Professional Documents
Culture Documents
2.0 Non-Directional OC Protection - Final
2.0 Non-Directional OC Protection - Final
OVERCURRENT PROTECTION
Non-Directional Overcurrent Protection
Stronger transmission
for a stronger nation.
Purpose of Protection
• Detect abnormal conditions
– Overload
– Short-Circuit
• Isolate faulty part of the system
Overcurrent Protection Principles
Design Criteria
Stronger transmission
for a stronger nation.
• Speed
– Instantaneous
– Time Delayed
• Discrimination
– Current
– Time
– Current and Time
• Reliability (Dependability and Security)
• Cost of protection against cost of potential hazards
Types of Overcurrent Protection
Stronger transmission
for a stronger nation.
Fuses
• Simple
• Can provide very fast fault clearance
– Less than 10ms for large fault current
• Limit fault energy
Arcing Time
Pre-arc Time
Prospective Fault Current
Total t
Operating
Time
Types of Overcurrent Protection
Stronger transmission
for a stronger nation.
Fuses - Disadvantages
• Issues on coordination
• Limited sensitivity to earth faults
• Single phasing
• Fixed characteristic
• Need replacing following fault clearance
Types of Overcurrent Protection
Stronger transmission
for a stronger nation. Instantaneous Overcurrent Relays
• Current settings chosen so that relay closest to fault
operates
50 IF2 50 IF1
• Problem
– Relies on there being a difference in fault level between the two
relay locations
– Cannot discriminate if IF1 = IF2
50 IF2 50 IF1
Types of Overcurrent Protection
Stronger transmission
for a stronger nation.
Definite/ Independent Time Overcurrent Relays
51 IF2 51 IF1
0.9 sec 0.5 sec
IS APPLIED CURRENT
(RELAY CURRENT SETTING)
• Electronic, multi-characteristic
• Fine settings, wide range
• Integral instantaneous elements
Types of Overcurrent Protection
Stronger transmission
for a stronger nation.
Numerical IDMT O/C Relays
I>1
I>2
TIME
I>3
I>4
CURRENT
operate first
• Other relays must have
R1 R2 IF adequate additional
operating time to prevent
T them operating
• Current setting chosen to
allow FLC
• Consider worst case
IS2 IS1 Max Fault Level I conditions, operating
modes and current flows
Overcurrent Protection Coordination
Stronger transmission
for a stronger nation.
Standard Inverse
• Commonly known as 3/10 characteristic
• Widely applied at all system voltages
• Used when:
– No coordination requirement with other types
such as fuses, thermal characteristics of
transformers and motors, etc.
– Fault levels do not vary significantly
– There is minimal inrush on cold load pickup
O/C Relay Characteristic
Stronger transmission
•
for a stronger nation.
Standard Inverse
• Mathematical expression
Where:
TMS = Time Multiplier Setting
M = ; = applied current
O/C Relay Characteristic
Stronger transmission
for a stronger nation.
Very Inverse
• Used to obtain greater time selectivity when
the limiting overall time factor is very low,
and the fault current at any point does not
vary too widely
• Gives longer time grading intervals
• Permits the same time multiplier setting for
several relays in series
O/C Relay Characteristic
Stronger transmission
• Inverse
for a stronger nation.
Very
• Mathematical expression
Where:
TMS = Time Multiplier Setting
M = ; = applied current
O/C Relay Characteristic
Stronger transmission
for a stronger nation.
Extremely Inverse
• Operating time is approximately inversely
proportional to the square of the current
• Particularly suitable for:
– grading with fuses
– protection of feeders which are subject to peak
currents on switching in
– used with auto-reclosers at low voltage distribution
– Protection against overheating
O/C Relay Characteristic
Stronger transmission
•
for a stronger nation.
Extremely Inverse
• Mathematical expression
Where:
TMS = Time Multiplier Setting
M = ; = applied current
O/C Relay Characteristic
Stronger transmission
for a stronger nation.
• Time Inverse
for a stronger nation.
Long
• Mathematical expression
Where:
TMS = Time Multiplier Setting
M = ; = applied current
O/C Relay Characteristic
Stronger transmission
for a stronger nation.
