- DX AHU System
- AHU Application Kit
- Supply Air Control Kit
Cooling tower
F.D Smoke Damper
Return Air
Exhaust
louver
V.D Supply air
RF
Out air
louver
S.A Diffuser
Cooling water supply
Cooling water return
F.T.A SR SS
7℃ .Pressure reducing valve
CWS
Cooling water circulation pump 2 way control valve SS
D.P.C.V
CWR
Differential CWR
CWS
pressure
automatic valve
37℃
32℃
Steam header
Steam trap
Chiller water Chiller water (F.T.A)
supply header return header
12℃
Condensed
Chiller Cold water circulation pump
water tank
Boiler water Steam boiler
feed pump
Internal Use Only
Introduction of AHU
Classification of Air Conditioning System
※ Diagram
System design
Heat Materials for
Name of HVAC type Remarks
transfer heat transfer Each
Central Individual
Floor
Office,
Single Duct Variable air volume ○ ○
Place that has big load variation
All air system Double Duct Constant air volume ○ Hospital (Individual control needs)
AHU VRF
Features
Big air volume,
high static pressure
Multi V AHU
Internal Use Only
Introduction of AHU
AHU Overview and Classification
AHU is an air conditioning solution for wide areas that can control all four air
conditioning factors (temperature, humidity, air current, and cleanliness).
700
400
- EA damper 120
- OA damper Return Supply
- Mixing damper 100
Fan Fan
80
50
Unit : CMM
Internal Use Only
DX AHU System
AHU Overview and Classification
Air conditioners are classified by the type of the internal coil, that is, connected heat source.
The general EHP AHU and DX AHU need to be separated when making a proposal.
The air conditioner that the EHP The condensing unit for cooling Connected to a chiller or boiler, and
refrigerant coil is installed, only is used as a cooling source, and composed of the water coil
and has no heating source. the separate electric heater or boiler that provides cold/hot water to the
is used as a heating source. air conditioner.
OA SA Cooling tower
OA SA
Pre OA SA
-heater
Multi V Multi V
ACP AC Manager
BMS
LonWorks BACnet
Internal Use Only
DX AHU System
Components for DX AHU System
DX AHU System is composed of AHU, outdoor unit and application Kit
Control kit
Communication kit
Control Device • 2 kinds of model
• 2 kinds of model • Model name : PRCKD20E
• Model name : PRCKA0 / PRDCA0 PRCKD40E
• Option PCB (Capacity adjustment) • Capacity
• Capacity : 28k ~ 192k - PRCKD20E (1~4 ODU)
# PRDCA0 : Included DI/DO function - PRCKD40E (5~8 ODU)
Expansion Device
(Ref. Piping) (Ref. Piping)
※ Application cases
Fan RA EA OA SA
(Supply, Return)
Outdoor Unit
EEV Kit
Wired
remote controller
Connection Pipe
Communication wire
Thermistor
Signal(On/Off)
Internal Use Only
AHU Application Kit
Scene2 : Communication Kit + Expansion Kit
※ Application cases
Fan RA EA OA SA
(Supply, Return)
Outdoor Unit
Expansion
Kit
8~56HP
MCC
Panel
AHU
Room air
Temp Sensor
(should be
installed into
the return air part) Communication Kit
Wired
remote controller
Connection Pipe
Communication wire
Thermistor
Signal(On/Off)
Internal Use Only
AHU Application Kit
Scene3 : Control Kit + Expansion Kit
※ Application cases
Temp. Senor / RA, SA(essential), OA, Mix(optional)
Smoke Detector(optional)
Fan AHU
(Supply, Return)
Control Kit
8~56HP
Wired
remote controller
MCC
Panel
8~56HP
Signal (On/Off)
Temp.
Sensor Discharge Air
Temp.
Temp.
Sensor
Comm. Kit
Indoor Air
Temp.
Temp.
Sensor Discharge Air
Temp.
Small scale : AHU ~ 20HP Medium scale : AHU 8 ~ 56HP Large scale : AHU 56 ~ 448(56x8EA)HP
Supply Air
Control Kit
Supply Air Supply Air (PRDCA0)
Control Kit Control Kit
or
ODU Dry Contact
(PQDSBCDVM0)
or
I/O Module
(PVDSMN000)
Local AHU Local AHU
controller or DDC controller or DDC
Local AHU
Connection Pipe Thermistor Wires (DI,DO,AI) controller or DDC
Communication wire Signal(On/Off)
Internal Use Only
Supply Air Control Kit
Supply Air Control Configuration
* Communication kit
• PRCKA0 (~20HP)
Multi V ODU AHU • Option PCB (Capa. adjustment)
- 28k,36k,42k,48k,76k,96k,115k,
134k,155k, 172k, 192k
Remote controller
EEV Kit
Comm. Kit Note :
- When return air is supplied. It can be applied.
Coil
- When the air inlet temp. of DX AHU is less than5℃, It can’t be applied.
