Professional Documents
Culture Documents
Footing
Footing
Introduction
Footing are structural elements that transmit to the soil
column loads, wall loads or lateral loads. If these loads are to
be properly transmitted, footing must be designed to prevent
excessive settlement or rotation and to minimize differential
settlement.
To limit settlement within tolerably small amount, it is
necessary.
i. To transmit the load of the structure to a soil stratum of
sufficient strength and
ii. To spread the load over a sufficiently large area of that
stratum to minimize bearing pressure.
Introduction
If adequate soil is not found immediately below the
structure, if becomes necessary to use deep foundations such
as piles to transmit the load to deeper, firmer layers.
P MC
qmax
min A I
Load, bearing Pressures & Footing Size
D and L=loads (service) at the level of base of base of footing
If eccentricity falls outside the kern distance
qmax qa
1
P 3m qmax b
2
2P
qmax
3mb
Design of “Plain Concrete” Wall Footing
Problem
Design a wall footing of plain concrete to carry 20 k/ft dead
load including the wall weight and 8 k/ft live load. Use
fc’=3000, an allowable soil pressure of 6 k/ft. The bottom of the
footing is 4 ft below the final grade.
Solution
W =20 + 8 = 28 k/ft
Assume 24” thick footing
24
Footing weight (145) 290 lb / ft
2
12
24
Soil Fill on footing (100) 200 lb / ft
2
12
qe = Effective soil pressure = 6000 – 490 = 5510 lb/ft2
28
Width of footing required 5.08 ft say 5' - 3"
5.510
Solution
Wu = (20) (1.2) + (8) (1.6) = 36.8 k/ft
36.8
Net soil pressure under factored loads 7.009 ksf
2.125
5.25 1
Mu (7.009)2.125
2
15.825 k / ft
(12)(22)3
Moment of Inertia 10648 in4
12
2” bottom concrete is neglected
ft 5 fc = modulus of rupture and ø = 0.65
ftI (0.65)(5 3000 )(10648)
Mn h 22
(12000)
2 2
= 14.36 k.ft/ft < Mu
ftI
Putting Mu h
2
Solution bh3
(0.65)(5 3000 )
(15.825)(12000) 12
h
2
h = 23.095”
with poor concrete h = 25.095”
Say total depth of footing = 26”
Now revise with new thickness
26
(145) 314.17 lb / ft 2
Footing weight 12
22
Soil back filling (100) 183.33 lb / ft 2
12
qe 6000 (314.17 183.33) 5502.5 lb / ft 2
28
Width of footing required 5.088 lb / ft
5.5025
Say 5’ – 3”
(12)( 24)3
I 13824 in4
12
ftI (0.65)(5 3000 )(13824)
Mn
h 24
(12000)
2 2
17.09 k.ft / ft So ok
Shear Check
Vc 2 fc b w d
2 3000 12 22.5
29577 lb
Mu 5.35
4 .5
2
54.17 k ft
2
Mn Mu
Re quired Rn
bd 2
bd 2
54.17 12000
221.1 psi
0.9 1216.5 2
fy 40,000
m 11.77
0.85fc 0.85 4000
1 2mR n
1 1
m fy
1 2 11.77 221.1
1 1 0.00572
11.77 40,000
200 200
min 0.005 or min 0.002 Therefore
fy 40,000
Solution
A s bd 0.005721216.5 1.133 in2
Use #9 @ 9 c / c A s 1.33 in2
Development Length
Length required for # 9 bars = 25” (Table A.11)
Length available = (4.5) (12) – 3 = 51” So O.K
bo=Perimeter
=4(a+d)
ii. Punching Shear
The ACI code give equation Vc 4 fcbo d (i) for nominal
punching shear on this perimeter.
For columns of very elongated x-section
4
Vc 2 fcbo d (ii)
c
Long side
Where c of column
Short side
bo
Test show that Vc decreases as the ratio increases.
d
According ACI code states that Vc in punching shear must
not be taken greater than
sd
Vc 2 fcbo d (iii)
bo
ii. Punching Shear
Where
αs = 40 for interior columns
αs = 30 for edge loading
αs = 20 for corner loading of a footing
Punching shear strength should be taken smallest of all three
equations.
a
c
b
Bearing-Load transfer for column to footing
At the base of the column,
the permitted design
bearing strength is
A2
Pn (0.85fc )A 1 (0.85fc )A 1 2
A1
A1 is column cross-sectional
area
A2 is the area of the portion of the
supporting footing as defined in
Fig.
