Professional Documents
Culture Documents
1 / 212
L&T-MHPS BOILERS
Index
Basics of Supercritical Plant
Special Feature for Supercritical Plant
Boiler Performance Parameter
Coal & ASH Characteristic
Start-up Curve
Boiler Startup checks
Boiler Startup Sequence
Boiler Light Up to Full Load up
Oil Burner Startup Sequence
Mill Startup Sequence
Operational Controls
Boiler Shutdown Sequence
Oil Burner Shutdown Sequence
Mill Shutdown Sequence
Boiler Forced Cooling Method
Boiler Trip Conditions
Special Operating Condition
a. FCB
b. Runback
c. Forced Cooling
Emergency Operating Condition
2 / 212
L&T-MHPS BOILERS
Basics of Supercritical Plant
(1) Why the Supercritical plant is selected?
User Needs
L&T-MHPS BOILERS
Basics of Supercritical Plant
Main Advantage
Plant Efficiency : Higher
- Reduction of Operation cost (i.e. fuel cost)
- Less CO2 discharge
4 / 212
L&T-MHPS BOILERS
Basics of Supercritical Plant
(2) What is supercritical pressure ?
1000
900
800
Sat
ura
700 ted
W at er
Line
Bulk Density [kg/m3]
600
779.3 kg/m3
500
400 No fixed
steam and
300 waterline
24.8 kg/m3
200 Quick
Steam
100 Line Generation
ed Steam
Saturat
0
0 4.9 9.8 14.7 19.6 24.5 29.4
L&T-MHPS BOILERS
Basics of Supercritical Plant
(3) What is supercritical temperature ?
1000
600℃
800
500℃
Enthalpy (kcal/kg)
600
→Supercritical
Steam/Water
400℃
400 (Saturated) Critical Temperature:
374.15℃
300℃
200 200℃
Water
0
0 10 20 30 40
Pressure (MPa)
Pressure vs. Enthalpy Chart for Sliding Pressure Boiler 6 / 212
L&T-MHPS BOILERS
Basics of Supercritical Plant
(4) Compared conceptual diagram
between Drum and Once-through type
L&T-MHPS BOILERS
Basics of Supercritical Plant
(4) Compared conceptual diagram
between Drum and Once-through type
Once-through Section
Burner
8 / 212
L&T-MHPS BOILERS
Basics of Supercritical Plant
Once-through Section
Burner
9 / 212
L&T-MHPS BOILERS
Basics of Supercritical Plant
(4) Compared conceptual diagram
between Drum and Once-through type
Complicated controllability
L&T-MHPS BOILERS
Basics of Supercritical Plant
Burner
Evaporation point
is obscure
11 / 212
L&T-MHPS BOILERS
Basics of Supercritical Plant
(5) What is the type of Once-through boiler?
The general feature of the once-through boiler is as
follows.
to • The boiler itself has no circulation system such
SH Steam Turbine as drum type boiler. It is better suited for high
pressure boiler.
Water • Water passes through water wall tube and
Separator becomes steam absorbing the heat from fire.
Furnace For this purpose, continuous feeding of the
water is necessary while firing.
• Holding water quantity is less than the drum
type so that the required steam quantity can be
BFP
generated in a short period of time.
Eco
• Balance control between feed water flow and
fuel flow is more difficult than drum type
because the pressure fluctuation is easy to
occur due to load fluctuation.
• High water purity is required due to no blow
down line and higher heat load.
12 / 212
L&T-MHPS BOILERS
Basics of Supercritical Plant
(5) What is the type of Once-through boiler?
The general feature of the once-through boiler is as
follows.
to • The boiler itself has no circulation system
SH Steam Turbine such as drum type boiler. It is better suited
for high pressure boiler.
Water • Water passes through water wall tube and
Separator becomes steam absorbing the heat from fire.
Furnace For this purpose, continuous feeding of the
water is necessary while firing.
• Holding water quantity is less than the drum
type so that the required steam quantity can be
BFP
generated in a short period of time.
Eco
• Balance control between feed water flow and
fuel flow is more difficult than drum type
because the pressure fluctuation is easy to
occur due to load fluctuation.
• High water purity is required due to no blow
down line and higher heat load.
13 / 212
L&T-MHPS BOILERS
Basics of Supercritical Plant
(5) What is the type of Once-through boiler?
The general feature of the once-through boiler is
as follows.
to • The boiler itself has no circulation system
SH Steam Turbine such as drum type boiler. It is better suited
for high pressure boiler.
Water • Water passes through water wall tube and
Separator becomes steam absorbing the heat from
Furnace fire. For this purpose, continuous feeding of
the water is necessary while firing.
• Holding water quantity is less than the drum
type so that the required steam quantity can
BFP
be generated in a short period of time.
Eco
• Balance control between feed water flow
and fuel flow is more difficult than drum
type because the pressure fluctuation is
easy to occur due to load fluctuation.
• High water purity is required due to no blow
down line and higher heat load.
14 / 212
L&T-MHPS BOILERS
Basics of Supercritical Plant
(5) What is the type of Once-through boiler?
The general feature of the once-through boiler is as
follows.
to • The boiler itself has no circulation system such
SH Steam Turbine as drum type boiler. It is better suited for high
pressure boiler.
Water • Water passes through water wall tube and
Separator becomes steam absorbing the heat from fire.
Furnace For this purpose, continuous feeding of the
water is necessary while firing.
• Holding water quantity is less than the drum
type so that the required steam quantity can
BFP
be generated in a short period of time.
Eco
• Balance control between feed water flow and
fuel flow is more difficult than drum type
because the pressure fluctuation is easy to
occur due to load fluctuation.
• High water purity is required due to no blow
down line and higher heat load.
15 / 212
L&T-MHPS BOILERS
Basics of Supercritical Plant
(5) What is the type of Once-through boiler?
The general feature of the once-through boiler is
as follows.
to • The boiler itself has no circulation system
SH Steam Turbine such as drum type boiler. It is better suited
for high pressure boiler.
Water • Water passes through water wall tube and
Separator becomes steam absorbing the heat from
Furnace fire. For this purpose, continuous feeding of
the water is necessary while firing.
• Holding water quantity is less than the drum
type so that the required steam quantity can
BFP
be generated in a short period of time.
Eco
• Balance control between feed water flow
and fuel flow is more difficult than drum
type because the pressure fluctuation is
easy to occur due to load fluctuation.
• High water purity is required due to no blow
down line and higher heat load.
16 / 212
L&T-MHPS BOILERS
Basics of Supercritical Plant
(5) What is the type of Once-through boiler?
The general feature of the once-through boiler is as
follows.
to • The boiler itself has no circulation system such
SH Steam Turbine as drum type boiler. It is better suited for high
pressure boiler.
Water • Water passes through water wall tube and
Separator becomes steam absorbing the heat from fire.
Furnace For this purpose, continuous feeding of the
water is necessary while firing.
• Holding water quantity is less than the drum
type so that the required steam quantity can be
BFP
generated in a short period of time.
Eco
• Balance control between feed water flow and
fuel flow is more difficult than drum type
because the pressure fluctuation is easy to
occur due to load fluctuation.
• High water purity is required due to no blow
down line and higher heat load.
17 / 212
L&T-MHPS BOILERS
Basics of Supercritical Plant
(6) Basic philosophy of the controllability of the Once-through type
18 / 212
L&T-MHPS BOILERS
Basics of Supercritical Plant
(6) Basic philosophy of the controllability of the Once-through type
Once-through Section
Degree of superheat
If increase the compressed water
feeding
Water Saturation Steam
Burner
Steam generation (pressure/load) is
controlled by feed water flow.
