Alarm’s are used to monitor the site in case of any fault occur then
alarm panel automatically generate the alarm for corresponding fault
occurred at site.
AMIT MISHRA 2
Why alarm’s are used at site?
External alarm is important at BTS site because in case of any fault occur
then as a maintenance engineer it will be easier for us to identify the
problem and rectify it accordingly.
We can check at DDF, where termination of alarm is done.
It provide security and stability to whole BTS site.
AMIT MISHRA 3
TYPES OF ALARM AT BTS SITE
BTS
SITE
ALARM
INTERNAL EXTERNAL
ALARM ALARM
AMIT MISHRA 4
PARAMETER OF EXTERNAL ALARM
ALARM NAME
ALARM
OR SYNTAX ALARM NO
TYPE(NO/NC)
OR TITLE
ALARM PORT
ALARM SEVERITY NO/PIN NO
ROUTE ROOT
COLOUR CODE OF CAUSE OF
CAUSE OF
ALARM ALARM
ALARM
AMIT MISHRA 5
ALARM NAME OR SYNTAX OR TITLE
AMIT MISHRA 6
PARAMETER DESCRIPTION CONTINUED
ALARM NO
Every operator decide a particular alarm no for it’s BTS site and accordingly
series of alarm is decided.
ALARM TYPE
ALARM TYPE
AMIT MISHRA 7
PARAMETER DESCRIPTION
CRITICAL
SEVERITY
CRITICAL
MAJOR
MAJOR
Major mean’s that ,it’s severity level is lesser than critical but it is also needed
attention as soon as possible.
for eg: low fuel level
MINOR
Minor mean’s that ,it’s severity level is lesser in compare to other alarm and site
may not get affected as much as in case of critical and major.
for eg- site on DG.
AMIT MISHRA 8
ALARM PORT
PORT
NO/PIN
NO
Alarm port or pin no is decided by operator
itself . OPERATOR
SPECIFIC
COLOUR
COLOUR CODE CODE
AMIT MISHRA 9
ROUTE OF ALARM
It decide the route of alarm or we can say that where alarm connection start
till termination of that alarm.
ROOT CAUSE
Root cause mean’s the exact cause of fault which led to the alarm at the site.
ROUTE
• IT DECIDE ROUTE OF
of
ALARM
ALARM
AMIT MISHRA 10
ALARM CABLE CONNECTION Alarm cable are PCM cable.
They exist in pair’s.
Each alarm will be connected to ddf with
these cable.(two wire is one pair)
37 pin D-type connector.
Alarm ddf installed on shelter wall.
Alarm’s are connected to sensor’s.
AMIT MISHRA 11
For connection of alarm these are needed.
D TYPE 37 PIN
AMIT MISHRA 12
TYPE OF EXTERNAL ALARM’S 1. DOOR OPEN
2. HIGH TEMPERATURE
3. DG FAIL’S TO START
4. DG FAIL’S TO STOP
5. LOW FUEL LEVEL
6. FIRE OR SMOKE
7. LOW LUBRICATION OIL PRESSURE
8. LOAD ON DG
9. AC FAIL’S TO START(AC-1/AC-2)
10.RECTIFIER MODULE PAIR FAIL’S
11.LOW BATTERY VOLTAGE
12.SITE ON DG
13.AC -1 FAIL’S
14.AC-2 FAIL’S
15.DG RUNNING WITHOUT LOAD
AMIT MISHRA 13
TO ELABORATE ABOVE DESCRIPTION TAKE EXAMPLE OF NOKIA FLEXI BTS
AMIT MISHRA 14
SYNTAX- ALARM NO- ALARM TYPE-
SEVERITY-
MAIN’S 7401/ALARM NORMALY
MINOR
FAILURE NO1 OPEN
COLOR
CODE-
