CP2000 Introduction
For Fans/Pumps/HVAC Drive
applications.
HVAC: Heater, Ventilating, Air
Conditioner.
V/F control、SVC (sensorless vector
control)
PID control and sleep/wake up function
Multi-pumps, circulation pumps control
Fire mode + BYPASS function
PLC(10K step) + Real Time Clock
VFD-soft link and LCD TP editor
Built-in BACnet
LCD keypad user friendly interface
Delta Confidential
Energy saving on HVAC
From the relations illustrated
above, we can reduce the
running frequency of the
motor according to the
load.
Delta Confidential
V/F,SVC TN Curve
V/F SVC
T-N(Nt/m) T-N(Nt/m)
30
25
20
15
10
0
0 500 1000 1500 2000
rpm rpm
Delta Confidential
Pump and Fan Control
*HVAC systems
Pressure RA1
Transducer
feedback
PID
RC1
RA2
M1 control
*Cooling tower fan drivers
PT M2 control
function select
RC2
RA3
M3 control
*Combustion air and
RC3
exhaust gas fans
of power plants
Delta Confidential
CP2000 Power Capability
460V 3 Phase 0.75kW~400kW
– Models under 37kW with built-in EMI filter for:
VFD007CP4EA-21, VFD015CP4EA-21,
VFD022CP4EA-21, VFD037CP4EA-21,
VFD040CP4EA-21, VFD055CP4EA-21,
VFD075CP4EA-21, VFD110CP4EA-21,
VFD150CP4EA-21, VFD185CP4EA-21,
VFD220CP4EA-21, VFD300CP4EA-21,
VFD370CP4EA-21
– Models under 37kW with built-in braking unit
– 45kw~400kW with built-in DC reactor,
optional for EMI filter、 optional for braking
unit
Delta Confidential
CP2000 Model name
Delta Confidential
Ordering information
Delta Confidential
FRAME size comparison
Delta Confidential
CP2000 TOP Features
Control method:V/F control & SVC control、PID control and sleep/wake up function、 Multi-
pumps control 、FIRE MODE、PLC、real time clock.
Optional cards : communication cards & I/O extension card, CANopen(DS-402)
Built-in : RS-485, MODBUS and BACnet
Delta Confidential
CP2000 TOP 1
Modular design
maintain free
Plug-in/out
terminal
Removable Fan
Delta Confidential
CP2000 TOP 2
Robust design
PCB Coating treatment, Designed for environment adaption
assure the reliable operation
in the harsh environment
*AFE2000, DC reactor, AC
reactor, and EMI filter are
options for the models
without built-in DC reactor
or EMI filter.
Delta Confidential
CP2000 TOP 3
Isolated Control PWB
Control PWB no touch with heat sink
Heat sink is isolated with control PWB system for preventing
CP2000 from damaging and environmental pollution
Delta Confidential
CP2000 TOP 3
Flange mounting:
Put all heat generated from inverter out.
Isolating all the dust from the environment.
Delta Confidential
CP2000 TOP 4
LCD Keypad
Delta Confidential
CP2000 TOP 4
LCD Keypad Features
Quick setting for user common usage, easy and fast to install.
Multi-language
Delta Confidential
CP2000 TOP 4
PLC program, Drive Parameter Copy/Backup/Restore to VFD_soft or
CP2000.
Delta Confidential
VFD-soft & TP Editor
Delta Confidential
CP2000 TOP 5
Built-in PLC (10K step): It can be used with the built-
in real time clock for special multi-pumps control.
