Every 40C rise in inlet air temperature results in a higher energy consumption by 1 % to
achieve equivalent output. Hence, cool air intake leads to a more efficient compression.
Effect of Pressure Drop Across Air
Inlet Filter on Power Consumption
Pressure Drop Increase in Power
Across air filter Consumption (%)
(mmWC)
0 0
200 1.6
400 3.2
600 4.7
800 7.0
For every 25 mbar (250 mm WC) pressure lost at the inlet due to choked
filters, the compressor performance is reduced by about 2 percent.
Regular filter cleaning is very important.
Is the pressure drop across the suction filter measured?
Else can arrangement be done to measure it?
We should adopt a practice to initiate note based on DP
Elevation
Percentage Relative
Barometric Volumetric Efficiency
Altitude
Pressure Compared with Sea Level
Meters
Mbar
At 4 bar At 7 bar
Sea level 1013 100.0 100.0
500 945 98.7 97.7
1000 894 97.0 95.2
1500 840 95.5 92.7
2000 789 93.9 90.0
2500 737 92.1 87.0
It can be seen from the table that an increase of 5.50C in the inlet to the
second stage results in a 2 % increase in the specific energy consumption.
Use of cold water reduces power consumption.
Are we getting perfect cooling after 1st stage?
Cooling Water Requirement
Minimum quantity of
Cooling Water required
Compressor Type
for 2.85 m3/min. FAD at 7
bar (lpm)
Single-stage 3.8
Two-stage 7.6
Single-stage with after-cooler 15.1
Two-stage with after-cooler 18.9