At least four dowels having area not
less that 0.005 times the x-
sectional area of the column and
the diameter of dowel should not
exceed the diameter of the
column bar by more than 0.15”.
Development Length
Dowel should have sufficient development length
0.02fy db
For compression bars, that is, ld 0.0003fy db
fc
The lapped length must be at least that required for a lap
splice in compression. i.e. the length of lap must not be less
than the usual development length in compression and must
not be less than 0.0005 fydb
Where bars of different sizes are lap spliced, the splice length
should be the larger of the development length of larger bar or
the splice length of the smaller bar.
Splice length for compression
For bar with fy 60,000 psi 0.0005 f d
y b
C=T
360
a 1.2384"
290.7
a
Mn 0.9 A s fy d
2
1.2384 1
0.9 9 40 20
2 12
523.29 k.ft
Mn Mu 480.66 k.ft
So use 15 # 7 bars each way
Solution
Bearing strength
øPn = ø(0.85fc’) Ag
= (0.7)(0.85 x 3000)(16)2
= 456960 lb = 456.96 k
Pu = 547.8 k
øPn < Pu thus column load can not be transferred by
concrete bearing alone and dowels bars are required.
Excess Pu = 547.8 – 456.96 = 90.84 k
Excess Pu 90.84
Required As 3.25 in2
fy (0.7)( 40)
Excess Pu 90.84
More correctly Required As
( fy 0.85fc ) (0.7)(40 0.85 3)
3.47 in2
Solution
Bearing strength
Use 4 # 9 bars As = 4 in2 Min As=(0.005)(16)2=1.28 in2
=(0.0003)(40000)(1.128)=13.56”
and can not be less than 8”
24” thick footing is adequate for straight dowels.
Solution
If bends are provided in dowels then the available length is
24-3.0(cover)-2x0.875(footing bars)-1.128(dowels)=
18.122” > 16.47”
Solution
Assume 24” thick footing d = 19.5”
24 36
qe 4000 150 100
2 12
3400 lb / ft 2
Vu = (1.125)(14)(5.25)
= 82.69 k
Vu 82.69 1000
d
2 fc b 0.85 2 4000 168
4.58 so O.K.
Solution
Two-Way Shear
bo = (4)(18 + 19.5) = 150”
37.5
2
1 2mR n 1 2 11.765 58
1 1 1 1
m fy 11.765 40,000
0.00146
A s 0.00146bd 0.00146 14 12 19.5
4.79 in2
200 200
min 0.005
fy 40,000
Solution
Longitudinal Steel in Short Direction
2
Use 26 17.3 18 bars in band width
3
Re st 26 18 8 bars
Solution
Dev. Length
For # 8 bar ld = 20”
Available (2.75)(12)-3=30” O.K
Bearing Strength
Pn (0.85fc )A g
1
0.7 0.85 4000 18
2
1000
771.12 k
1 2mR n
1 1
m fy
1 2 23.53 98.544
1 1
23.53 60,000
0.001675
200 200
min 0.0033
fy 60,000
Solution
Longitudinal Steel
So min holds
As = bd = 0.0033 x 9 x 12 x 37.5 = 13.365 in2
Use 17 # 8 bars
0.04 A b fy 1.3 0.04 0.79 60,000
l d 1 .3
fc 3000
45
Available length = 6.39 x 12 – 3 = 73.68 in So O.K
For bottom bars ld = 34.62 in
Available 2.84 ft 34.08 – 3 31.08”
For hooked bars
1200db 1200 1
Re quired d 21.9
fc 3000
Solution
Transverse Beams
d
The ACI code recommends band width from the face
of the column 2
Interior Column
d
Width of beam 24 2 24 37.5 61.5
2
690 x 1000
Upward load /ft 76666.67 lb / ft
9
3 .5
Mu 76666.67 3.5
2
5635000 lb.in
Solution
fy
Use 13 # 7 bars with As = 7.8 in2
Exterior Column
37.5
Width of beam= 18 36.75"
2
Minimum steel criteria holds
200
A
s 35.75 36.5 4.47 in 2
fy
Use 8 # 7 (As = 4.8 in2)
Solution
Development Length
for # 7 bars in tension ld = 26” (Table)
Available 61.5” So O.K
Bearing Strength
Interior Columns
øPn = ø(0.85fc’) A1 = (0.7)(0.85fc’)(24 x 24)
= 1028160lb 1028.16 k
Pu = 690 k < øPn So nominal dowels
As = 0.005 x 24” x 24” = 2.88 in2
Use 4 # 8 dowels (As = 3.14 in2) dev.length 22” So O.K
Solution
Bearing Strength
Edge column