Professional Documents
Culture Documents
Digital Differential Relays For Transformer Protection Using Walsh Series and Least Squares Estimators
Digital Differential Relays For Transformer Protection Using Walsh Series and Least Squares Estimators
Digital Differential Relays For Transformer Protection Using Walsh Series and Least Squares Estimators
6
i j 0 ?!
j1
Problems in transformer
differential protection:
inrush current,
CT inaccuracy,
CT saturation,
over-excitation.
Current [A]
-5
-3 -2 -1 0 1 2 3
1
Primary
-1
0 1 2 3 4 5 6 7
2
Secondary
-2
0 1 2 3 4 5 6 7
Time
WE HAVE USED TWO METHODS:
1 2n
Ŵn n f (KT) Wal (KT)
2 k 1
Walsh Series (Ctd):
W=A * F
F=A-1*W
where
F=[ F0 F1 F2 F3 F4 F5 F6 F7 F8]
A-1=AT
I1peak F F
1
2
2
2
X est = LPI(A) * B
T 1 T
LPI(A) = ( A * A ) * A
Sampling:
12 point window (for half cycle estimation)
or
24 points (for full cycle estimation)
with
24 sample/cycle sampling system
Least square frequncy response for
fundamental frequency
1.5
cosine filter
0.5
0
0 500 1000 1500
1.5
1
sine filter
0.5
0
0 500 1000 1500
frequency [HZ]
The Decision Space
Differential Relay Characteristics Curve
45
40
35
Fault Zone
30
25
|Idif|
20
15
Non-Fault Zone
10
0
0 50 100 150
|Ires|
Inrush Pattern Recognition
-100
Ihb
-200
0 50 100 150
200
Ilb
100
Ila, Ilb, Ilc
0
Ilc
-100
Ila
-200
0 50 100 150
Sample (Time)
High and Low Voltage Side
Currents for Internal Fault
Internal Fault Currents, High and Low voltage Sides
200
Iha
100
Iha, Ihb, Ihc
0
Ihb
-100
Ihc
-200
0 50 100 150
50
Ila
Ila, Ilb, Ilc
Ilc
Ilb
-50
0 50 100 150
Sample (Time)
High and Low Voltage Side
Currents for Inrush Current
Inrush Currents, High and Low voltage Sides
100
Iha
50
Iha, Ihb, Ihc
-50 Ihb
Ihc
-100
0 50 100 150 200 250
0.02
Ilb
0
Ila, Ilb, Ilc
Ilc
-0.02 Ila
-0.04
0 50 100 150 200 250
Sample (Time)
Three Phases Differential Currents
in External Fault
Differential Currents Vs. Sample (time)
80
Idiffb
70 Idiffa
60
50
40
30
20
10
Idiffc
0
0 50 100 150
Sample (Time)
. Three Phases Differential
Currents in Internal Fault
Differential Currents Vs. Sample (time)
160
Idiffa
140
120
100
80
60
40
Idiffb
20 Idiffc
0
0 50 100 150
Sample (Time)
Three Phases Differential Currents
in Inrush Current
Differential Currents Vs. Sample (time)
Idiffa
90
80
Idiffc
70
Idiffb
60
50
40
30
20
10
0
0 50 100 150 200 250
Sample (Time)
Decision Space in External Fault
for three Phases
Fault Zone Bound:Solid line ,Idiff Locus:Dotted line
300
200
|Idiffa|
100
0
0 100 200 300 400 500 600 700 800
300
200
|Idiffb|
100
0
0 100 200 300 400 500 600 700 800
300
200
|Idiffc|
100
0
0 100 200 300 400 500 600 700 800
Irest1
Decision Space in Internal Fault for
Three Phases
Fault Zone Bound:Solid line ,Idiff Locus:Dotted line
|Idiffa| 200
100
0
0 50 100 150 200 250 300 350
150
100
|Idiffb|
50
0
0 50 100 150 200 250 300 350
150
100
|Idiffc|
50
0
0 50 100 150 200 250 300 350
Irest1
Decision Space in Inrush Current
for Three Phases
Fault Zone Bound:Solid line ,Idiff Locus:Dotted line
|Idiffa| 100
50
0
0 50 100 150 200
60
40
|Idiffb|
20
0
0 50 100 150 200
60
40
|Idiffc|
20
0
0 50 100 150 200
Irest1
Second/Fundamental Harmonic
Ratio for External Fault
Ratio of Second Harmonic to Fundamental (External Fault)
1.5
1
Irest2/Irest1
0.5
0
0 50 100 150 200 250
Samples (Time)
Second/Fundamental Harmonic
Ratio for Internal Fault
Ratio of Second Harmonic to Fundamental (Internal Fault)
1.5
1
Irest2/Irest1
0.5
0
0 50 100 150 200 250
Samples (Time)
Second/Fundamental Harmonic
Ratio for Inrush Current
Ratio of Second Harmonic to Fundamental (Inrush)
1.5
1
Irest2/Irest1
0.5
0
0 50 100 150 200 250
Samples (Time)
General Trip Alarm for External
Fault
Tripping Command of Phases(External Fault)
2
1.5
No Trip Command
1
Trip Signal
0.5
-0.5
-1
0 50 100 150
Samples
General Trip Alarm for Internal
Fault
Tripping Command of Phases(Internal Fault)
2
1
Trip Signal
0.5
-0.5
-1
0 50 100 150
Samples
General Trip Alarm for Inrush
Current
Tripping Command of phases (Inrush)
2
1.5
1
No Trip Command
Trip Signal
0.5
-0.5
-1
0 50 100 150 200 250
Samples
Summary
A digital differential relay for transformer
protection was presented.
Two estimator systems: Walsh series and least
squares algorithms were formulated and
designed.
The differential protection decision maker
subsystem was introduced.
Current signals harmonic components and
second harmonic restraint concept were utilized
in decision maker subsystem.
Conclusion
In a practical case study, the designed
relay performance was tested under three
real circumstances: external fault, internal
fault and inrush current.
It was shown -using graphs and
illustrations- that the presented relay
issues trip alarm for transformer internal
fault, and does not issue trip alarm for
external fault and inrush current situations.
Conclusion (Ctd)
It were seen that both estimation
algorithms perform their job correctly.
Walsh series acts better than least
squares algorithm, especially on second
harmonic estimation.
An anti alias filter (for example a
Butterworth one) will improve response of
the estimator.