEM
Connected Load
Connected load is the sum of the nameplate ratings of all the equipment utilising
electricity inside the consumer installation.
Average load is energy consumption recorded divided by the operating hours of
the plant.
Load Factor = (Average Load)/ (Maximum Demand) always less than 1.
Diversity Factor = (Connected Load)/ (Maximum Demand) always more than
1.
Utilisation Factor=(Average Load)/(Connected Load) always less than 1.
Utilisation Factor = (Load Factor) / (Diversity Factor)
Power Factor
UNIT I
ELECTRICAL SYSTEM
UNIT I
ELECTRICAL SYSTEM
Once the power factor capacitors are installed, they continuously need to be
monitored for their performance. Their performance depends on voltage as
well as ambient temperature.
The capacitor before failing totally, gives a number of indications showing the
deterioration of their performance. This can be monitored by recording the
daily reading or hourly reading of the consumption and power factor by the
user. However specialised testing can be done by the manufacturer to know
the exact reason for the failure.
Transformer
The transformer is one of the most widely used electrical equipment. The main
function of the transformer is to either increase voltage or to reduce voltage.
UNIT I
ELECTRICAL SYSTEM
UNIT I
Control Used for Voltage Fluctuation
The control of voltage in a transformer is
important due to frequent changes in the supply
voltage level. Voltage regulation in transformers
is done by altering the voltage transformation
ratio with the help of tapping.
ELECTRICAL SYSTEM
CHAPTER II
ELECTRIC MOTORS
UNIT I
ELECTRIC MOTORS
Introduction
Motors convert electrical energy into mechanical energy by the interaction
between the magnetic fields set up in the stator and rotor windings. Electric
motors are undoubtedly the largest prime movers used. Industrial electric motors
can be broadly classified as:
induction motors
direct current motors
synchronous motors
All
motor types have the same four operating components which are:
stator (stationary windings)
rotor (rotating windings)
bearings
frame (enclosure)
Types of Motors
There are two main types of motors:
DC Motors
AC Motors
UNIT I
Industrial Classification of Motors
Industrial electric motors are generally classified as:
direct current motors (DC motors)
synchronous motors (AC motors)
induction motors (induced magnetic field)
ELECTRIC MOTORS
UNIT I
ELECTRIC MOTORS
Advantages of DC Motors
The main advantage of DC motors is speed control, which does not affect the
quality of power supply. It can be controlled by adjusting:
the armature voltage increasing the armature voltage will increase the speed
the field current reducing the field current will increase the speed
UNIT I
ELECTRIC MOTORS
Disadvantages of DC Motors
The disadvantages of these motors are mainly their initial cost and maintenance
of brushes and the commutator. Moreover they require a separate cooling
arrangement.
UNIT I
ELECTRIC MOTORS
Synchronous/AC Motors
In these motors, the stator is given a three phase A.C. supply. The Rotor is
given a DC supply through brushes and slip rings. The stator produces a
rotating magnetic field and the rotor field is locked into the synchronism of the
rotating magnetic field.
The main advantage of this motor was that by controlling the rotor
excitation, the power factor of the motor could be controlled and the motor
could be made to operate with a leading power factor.
UNIT I
ELECTRIC MOTORS
Induction Motors
Induction motors are the most commonly used prime mover for various
equipment in industrial applications.
In induction motors, the induced magnetic field of the stator winding induces
a current in the rotor.
This induced rotor current produces a second magnetic field, which tries to
oppose the stator magnetic field, and this causes the rotor to rotate.
UNIT I
The Power Factor
The power factor of the motor is given as:
Power factor = Cos = kW/kVA
ELECTRIC MOTORS
UNIT I
ELECTRIC MOTORS
Motor Load
Because the efficiency of a motor is difficult to assess under normal operating
conditions, the motor load can be measured as an indicator of the motors
efficiency. As loading increases, the power factor and the motor efficiency increase
to an optimum value at around full load.
UNIT I
ELECTRIC MOTORS
CHAPTER III
COMPRESSED AIR SYSTEM
UNIT I
Introduction
Classification of Compressors
Compressors are broadly classified as : Positive Displacement Compressors
Dynamic (Centrifugal) Compressors
UNIT I
Dynamic compressors
Dynamic compressors increase the air velocity, which is then converted to
increased pressure at the outlet. They are basically centrifugal compressors and
are further divided into:
radial type
axial flow type
Compressor Capacity
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature, total pressure, and composition
existing at the compressor inlet.
UNIT I
Inter-stage
coolers
Moisture Drain
Traps
They prevent
dust from
entering the
compressor and
are normally
specified in
terms of microns
(indicating the
size below which
dust cannot be
prevented).
Hence before
choosing a filter,
it is worthwhile
to assess the
dust conditions
in the
surroundings.
During
compression the
temperature of
air increases,
especially when
multistage
compressors are
used, each
stage needs
cooling. Hence
coolers are
required and
they are mostly
water-cooled.
These are used
to remove the
rest of the
moisture which
may be left at
various
locations in the
pipelines.
Air Receivers
Air receivers are
provided to be
storage and
smoothening
vital air output reducing
pressure
variations from
the compressor.