Delta Confidential
CP2000 TOP 6
Most common used, various high speed network
Built-in BACnet
Delta Confidential
CP2000 Options List
Category Option Name Model Number
Network Communication DeviceNet CMC-DN01
EtherNet/IP CMC-EIP01
Modbus TCP/IP CMC-MOD01
Profibus DP CMC-PD01
CANopen EMC-COP01
CANopen Breakout Box TAP-CN03
CANopen Communication Cable
500mm TAP-CB03
CANopen Communication Cable
1000mm TAP-CB04
Input/Output Digital Input EMC-D42A/EMC-D611A
Digital Output EMC-D42A/EMC-R6AA
Keypad LED Keypad KPC-CE01
Panel Mounting Kit (MKC-KPPK)
Flange Mounting Kit Frame A MKC-AFM/MKC-AFM1
Frame B MKC-BFM
Frame C MKC-CFM
USB/RS-485 Communication
Interface IFD6530
Delta Confidential
CP2000 TOP 7
LN
VFD-CP2000
UVW
RY00
MO3
MO6
MO5
MO4
MO2
MO1
RC3
RC2
RC1
RA2
RA3
RA1
RB1
Multi-pumps control
1: Fixed Time Circulation (by time)
2: Fixed amount circulation (by PID)
M1
M3
Contactor
M4
Contactor
UVW
CP2000
UVW
M0
RY00
MO3
MO6
MO5
MO4
MO2
MO1
RC3
RC2
RC1
RA2
RA3
RB3
RB2
RA1
RB1
MO12
MO11
MO10
MO6
MO9
MO8
MO7
MO5
MO4
MO3
RC3
RC2
RC1
RA3
RA2
RB2
RA1
RB1
Contactor
Contactor
M1
M1
Contactor
Contactor
Contactor
M2
M2
Contactor
Contactor
Contactor
M3
M3
Contactor
Contactor
Contactor
M4 M4
Contactor
Fixed amount circulation (Max: 4 pumps) Fixed amount control (Max: 8 pumps)
Delta Confidential
CP2000 TOP 8
Fire mode + bypass function
Application: ventilating of
building, tunnel, subway, etc.
Delta Confidential
CP2000 TOP 9
Flying start function lets high inertial load situation can
run smoothly in start without error happened. (No need
to stop the motor)
Momentary power off (within 5s on LV), the speed
searching function can make the motor continue running
without stopping the motor to save start time.
Delta Confidential
CP2000 TOP 10
Skip frequency function avoids the motor vibration at a specific
frequency band and protects the equipment. It offers 3 zones for
use.
Delta Confidential
CP2000 TOP 10
DEB (Deceleration Energy Backup) This function allows
the AC motor drive decelerates to stop after power loss.
When the momentary power loss occurs, this function
can be used for the motor to decelerate to 0 speed with
deceleration stop method. When the power is on again,
motor will run again after DEB return time.
Delta Confidential
WHY CHANGE CP2000 VFD-F C2000
Special Application Application on customer side
TO CP2000 ? Product Highlights
DEB Available N/A Available Deceleration time setting for While operating a crane, a deceleration
(Deceleration Energy spontaneous power down + DC brake + is required to stop loading when there
Backup) Delay braking time: Keep a crane to is an spontaneous power down.
have stable fixed output frequency while
deceleration and emergency
FIRE MODE Available V1.302 N/A Use bypass function to switch to the Keep the drive in control without being
+ mains power supply. interrupted by any error when there is
BYPASS an emergency. Keep this drive in
Available control until the mains power supply is
+ out or until this drive’s failure.
BYPASS
Delta Confidential
WHY CHANGE CP2000 VFD-F C2000
Applications
Applications on Customer
to CP2000 ? Side
Product Highlights
Administration of parameters,
Administration of PC Link parameters,
VFD_soft Available Available Available and monitoring of related
copy, download and upload to CP2000
curves
Available Available
Auto acceleration Auto adjust acceleration/deceleration
N/A Energy saving
/deceleration time in accordance to the loading rate.
Delta Confidential
YASKAWA
CP2000 Danfoss FC102 ABB ACH550
E1000
WHY CHANGE CP2000 ?
