If the building cooling plant or HVAC system is to be replaced, implementation
of lighting improvements done in conjunction with the replacement can reduce
the required plant size.
LIGHTING TERMINOLOGY
Efficacy—Is the amount of visible light (lumens) produced for the amount of power
(watts) expended. It is a measure of the efficiency of a process but is a term used in
place of efficiency when the input (W) has different units than the output (lm) and
expressed in lm/W.
Color Rendering—A parameter that describes how a light source renders a set of
colored surfaces with respect to a black body light source at the same color
temperature. The color rendering index (CRI) runs from 0 to 100. It depends upon
the specific wavelengths of which
the light is composed. A black body has a continuous spectrum and contains all of
the colors in the visible spectrum. Fluorescent lamps and high intensity discharge
lamps (HID) have a spectrum rich in certain colors and devoid in others. For
example, a light source that is rich in blues and low in reds could appear white, but
when reflected from a substance, it would make red materials appear faded. The
LEDs (Light Emitting Diodes)
Un diodo emisor de luz (LED) es un dispositivo semiconductor que convierte la
electricidad en luz. La iluminación LED existe desde la década de 1960. Al
principio, los LED blancos solo eran posibles mediante grupos "arco iris" de
tres LED (rojo, verde y azul) controlando la corriente de cada uno para producir
una luz blanca general. Esto cambió en 1993 cuando Nichia creó un chip azul
de indio y galio con un recubrimiento de fósforo que se usa para crear el
cambio de onda necesario para emitir luz blanca desde un solo diodo. Este
proceso es mucho menos costoso por la cantidad de luz generada.
El DOE estima que los LED podrían reducir el consumo de energía de
iluminación nacional en un 29% para 2025 para un ahorro de $ 125 mil
millones.
Las aplicaciones de LED
incluyen:
• Señales de salida LED applications include:
• iluminación de plantas • Exit signs
• Señales de tráfico • Growlights
• iluminación decorativa • Traffic signals
• luces posteriores del auto • Holiday lighting
• Instrumentación • Car taillights
• Señales • Instrumentation
• iluminación general • Signs
• linternas • Some general lighting
• Flashlights
In the last few years, white LEDs have become commercially available in sizes that make them useful for typical incandescent lamp and CFL replacements. Today these white LEDs can easily replace 60 and 75 watt incandescent lamps. Also, several companies are
making fluorescent tubes with LEDs in them so that a standard fluorescent tube can be replaced easily with an LED tube of the same size and length. The LED lamps have a potentially long lifetime of about 50,000 hours if they have heat dissipating designs which
include some form of heat sinks. Heavy metal ceramic shells, strips of metal, metal plates, liquid cooling, heat pipes, or other devices accomplish this function. Without something of
this nature, the LED is going to overheat and fail at an early age. Several LED lighting suppliers are now providing unconditional five-year guarantees for their LED lamps. This is a 43,800-hour guarantee, which is short of 50,000 hours, but not too bad. With this
guarantee, you can perform your life cycle cost analysis with this lifetime assured. Just make sure you buy your lamps from a reputable dealer who you think will be around for the next five years.
En los últimos años, los LED blancos se han comercializado en tamaños que los hacen útiles
para reemplazos de lámparas incandescentes y CFL típicos. Hoy en día, estos LED blancos
pueden reemplazar fácilmente las lámparas incandescentes de 60 y 75 vatios. Además, varias
compañías están fabricando tubos fluorescentes con LED para que un tubo fluorescente
estándar pueda reemplazarse fácilmente con un tubo LED del mismo tamaño y longitud. Las
lámparas LED tienen una vida útil potencialmente larga de aproximadamente 50,000 horas si
tienen diseños de disipación de calor que incluyen alguna forma de disipadores de calor. Las
carcasas de cerámica de metal pesado, tiras de metal, placas de metal, refrigeración líquida,
tubos de calor u otros dispositivos cumplen esta función. De otra forma, el LED se
sobrecalentará y fallará a una edad temprana. Varios proveedores de iluminación LED ahora
ofrecen garantías incondicionales de cinco años para sus lámparas LED. Esta es una garantía
de 43.800 horas, que es inferior a 50.000 horas, pero no está mal. Con esta garantía, puede
realizar su análisis de costos del ciclo de vida con esta vida asegurada. Solo asegúrese de
comprar sus lámparas a un distribuidor acreditado que cree que estará disponible durante los
próximos cinco años.