PIN NO-7/25
GREEN&
GREEN/WHITE
AMIT MISHRA 15
ALARM CONFIGURATION CONTINUED
SYNTAX-
ALARM NO- ALARM TYPE-
RECTIFIER SEVERITY-
7402/ALARM NORMALY
MODULE MINOR
NO2 OPEN
FAILURE
COLOR
PIN NO-8/26 CODE-BLUE&
BLUE/WHITE
POWER
ROUTE OF ALARM DDF BTS
PLANT
AMIT MISHRA 16
ALARM CONFIGURATION CONTINUED
COLOR CODE-
PIN NO-9/27 VOILET&
WHITE
VOILET
POWER
ROUTE OF ALARM DDF BTS
PLANT
AMIT MISHRA 17
ALARM CONFIGURATION CONTINUED
COLOR
PIN NO-
CODE-GREY&
10/28
WHITE GREY
ROUTE OF ALARM
POWER
DDF BTS
PLANT
AMIT MISHRA 18
ALARM CONFIGURATION CONTINUED
ROUTE OF ALARM
PIU/
DDF BTS
AMF
AMIT MISHRA 19
ALARM CONFIGURATION CONTINUED
COLOR CODE-
PIN NO- LIGHTGREEN&
12/30 BLACK/
GREEN
AMIT MISHRA 20
ALARM CONFIGURATION CONTINUED
COLOR
PIN NO-
CODE-LIGHT
13/31
BLUE&BLACK
FUEL
ROUTE OF ALARM PIU/AMF DDF BTS
SENSOR
AMIT MISHRA 21
ALARM CONFIGURATION CONTINUED
COLOR
PIN NO-
CODE-WHITE
14/32
BLACK/WHITE
PIU/
ROUTE OF ALARM DDF BTS
AMF
AMIT MISHRA 22
ALARM CONFIGURATION CONTINUED
COLOR CODE-
PIN NO- LIGHT GREY&
15/33 LIGHT GREY
/BLACK
MICRO
ROUTE OF ALARM- DDF BTS
CONTROLLER
AMIT MISHRA 23
ALARM CONFIGURATION CONTINUED
COLOR
PIN NO- CODE-
16/34 GREEN&
GREEN/WHITE
DOOR
ROUTE OF ALARM- PIU/AMF DDF BTS
SENSOR
AMIT MISHRA 24
ALARM CONFIGURATION CONTINUED
SYNTAX-
ALARM NO- ALARM TYPE-
HIGH SEVERITY-
7411/ALARM NORMALY
TEMPERATUR MAJOR
NO11 OPEN
-E
COLOR CODE-
PIN NO- ORANGE/
17/35 RED&ORANGE/LI
GHT GREY
MICRO
ROUTE OF ALARM- DDF BTS
CONTROLLER
AMIT MISHRA 25
ALARM CONFIGURATION CONTINUED
COLOR CODE-
PIN NO- ORANGE
18/36 /BLACK&ORA-
NGE/GREEN
FUEL
ROUTE OF ALARM- PIU/AMF DDF BTS
SENSOR
AMIT MISHRA 26
APART FROM THESE ALARM’S OF NOKIA FLEXI BTS WE HAVE FEW MORE AS FOLLOW’S
COLOUR
PIN NO-
CODE-
OPERATOR
OPERATOR
SPECIFIC
SPECIFIC
AMIT MISHRA 27
APART FROM THESE ALARM’S OF NOKIA FLEXI BTS WE HAVE FEW MORE AS FOLLOW’S
MICRO
ROUTE OF ALARM- CONTROLLER
DDF BTS
AMIT MISHRA 28
APART FROM THESE ALARM’S OF NOKIA FLEXI BTS WE HAVE FEW MORE AS FOLLOW’S
MICRO
ROUTE OF ALARM- CONTROLLER
DDF BTS
AMIT MISHRA 29
LIST OF DIFFERENT OPERATOR EXTERNAL ALARM
Ericsson RBS2954 DG on
DG fail’s to start
Main fail’s
DG fuel level
LLOP
DG fails to stop
Cabinet temperature
Fire & smoke
Door smoke
BFU fault
Spare
SMPS input fail
Battery low voltage
DC disconnected alarm
Battery breaker off
Battery disconnected
AMIT MISHRA 30
LIST OF DIFFERENT OPERATOR EXTERNAL ALARM
Ericsson RBS2964 DG on
DG fail’s to start
Main fail’s
DG fuel level
LLOP
DG fails to stop
Cabinet temperature
Fire & smoke
Door open
BFU fault
Spare
SMPS input fail
Battery low voltage
DC disconnected alarm
Battery breaker off
Battery disconnected
AMIT MISHRA 31
LIST OF DIFFERENT OPERATOR EXTERNAL ALARM
AMIT MISHRA 32
LIST OF DIFFERENT OPERATOR EXTERNAL ALARM