Product Highlights
N/A
DWELL Available Available Available
Delta Confidential
Comparison Chart on Functions
DELTA_CP2000 YASGAWA E1000 Danfoss_FC102 ABB_ACH550
Delta Confidential
Comparison Chart on Functions
Comparison of different brands
DELTA_CP2000 YASGAWA E1000 Danfoss_FC102 ABB_ACH550
0.00~600.00Hz
230V 55KW and above are
7.5~90 kW: 0 Hz to 650 Hz
Output Frequency Range 0.00~400.00Hz 0 to 1000Hz 0~500Hz
110~250 kW: 0 Hz to 267 Hz
440V 90KW and above are
0.00~400.00Hz
DeviceNet, LONWORKS,
PROFIBUS DP, CANOpen,
RS485, PROFIBUS, DeviceNet, MODBUS RS485, PROFIBUS, Mosbus RTU, FC protocol,
ControlNet, CC-Link,
Communication Options CANOpen, Modbus-TCP Slave, DeviceNet, CANopen,CC- Profibus, DeviceNet,
Modbus TCP, Ethernet/IP,
EtherNet/IP Slave, BACnet LINK LonWorks,N2,BACnet
PROFINET IO, Power Link,
EtherCat, BACnet
Delta Confidential
Comparison Chart on Functions
Comparison of different brands
DELTA_CP2000 YASGAWA E1000 Danfoss_FC102 ABB_ACH550
AVI 1: 4~20mA/0~10V(AVI
Switch), Factory setting is 3 programmable analog inputs 2 programmable analog
0~10V A1: 0 V to 10 V 3, programmable inputs
Analog Input ACI: 4 ~ 20mA/0~10V(ACI A2: 0 V to 10 V and 4 mA to 20 0V to 10V(Scaleable) AI1: 0 V to 10 V/ 0(4) mA to
Switch) Factory setting is Ma 0/4 mA to 20 mA (Scaleable) 20 mA
4~20mA A3: 0V TO 10V AI2: 0(4) 20 mA/ 0V to 10V
AVI 2: 0~10VDC
8 fully programmable isolated 8 fully programmable isolated 3 fully programmable isolated 6 fully programmable
Digital Input digital inputs; switchable digital inputs; switchable digital inputs; switchable isolated digital inputs;
PNP/NPN PNP/NPN PNP/NPN switchable PNP/NPN
AFM1: 0~10V→-
10~+10V(AFM Switch Factory
setting is 0~10V) 1, programmable (0/4 mA to 20 1, programmable (0/4 mA to 20 2, programmable (0/4 mA to
Analog Output
AFM2: mA) mA) 20 mA)
0~10V→4~20mA(AFM Switch
Factory setting is 0~10V)
RA1/RB1/RC1/RA2/RC2/RA3
/RC3:
Resistive Load
5A(N.O.)/3A(N.C.) 250VAC 4, programmable 2, programmable 3 relay output
Digital Output 5A(N.O.)/3A(N.C.) 30VDC 30 V DC/5 A (resistive load), 240VAC, 2A and 400VAC, 2A 30 V DC/2 A
Inductive Load (COS 0.4) 250 V AC/2 A (inductive load) 3 relays 250 V AC/2 A
2.0A(N.O.)/1.2A(N.C.)
250VAC
2.0A(N.O.)/1.2A(N.C.)
30VDC
Delta Confidential
Comparison Chart on Functions
Comparison of different brands
DELTA_CP2000 YASGAWA E1000 Danfoss_FC102 ABB_ACH550
DC braking,
0.75~7.5kW: built-in braking
DC Braking, AFE2000, DC Braking, Brake units, AHF
Braking system DC Braking, REGEN braking chopper
Braking unit, Braking Resistor (Active Harmonic Filter)
others: Compact-size brake
units
Delta Confidential
VFD-CP2000 position
Variable Normal Machinery torque Servo
market Torque usage field control characteristic
FOC VL VE
VJ
B
FELXIABLE
VFD-CP2000
E
F
S/M
ECONOMICAL EL
Delta Confidential
CP2000 FIELD APPLICATIONS
COOLING PUMP TOWER FANS Build Automation (HVAC)
Delta Confidential
HVAC
Delta Confidential
HVAC Drive power segment
Applications of public works
Delta Confidential
Industrial tower blower
Main Application: V/F control, energy saving
Delta Confidential
Exhausted gas treatment system
Main application :V/F variable torque control
Delta Confidential
Air Treatment application
Main application :V/F variable torque control
Delta Confidential
Tunnel Blower
Main application :V/F variable torque control
Delta Confidential
Water Treatment
Main application :V/F variable torque control
Delta Confidential