UNIT I
ENERGY EFFICIENCY IN
ELECTRICAL UTILITIES
UNIT II
CHAPTER I
HVAC AND REFRIGERATION SYSTEM
UNIT II
Introduction
UNIT II
Air-Conditioning Systems
Depending on applications, there are several options / combinations, which are
available for use as given below:
UNIT II
UNIT II
UNIT II
Evaporator
Absorber
UNIT II
Condenser
To complete the refrigeration cycle, and thereby ensuring the refrigeration takes
place continuously, the following two functions are required:
To concentrate and liquefy the evaporated refrigerant vapour, which is
generated in the high pressure generator.
To supply the condensed water to the evaporator as refrigerant (water).
UNIT II
UNIT II
A clear understanding of the cooling load to be met is the first and most
important part of designing/selecting the components of a refrigeration
system.
Important factors to be considered in quantifying the load are the actual
cooling need, heat (cool) leaks, and internal heat sources (from all heat
generating equipment).
Consideration should also be given to process changes and/or changes in
ambient conditions that might affect the load in the future.
UNIT II
Cold Insulation
Insulate all cold lines / vessels using economic insulation thickness to
minimise heat gains; and to choose appropriate (correct) insulation.
Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling
and segregation of critical areas for air conditioning by air curtains.
Building Heat Loads Minimisation
Cold Insulation
CHAPTER II
FANS AND BLOWERS
UNIT II
Introduction
Fans and blowers provide air for ventilation and industrial process
requirements.
Fans generate a pressure to move air (or gases) against a resistance caused
by ducts, dampers, or other components in a fan system.
The fan rotor receives energy from a rotating shaft and transmits it to the air.
Industrial Fans
Industrial fans and blowers are machines whose primary function is to provide
a large flow of air or gas to various processes of many industries.
This is achieved by rotating a number of blades, connected to a hub and shaft
and driven by a motor or turbine.
UNIT II
Types of Fans
Fans are divided into two general categories:
Centrifugal flow
In centrifugal flow, airflow changes direction twice once when entering and
secondly, while leaving (forward curved, backward curved or inclined, radial)
Axial flow
In axial flow, air enters and leaves the fan with no change in direction (propeller,
tube axial, vane axial)
Centrifugal
Flow
Axial Flow
UNIT II
Types of Blowers
Blowers can achieve much higher pressures than fans, as high as 1.20 kg/cm2.
They are also used to produce negative pressures for industrial vacuum systems.
Major types of blowers are:
Centrifugal Blowers
Centrifugal blowers look more like centrifugal pumps compared to fans.
In multi-stage blowers, air is accelerated as it passes through each impeller. In
a single-stage blower, air does not take many turns, and hence it is more
efficient.
Positive-Displacement Blowers
Positive-displacement blowers have rotors, which "trap" air and push it through
the housing.
Positive-displacement blowers provide a constant volume of air even if the
system pressure varies.
UNIT II
System Characteristics
The term system resistance is used while referring to the static pressure. The
system resistance is the sum of static pressure losses in the system.
The system resistance varies with the square of the volume of air flowing
through the system.
System resistance increases substantially as the volume of air flowing through
the system increases; square of air flow. Conversely, resistance decreases as
flow decreases.
System Characteristics
UNIT II
Fan Characteristics
The fan curve is a performance curve for the particular fan under a specific
set of conditions. The fan curve is a graphical representation of a number of
interrelated parameters.
Typically, a curve will be developed for a given set of conditions usually
including fan volume, system static pressure, fan speed and brake
horsepower required to drive the fan under the stated conditions.
UNIT II
Fan Laws
The fans operate under a predictable set of laws concerning speed, power and
pressure. A change in speed (rpm) of any fan will predictably change the pressure
rise and power necessary to operate it at the new RPM.
UNIT II
Forward curved fans have large hub-to-tip ratios compared to backward curved
fans and produce lower pressure.
Radial fans can be made with different heel-to-tip ratios to produce different
pressures.
At both design and off-design points, backward-curved fans provide the most
stable operation.
Centrifugal fans are suitable for low to moderate flow at high pressures, while
axial-flow fans are suitable for low to high flows at low pressures.
UNIT II
Flow Control Strategies
Various ways to achieve a change in
flow are:
Pulley Change
Damper Controls
Variable Speed Drives
Series and Parallel Operation
CHAPTER III
PUMPS AND PUMPING SYSTEM
UNIT II
Introduction
A pump is a device used to move fluids, such as liquids, gases or slurries. A pump
displaces a volume of fluid by physical or mechanical action.
UNIT II
Types of Pumps
Pumps have a variety of sizes for a wide range of applications. They can be
classified according to their basic operating principles as:
Dynamic pumps: Dynamic pumps are characterised by their mode of
operation; a rotating impeller converts kinetic energy into pressure or velocity
that is needed to pump the fluid.
UNIT II
Centrifugal Pump
The two main parts of the centrifugal pump are:
The impeller, which is the only moving part, is attached to a shaft and driven
by a motor. Impellers are generally made of bronze, polycarbonate, cast iron,
stainless steel as well as other materials.