Lumen maintenance of LEDs should be at least 70% of initial lumens at end of life. Some are even better than 80% at end of life. Many
different color temperatures are now available, from warm white to cool white and above. Efficacies now range from 40 to over 100 lumens
per watt. One manufacturer’s LED lamp, now commercially available, produces 100-110 lumens per watt at their full power of 10 watts, and
up to 160 lumens/watt at around 2 watts input power. Several manufacturers currently have LEDs with efficacies of over 200 L/W in the
early stages of commercial development. This will only increase over time.
Larger LED lights are also commercially available today. Several companies make LED replacements for 250 W and 400 W metal halide
lamps. These are large lamp replacements since they need large heat sinks to keep the LED lamp cool. One of the 400 W metal halide
replacements uses about 180 W for the LED. There are fewer lumens produced, but they are typically higher CRI.
El mantenimiento de la luz de los LED debe ser al menos el 70% de las luces iniciales al final de la vida útil.
Algunos son incluso mejores que el 80% al final de la vida.
Ahora se encuentran disponibles muchas temperaturas de color diferentes, desde el blanco cálido hasta el
blanco frío y superior.
La eficacia ahora oscila entre 40 y más de 100 lúmenes por vatio. La lámpara LED de un fabricante, ahora
disponible comercialmente, produce 100-110 lúmenes por vatio a su potencia máxima de 10 vatios, y hasta 160
lúmenes / vatio a una potencia de entrada de alrededor de 2 vatios. Varios fabricantes tienen actualmente LED
con una eficacia de más de 200 L / W en las primeras etapas de desarrollo comercial, esto aumentará con el
tiempo.
Las luces LED más grandes también están disponibles comercialmente en la actualidad. Varias compañías hacen
reemplazos de LED para lámparas de halogenuros metálicos de 250 W y 400 W. Estos son reemplazos de
lámparas grandes ya que necesitan grandes disipadores de calor para mantener fresca la lámpara LED. Uno de
los reemplazos de haluro metálico de 400 W usa aproximadamente 180 W para el LED. Se producen menos
lúmenes, pero generalmente tienen un IRC más alto.
(El índice de reproducción cromática (IRC) es la medida utilizada en relación a una fuente de luz para medir su
capacidad de mostrar los colores de un objeto de manera "real". Esto tomando como referencia
la iluminación natural.)
MOTORS AUDIT
Motors account for a significant portion of energy usage and
demand in commercial and industrial applications. It is suggested
that information be collected on motors 5 HP and larger. Nameplate
information should be gathered as well as the condition, operating
hours and operating environment of the motor. Motor loading can
be measured or assumed, depending on each situation. In some
cases, data loggers can be used to collect data over a specified
time period.
Motor Basics
The primary motor used in commercial and industrial
applications is the AC three-phase induction motor. Three
phase induction motors comprise 85 to 90 % of motors in
use due to the following characteristics:
• Simple in design
• Efficient
• Rugged
• Low cost
• Reliable
• Adaptable to VFDs
Motor Speed
The speed of a three-phase induction motor depends on the number of poles in the motor,
and the frequency of the alternating current.
The speed of the rotating magnetic field is called the synchronous speed and the equation is
as follows:
The majority of motors today are two, four or six poles, or 3,600 RPM, 1,800 RPM or 1,200
RPM motors respectively. By using belts, pulleys, gears, VFDs, etc., any load speed can be
obtained
Note that the motor shaft rotates a little slower than the rotating
magnetic field due to slip. The full load RPM on the nameplate reflects the actual
shaft speed, and is a little lower than the synchronous speed. For example, the motor
nameplate full load speed may say 3,550 RPM, which means it is a 3,600 RPM two pole
motor.
Electric Motor Efficiency
Efficiency is a measure of the ability of a motor to convert electrical into mechanical energy.
In order to do an economic analysis of a motor replacement, the efficiency of the existing
motor must be determined. The efficiency ratings on motors:
• Represents full load efficiency. The efficiency drops off as the motor is more lightly loaded.
• Manufacturers only guarantee that the motor meets nominal efficiency rating which is
defined as: “the average efficiency of a large population of motors of the same design.”
• Motors built after 1982 will have the nominal efficiency expressed as a numerical value on
the nameplate.