ZTE ZXG 10
AMIT MISHRA 33
ALARM DEFINED IN ERICSSON SITES:
AMIT MISHRA 34
EXTERNAL ALARMS FOR BTS (RBS 2954) SITES:
AMIT MISHRA 35
BELOW MENTIONED COLOUR CODE OF RBS(2954)-
AMIT MISHRA 36
EXTERNAL ALARM IN HUAWEI 3900 BTS AND COLOUR CODE-
NO: port SLOT DDF ALARM NO: port SLOT DDF ALARM
RECTIFIER
1 0 18 1 INTRUDER 9 0 19 1 HIGH
VOLTAGE
TOWER
A/C
2 1 18 2 10 1 19 2 LIGHT
FAILURE
FAILURE
HIGH
RECTIFIER
ROOM
3 2 18 3 11 2 19 3 2/MORE
TEMPERA
FAILURE
TURE
TOWER
FIRE
4 3 18 4 12 3 19 4 AMPLIFIE
ALARM
R FAIL
RECTIFIER
FIRE
5 4 18 5 13 4 19 5 LOW
FIGHTING
VOLTAGE
RECTIFIER
MAINS
6 5 18 6 14 5 19 6 COMMON
FAILURE
ALARM
GENERAT
GN AUTO
7 6 18 7 OR 15 6 19 7
MODE
FAILURE
LOW FUEL
GENERAT
8 7 18 8 16 7 19 8 IN MAIN
OR RUN
TANK
AMIT MISHRA 37
HUAWEI EXTERNAL ALARMS(COLOURS)
AMIT MISHRA 38
INSTALLATION OF ALARM AT OUTDOOR (AC/FAN COOLED) NOKIA BTS SITE
AMIT MISHRA 39
INSTALLATION OF ALARM AT OUTDOOR (AC/FAN COOLED) NOKIA BTS SITE
ALARM
NO1-RECTIFIER & BTS DOOR CABINET ALARM- GREEN & WHITE GREEN
ALARM
NO2-RECTIFIER MAJOR ALARM-BLUE & WHITE BLUE
ALARM
NO3-RECTIFIER MINOR ALARM-VIOLET & WHITE VIOLET
ALARM
NO4-LOW DC VOLTAGE-GREY & WHITE GREY
ALARM
NO5-HEAT MANAGEMENT ALARM(FOR AC CABINET ONLY)-BLUE/BLACK
&BLACK BLUE
ALARM NO7-TEMPERATURE ALARM(FOR FAN COOLED CABINET ONLY)-LIGHTBLUE
&LIGHT BLUE/ BLACK
AMIT MISHRA 40
INSTALLATION OF ALARM AT OUTDOOR (AC/FAN COOLED) NOKIA BTS SITE
AMIT MISHRA 41
INSTALLATION OF ALARM AT OUTDOOR (AC/FAN COOLED) NOKIA BTS SITE
AMIT MISHRA 42
INSTALLATION OF ALARM AT OUTDOOR (AC/FAN COOLED) NOKIA BTS SITE
Install the krone on rack and fix this rack in rectifier cabinet.
Use proper size bolt’s and washer.
AMIT MISHRA 43
INSTALLATION PROCESS CONTINUE-
AMIT MISHRA 44
INSTALLATION PROCESS CONTINUE-
Route this cable properly with ties and fix it near the Rectifier I/O
ports
• Connect Green & White Green (Alarm nu 1) with Pins 8 & 9 of CON1
(X1)
• Connect Grey & White Grey (Alarm nu 4) with Pins 9 & 10 of CON2
(X2)
• Connect Blue & White Blue (Alarm nu 2) with Pins 18 & 19 of CON2
(X2)
• Connect Light Blue & Light Blue Black (Alarm nu 7) with Pins 12 & 13
of CON2 (X2) (Only for Fan Cool Rectifier Cabinets)
AMIT MISHRA 45
CON 2
( X2 )
CON 1
( X1 )
AMIT MISHRA 46
INSTALLATION PROCESS CONTINUE-
AMIT MISHRA 47
INSTALLATION PROCESS CONTINUE-
AMIT MISHRA 48
INSTALLATION PROCESS CONTINUE-
AMIT MISHRA 49
INSTALLATION PROCESS CONTINUE-
AMIT MISHRA 50
INSTALLATION PROCESS CONTINUE-
AMIT MISHRA 51
SUMMARY
Overall summary is that on any BTS site external alarm’s are important.
Alarm’s make fault finding easy.
External alarm’s make BTS site safer and easy to maintain.
Each alarm has it’s own importance cannot be neglected.