Professional Documents
Culture Documents
Earthing Concepts
Earthing Concepts
3
Earthing in a EHV Substation
I.E.Rules 1956
Rule 92
Every substation /generating station exposed to
lightning shall adopt efficient means for diverting
the electrical surges due to lightning to earth
Earth lead of any lightning arrestor shall not pass
through any iron or steel pipe.
It shall be taken directly, as far as possible, to a
separate earth electrode and/or junction of the
earth mat.
Bends Shall be avoided where ever practicable
Earth screen if provided for lightning protection
shall be connected to main earth grid.
4
Earthing in a EHV Substation
I.E.Rules 1956
Functioning of earthing in a substation
It shall be capable of passing maximum earth fault current
The passage of fault current does not result in any thermal
or mechanical damage to the insulation of connected plant /
equipment
Every exposed conductor part and extraneous conductive
part may be connected to the earth.
There is no danger to the personnel
Ensure equi-potential bonding within the power system
No dangerous potential gradients (step or touch or transfer
potentials) shall occur under normal or abnormal operating
conditions
To minimize electromagnetic interference between power
and control/ communication system
5
Earthing System
Points to be earthed in a substation
The neutral point of each separate system
should have an independent earth, in turn
interconnected with the station grounding mat.
Equipment frame work and other non-current
parts (two connections)
All extraneous metallic frame works not
associated with equipment ( two connections)
Lightning arrestors should have independent
earths, in turn connected to the station
grounding grid.
6
Earthing System
Points to be earthed-contd
Over head lightning screen shall also be
connected to main ground mat.
Operating handles of Isolators with a auxiliary
earth mat underneath, if necessary.
Peripheral fencing
Buildings inside the switch yard.
Transformer Neutrals shall be connected
directly to the earth electrode by two
independent MS strips
7
Earthing and grounding -distinction
8
Earthing and grounding -distinction
12
Substation earthing
Design of Earth mat
Design depends upon the following parameters
Durational and magnitude of the fault current
Resistivity of the surface layer of the soil
Resistivity of the soil
Magnitude of current that the human body can
safely carry
Permissible earth potential raise that may take
place due to the fault conditions
Shock duration
Material of Earth- mat conductor.
Earth- mat geometry
13
Substation earthing
Design of Earth mat
14
Earth mat parameters
Let go current
Maximum safe current a person can tolerate
and still release grip of an energised object,
using muscles affected by the current
The magnitude of let go current adopted in
calculating maximum permissible step and
touch potentials (As per IEEE 80 1976)
for man 9 milli amps
for woman 6milli amps
15
Substation Earthing
Non-fibrillation current
Developed by Dalziel and approved by AIEE80-1963
Magnitude of power frequency alternating current
(mA) that a human body of average weight( 50kgs to 70
kgs) can with stand without ventricular fibrillation,
I =0.116 for a body of 50kgs wt.
t
I =0.157 for a body of 70kgs wt.
t
Av. Value of human body resistance (dry) 8 to 9 K-
ohms
Adopted value for designing Earthing system 1Kohms
16
Substation Earthing
Non fibrillation current contd
Non fibrillating current adopted for earth grid design
in India.
Magnitude of power frequency alternating current
that a human body of average weight( 50kgs to 70
kgs) can with stand without ventricular fibrillation,
I =0.165
t
I = rms current through human body in amps
t =durtation of shock in seconds
Assumption /considerations in deriving the above
equation
--The duration of shock is from 8 milli-seconds to 3
seconds
17
Substation Earthing
Fault duration and magnitude
During a line to earth or double line earth fault
current through earthing system causes
a) Heating of earthing conductor
b) Potential gradients in the soil
For earthing design single line to ground fault
is considered as
Most of the faults are of this type
Current through earth in case of single line
to earth fault is higher that in the later case.
18
Substation Earthing
Fault duration and magnitude-contd.
For determining maximum permissible step and
touch potentials
Fault duration corresponding to maximum fault
clearing time of back up protection relays are
considered
Normally in modern sub station clearance time
of primary protection is 0.2 sec, ie., 200 milli sec
and clearance time for back up protection is 0.5
sec, ie., 500 milli sec
A fault duration time of 0.5 sec (500 mill sec) is
adopted for design 19
Substation Earthing
Fault duration and magnitude-contd.
