BS 7671:2018
“The 18th edition IET Wiring
Regulations”
Update
tony@cibse-electricalservicesgroup.co.uk
installations or locations
Part 3 – Assessment of
erection of equipment
Part 5 – Selection and
Part 7- Special
testing
safety
Part 2 – Definitions
Presenter: Dr Tony Sung CEng FCIBSE, FIET
Joint Seminar of CIBSE Yorkshire Region & CIBSE Electrical Services Group (8th Mar 2019)
Sequence of the plan of BS 7671:2018 - Layout
Part 1 – Scope, object and fundamental requirements
installations or locations
Part 3 – Assessment of
erection of equipment
Part 5 – Selection and
NORMATIVE
Part 7- Special
(i.e, prescriptive)
testing
safety
Part 2 – Definitions
Presenter: Dr Tony Sung CEng FCIBSE, FIET
Joint Seminar of CIBSE Yorkshire Region & CIBSE Electrical Services Group (8th Mar 2019)
BS 7671:2018
Part 1
Reg 133.1.3 When an item of equipment is not BS/IEC
compliance or being used outside the scope of its
standard - the Designer (and Installer) shall confirm
that it will meet the safety requirements of BS 7671.
Reg 411.3.1.2
Metallic pipes entering the building, with
insulating section at entry point, protective
equipotential bonding not required
For all other cases, Reg 443.5 a risk assessment (CRL) has to be
performed in order to determine if protection against
transient overvoltage is required.
521.10.202
Requirements for the methods of support of wiring
systems - applies throughout the installation and not
just in escape routes. Wiring systems shall be
supported such that they will not be liable to
premature collapse in the event of a fire.
EVERYWHERE – not just escape routes!
542.2.8
Earth electrode parts connections to be robust
Table 710
Deleted
710.415.2.1
No. of supplementary equipotential bonding connection points now a
Note.
Group 1 – one per patient location
Group 2 – 25% of total number IT supplied socket-outlets
710.421.1.201
final circuits supplied by medical IT system in medical locations of
group 2, AFDD shall not be used.
PME supply
The exception concerning reasonably practicable has
been deleted.
BS 1363-2 socket-outlets to be marked EV
The recommendations
within the scope of this
appendix apply for new
electrical installations and
modification of existing
electrical installations.
Much of this appendix will
not apply to domestic and
similar installations.