19 / 212
L&T-MHPS BOILERS
Basics of Supercritical Plant
(6) Basic philosophy of the controllability of the Once-through type
(c) Steam temperature control by enthalpy
1000
SH Outlet
800 600℃
Superheater
W.W Outlet
500℃
Enthalpy (kcal/kg)
600
Saturation Water Wall
400 (Water/Steam) 400℃
W.W Inlet Economizer
300℃
Eco. Inlet
200 200℃
35% 50% 75% 100% BMCR
Water
0
0 10 20 30 40
Pressure (MPa) 20 / 212
L&T-MHPS BOILERS
Basics of Supercritical Plant
(6) Basic philosophy of the controllability of the Once-through type
(c) Steam temperature control by enthalpy
1000
SH Outlet
800 600℃
Superheater
W.W Outlet
500℃
Enthalpy (kcal/kg)
600
Saturation Water Wall
400 (Water/Steam) 400℃
W.W Inlet Economizer
300℃
Eco. Inlet
200 200℃
35% 50% 75% 100% BMCR
Water
0
0 10 20 30 40
Pressure (MPa) 21 / 212
L&T-MHPS BOILERS
Basics of Supercritical Plant
(6) Basic philosophy of the controllability of the Once-through type
(d) Tentative steam temperature is controlled by spray water
SH
W
S
Furnace
ECO
L&T-MHPS BOILERS
Basics of Supercritical Plant
(6) Basic philosophy of the controllability of the Once-through type
(d) Tentative steam temperature is controlled by spray water
Temp is decreased by spray water
temporarily
SH SH
W W
S S
Furnace Furnace
L&T-MHPS BOILERS
Basics of Supercritical Plant
(6) Basic philosophy of the controllability of the Once-through type
(d) Tentative steam temperature is controlled by spray water
Finally, SH outlet temp. become
same as no spray condition
SH SH WS outlet steam temperature is
increased.
W W
S S Heat Input : Constant
Furnace Furnace
L&T-MHPS BOILERS
Basics of Supercritical Plant
(6) Basic philosophy of the controllability of the Once-through type
(d) Tentative steam temperature is controlled by spray water
No spray condition
Steam Temp. (deg C)
25 / 212
L&T-MHPS BOILERS
Basics of Supercritical Plant
(6) Basic philosophy of the controllability of the Once-through type
(d) Tentative steam temperature is controlled by spray water
Spray injection
Steam temperature
decreasing tentatively.
Steam Temp. (deg C)
26 / 212
L&T-MHPS BOILERS
Basics of Supercritical Plant
(6) Basic philosophy of the controllability of the Once-through type
(d) Tentative steam temperature is controlled by spray water
WS outlet
temperature Steam temperature
recovery. recovery.
Steam Temp. (deg C)
27 / 212
L&T-MHPS BOILERS
Basics of Supercritical Plant
(6) Basic philosophy of the controllability of the Once-through type
(e) Pressure control under superheated condition at WW outlet
1000
SH Outlet
800 600℃
Superheater
W.W Outlet
500℃
Enthalpy (kcal/kg)
600
Saturation Water Wall
400 (Water/Steam) 400℃
W.W Inlet Economizer
300℃
Eco. Inlet
200 200℃
35% 50% 75% 100% BMCR
Water
0
0 10 20 30 40
Pressure (MPa) 28 / 212
L&T-MHPS BOILERS
Basics of Supercritical Plant
(6) Basic philosophy of the controllability of the once-through type
Supercritical
Drum
Once-through
Main
Main steam
steam Wet Fuel Flow
pressure Fuel Flow
pressure Dry Feed Water Flow
29 / 212
L&T-MHPS BOILERS
Basics of Supercritical Plant
(7) Characteristics of sliding pressure operation
8.43
Sliding pressure range
35% 100%
For Reference Generator load
30 / 212
L&T-MHPS BOILERS
Basics of Supercritical Plant
(7) Characteristics of sliding pressure operation
L&T-MHPS BOILERS
Basics of Supercritical Plant
(8) Strict control of water quality
All feed water evaporates in the Boiler
and conveyed to the Turbine
SH Contaminants in feed water cannot be
Water blown out
Separator
The heat load at water wall is higher
WSDT than the drum one.
Contaminants in feed water is easier to
Furnace adhere to water wall as scale.
BCP
BFP
Eco High water purity required !
Condensate polisher system
Clean-up operation during start-up
32 / 212
L&T-MHPS BOILERS
Basics of Supercritical Plant
(8) Strict control of water quality
Once-through
Item
AVT
L&T-MHPS BOILERS
Basics of Supercritical Plant
(8) Strict control of water quality
Boiler Clean-up Operation Completion Criteria
Required Water Quality
Once-through
Item
AVT
34 / 212
L&T-MHPS BOILERS
Basics of Supercritical Plant
(8) Strict control of water quality
Once-through
Item
AVT
L&T-MHPS BOILERS
Basics of Supercritical Plant
(8) Strict control of water quality
Once-through
Item
AVT
L&T-MHPS BOILERS
Basics of Supercritical Plant
(8) Strict control of water quality
Once-through
Item
AVT CWT
L&T-MHPS BOILERS
Basics of Supercritical Plant
(8) Strict control of water quality
Once-through
Item
AVT CWT
38 / 212
L&T-MHPS BOILERS
Special System for Supercritical Plant
(1) Special Feature for once-through boiler
Once-through boiler has start-up system
including BCP.
SH
Water To maintain minimum flow and to equalize
Separator flow to many parallel tubes, it is always
necessary to feed water to the boiler at
WSDT
rate of 25% load while firing.
Furnace
L&T-MHPS BOILERS
Special System for Supercritical Plant
(1) Special Feature for once-through boiler
Once-through boiler has start-up system
including BCP.
SH
Water However, the steam generation is low
Separator conditions which is less than at rate of
25% load, the heat loss is very high
WSDT
accordingly.
Furnace
BCP
L&T-MHPS BOILERS
Special System for Supercritical Plant
(1) Special Feature for once-through boiler
Once-through boiler has start-up system
including BCP.
SH
Water During start-up of the boiler, approx. 5%
Separator load flow is fed to the boiler continuously
by BFP and balance approx. 20% required
WSDT
to maintain 25% load flow through
economizer and furnace water wall tubes
Furnace
is supplied by the BCP.
BCP 20% load flow
Eco
BFP
5% load flow
25% load flow
41 / 212
L&T-MHPS BOILERS
Special System for Supercritical Plant
(1) Special Feature for once-through boiler
Once-through boiler has start-up system
including BCP.
SH
Water The steam water mixture flows to water
Separator separator (WS), where it is separated to
steam and water. The separated steam
WSDT
flows to the superheater and water flows
to water separator drain tank (WSDT).
Furnace
BCP
Eco
BFP
42 / 212
L&T-MHPS BOILERS
Special System for Supercritical Plant
(1) Special Feature for once-through boiler
Once-through boiler has start-up system
including BCP.
SH
Water The BCP takes the suction from
Separator
WSDT and re-circulates approx.
20% load flow.
WSDT
The recirculation flow joins the
approx. 5% BFP flow and
Furnace
approx. 25% is fed to the boiler.
BCP
The excess 5% load flow is
BFP
discharged to condenser from
Eco WSDT as per the water level in
WS.
Indicated system is called
CONDENSER “Start-up system”.
