باور بوينت شرح الكود الانجليزىCPD Presentation- Pressurisation
باور بوينت شرح الكود الانجليزىCPD Presentation- Pressurisation
“I J O’Hea.
Colt Founder”
Current UK Business markets
Smoke Control
Solar Shading
Natural Ventilation
Louvre
Environmental Comfort Control
WHY PRESSURISE?
– Natural AOV’s
– Natural Shafts
– Mechanical ColtShaft
WHY PRESSURISE?
• Alternative to natural ventilation when escape stairs or
fire fighting stairs are landlocked
• fire fighting shafts over 10m deep and over 30m tall (Class B)
INSTALLATIONS
– Is there a lift?
Pressurise the stairs only. Only used where the staircase is entered via a
simple lobby (i.e. a lobby without lifts or other possible escape route) or
directly from the accommodation.
Stairs
+ve Simple
lobby
Air supply
Accommodation
STAIRS, LOBBY & LIFT
Lift
+ve Accommodation
Air supply
+ve
Stairs
STAIRS, LOBBY & LIFT
+ve
Lift
+ve
Lobby Accommodation
Air supply
+ve
Stairs
WHAT PERFORMANCE IS REQUIRED?
Door opening
force not to
exceed 100N
Stairs
First floor
Ground floor
CLASS A - DOOR OPEN
Ductwork
system Smoke detector
Stairs
First floor
Ground floor
CLASS A: MoE - Defend in Place
Accommodation
First floor
Ground floor
CLASS B - DOORS OPEN
Lift door
open if
fitted
Stairs
First floor
Ground floor
Closed Door Requirements Open Door Requirement
Class Stair Lift Shaft Lobby Velocity Open Doors
(Pa) (Pa) (Pa) (m/s)
A 50 50* 45* 0.75 Stair door on fire floor
C 50 50* 45* 0.75 Stair door on fire floor + 10Pa pressure difference
with final exit door open only
D 50 50* 45* 0.75 Stair door on fire floor and final exit door + 10 Pa
pressure difference with final exit door open and
one stair door other than the fire floor
E 50 50* 45* 0.75 Stair door on fire floor and another floor and final
exit door + 10 Pa pressure difference with final exit
door and two stair doors open other than the fire
floor
Ductwork
system Smoke detector
Stairs
First floor
Ground floor
CLASS C – EXIT DOOR OPEN
Stairs
First floor
Ground floor
CLASS C - DOOR OPEN
FIRE FLOOR
Accommodation air release
0.75 m/s average velocity
ventilator
Ductwork
system Smoke detector
Stairs
First floor
Ground floor
EQUIPMENT
• Fans
– ambient rated
– duty + standby (or standby motor) if only one MOE
route; usually in series to save space
– One fan set may supply stairs, lobbies and lift shaft
– not usually attenuated unless needed for test periods
– In 1 hour fire rated enclosure or roof
• Power supplies
– primary + secondary
– Mains + generator or separate mains supply
• Pressure relief
– usually gravity damper in stair
– inverter control of fans possible but difficult due to
response speed requirement
EQUIPMENT
• Ductwork
– separate vertical ducts for stair, lobbies, lift shaft
– ambient rated unless breaching fire compartmentation
– Builders work shafts are suitable if well sealed
– VCD required at each tee and grille for balancing
– Two separate inlets facing different directions with
smoke detector operated inlet dampers if at roof level
– 5m away from any smoke exhaust
• Grilles
– one per 3 storeys in stair
– one per lobby
– one per 30m in lift shaft
EQUIPMENT
• Class B initiation
– Can be manual switch from MOE state or direct from
automatic fire detection system
• P = 0.5 ( Q2/A2 )
• Q = 0.83 (A P0.5 )
– add 50% safety margin + 15% margin for duct leakage + 20%
duct pressure loss margin
• While the test method aims to neutralise the effects of wind, testing
on windy (and especially blustery) days should be avoided if
possible
• On day of test, ensure all other H&V systems are shut down
MEASUREMENT TECHNIQUES
• PRESSURE DIFFERENTIAL
51
PERFORMANCE TESTING
Pressures
• On each floor in turn open all doors, allow them to close and then
measure the pressure differential across each relevant door
Velocities
• Proposals are:
– Delete ‘kit’ references and CE marking
– Simplify system requirements
– Reduce costs
– Not likely to be published until 2011
The End
Any Questions?