Earthing conductor once placed under
earth may not be inspected normally.
Prudent to make it capable of carrying
maximum possible current for maximum
time.
If felt necessary and if it is economical,
fault duration of 1 sec can be adopted for
design.
20
Substation Earthing
Soil resistivity
To design most economically and technically
sound earthing system accurate data of soil
resistivity and its variation with in substation soil
is essential.
Resistivity of soil in many substations has been
found varying -at times between 1 and 10,000
ohm meters.
Variation in soil Resistivity with depth is more
predominant as compared to variation in
horizontal distances.
21
Substation Earthing
Soil resistivity
Large variations in stratification of earth layers will
result in large variations in earth resistivity.
25
Substation Earthing
Measurement of Soil resistivity
There point method
Two temporary electrodes spikes are driven in to the
earth at 150ft and 75ft respectively from earth
electrode under test.
Former is for current and the later is for voltage.
Ohmic values of earth electrode resistances are
obtained using earth meager
R = log 10 (4L/P) where
2
R = Electrode resistance in ohm
L = Length in cms of the rod driven under ground
D = Dia in cms of the rod
= Earth resistivity in ohm-meter
26
Resistance of the earthing system
R= +
4r L
= Soil resistivity in ohm meter
L = Length of conductor buried in meters
r = radius in meters of circle having the same
area as that occupied by the earth mat.
The value of the R should be less than the
impendence to ground values stated below
27
Earthing System
Permissible resistance of earthing system
29
Substation Earthing
Step and touch potential-contd
In any switch yard, chances of exposure to
Touch potential is higher than that to step
potential.
Resistance offered by the feet of a person
against Touch potential is much less
compared to that against Step potential.
Hence Touch potential is more critical for
design while Step potential is usually
academic.
30
Substation Earthing
Step and touch potential- contd.
Step potential is independent of the diameter
( cross- section) of the earthing conductor.
For 400% increase in diameter, reduction in Touch
potential is only 35%.
Thus cross- section has minor influence on Touch
and Step potentials.
Length of earthing conductor has significant effect
on Touch and Step potentials.
31
Substation Earthing
Step and touch potential
Tolerable Step and touch potentials (CBIP Publication no. 223)
E step (LMT) = 0.116 (1000+1.5Cs(hs.K.)s) (volts)
t
E touch (LMT) = 0.116 (1000+ 6Cs.(hs.K.)s) (volts)
t
Where Cs= Reduction factor for de-rating normal
value of surface layer resisvity, a function of
K.
K= -- s
+ s
, s are resistivities of soil and surface layer respectively.
33
Substation Earthing
Step and touch potential-contd.
Sample calculation for E step (LMT) and E touch (LMT)
Data
Weight of the man =70kgs
Fault duration =0.5 sec
Resistivity Soil = =100 ohm-mt, Surface layer =s=2000
ohm-mt,
h= Thickness of gravel in cm.=10cm
From (3), Cs=0.705
From table in slide 24 for a 70 kgs man and for a shock duration of
0.5 sec IB= 222mA
From (1) E step (LMT)= 691V
From (2) E touch (LMT) =2100V
34
Earthing System
Size of earth mat conductor
Methodology of design as adopted in APTransco
Size of earth mat conductor (steel strip ) Shall be :
A (Steel) = 0.0013 x I t sq. mm for bolted joints
= 0.011 x I t sq. mm for welded joints
Where A = Area of Cross section
I = Fault current in Amps. at the station
= Fault MVA x 1000
3 x system kV
and t = Time in seconds during which current is
applied
35
Earthing materials
Determination of size of conductor for earth mat.
- Based on thermal stability determined by an approximate
formula of IEEE - 80-1986
A = I/ ( TCAP x10 4) I n (Ko + Tm)
tc x ir r (Ko + Ta)
Where
In case of steel
A = I x 12.3 tc mm for welded joints
= I x 15.13 tc mm for bolted joints
In case tc = Duration of current =1sec
A = 12.3 x I mm for welded joints
= 15.3 x I mm for bolted joints
36
Earthing materials
Based on Mechanical ruggedness of conductor and for easy installation.