43 / 212
L&T-MHPS BOILERS
Boiler Performance Parameters
SH Out
3 Kg/cm2 (a) 256 254.4
Press
HPT-IN
Kg/cm2 (a) 247 247
Press
4
HPT-IN
◦C 565 565
Temp
HPT-Out
Kg/cm2 (a) 58.61 56
Press
5
HPT-Out
◦C 340.4 336.7
Temp
44 / 212
L&T-MHPS BOILERS
Boiler Performance Parameters
D W B D W B
11 Total Coal Flow tph
468 558 377 431 507 343
45 / 212
L&T-MHPS BOILERS
Coal Characteristics
2 Ash (%) 40 44 34
3
Volatile Matter (%) 19 18 22
HGI
5 55 50 60
7 YGP (mg/Kg) 75 80 70
46 / 212
L&T-MHPS BOILERS
Ash Characteristics
Hemispherical Temp
4b 1300 1250 1350
(◦C)
47 / 212
L&T-MHPS BOILERS
LMB Unit Startup Sequence
48 / 212
L&T-MHPS BOILERS
LMB Unit Startup Sequence
49 / 212
L&T-MHPS BOILERS
LMB Unit Startup Sequence
50 / 212
L&T-MHPS BOILERS
LMB Unit Startup Sequence
51 / 212
L&T-MHPS BOILERS
Start-up Condition
Boiler Startup Condition
Sr. No Operation Mode WS Inlet Fluid Temp (◦C)
1 Cold Start ≤ 120 ◦ C
2 Warm Start > 120 & ≤ 260 ◦ C
3 Hot Start > 260 ◦ C
L&T-MHPS BOILERS
Startup Condition
• Boiler Start-up mode is selected when MFT resets (5 Sec Pulse)
• Unit Startup mode resets when any of the following conditions are
satisfied:
53 / 212
L&T-MHPS BOILERS
Steam admission Criteria for Unit Startup
Sr. No Start-up MS Press MS Temp HRH temp
Mode
54 / 212
L&T-MHPS BOILERS
Start- Up Curves
55 / 212
L&T-MHPS BOILERS
Start- Up Curves
56 / 212
L&T-MHPS BOILERS
Start- Up Curves
57 / 212
L&T-MHPS BOILERS
Preparation of Boiler Start-up
Before Boiler start-up, Operator shall confirm the following conditions:
Instrument & Service Headers Pressure > 6 KSC
EDG System
Electrical Distribution System is in service
Water Treatment system is in service
Waste Water treatment is in service
Service water system is in service.
Cooling water system is in service.
ACW Header Charged
Fire Protection System charged for Boiler area
Pre-boiler cleanup completed with required criteria
DM Water Stock availability in DMST & CST
Boiler Auxiliaries Power ON
ESP System
Chimney
Ash Handling System (Bottom Ash, Eco Hoppers, AH Hoppers, ESP Hoppers)
Coal Handling System including Coal Stock
Aux Steam Header charged. Aux Steam Pressure > 15 KSC & Temp > 250° C
Coal Mill reject handling System is available
LDO tank Level is normal
DC Scanner Air fan is available
Ensure all interlocks are in place and none of them have been bypassed. 58 / 212
L&T-MHPS BOILERS
Boiler Startup Sequence
59 / 212
L&T-MHPS BOILERS
Boiler Startup Sequence
60 / 212
L&T-MHPS BOILERS
Boiler Startup Sequence
61 / 212
L&T-MHPS BOILERS
Air and Flue Gas System Start-up
There are three (3) kinds of start up operational modes, namely cold start up, warm
start up and hot start up.
In all cases the draft system is started up before the boiler firing. The draft system
operation is balanced draft.
L&T-MHPS BOILERS
Boiler Startup- Furnace Purge
Furnace Purge Condition
1.All System Power including flame detector is available and normal.
2.Any Air & Flue gas line in service (A or B side AH & FDF are in service)
3.Any Induced draft (I.D) fan in service.
4.More than 31% of combustion air flow (764.5 tph) is established.
5.Windbox damper controller on Auto Mode (Damper not close).
6.All Ignitor sparks rods are retracted.
7.All Oil Burner valves are closed.
8.LDO Shutoff valve is closed.
9.LDO Leak check valve is closed.
10.“NO FLAME” is detected on all Flame detectors
11.All Coal Feeders are off
12.Both PAF are off.
13.No MFT Condition is existed
14.MFT
15.LDO leak test not abnormal
16.LDO supply pressure is normal. 63 / 212
L&T-MHPS BOILERS
Boiler Startup- Furnace Purge
Sequence flow diagram
for furnace purge :
64 / 212
L&T-MHPS BOILERS
Boiler Startup- LDO Leak Test
Sequence flow diagram
for LDO Leak test :
65 / 212
L&T-MHPS BOILERS
Boiler Startup- LDO Leak Test
Leak Test is performed to check leakage upto burner valves for each fuel
piping before burning fuel.
Permissive:
L&T-MHPS BOILERS
LEAK TEST
PT
FT
BURNER
VALVE
SHUT OFF
VALVE Leak
Charging
Test
CHARGE
VALVE
Boiler Startup- LDO Leak Test
60 sec or until LDO supply header pressure (PT: HHF30CP104) reaches 12.77 KSC
3 minutes
LDO header pressure is kept within the specified value (Maximum allowable pressure
drop is 1.5 KSC ) for preset period of 3 minutes
68 / 212
L&T-MHPS BOILERS
Boiler Startup
Arrangement of Burner Elevation (Shows only one corner)
69 / 212
L&T-MHPS BOILERS
Boiler Startup
Arrangement of Burner
Wind box Assembly (Shows only
one corner)
70 / 212
L&T-MHPS BOILERS
Boiler Startup- Pre checks Before Light up
1. Pre-checks for Boiler light up (for Hot Clean up)
71 / 212
L&T-MHPS BOILERS
Boiler Light Up Preparation
2. Preparation
72 / 212
L&T-MHPS BOILERS
Boiler Light Up
3. Light up
Light up Sequence is as follows:-
UNIT START UP
Elevation EF 2 3
Elevation CD 1 4
Elevation AB 4 1
73 / 212
L&T-MHPS BOILERS
START-UP OF OIL
BURNER
IGNITOR
PI
BURNER VALVE
PI BURNER GUN
74 / 212
L&T-MHPS BOILERS
START-UP OF OIL
BURNER
Corner- 8 Corner- 7 Corner- 6 Corner- 5
75 / 212
L&T-MHPS BOILERS
START-UP OF OIL
BURNER
In-service condition
Atomize
valve
Air
Steam To Burner
Purge
valve
Burner
valve
Oil To Burner
Atomize
valve
Steam To Burner Air
Air Air
Purge
valve
Burner
valve
Oil To Burner
76 / 212
L&T-MHPS BOILERS
Boiler Light Up- Post Checks
77 / 212
L&T-MHPS BOILERS
SCAPH CHARGING
4. SCAPH Charging
Purpose:
During start-up and low loads it is not possible to heat the combustion air to
required temperatures by air preheater.
Steam coil air preheater is used to heat combustion air during low load boiler
operation and to maintain minimum cold end temperature.
78 / 212
L&T-MHPS BOILERS
SCAPH CHARGING
Permissive:
•Boiler MFT Reset
•Any Fuel Oil Burner in service
•Aux Steam Header Pressure > 15 KSC
•SCAPH-A & B inlet & outlet Secondary Air ON-OFF MOD open with bypass MOD
closed.
AVG Cold End Temp of AH = Avg Temp of AH inlet Sec Air Temp + Avg Temp of AH Outlet Flue Gas
Temp
Mix Comb Ratio Avg Cold
2 End Temp of AH
0 100
0.25 100
0.5 100
0.75 76
1 76 79 / 212
L&T-MHPS BOILERS
SCAPH CHARGING
•FDF Stopped
Above condition is to protect the tube from over heating in absence of Cooling
Media.
During SCAPH in Operation, Boiler Flash tank & DRT level to be monitored and
controlled.