The diffuser (also called volute) houses the impeller and captures and directs
the water off the impeller.
Working
UNIT II
System Characteristics
In a pumping system, the objective, in most cases, is either to transfer a liquid
from a source to a required destination, e.g. Filling a high level reservoir or to
circulate liquid around a system.
Pressure is needed to make the liquid flow at the required rate and this must
overcome head losses' in the system.
Losses are of two types:
Static Head: The static head is simply the difference in the height of the
supply and destination reservoirs
Friction Head: The friction head (sometimes called dynamic head loss) is the
friction loss on the liquid being moved, in pipes, valves and equipment in the
system.
UNIT II
UNIT II
ENERGY EFFICIENCY IN
ELECTRICAL UTILITIES
UNIT III
CHAPTER I
COOLING TOWER
UNIT III
COOLING TOWER
Introduction
The primary task of a cooling tower is to reject heat into the atmosphere. They
represent a relatively inexpensive and dependable means of removing low-grade
heat from cooling water.
Mechanical draft: Mechanical draft towers utilise large fans to force or suck
air through circulated water. The water falls downward over fill surfaces,
which helps to increase the contact time between the water and the air - this
helps to maximise heat transfer between the two.
UNIT III
COOLING TOWER
Tower Materials
Following are a few of the materials used in the construction of cooling towers:
Galvanized Steel
Stainless steel
Concrete
Glass Fibre
UNIT III
COOLING TOWER
Performance Parameters
Range is the difference between the cooling tower water inlet and outlet
temperature.
Approach is the difference between the cooling tower outlet cold water
temperature and the ambient wet bulb temperature.
UNIT III
COOLING TOWER
Capacity
Range
Range is a direct function of the quantity of water circulated and the heat load.
Increasing the range as a result of added heat load does require an increase in
the tower size.
If the cold water temperature is not changed and the range is increased with a
higher hot water temperature, the driving force between the wet bulb
temperature of the air entering the tower and the hot water temperature is
increased, the higher level heat is economical to dissipate.
UNIT III
COOLING TOWER
The counter-flow and cross flows are two basic designs of cooling towers
based on the fundamentals of heat exchange.
Cross-flow cooling towers are provided with splash fill of concrete, wood or
perforated PVC.
Counter-flow cooling towers are provided with both film fill and splash fill.
Counter flow heat exchange is more effective as compared to cross flow or
parallel flow heat exchange.
UNIT III
COOLING TOWER
Optimise cooling tower fan blade angle on a seasonal and/or load basis.
Correct excessive and/or uneven fan blade tip clearance and poor fan
balance.
CHAPTER II
LIGHTING SYSTEM
UNIT III
LIGHTING SYSTEM
Introduction
Types of Lamps
Incandescent Lamps
Reflector Lamps
Gas Discharge Lamps
UNIT III
LIGHTING SYSTEM
Ignitors: These are used for starting high intensity Metal Halide and
Sodium vapour lamps.
Lighting Terminology
UNIT III
LIGHTING SYSTEM
UNIT III
LIGHTING SYSTEM
CHAPTER III
DG SET SYSTEMS
UNIT III
DG SET SYSTEMS
Introduction
UNIT III
DG SET SYSTEMS
UNIT III
DG SET SYSTEMS
Selection Considerations
UNIT III
DG SET SYSTEMS
UNIT III
DG SET SYSTEMS
Sizing of a Genset
High Speed Engine or Slow/Medium Speed Engine
Capacity Combinations
Air Cooling Vs. Water Cooling
Safety Features
Parallel Operation with Grid
Site Condition Effects on Performance Derating
Unbalanced Load Effects
Operational Factors
Genset
UNIT III
DG SET SYSTEMS
Load Characteristics
Some of the load characteristics influence the efficient use of a D.G.set. These
characteristics are entirely load dependent and cannot be controlled by the
D.G.set. Some of these characteristics are:
Unbalanced Load: Unbalanced loads on the A.C. generator lead to an
unbalanced set of voltages and additional heating in the A.C. generator.
Transient Loading: On many occasions, to contain the transient voltage
dip arising due to the transient load application, a specially designed
generator may have to be selected.
Special Loads: Special loads like the rectifier loads, welding loads, furnace
loads need an application check.
UNIT III
DG SET SYSTEMS
CHAPTER IV
ENERGY EFFICIENT TECHNOLOGIES IN
ELECTRICAL SYSTEMS
UNIT III
UNIT III
UNIT III
Soft Starter
UNIT III
The induction motor is the workhorse of the industry. It is cheap rugged and
provides high power to weight ratio.
On account of high cost-implications and limitations of the D.C. System,
induction motors are preferred for variable speed applications, the speed of
which can be varied by changing the supply frequency.
UNIT III
The iron loss of any transformer depends on the type of core used in the
transformer.
The expected reduction in energy loss over conventional (Si Fe core)
transformers is roughly around 70%, which is quite significant.
By using an amorphous core with unique physical and magnetic properties,
these new types of transformers have increased efficiencies even at low loads
- 98.5% efficiency at 35% load.
Electronic Ballast
UNIT III