Internal Use Only
AHU Application Kit
Application cases : Comm. Kit + EEV Kit
(2/6)
AHU
Remote controller
Ref. pipe
(Group control)
comm. line
R.C cable
EEV signal Item Model Specification
Pipe sensor EEV PRLK048A0 ~ 10HP
EEV PRLK096A0 ~ 20HP
EEV Kit
Comm. Kit Note :
- When return air is supplied. It can be applied.
Coil
- When the air inlet temp. of DX AHU is less than5℃, It can’t be applied.
Internal Use Only
AHU Application Kit
Application cases : Comm. Kit + EEV Kit
(3/6)
Remote controller
Cassette, Wall mounted (Total 10HP)
Ref. pipe
comm. line Remote controller
R.C cable
EEV signal Item Model Specification
Pipe sensor EEV PRLK048A0 ~ 10HP
EEV PRLK096A0 ~ 20HP
EEV Kit
Comm. Kit Note :
- When return air is supplied. It can be applied.
Coil
- When the air inlet temp. of DX AHU is less than5℃, It can’t be applied.
Internal Use Only
AHU Application Kit
Application cases : Comm. Kit + EEV Kit
(4/6)
AHU (4Coils)
Multi V ODU (~80HP)
..
.
Ref. pipe
Remote controller
comm. line
(Group control)
R.C cable
EEV signal Item Model Specification
Pipe sensor
EEV PRLK048A0 ~ 10HP
EEV PRLK096A0 ~ 20HP
EEV Kit
Comm. Kit Note :
- When return air is supplied. It can be applied.
Coil
- When the air inlet temp. of DX AHU is less than5℃, It can’t be applied.
Internal Use Only
AHU Application Kit
Application cases : Comm. Kit + EEV Kit
(6/6)
* Communication kit
• PRCKA0 (~20HP)
Multi V ODU (~56HP) AHU
• Option PCB (Capa. adjustment)
: Don’t need to be modified
Remote controller
Remote controller
(Group Control)
X
u lt
Fa
AHU
Remote controller
Ref. pipe (Group control)
comm. line
Item Model Specification
R.C cable
PATX13A0E 8~16HP
Pipe sensor
PATX20A0E 18~26HP
Expansion kit
PATX25A0E 28~36HP
PATX35A0E 38~46HP
Expansion Kit PATX50A0E 48~56HP
Comm. Kit Note :
Coil - Expansion kit should make only one cycle.
Internal Use Only
AHU Application Kit
Application cases : Control Kit + Expansion kit
(1/4)
Remote controller
(AHU exclusive)
AHU
X
Multi V ODU (~56HP) AHU
u lt
Multi V ODU (~56HP)
Fa
X
Remote controller
(AHU exclusive)
Ref. pipe
comm. line Item Model Specification
R.C cable PATX13A0E 8~16HP
Pipe sensor PATX20A0E 18~26HP
Expansion kit
PATX25A0E 28~36HP
PATX35A0E 38~46HP
Expansion Kit PATX50A0E 48~56HP
Control Kit Note :
Coil - All ODU should be connected to controller kit directly.
Internal Use Only
AHU Application Kit
Application cases : Control Kit + Expansion kit
(4/4)
u lt
Multi V ODU (~56HP) Fa
X
Remote controller
(AHU exclusive)
Ref. pipe
comm. line Item Model Specification
R.C cable PATX13A0E 8~16HP
Pipe sensor PATX20A0E 18~26HP
Expansion kit
PATX25A0E 28~36HP
PATX35A0E 38~46HP
Expansion Kit PATX50A0E 48~56HP
Control Kit Note :
Coil - Each ODU should compose an independent refrigerant cycle
with one Expansion kit.
Internal Use Only
Supply Air Control Kit
Inside of Supply Air Control Kit
(1/2)
* AI : Analog Input
* AO: Analog Output
* DI : Digital Input
* DO: Digital Output
Internal Use Only
Supply Air Control Kit
Supply Air Control Kit : Capacity Control
(2/2)
■ Capacity Control Range
Tolerance
Target Low Target High
Input Heating coil
Capacity of Pressure Cooling coil Pressure
voltage AI Low High temperature Control
Unit [%] [For Cooling, temperature [°C]* [For Heating,
No. [Vdc] [Vdc] [Vdc] [°C]
kPa gage] kPa gage]
Controlled by Controlled by
0 0 0.4 100% N/A N/A
ODU ODU
1 0.6 1.4 100 800 10.5 3,000 50.5
2 1.6 2.4 90 830 11.3 2,990 50.3
3 2.6 3.4 80 870 12.5 2,730 47.3
4 3.6 4.4 70 930 14 2,560 45.1 DI will determine fan mode and
operation mode
5 4.6 5.4 60 990 15.8 2,340 41.7
6 5.6 6.4 50 1,070 17.9 2,080 36.8
7 6.6 7.4 45 1,100 19 1,950 34.0
8 7.6 8.4 40 1,160 20.3 1,800 30.5
If it is 9V, DO 01-4 is close, DO
9 8.6 9.4 Comp. off - -
01-2 is open.
10 9.6 10 All off - - ODU and FAN are Off.
Due to LG policy of innovation, the values are changeable without previous notifications.
* Measured in R&D chamber respecting laboratory protocols, real temperature on site may vary.