80 / 212
L&T-MHPS BOILERS
Boiler Light Up- Fuel Flow Demand
FUEL Initial Fuel Set Press Rising Steam Admiss Steam Admiss Steam Admiss Start up Fuel Common Fuel
SET Fuel Set Fuel Set-1 Fuel Set-2 Fuel Set-3 Set Set
COND BLU HPTB MIN STEAM GEN SYNCH MW > 20% HPTB MWD > 50%
POS IN ADMISSION TMCR CLOSED TMCR
FUEL
DEMAN Cold Mode- Cold Mode- Cold Mode- Cold Mode- Cold Mode- Cold Mode-
Cold Mode-
D 100 tph 110 tph 160 tph 170 tph Fx (BID) Fx (BID)
40 tph
Warm Warm Warm Warm Warm Warm
Warm
Mode- Mode- Mode- Mode- Mode- Mode-
Mode-40 tph
100 tph 115 tph 165 tph 175 tph Fx (BID) Fx (BID)
Hot Mode-
Hot Mode- Hot Mode- Hot Mode- Hot Mode- Hot Mode- Hot Mode-
40 tph
100 tph 115 tph 175 tph 185 tph Fx (BID) Fx (BID)
81 / 212
L&T-MHPS BOILERS
Boiler Pressurization & Temperature Rising
SH3
RH2
SH2
RH1 G
HPT IPT LPT LPT
SH1 HPTB system in-service
W W WDC M
M
S S
LX
D M
T M
DEA CP
WW LP4
M
M
BCP HP8
M
GSC
M
BR LP3
M
ECO HP7 M
T T
FX
FX
LP1/2 CPS
M
M
HP6
M
M M
Flash
Pipe
82 / 212
L&T-MHPS BOILERS
Schematic Diagram of Turbine By-Pass System
Main Steam
HP TB Valve LP TB Valve
HP IP
SH
Turbine Turbine
RH
Boiler
To Deaerator
83 / 212
L&T-MHPS BOILERS
HP Turbine By Pass System
Functions:
84 / 212
L&T-MHPS BOILERS
HP Turbine bypass control
• When Main steam pressure reaches to 20 KSC, Hp turbine bypass
valve open to its minimum opening condition.
L&T-MHPS BOILERS
HP Turbine bypass control
86 / 212
L&T-MHPS BOILERS
Coal Mill In Service- During Pressurization & Temp Rising
6. Steps to take Coal Mill in Service
Steps -1: Confirm following pre-operating condition:
a. Coal bunker outlet valve in open condition
b. Confirm Coal Feeder “Coal ON” belt
c. Confirm Mill outlet valve & coal burner inlet valve full open
d. Confirm 1ry Cold Air Damper minimum position
e. Confirm line up of Mill reject system
f. Confirm Mill lube oil system is in operation
g. Confirm Mill Hydraulic System is in Operation
h. Confirm Mill Static Separator opening-40 %
i. Confirm Mill seal Fan is in operation & Individual Mill Seal air valve is in
open condition.
j. Confirm Coal Feeder Seal air valve is in open condition.
k. Confirm PA Header Pressure as per Fx
87 / 212
L&T-MHPS BOILERS
Coal Mill In Service- During Pressurization & Temp Rising
Steps -2: Operator shall put all the drives related to D coal burner in Auto
Step-3: Operator shall start “Coal Burner light Off BP” from SG-DCS
88 / 212
L&T-MHPS BOILERS
89 / 212
L&T-MHPS BOILERS
90 / 212
L&T-MHPS BOILERS
91 / 212
L&T-MHPS BOILERS
92 / 212
L&T-MHPS BOILERS
93 / 212
L&T-MHPS BOILERS
Purging will be
done for 5 min
at PA flow
more than 70%
flow.
94 / 212
L&T-MHPS BOILERS
Hot PA CD will
start opening
Hot PA& On Off
Warming damper
will be will be
started, opened
once once
the Onthe
Off purging is
dampercompleted.
is
opened.
95 / 212
L&T-MHPS BOILERS
When the pulv
O/l temp will
be more than
75 deg, Coal
feeder will be
started.
96 / 212
L&T-MHPS BOILERS
Coal Mill In Service
Steps -5: Firing Condition PB Start
-Ensure Coal Feeder gets ON. Initial Coal Feeding shall be as below:-
97 / 212
L&T-MHPS BOILERS
Coal Mill In Service
98 / 212
L&T-MHPS BOILERS
Steam Admission- Schematic
SH3
RH2
SH2
RH1 G
HPT IPT LPT LPT
SH1
W W WDC M
M
S S
LX
D M
T M
DEA CP
WW LP4
M
M
BCP HP8
M
GSC
M
BR LP3
M
ECO HP7 M
T T
FX
FX
LP1/2 CPS
M
M
HP6
M
M M
Flash
Pipe
99 / 212
L&T-MHPS BOILERS
Synchronization- Schematic
SH3
RH2
SH2
RH1 G
HPT IPT LPT LPT
SH1
W W WDC M
M
S S
LX
D M
T M
DEA CP
WW LP4
M
M
BCP HP8
M
GSC
M
BR LP3
M
ECO HP7 M
T T
FX
FX
LP1/2 CPS
M
M
HP6
M
M M
Flash
Pipe
100 / 212
L&T-MHPS BOILERS
Turbine Rolling & Synchronization
101 / 212
L&T-MHPS BOILERS
Load Increase to 40 % Load
8. Load Increase to 40 % Load
Steps -1: 2nd Coal Burner warming starts
L&T-MHPS BOILERS
WET to DRY Transfer
Step-4: WET to DRY Transfer
L&T-MHPS BOILERS
Wet / Dry Transfer
SH3
RH2
SH2
RH1 G
HPT IPT LPT LPT
SH1
W W WDC M
M
S S
LX
D M
T M
DEA CP
WW LP4
M
M
BCP HP8
M
GSC
M
BR LP3
M
ECO HP7 M
T T
FX
FX
LP1/2 CPS
M
M
HP6
M
M
M
M M
Flash
Pipe
(1) Wet/Dry Changeover Condition (Simplified)
WET Mode
BCP Start
BR Valve
Full Close
MFT
Change-over timing
Synchronized depends on BCP
BID < 22% start/stop
MW
20% 30% 100% 30% 20%
Steam Press
Control
TB Valve WFR BID WFR
TB Valve
Steam Press Close on Back up Press mode
Control
WFR
Not used Steam Steam Press
Degree of Superheat Control
Press Control
or Steam Temp. Control
Control
Comparison of Dry Mode and Wet Mode
Wet Mode (Circulation Mode)
Dry Mode (Once-Through Mode)
Same System as Drum Boiler
to to
SH Steam Turbine SH Steam Turbine
Water Water
Separator Separator
-MW increased to 30 %
-LDO master will come in standby mode. CV will start closing gradually. Guns need
to be taken out of service based on LDO header pressure.
-GH, EF & CD will be taken out of service one by one and Mill D, E & F shall be
loaded to compensate for the reduction of LDO flow.
-Load set to 40% and gradually MW increased to 40%
108 / 212
L&T-MHPS BOILERS
Load Increase to 50% Load
-Load increased to 50 %
-Fuel changeover is also being done during this from Oil to coal (Exclusive coal
firing established during this).
