Professional Documents
Culture Documents
For
Unit #3
DCS Area:
SHUTDOWNWORK
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
DCS,EWS&OWS
AllPanelsandCabinetsinUnit#3DCSRoom.
.Allworkstationscleaningcompleted.
4thextractionsteamtoauxsteamspray
watercontrolvalvetemperaturesetpoint
correctedinDrop10/60Task4Sheet810
GeneratorstatorcoolingwaterFCVlogic
loadedinDROP13/63Task4sheet887.
Reheatertemperaturecontrolthroughburner
tiltinglogicloadedindrop6/4/421
RGMOlogicloadedindrop6sheetno
100,110,200.
CoolingtowerPCCAutochangeovergraphics
loaded.
TSI1Forbid,TSI2forbidthese2DOs
configuredinDCSlogic&Graphics.
Unit3to4DGbuscouplerlogic&Graphics
implemented&trialtaken.
1noofDIchannelconfiguredforunit3DG
emergencystoppushbutton.
BackupofUnit3DCS&CommonsystemDCS
taken&storedinExternalHarddisk.
DCSsystemconfiguration(Network&Switch
level)Graphicsimplementationisunder
progressbyEMERSONvendor.
InMFTpanelonenumberoffusefoundblown
&samehasbeenreplaced.
Interlock & Protection checking of BTG area jointly with
Operations is under Progress.
SPARESUSED
REMARKS
NONE
Followingproblemswerenoticedinshutdown:
1.
2.
3.
4.
HistorianBackupDVD&Harddisktobesuppliedby
Sepco.
AllRemoteNoderedundancyisnotcoming.
ShiftinchargePCcouldnotbeshiftedduetoLancable
unavailable.
CommonSystemDCSpowersupplymoduleRedcolor
indicationinGraphicscouldnotberesolvedbyDCS
vendor.Needtochangehardware.