Practice Improvement Cooperation Innovation

PCS-996 DFR

NR Electric Co., Ltd.


Application 2

Remote DFR Management Station

UPLINK

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

IEC 61850 or IEC60870-5-103+FTP

Station 1 Station n
Local DFR HMI Local DFR HMI

UPLINK UPLINK

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

www.nrelect.com 2
Hardware 3

• Front view

HEALTHY PCS-996
ALARM DISTURBANCE&FAULT RECORDER
REC

C GRP
ENT

ES

www.nrelect.com 3
Hardware 4

• Rear View

NR1102J NR1156A NR1401 NR1401 NR1401 NR1504 NR1504 NR1504 NR1504 NR1504 NR1102J NR1301
1 2 3 5V OK ALM
TX TX
RX RX BO_ALM BO_FAIL
4 5 6
TX TX
RX RX

1 BO_COM1
DANGER DANGER DANGER 2 BO_FAIL

3 BO_ALM

4 BO_COM2

5 BO_FAIL

6 BO_ALM

7 OPTO+

8 OPTO-

10 PWR+

11 PWR-

12 GND

www.nrelect.com 4
Hardware 5

• 36 AI, 90 BI

• 36 AI, 84 BI, 4 BO

• 48 AI, 54 BI

• 48 AI, 48 BI, 4 BO

• 24AI, 126 BI

• 24AI, 120 BI, 4 BO

www.nrelect.com 5
Hardware 6

• AI module
1401 1401 1401
I1 01 I1n 02 U1 01 U1n 02 I1 01 I1n 02

I2 03 I2n 04 U2 03 U2n 04 I2 03 I2n 04

I3 05 I3n 06 U3 05 U3n 06 I3 05 I3n 06

I4 07 I4n 08 U4 07 U4n 08 I4 07 I4n 08

I5 09 I5n 10 U5 09 U5n 10 I5 09 I5n 10

I6 11 I6n 12 U6 11 U6n 12 I6 11 I6n 12

U1 13 U1n 14 U7 13 U7n 14 I7 13 I7n 14

U2 15 U2n 16 U8 15 U8n 16 I8 15 I8n 16

U3 17 U3n 18 U9 17 U9n 18 I9 17 I9n 18

U4 19 U4n 20 U10 19 U10n 20 I10 19 I10n 20

U5 21 U5n 22 U11 21 U11n 22 I11 21 I11n 22

U6 23 U6n 24 U12 23 U12n 24 I12 23 I12n 24

www.nrelect.com 6
Hardware 7

• BI module
-KM +KM
1504
01 Opto +

02 Binary input 01

03 Binary input 02

04 Binary input 03

05 Binary input 04

06 Binary input 05

07 Binary input 06

08 COM1 -

09 Binary input 07

10 Binary input 08

11 Binary input 09

12 Binary input 10

13 Binary input 11

14 Binary input 12

15 COM2 -

16 Binary input 13

17 Binary input 14

18 Binary input 15

19 Binary input 16

20 Binary input 17

21 Binary input 18

22 COM3 - www.nrelect.com 7
Hardware 8

• BO module
-KM +KM 1525
01 Binary
output 01
02
03 Binary
output 02
04
05 Binary
output 03
06
07 Binary
output 04
08
09 Binary input 01

10 Binary input 02

11 Binary input 03

12 Binary input 04

13 Binary input 05

14 Binary input 06

15 Binary input 07

16 Binary input 08

17 Binary input 09

18 Binary input 10

19 Binary input 11

20 Binary input 12

21 OPTO+

22 OPTO-
www.nrelect.com 8
Hardware 9

• CPU module

NR1102J

TX
RX

TX
RX

www.nrelect.com 9
Operation Theory 10

• 4 Triggering conditions
 Triggered by voltage

1 Up over upper limit

2 Up under lower limit

3 Sudden increase of Up over limit

4 Sudden decrease of Up lower limit

5 U2 over upper limit

6 Uo over upper limit


Absolute value of sudden change of Uo
7
over limit
8 Frequency over upper limit

9 Frequency under lower limit

10 Absolute value of df/dt over limit

www.nrelect.com 10
Operation Theory 11

 Triggered by current

1 Ip over upper limit


Absolute value of sudden change of Ip over
2
limit
3 I2 over upper limit

4 I0 over upper limit


Absolute value of sudden change of I0 over
5
limit
6 Power swing

www.nrelect.com 11
Operation Theory 12

 Triggered by binary input

Triggered by rising/falling edge


1
(i.e.: 0->1 or 1->0)
Triggered by rising edge
2
(i.e.: 0->1)
Triggered by falling edge
3
(i.e.: 1->0)
4 Triggered by low potential

5 Triggered by high potential

 Manual trigger

www.nrelect.com 12
Operation Theory 13

• Trigger record typical behavior


- Period A :pre-fault, 9600Hz, >40ms

- Period B :fault, 9600Hz, >100ms

- Period C :post-fault, 9600Hz, 1s

t = 0ms: The start time of disturbance

A B C

S T

www.nrelect.com 13
Operation Theory 14

• Continuous record behavior


Record the data continuously without any trigger at rate of 1200Hz
at least 7 days.

www.nrelect.com 14
Operation Theory 15

• Storage of records
Triggered records and continuous records store in the local CF card. If
space expires, the eldest data will be covered by latest data.

Capacity: 16/128G. More than 30,00 records for trigger , 7 days for
continuous, 6 months for slow records, which can meet the
requirement of DFR for the whole lifecycle

www.nrelect.com 15
Operation Theory 16

• Analyze Functions
The recorder can analyze the fault line, fault type, fault phase, fault
location, etc, in real time

Waveform analyze tool provide more analyze functions

www.nrelect.com 16
PCS-996 17

www.nrelect.com 17
PCS-996 18

• Sequence component analysis

www.nrelect.com 18
PCS-996 19

• Harmonic analysis

www.nrelect.com 19
PCS-996 20

• Impedance locus analysis

www.nrelect.com 20
Content 21

• Application
• Hardware
• Operation theory
• Communication

www.nrelect.com 21
Communication 22

• Ethernet communication

SCADA

Switch

Switch

IED IED IED

www.nrelect.com 22
Thanks for Your Attention!
www.nrelect.com