-Oil gun shutdown sequence is shown in next slide
109 / 212
L&T-MHPS BOILERS
Shut down Sequence of Oil Burner during Load Up
SHUT-DOWN SEQUENCE OF OIL BURNER
(STEP1) IGNITOR
PI
BURNER VALVE
PI BURNER GUN
110 / 212
L&T-MHPS BOILERS
Shut down Sequence of Oil Burner during Load Up
SHUT-DOWN SEQUENCE OF OIL BURNER
(STEP2) IGNITOR
PI
BURNER VALVE
PI BURNER GUN
111 / 212
L&T-MHPS BOILERS
Shut down Sequence of Oil Burner during Load Up
SHUT-DOWN SEQUENCE OF OIL BURNER (STEP2 :
60sec after) IGNITOR
PI
BURNER VALVE
PI BURNER GUN
112 / 212
L&T-MHPS BOILERS
Shut down Sequence of Oil Burner during Load Up
SHUT-DOWN SEQUENCE OF OIL BURNER (STEP3 :
180sec after) IGNITOR
PI
BURNER VALVE
PI BURNER GUN
113 / 212
L&T-MHPS BOILERS
Shut down Sequence of Oil Burner during Load Up
SHUT-DOWN SEQUENCE OF OIL BURNER (STEP4 :
60sec after) IGNITOR
PI
BURNER VALVE
PI BURNER GUN
114 / 212
L&T-MHPS BOILERS
Shut down Sequence of Oil Burner during Load Up
SHUT-DOWN SEQUENCE OF OIL BURNER (STEP5 :
60sec after) IGNITOR
PI
BURNER VALVE
PI BURNER GUN
115 / 212
L&T-MHPS BOILERS
Shut down Sequence of Oil Burner during Load Up
SHUT-DOWN SEQUENCE OF OIL BURNER
(STEP6) IGNITOR
PI
BURNER VALVE
PI BURNER GUN
116 / 212
L&T-MHPS BOILERS
Shut down Sequence of Oil Burner during Load Up
DIESEL OIL BURNER TRIP
BURNER GUN CONTINUE TO BE AT
INSERT POSITION.
PI
BURNER VALVE
PI BURNER GUN
117 / 212
L&T-MHPS BOILERS
Load up to 75 % & 100% Load
10. Load up to 75% (5th Mill in Service)
- Load set to 75%
- 5th Mill warming starts & thereafter Coal firing starts
- Load increased to 75%.
118 / 212
L&T-MHPS BOILERS
Coal Firing Sequence during Load up
Coal Firing sequence during load-up is as follows:
Mill D Mill E Mill F Mill G Mill C Mill B
Note: In case of worst coal operation, Mill H shall be taken in service.
Load Band Vs No of Coal Mills
Design Coal Worst Coal
Load Band Used Mill No Load Band Used Mill No
Bef Synch- 10% TMCR 1 Bef Synch- 10% TMCR 1
10% - 25% TMCR 2 10% - 25% TMCR 2
25% - 30% TMCR 3 25% - 30% TMCR 3
30% - 50% TMCR 4 30% - 40% TMCR 4
50% - 75% TMCR 5 40% - 50% TMCR 5
75% - 100% TMCR 6 50% - 75% TMCR 6
- - 75% - 100% TMCR 7
119 / 212
L&T-MHPS BOILERS
Inerting & Clearing Time Chart for Mill Trip
Inerting & Clearing Time Chart (For Mill Trip):
Inert System-In Service
Inerting Start
120 / 212
L&T-MHPS BOILERS
Inerting & Clearing Time Chart for Mill Trip
Inerting & Clearing Time Chart (For Mill Trip):
Inert System-Out Of Service
121 / 212
L&T-MHPS BOILERS
MODE OF OPERATION
Modes Of Operation
1. BS Mode :
This mode is active during unit start-up. This mode remain active till HPTB gets closed
during dry mode of operation after which mode gets changed to CC Mode.
Pre-requisites;
- Feed water & Fuel Flow control must be in Auto.
Features:
- HPTB will control the Main Steam Pressure.
- Operator will manually control the MW from TG-DCS load setter
- BID is based on actual Feedwater flow
- Wet to Dry transfer will take place at 25% TMCR load
- Load setter faceplate is disabled in CMC HMI
122 / 212
L&T-MHPS BOILERS
MODE OF OPERATION
Modes Of Operation
2. CC Mode :
This is the normal and main control mode for unit operation wherein boiler & turbine runs
in parallel coordinate mode. MWD is given to both boiler & turbine so that energy input
to boiler matches the energy output from turbine.
Pre-requisites;
- Feed water , Fuel Flow , Air flow & Furnace draft control must be in Auto.
Features:
- Turbine Governor will control the MW with Main steam Pressure correction
- BID will control the MWD with Main steam pressure correction.
- Load setter face plate is only enable in this mode in CMC HMI.
123 / 212
L&T-MHPS BOILERS
MODE OF OPERATION
Modes Of Operation
3. BF Mode :
If the turbine master is changed to Manual during CC Mode , the operation mode changes to
BF mode.
Pre-requisites;
- Feed water , Fuel Flow , Air flow & Furnace draft control must be in Auto.
Features:
- Load setter face plate is only enable in TG-DCS
- Main Steam Pressure setter mode switches to Manual and Main steam pressure can be
set from operator face plate in CMC HMI of station DCS.
- Turbine Master is in Manual & BID is in auto.
- MS Pressure is controlled by BID with correction on Actual MW.
- Turbine governor controls actual MW
- MWD track the actual MW signal
124 / 212
L&T-MHPS BOILERS
MODE OF OPERATION
Modes Of Operation
3. BF Mode :
Note: Turbine Master can be Put on “AUTO” mode when both the following conditions are
satisfied:
1. Any of the 3 turbine Controller “ON”- Load Controller / Initial Pressure Controller /
Position Controller.
Mode based on this command and acknowledge the same by sending the “DCS
OPERATION ON FEEDBACK”.
125 / 212
L&T-MHPS BOILERS
MODE OF OPERATION
Modes Of Operation
4. BI Mode :
In this mode, BID shall be in manual & Turbine master shall be in Auto. During runback or
FCB, this mode is selected automatically.
Pre-requisites;
- Feed water , Fuel Flow , Air flow & Furnace draft control must be in Auto.
Features:
- Turbine Master will control will the MS Pressure.
- BID will control the MW
- In case of runback or FCB, this mode is automatically selected and BID set points is set
automatically based on the target load specified for each runback.
- In case of normal mode/operation, BID can be set through Load setter face plate
available in S-DCS.
- MWD tracks the actual MW signal
126 / 212
L&T-MHPS BOILERS
MODE OF OPERATION
Modes Of Operation
5. BM Mode :
Under dry condition, If feedwater control change to Manual, then BM mode is automatically
selected.
During Wet condition, if fuel control changes to Manual, then also BM mode is selected
automatically.
Features:
- BID tracks the actual MW in wet operation and is based on actual feed water flow in dry
mode of operation.
- MWD tracks the actual MW signal.
- MS Pressure is control by Turbine Master, if it is in Auto.
127 / 212
L&T-MHPS BOILERS
LOAD CHANGE RATE
Load change rate
In auto mode (Normal mode of operation), Load change rate is as follows:-
Load change rate is blocked i.e rate is forced to Zero when the load increase / decrease
block condition is active.
128 / 212
L&T-MHPS BOILERS
LOAD CHANGE RATE
Load change rate
Increase Block Condition are as below:-
Fuel flow upper limit
Air flow upper limit
Fuel Flow Feedwater demand decrease cross limit activated
Feed water flow Fuel flow demand decrease cross limit activated
Air flow Fuel flow demand decrease cross limit activated
129 / 212
L&T-MHPS BOILERS
LOAD CHANGE RATE
Load change rate
Decrease Block Condition are as below:-
130 / 212
L&T-MHPS BOILERS
Operation & Control Timing Chart for Start-Up
131 / 212
L&T-MHPS BOILERS
OPERATION CONTROLS
132
132
L&T-MHPS BOILERS
Start up Control of Boiler
• Wet Operation (1/3)
HPTB
SH3
HPT IPT G
SC2 SH2
RH1
From BFP
SC1 SH1 intermediate stage
RH2 RSC
Partially LPT
Evaporated
WS WS LPTB
WS Separate
DT COND
T
WDC
Furnace M
CEP
BCP
Drain is flown into ECO
BR Condensate
ECO inlet or Condenser. Polisher
BFP BFBP
HP LP
DEA
HTR HTR
133
133
L&T-MHPS BOILERS
Start up Control of Boiler
• Wet Operation (2/3)
Steam Flow
Water Flow
through
SH3
Furnace
SC2 SH2 Steam
Flow Recirculation
SC1 SH1 Flow
W W
S S
25% Flow WET
W
S
D Load (%)
T WDC
Furnace
Recir.