•IEC
Characteristics
• SI t =
• VI t =
• EI t = LTI
SI
• LTI t = VI
EI
R1 R2 IF
R1 R2 IF
T
Traditionally
• Breaker Operate Time = 0.1 Grading
• Relay overshoot = 0.05 Margin
• Allow for errors = 0.15 I
• Safety margin = 0.1
• Total = 0.4 s
O/C Relay Current Grading Margin –
Between Relays
Stronger transmission
for a stronger nation.
R
I
Tf
R
Tr
IF max I
Calculation
• Calculate relay operating time required, Treq
– Consider grading margin
– Fault level
• Calculate op time of inverse characteristic with TMS
=1, T1
• TMS = Treq/T1
Plotting of Characteristic
Stronger transmission
200/5 100/5
B A IFMAX=1400A
Is = 5 A Is = 5 A, TMS = 0.05, SI
200/5 100/5
B A IFMAX=1400A
Is = 5 A Is = 5 A, TMS = 0.05, SI
• Relay
A set to 100A, hence PSM = 1400/100 = 14
Relay A operate time = t = = = 0.13
• Relay B operate time = 0.13 + grading margin = 0.13+0.14 =
0.53s
• Relay A uses SI curve so Relay B should also use SI curve
OCR Grading Example
Stronger transmission
for a stronger nation.
200/5 100/5
B A IFMAX=1400A
Is = 5 A Is = 5 A, TMS = 0.05, SI
• Relay B set to 200A, hence PSM = 1400/200= 7
Relay B operate time = t (@TMS = 1) = = 3.53s
• Required TMS = = = 0.15
• Set Relay B to 200A, TMS = 0.15, SI
• • A phase-phase fault at
for a stronger nation.
Delta/Wye Transformer
51 51 IPP
HV LV
HV2
• No operation for LV fault
HV1 • Fast operation for HV
LV
Time
Fault
• Reduces operate time
required for upstream
relays
If(LV) Current
If(HV)
1.3 If(LV)
EARTH FAULT PROTECTION
Earth Fault Protection
Stronger transmission
3-Wire System
BUS 2
BUS
1 X
R+jX
A
230/69kV
S
51-P
51-Y
PHASE I>P= 1.5 – 2 x RATED CURRENT
PHASE: I>Y= 75 - 120% OF THE LINE
NEUTRAL IE>P= 30% RATED CURRENT AMPACITY (SHOULD BE LESS THAN AVAILABLE
SHORT CIRCUIT AT BUS 5)
NEUTRAL: I>X & I>Y= 20 – 30% PHASE PICK-UP
Pick-up Setting (50P/50N)
Stronger transmission
for a stronger nation.
BUS
BUS
2
1 R+jX
PHASE: I>>S= DISABLE X
NEUTRAL: IE>>S= DISABLE
50-X
A
230/6 50-S PHASE: I>>X = 1.2 – 1.3 x 3Ø FAULT @ BUS 2
9kV
NEUTRAL: I>>X = 1.2 – 1.3 x 1L-G FAULT @ BUS 2
S
50-P
50-Y
PHASE I>>P= 1.2 – 1.3 x 3Ø
FAULT AT BUS 1 OR 8 x PHASE: I>>Y= 1.2 – 1.3 x 3Ø FAULT AT
XFORMER RATED CURRENT NEAREST BUS (BUS 3)
NEUTRAL IE>>P= 1.7 x 1LG NEUTRAL: I>>Y= 1.2 – 1.3 x 1L-G FAULT AT
FAULT AT BUS 1 NEAREST BUS (BUS 3)
Relay Coordination
Stronger transmission
for a stronger nation.
51-P
51-Y
PHASE: tP= 0.4 s for 3Ø FAULT
at BUS 1 GROUND: tP= PHASE: tY= 0.4 s for 3Ø FAULT @ FARTHEST
0.75 s for L-G FAULT at BUS 1 BUS (BUS 5) GROUND:
CURVE: IEC SI tEY= 0.4 s for 1LG FAULT @ BUS 5 CURVE: IEC
SI
CHECKLIST FOR COORDINATION OF
OVERCURRENT PROTECTION
Checklist for Coordination of Overcurrent
Protection
Stronger transmission
for a stronger nation.