Ratio of max width to thickness =7.5
Thickness for flat shall not be less than = 3mm (As
adopted 5to 6mm)
Minimum dia for steel rod = 5mm
Standard sizes of conductor as, As per IS 1730 1989
(I)10 x 6mm (II)20x6mm
(II)30 x 6mm (IV)40 x 6mm
(IV)50 x 6mm (VI)60 x 6mm
(VI)50 x 8mm (VIII)65 x 8mm
(IX)75 x 12mm (X)100 x 16mm
- For 33kV Substations 75x8mm and 50x6mm
37
Earthing materials
Up to 220 kV substation
Earth mat
a) Peripheral or main earth mat : 100x 16m MS flat
b) Internal earth mat : 50x8m MS flat placed at 5 m apart
c) Branch connections : cross section not less than 64.5 sq.m
d) Raisers : 50x8m MS flat
Where necessary, 40mm rods will be driven in to earth vertically along the
periphery of the earth mat.
38
Pipe earthing
a) EHT Substations : (i) Cast iron pipes 125
mm in diameter
2.75 m long and not less than 9.5 mm
thick.
(ii) Pipes 50.8 mm in dia and
3.05 m long
40
Earthing system
Lowering of earth impedance
2) Lowering of earth impedance
In places where soil resistivity is high steps to be taken to reduce
earth impedance by one or combination of following:-
41
Earthing System
Earthing of switch yard fencing
Two methods of fence earthing
a) Extension of substation earth grid up to 0.5 to 1.5 m beyond the
fence, bonding the fence to the grid at regular intervals.
b) Keeping the fence beyond the perimeter of the switch yard
earthing grid, providing its own earthing system not
connecting to the main earthing grid.
In the former case substantial reduction in the effective
substation earthing resistance is possible but at additional
cost.
In the later case any inadvertent connection could give rise to
dangerous potential under fault condition unless special care
is taken.
Electrical isolation of fence into short section with individual
earthing is required where fence is closer to a single phase
reactor or an electrical plant generating large electromagnetic
fields.
42
Earthing System
Earthing of switch yard fencing- con
Methods of earthing of fencing As per CBIP report
A.
Design permits extension of earth mat within 1.5mt inside
perimeter fencing
Electrical isolation of fencing can be ensured
Isolate fencing for earth mat
Running of independent earth conductor underneath boundary
and connecting it to fencing at frequent intervals.
B.
Design permits extension of earth mat up to fencing
Calculated touch potential within safe limit
Extending the earth mat up to perimeter fencing and connecting
the fencing at frequent intervals to earth mat
Spreading crushed metal 1.5mt beyond fencing
43
Earthing System
Earthing of switch yard fencing- con
C.
Design permits extension of earth mat up to
fencing
Calculated touch potential beyond the fence
above the permissible limit for touch potential
Termination of earth mat within 1.5 mt of
fencing
Fence electrically isolated and independently
earthed by running an earthed conductor
underneath the fence connecting it to the fence
at frequent intervals
44
Earthing of gas insulated substation
In GIS multi-components like buses, switch gear
associated equipment are present in an earthed
metallic housing
They are subjected to same magnitude of fault
current and require low impendence earthing
Compared to a conventional substation, as GIS
requires only 25% of land area design of earth
mat is comparatively difficult.
Metallic enclosures of GIS have induced
currents, specially during internal earth faults.
45
Earthing of gas insulated substation
Inductive voltage drop occurring with GIS assembly shall be
taken into account for the design of earth mat
Touch voltage criteria = (FA)2+(EG)2 < ET (max)
Where FA = Actually calculated touch voltage
EG = Max value of metal to metal voltage difference
on and between GIS enclosures or
between GIS enclosures and supporting
structures
ET (max) = maximum permissible touch
voltage
Metallic enclosures of GIS may be continuous or not
In either case provision of earth bond frequently is essential to
minimize hazards of touch potential
In addition, earthing of GIS structures and service platforms at
frequent intervals are to be done.
46
Substation Earthing
Case studies
Karimnagar132kV ss
Kamalapuram 132kV ss fencing giving
shock
Auxiliary Earth grid at RTPP
47
Thank you
48