BCP 25% Minimum
Flow Flow for
BR
ECO Furnace
BFP Protection
HP
HTR
134
L&T-MHPS BOILERS
Start up Control of
• Wet Operation Boiler
(3/3)
WDC A/B
SH3
SC2 SH2
SC1 SH1
W W α γ γ’ γ”
S S
W
S
D
γ”
LT FX
Furnace
T WDC W B
γ’ A
S WD
BCP START γ
BR BR C
D
ECO PI
△
FT
FX
T
BFP
HP α
HTR
135
L&T-MHPS BOILERS
Start up Control of Boiler
• Dry Operation (1/2)
SH3
SC2 SH2
SC1 SH1
W W
S S
DRY
W
S
D Load (%)
T WDC
Furnace
Furnace
BCP
ECO
BR
Evaporated Feed Water Flow
BFP
= Steam Flow
HP
HTR
136
L&T-MHPS BOILERS
Start up Control of Boiler
• Dry Operation (2/2)
WDC A/B
SH3
SC2 SH2
SC1 SH1
W W α γ
γ γ
S S ”
W No Level WSD
S T
D LT
” ’
γLeve
T WDC W
Furnace B
l
γ’ A
BCP S WD
γ
Stop BR C
BR
D
ECO
FT
Close T
BFP
HP α
HTR No Level
137
L&T-MHPS BOILERS
MS Temp. Control at Wet Operation
• Main steam Temperature is controlled by SH Spray during
Wet mode of operation.
138
138
L&T-MHPS BOILERS
MS Temp. Control at Wet Operation
1ry SH Spray Control Features:
139
139
L&T-MHPS BOILERS
MS Temp. Control at Wet Operation
Over Injection/ Steam Saturation Protection
140
140
L&T-MHPS BOILERS
MS Temp. Control at Dry Operation
Steam temperature control by WFR
L&T-MHPS BOILERS
RH Temperature Controls
RSV
2ry
RH ICV
1ry
RH
1.Deaerator
2. Soot Blwr 3.
Aux. Steam Hdr
142
142
L&T-MHPS BOILERS
RH Temperature Controls
143
143
L&T-MHPS BOILERS
RH Temperature Controls- Back Pass Damper
In Back
pass flue
gas split
into 2
streams
Back Pass
Damper
Down
stream of
damper
flue gas
144 rejoin
1st Pass Damper 2nd Pass Damper 144
L&T-MHPS BOILERS
RH Temperature Controls- Back Pass Damper
Control
• The SH/RH Gas Damper controls RH Steam Temperature
by adjusting the amount of flue gas passing through the
RH / SH to vary the amount of heat absorption in the RH.
145
145
L&T-MHPS BOILERS
RH Temperature Control- Burner Tilt
• Burner tilt is provided to enhance the controllability during load
change.
• Burner tilt is also used to control the RH steam temperature
imbalance.
• Right & Left side fire balls are relatively moved and control the
temperature imbalance.
• 1,2,7,8 Nozzles are tilting as a group & 3,4,5,6, Nozzles are also
tilting as a group.
• Burner Assy shall be kept at horizontal position when the
following conditions are satisfied.
1. All Coal feeder stop. 2. All LDO Burner valves closed 3. All
HFO burner valves closed
146
146
L&T-MHPS BOILERS
RH Temperature Controls- Reheater Spray
1. RH Spray is used only during
emergency condition ( When
Hot RH steam Temp goes
abnormal).
147
147
L&T-MHPS BOILERS
Air Flow Control
The set point is based on Air Flow demand (AFD) calculated as a
function of firing rate demand (FRD) and Boiler Input rate (BIR-Air)
and corrected to ensure complete combustion by monitoring for flue gas
oxygen and multiplying the demand with Air Fuel Ratio (AFR).
The AFD is cross-limited with total fuel flow to prevent fuel rich
condition in the furnace.
L&T-MHPS BOILERS
Air Flow Control
FDF blade pitch demands are forced to maximum (100%) open
while both FDF are stopped so that natural ventilation of the furnace
could be done
L&T-MHPS BOILERS
Furnace Draft Control
Purpose:
Instrument Used:
Control Drives
150
L&T-MHPS BOILERS
Furnace Draft Control
The PAF and FDF blade position is used as the feed forward
signal to improve response during a load change.
L&T-MHPS BOILERS
Fuel Flow Control
1. LDO Control :
For more than 2 Oil burners- LDO FCV changes to Flow control
mode.
152
L&T-MHPS BOILERS
Fuel Flow Control
153
L&T-MHPS BOILERS
Fuel Flow Control
2. Coal Flow Control :
For more than 3 Coal burners- Coal Master will become auto. It
will divide the fuel demand equally among all running Coal Feeders.
Bias Option is there for an operator to adjust the feed rate of fuel
between running feeders.
L&T-MHPS BOILERS
Fuel Flow Control
Fuel flow demand is cross limited with Feed water flow and Air
flow 155
L&T-MHPS BOILERS
Water / Fuel Ratio Control
WFR takes care of heat absorption of actual heating value of fuel
& burner elevation in service
WFR controls:
L&T-MHPS BOILERS
Water / Fuel Ratio Control
The Water/Fuel Ratio (WFR) demand is generated by the following
method.
When the boiler is in WET mode, the Main Steam pressure is
controlled by the Fuel flow. Therefore in this case, the WFR
demand is adjusted to control the Main Steam Pressure.
When the boiler is in DRY mode, the WFR demand controls the
Superheat Rate of the Main Steam temperature (Secondary SH
Outlet Steam temperature).
In addition, to assist the Main Steam Temperature control, steam
temperature error of water separator inlet temp is added as FF
signal to Water/Fuel Ratio.
Variable gain for the Water Separator Inlet steam superheat rate
and Secondary SH Outlet steam temperature is also provided to
change the control gain as per load demand
157
L&T-MHPS BOILERS
Water / Fuel Ratio Control
WFR control the MS Pressure in wet mode and MS temperature in
dry mode till its upper and lower limit.
Upper & Lower limit control is provided to judge the Calorific value
of Fuel.
L&T-MHPS BOILERS
Shutdown Sequence
1. Sixth Coal Burner shutdown
During unit load down “sixth coal burner shutdown” is initiated when MW load is set to
75%.
159 / 212
L&T-MHPS BOILERS
Shutdown Sequence
During unit load down “fourth coal burner shutdown” is initiated when MW load is set to
30%.
- During unit load down from 50% to 30%, Oil burner light up function starts when MW <
40%.
-One elevation of Oil burner light up take places.
-Coal Master will reduce coal flow automatically to compensate the increase of oil flow.
160 / 212
L&T-MHPS BOILERS
Shutdown Sequence
-Oil flow increases automatically
-MW decreases to 20% Load.
161 / 212
L&T-MHPS BOILERS
Shutdown Sequence
7. Last Oil Burner shutdown
- Last Oil burner shutdown activates when the following conditions established:
Generator Circuit breaker is open
Not more than one elevation of Oil burner is in service.
With the last gun purge completed and all oil burner guns are retracted, this function is
completed, and then MFT is activated.