Motor Loading Determination
Motors rarely are operated at 100% of their full load rating. This means that motors are
loaded or have a load factor of less than 100%. Load factor is defined as:
Motor loading can be estimated in three ways:
Si no se realizan mediciones, se sugiere que calcule la carga del
motor entre 60% y 70%. Esta es una carga de motor típica en una
aplicación de ventilador o bomba. Tenga en cuenta que algunos
compresores de aire pueden tener un mayor factor de carga.
Motor Economics
¿Por qué el propietario de un negocio reemplazaría un motor de eficiencia estándar que funciona con uno
eficiente en energía? Sobre la base del primer costo, los motores energéticamente eficientes pueden ser
hasta un 25% más que el costo de un motor estándar, pero los ahorros en el costo operativo pueden superar
estos costos de capital adicionales.
Cálculos de demanda y uso de energía
Para determinar los requisitos de potencia de un motor, se pueden usar las siguientes ecuaciones:
AUDITORIA DEL SISTEMA DE DISTRIBUCIÓN DE ELECTRICIDAD
El funcionamiento ineficiente de los sistemas de distribución eléctrica proviene principalmente de un bajo factor de
potencia. La corrección del factor de potencia es rentable cuando se imponen penalidades a los servicios públicos.
Se pueden mejorar los factores de baja potencia, con dispositivos de corrección del factor de potencia y motores de alta
eficiencia. Adicional Se puede ahorrar energía mediante la instalación de transformadores energéticamente eficientes y
reemplazar motores existentes por motores pequeños y / o de mayor eficiencia, o mediante la instalación de motores de
velocidad variable.
La demanda de potencia total de una carga se compone de dos componentes, a saber, la parte resistiva y la parte reactiva.
La parte resistiva de una carga no se puede agregar directamente al componente reactivo ya que está esencialmente
noventa grados fuera de fase con el otro. La potencia resistiva pura se conoce como POTENCIA ACTIVA cuya unidad es el
vatio, mientras que la potencia reactiva tiene como unidad a los voltios amperios reactivos. Para calcular el voltio amperio
total de la carga (POTENCIA APARENTE) es necesario analizar el triángulo de potencia indicado a continuación:
La potencia nominal estándar de un motor se conoce como potencia
APARENTE.
Para relacionar la potencia aparente del motor con un kilovatio (kW),
multiplique la potencia por .746 (Factor de conversión) y divida por
Eficiencia del motor.
La eficiencia del motor y los factores de potencia varían con la carga. Valores típicos se muestran en
la Tabla 7-4. Los valores se basan en un ventilador totalmente cerrado refrigerado motores (TEFC)
funcionando a 1800 RPM
MEJORAS EN LA EFICIENCIA DEL FACTOR DE POTENCIA
La ESEA debe recopilar los siguientes datos:
• Factor de potencia de la planta
• Fecha, tipo, potencia, velocidad, carga completa y carga parcial de la placa del motor,
amperaje.
• Los datos de la placa de identificación deben compararse con el amperaje real del
motor en funcionamiento.
Como se indica en la Tabla 7-4, los motores pequeños y parcialmente cargados contribuyen a factores de
baja potencia y eficiencia eléctrica para edificios y plantas.
La ESEA debe determinar qué motores son de gran tamaño y pueden ser reemplazado por un tamaño de
marco más pequeño.
Un segundo método para mejorar el factor de potencia de la planta o del edificio es utilizar motores
energéticamente eficientes. Motores energéticamente eficientes disponibles.
de fabricantes como Magnetic. Los motores energéticamente eficientes son aproximadamente 30 por
ciento más caro que su contraparte estándar.
Según el costo de energía, se puede determinar si la inversión adicional es justificado.
Con énfasis en la conservación de energía se están introduciendo motores eficientes.
Las Figuras 7-12 y 7-13 ilustran una comparación típica entre
motores de eficiencia energética y motores estándar.
Un tercer método para mejorar el factor de potencia es
agregar bancos de condensadores para reducir el kVAR
reactivo total. La corriente de la línea también se reducirá,
por lo que también se reducirá la pérdida I2R correspondiente
a través de los conductores.
La tabla 7-5 se puede usar para estimar la capacitancia
conectiva requerida. No instale bancos de condensadores sin
primero medir la calidad de la energía para asegurarse de
que no haya problemas de armónicos.