Installations monitoring
and control
Safety
Reliability
Availability
Maintenability
Either a TTA or a PTTA equipment meeting IEC 60439 afford the same quality level
7
Safety
Reliability
Availability
Maintenability
8
Incoming
Functional unit
Outgoing
Auxiliary
10
11
Form 1
Form 2a
Form 3a
Form 4a
Form 2b
Form 3b
Form 4b
1. Maintenance people should not be in a dangerous situation, e.g. parts not under maintenance
should not create dangerous situation in parts under maintenance
2. Maintenance in one part should not create a dangerous situation in another part e.g. a screw or a
tool falls in another part
3. Danger in one part should not expand to other parts e.g. an arc in one part should not influence
other parts
12
F = Fixed
D = Disconnectable
W = Withdrawable
Identification
several configurations:
n1 temperature rise limits
n2 dielectric properties
n3 short-circuit withstand
n4 protective circuit effectiveness
n5 clearances and creepage distances
n6 mechanical operation
n7 degree of protection.
3 routine tests are performed by the panelbuilder on each
particular switchboard:
n8 general inspection
n9 insulation/dielectric test
n10 protection measures.
15
16
Test n1
(8-2-1): temperature rise limits
Test performed by the manufacturer
How to proceed:
to measure the temperature of each equipment, after a
delay allowing a stabilized temperature, when each circuit
is used at its rated power and when the complete
switchboard is loaded with an appropriate diversity factor
Result to be obtain
temperature rise shall not exceed what the different
equipment can withstand
the temperature of accessible surfaces has to be checked
17
Test n2
(8-2-2): dielectric properties
Test performed by the manufacturer
18
Test n3
(8-2-3): short-circuit withstand
Test performed by the manufacturer
Ipk (kA)
Icw 5
1.5
Ipk 7.5
5 < Icw 10
1.7
10 < Icw 20
20 < Ipk 40
20 < Icw 50
2.1
50 < Icw
2.2
19
Test n4
(8-2-4): effectiveness of the protective
circuit
Test performed by the manufacturer
20
Test n5
(8-2-5): clearance and creepage distances
Test performed by the manufacturer
21
Test n6
(8-2-6): mechanical operation
Test performed by the manufacturer
22
Test n7
(8-2-7): degree of protection (IP, IEC
60529)
Test performed by the manufacturer
IP
Note: in case of only protection of persons is needed, the 2 IP digits are replaced by x.
Example: IPxxB.
23
24
Test n8
(8-3-1): general inspection
Test performed by the panelbuilder
25
Test n9
(8-3-4): insulation resistance/(8-3-2):
dielectric test
Test performed by the panelbuilder
26
Test n10
(8-3-3): protective measures
Test performed by the panelbuilder
27
Specifiers/consultants:
the certainty to prescribe a switchboard which ensures
the level of safety required by the user
Panel-builder / Installer:
confidence in products and swichboards systems,
following the standard
increase efficiency, easy to show conformity
Manufacturer:
products tested in real configurations
detailed instructions for fautless construction.
29