Recommended:
1. In case, long unit shutdown is planned, Operator should carry out all soot blower & wall
blower operation before unit shutdown.
162 / 212
L&T-MHPS BOILERS
163 / 212
L&T-MHPS BOILERS
Coal Flow min
command will be
given to Coal
feeder. After PA flow >
70% flow, Hot PA
On Off damper
Coal Burner
will be closed.
Purging will be
started when
coal flow is
minimum.
164 / 212
L&T-MHPS BOILERS
When Pulv O/L
temp < 55 deg,
Coal feeder will
be stopped.
165 / 212
L&T-MHPS BOILERS
166 / 212
L&T-MHPS BOILERS
167 / 212
L&T-MHPS BOILERS
Shutdown Sequence
8. For Hot Box up
- After MFT activates, Air & Gas system shall be shutdown and following condition
shall be kept:-
All Fans blade pitch shall be closed
All Fans Outlet damper / gate shall be closed
All Boiler drain / vents shall be kept closed.
All Sampling line isolation valves shall be closed.
Boiler MSSV along with integral bypass valve shall be closed.
Both RAPH with GAS, SA & PA inlet and outlet dampers in closed condition
Scanner Cooling Air Fan
Fans Lube Oil Pumps (till Lube Oil temperature < 40 deg C)
Fans Control Oil Pump (till control Oil temperature < 40 deg C)
168 / 212
L&T-MHPS BOILERS
Shutdown Sequence
9. For Natural Cooling
- After Air & Gas system shutdown, following condition shall be kept:-
All Fans blade pitch shall be 100% opened.
All Fans Outlet damper / gate shall be kept opened.
All Boiler drain / vents shall be opened as per MS Pressure.
All Sampling line isolation valves shall be kept opened.
Boiler MSSV along with integral bypass valve shall be kept opened.
Both RAPH with GAS, SA & PA inlet and outlet dampers in closed condition till AH
inlet flue gas temperature < 100 deg C
Scanner Cooling Air Fan till WS inlet temp < 90 deg C
Fans Lube Oil Pumps (till Lube Oil temperature < 40 deg C)
Fans Control Oil Pump (till control Oil temperature < 40 deg C)
169 / 212
L&T-MHPS BOILERS
Boiler Forced Cooling
10. For Forced Cooling
Purpose:
Forced cooling are intended for shortening the time for work after unit shutdown.
170 / 212
L&T-MHPS BOILERS
Boiler Forced Cooling
10. For Forced Cooling
171 / 212
L&T-MHPS BOILERS
Boiler Forced Cooling
A.Boiler Forced Cooling (Incase of no inside work at Boiler)
2.Turbine inlet drain valve is closed. HPBP valve is also closed if required
3.Supply feed water (25% TMCR). Start BCP in accordance with WSDT level.
4.Turbine inlet drain valve (other drain valves) is closed at less than main steam pressure
3 KSC.
5.BCP & MDBFP is stopped when WW outlet temperature and AH inlet gas temperature
becomes less than 90 & 100 deg C respectively.
6.Decrease the air flow bias. After “Zero bias”, A & G system to be shutdown
172 / 212
L&T-MHPS BOILERS
Boiler Forced Cooling
B.Boiler Forced Cooling (Incase of inside work at Boiler)
173 / 212
L&T-MHPS BOILERS
Air and Flue Gas System Shutdown
RAPH shall be kept running till AH inlet flue gas temp < 100 deg C.
AC Scanner Air fan shall be kept running till WSDT inlet temp < 90 deg C.
L&T-MHPS BOILERS
Boiler Trip Condition
1. Boiler Trip PB Operated
2. All BFP Stop
3. All Flame Loss
4. All Fuel Loss
5. Unstable Combustion
6. Reheater Protection
7. Both FDF Stop
8. Both IDF Stop
9. Feed water flow very low (< 330 TPH)
10. Boiler Outlet Main Steam Pressure very high (> 284.2 KSC)
11. Furnace Pressure Very High (> 400 mmwc)
12. Furnace Pressure very low (< 400 mmwc)
175 / 212
L&T-MHPS BOILERS
Boiler Trip Condition
13. WW outlet temp very high
14. 1ry SH outlet steam temp very high
15. Boiler Metal Temp Very High
16. Air flow very low < 26% BMCR (< 641.9 tph)
17. WSDT level very high (> 14.4 mtr)
18. Turbine Trip with Condenser vacuum very low
19. S-DCS Failure
20. SG-DCS Failure
All above condition signal are given to the BPS with Hardwired signal from
local or through other system such as SG-DCS, S-DCS, TG-DCS, TPS etc.
176 / 212
L&T-MHPS BOILERS
Boiler Trip Condition Explanation
1. Boiler Trip PB Operated
This is for emergency trip by the Operator. There are two no's of Push Button
located in Operator Console. Either of the button shall be pressed to trip the
boiler.
Boiler trip from ALL BFP STOP is given to prevent the damage of water wall
tubes due to extreme unbalance of water / Fuel ratio.
All Flame Loss –MFT is initiated when at least one Coal Feeder is in service with
either Furnace A Flame loss or Furnace B flame loss
177 / 212
L&T-MHPS BOILERS
Boiler Trip Condition Explanation
4. All Fuel Loss
MFT is provided from “ALL FUEL LOSS” condition when all CF /MILL stopped and all
Oil burner valves closed.
5. Unstable combustion
This MFT is applicable for only Oil Firing. This is judged by following two condtions:
1. Oil Burner Header Pressure Low Low (< 5.2 KSC) for 3 sec.
2. Atomizing Air Header Pressure Low Low (< 3 KSC) for 3 sec.
6. Reheater Protection:
Boiler trip is initiated to protect the reheaters against burning in the case that excessive
boiler heat input is charged in the state of blocked steam across reheater.
L&T-MHPS BOILERS
Boiler Trip Condition Explanation
Reheater protection acts when following two condition establish:
1. If steam block condition persist for more than 10 sec for fuel more than 30%
BMCR
OR
2. If steam block condition persist for more than 20 sec for fuel more than 20%
BMCR
179 / 212
L&T-MHPS BOILERS
Special Operating Condition
1. Run Back:
It is provided when any major running equipment / auxiliaries gets trip during
plant operation so that overloading does not happen on other running
equipment. After runback, plant control automatically comes in BI Mode and
Load automatically reaches target load as specified for each auxiliaries.
Runback signals reset 10 minutes after BID reaches specified target load. This 10
minutes are given for plant stabilization.
Once runback signal resets, Operator can switch the Unit Mode based on actual
plant condition at that instant.
L&T-MHPS BOILERS
Special Operating Condition
2. Fast Cut Back
FCB occur in an event of transmission line trouble or during sudden load throw
off when turbine generator either trips or comes to Islanding operation with
house load of 40 MW.
In order to swiftly reach to house load or “0” MW from normal load, Boiler
control rapidly decreases fuel flow, feedwater flow, air flow based on the BID
corresponding to target load.
FCB may occur during BID > 60 % , BID< 60% or during 20% to 30% BID.
When FCB occur during BID> 60%- Target load shall be 60% TMCR
FCB between 60% to 30% - Target load will be the last set point
FCB between 20% to 30%- Target load shall be 20% since boiler operation in
this transient Zone is not recommended.
181 / 212
L&T-MHPS BOILERS
Special Operating Condition
Runback for Main Auxiliaries & FCB conditions are mentioned below:
1 x TDBFP 1 TDBFP Trip 396 MW (+66 60%(+10%, if 100% / min Under both TDBFP
MW, if MDBFP MDBFP ON) running
ON)
L&T-MHPS BOILERS
Special Operating Condition
Runback for Main Auxiliaries & FCB conditions are mentioned below:
183 / 212
L&T-MHPS BOILERS
Boiler Emergency
184 / 212
L&T-MHPS BOILERS
Objective
185 / 212
L&T-MHPS BOILERS
Emergency
Emergency is
Unexpected
Dangerous/Abnormal
Starts slowly but Grow at a faster rate
Requires immediate attention/prompt action
If not properly/urgently handled can result in to
heavy loss.
186 / 212
L&T-MHPS BOILERS
How to Handle Emergency
Control process to avoid the emergency (Prevention is
better than cure)
Be cool and calm
Act wisely and immediately
Take proper actions
Emergency preparedness will help in handling the
emergency
Every body’s responsibility/Requires to work across the
boundary
After handling the emergency analyze the action taken
and plan for the improvement
187 / 212
L&T-MHPS BOILERS
Boiler Emergencies: Actuation of MFT
Cause:
Boiler Emergency PB Pressed
Feed water flow very low
Boiler Outlet steam pressure very High
Loss of All Flame
Loss of All Fuel
Both FD Fan Stop
Both ID Fan stop
Furnace draft very high/ very Low: ±3.9kPa (3s) [±400mmAq]
188 / 212
L&T-MHPS BOILERS
Boiler Emergencies: Actuation of MFT
Cause: ( Cont..)
Turbine Trip with Condenser vac. Very low or all CW Pumps trips
Air flow very low
Water wall outlet temperature very high
Primary SH Outlet temperature very high
S-DCS Failure
SG-DCS failure
Reheater protection : Gas temperature at secondary reheater inlet -
20%MCR(20s)
L&T-MHPS BOILERS
Boiler Emergencies: Actuation of MFT
Effect:
All Fuel Oil Burner valves and Emergency shut off valves
Closes
All Coal Feeders, Pulversizers and PA fan trips.
Inert steam is supplied to pulversizers
Turbine is tripped
FDF, IDF and AH are kept running at 30 % air flow
SH and RH desuperheater valves are closed.
WSDT Level start Increasing
190 / 212
L&T-MHPS BOILERS
Boiler Emergencies: Actuation of MFT
Action:
Check that the boiler had gone for the safe shut down.
Check the running auxiliaries and ensure that they are running
steady
Investigate the cause of the MFT and rectify the same.
Restart the boiler after rectifying the cause
Control WSDT level through WDC
191 / 212
L&T-MHPS BOILERS
Boiler Emergencies: Tube Leakage
Cause:
Over Heating
Erosion
Blockage in tube
L&T-MHPS BOILERS
Boiler Emergencies: Tube Leakage
Effect:
Makeup water flow increase.
Feed water demand increase.
Main steam pressure decrease.
BID increase
Main steam temperature increase.
Flue gas flow increase./ID fan Loading increases
Furnace Draft will go to positive side
Tube leakage detection system will indicate the tube leakage
Leakage Sound observed in the boiler
Flue Gas temperature start decreasing 193 / 212
L&T-MHPS BOILERS
Boiler Emergencies: Tube Leakage
Action:
Shut down the boiler and start the force cooling of the boiler.
194 / 212
L&T-MHPS BOILERS
Boiler Emergencies: ID Fan Trip
Cause:
Electrical relay operated
195 / 212
L&T-MHPS BOILERS
Boiler Emergencies: ID fan Trips
Effect:
Related FDF stopped.
Related PAF stopped.
Change to one side air and gas system operation.
IDF Runback operate
Load set will set to 50 % Load
Action:
Confirm the stabilize of plant condition after RUNBACK.
Find out the cause of trip rectify it
Start the fan again and normalize the system
196 / 212
L&T-MHPS BOILERS
Boiler Emergencies: FD Fan Trip
Cause:
197 / 212
L&T-MHPS BOILERS
Boiler Emergencies: FD fan Trips
Effect:
Related IDF stopped.
Related PAF stopped.
Change to one side air and gas system operation.
FDF Runback operate
Load Set to 50 % Load
Action:
Confirm the stabilize of plant condition after RUNBACK.
Find out the cause of trip rectify it
Start the fan again and normalize the system
198 / 212
L&T-MHPS BOILERS
Boiler Emergencies: PA Fan Trip
Cause:
Electrical relay operated
Fan bearing Temperature High
Motor Bearing temperature high
Fan or Motor Vibration High
Related ID or FD fan tripped (Runback operated)
Load set to 50% Load
Effect:
Pulverizer primary air flow decrease.
Pulverizer/furnace differential pressure decrease.
Pulverizer inlet hot air pressure decrease.
199 / 212
L&T-MHPS BOILERS
Boiler Emergencies: PA fan Trips
Effect (Cont…)
Other PAF blade pitch demand increase.
Other PAF Motor current will increase
Related FDF and IDF Trips.
PAF Runback operate.
Action:
Control the Mill Inlet Air flow, If required trip 1 or 2 mill to
maintain PA header Pressure
If Motor Current increases too much or stall alarm comes, take
PAF blade pitch in Manual mode for control
Confirm the stabilize of plant condition after RUNBACK.
Find out the cause of trip rectify it
Start the fan again and normalize the system 200 / 212
L&T-MHPS BOILERS
Boiler Emergencies: AH Motor Trips
Cause:
Electrical relay operated
Gear Box Bearing Temperature High
Motor Overload
Effect:
Related IDF / FDF and PAF stopped.
AH-A air motor back-up start.
Change to one side air and gas system operation.
AH Runback operate
Load Set will change to 50% Load
201 / 212
L&T-MHPS BOILERS
Boiler Emergencies: AH Motor Trips
Action:
202 / 212
L&T-MHPS BOILERS
Boiler Emergencies: Coal Feeder Trips
Cause:
Electrical relay operated
No-Coal on Belt
Discharge Chute Pluggage
Local PB Operated
Belt Motion Monitor
Effect:
Pulverizer hot air shut-off damper close.
Change to BI and TF control mode.
Runback Pulverizer operate.
203 / 212
L&T-MHPS BOILERS
Boiler Emergencies: Coal Feeder Trips
Action:
Find out the cause of trip Rectify it and start the feeder again.
204 / 212
L&T-MHPS BOILERS
Boiler Emergencies: Seal Air Fan Trips
Cause:
Electrical relay operated
Motor Current high
Local PB Operated
Effect:
Stand by seal air fan starts on Auto and seal air header
pressure is maintained.
If the stand by seal air fan had not started on auto, Seal air
header pressure drops Seal air DP decreases
All mills trips on seal air DP low.
Boiler MFT will happen
205 / 212
L&T-MHPS BOILERS
Boiler Emergencies: Coal Mill Fire
Cause:
Coal accumulation in the mill or duct
Effect:
Pulv lower-upper house diff press increase.
Primary air flow decrease.
Pulv inlet air temp increase.
Pulv/furnace diff press increase.
Hot air gate close by outlet temp HH.
Pulv trip by outlet temp HH of trip point.
206 / 212
L&T-MHPS BOILERS
Boiler Emergencies: Coal Mill Fire
Actions:
Confirm the behavior of the plant process.
207 / 212
L&T-MHPS BOILERS
Boiler Emergencies: Condenser Tube Leakage
Cause:
Tube leakage
Effect:
208 / 212
L&T-MHPS BOILERS
Boiler Emergencies: Condenser tube leakage
Action:
209 / 212
L&T-MHPS BOILERS
Boiler Emergencies: Feed water flow reduced
Cause:
Tripping of BFP.
Failure of Feed water controller
Effect:
210 / 212
L&T-MHPS BOILERS
Boiler Emergencies: Feed water flow reduced.
Action:
Take the Feed water control on Manual mode and control it, if
the controller is failed.
211 / 212
L&T-MHPS BOILERS
THANK YOU
212 / 212
L&T-MHPS BOILERS