Professional Documents
Culture Documents
Condition Monitoring
of Power Transformers
1
1. INTRODUCTION
Electrical distribution equipment is generally
designed for a certain economic service life.
2
INTRODUCTION
Generally due to poor quality of raw material,
workmanship and manufacturing techniques or due
to frequent electrical, mechanical and thermal
stresses during the operation, many equipment fail
much earlier than their expected economic life span.
4
For electrical utilities this implies for example to
fulfill requirements from customers and authorities
on reliability in power supply at a minimal totalcost.
5
Maintenance Management
6
Condition Based Monitiring
7
What is CBM?
10
Defining condition and future performance
Need understanding of:
Operating context
12
Oil & Paper Tests in Main Tank & OLTC
13
Oil & Paper Tests in Main Tank & OLTC
14
Oil & Paper Tests in Main Tank & OLTC
2. DGA
15
Insulation Condition Assessment
Life Span of Power Transformers Depends on
Integrity of Insulation
Most Commonly Used Insulations for Power
Transformers
OIL
• Provides overall insulation to the transformers
• Acts as coolant in extinguishing arcs
• Provides the means to monitor insulation
condition and operation of
transformers
PAPER
Provides insulation to the conductor in the
transformer windings 16
Insulation Condition Assessment
PRIMARY STRESSES
18
Insulation Condition Assessment
19
Insulation Condition Assessment
20
Insulation Condition Assessment
21
Insulation Condition Assessment
Degradation By-Products
1. It can be observed that by-products related to paper
degradation
can include the followings:
• CO
• CO2
• H2O
• Organic acids
• Free glucose molecules
2. With H2O and organic acids present in the oil, the free
glucose
molecules can degrade to 5-hydroxymethyl-2-furfuryl or
5H2F
23
Insulation Condition Assessment
Degradation By-Products
3. 5H2F is an unstable free glucose molecule and can
decompose
further to other furaldehyde as follows:
• 2-furfuryl alcohol (2FOL)
• 2-furaldehyde (2FAL)
• 2-acetyl furan (2ACF)
• 5-methyl-2-furfuryl (5M2F)
4. All these 5 compounds of glucose or degradation of glucose
are
known as Furans.
5. 2FAL is the most stable in the group
6. Furan generation is exclusively due to paper degradation
unlike
CO, CO2, H2O or acids which can also be produced through oil
oxidation or breakdown.
24
Insulation Condition Assessment
26
Insulation Condition Assessment
28
Insulation Condition Assessment
29
Insulation Condition Assessment
30
Insulation Condition Assessment
31
Insulation Condition Assessment
32
Insulation Condition Assessment
33
Insulation Condition Assessment
34
Oil Quality Screening Tests
Water Content (D 1533 / IEC 733)
A low water content is necessary to obtain and maintain
acceptable electrical strength and low dielectric losses in
insulation systems.
Color (D 1500) The color of a new oil is generally
accepted as an index of the degree of refinement. For
oils in service, an increasing or high color number is an
indication of contamination, deterioration, or both.
Dielectric Breakdown (D 877 / D 1816 / IEC 156)
It is a measure of the ability of an oil to withstand electrical
stress at power frequencies without failure. A low value
for the dielectric-breakdown voltage generally serves to
indicate the presence of contaminants such as water,
dirt, or other conducting particles in the oil.
35
Oil Quality Screening Tests
Neutralization Number, NN (D 664)
A used oil having a high neutralization number indicates that
the oil is either oxidized or contaminated with materials such as
varnish, paint, or other foreign matter.
Interfacial Tension, IFT (D 971)
The interfacial tension of an oil is the force in dynes per
centimeter or millinewton per meter required to rupture the oil
film existing at an oil-water interface. When certain
contaminants such as soaps, paints, varnishes, and oxidation
products are present in the oil, the film strength of the oil is
weakened, thus requiring less force to rupture. For oils in
service, a decreasing value indicates the accumulation of
contaminants, oxidation products, or both.
36
Oil Quality Screening Tests
37
Insulation Condition Assessment
39
Insulation Condition Assessment
40
Insulation Condition Assessment
41
Insulation Condition Assessment
IEEE Limit
42
Insulation Condition Assessment
43
Insulation Condition Assessment
44
Insulation Condition Assessment
45
Insulation Condition Assessment
46
Exercise (Oil Condition)
20
39
Exercise (Oil Condition)
Transformer Gas Analysis
Component ppm in oil
HYDROGEN (H2) 10
OXYGEN (O2) 26200
NITROGEN (N2) 48500
CARBON MONOXIDE (CO) 41
METHANE (CH4) 5
CARBON DIOXIDE (CO2) 570
ETHYLENE (C2H4) 2
ETHANE (C2H6) 2
ACETYLENE (C2H2) 1
Exercise (Oil Condition)
48
Exercise (Paper Condition)
49
Exercise (Oil + Paper Condition)
50
Insulation Condition Assessment
51
Insulation Condition Assessment
52
Insulation Condition Assessment
• Transformer Age
• Operational Criterion – number of faults,
switching, lightning, etc.
• DGA Criterion (oil) – Individual
concentrations of CH4, C2H2,
C2H4, C2H6 & H2 in ppm & Roger’s/IEEE
Ratio
• DGA Criterion (paper) – Individual
concentrations of CO2 & CO in
ppm & CO2/CO Ratio
• Furan Criterion – 2FAL concentration in
ppb & others if detected
53
Insulation Condition Assessment
Correlation between TS, DP and Furan
54
Insulation Condition Assessment
Degree of Polymerization
56
Insulation Condition Assessment
57
LTC – OIL ANALYSIS
58
Case Study
59
LTC – OIL ANALYSIS
60
LTC – OIL ANALYSIS
61
Transformer Basic On-Site & Off Line Diagnostic Testing
62
Electrical Tests
63
Electrical Tests
2. Advanced DiagnosticTests
Frequency Response Analysis (FRA)
Recovery Voltage Measurement (RVM)
Polarization Depolarization (PDC)
Frequency Dielectric Spectroscopy (FDS)
Partial Discharge (PD)
OLTC Motor Current Signature Analysis (MCSA)
OLTC Vibration Signature Analysis (VSA)
64
On-site Testing
65
On-site Testing
66
Damaging Factors of Insulation
67
Insulation Condition Assessment
68
Insulation Condition Assessment
69
Basic Electrical Tests
Insulation Resistance
Reading corrected to 20oC
70
Basic Electrical Tests
Polarization Index
71
Basic Electrical Tests
72
Insulation Resistance Test
73
Insulation Resistance Test
74
Insulation Resistance Test
75
Inaccuracies can occur during IR
measurement
due to the following
76
Test procedures
77
Temperature Correction
78
Conversion Factors For Converting
Insulation Resistance Test Temperature to 20°C
79
Polarization Index
80
Interpretation
81
Step Voltage Test
82
Basic Electrical Tests
PI
If a PI falls by 30% or more from the previous value then remedial
action such as cleaning, oil-filtering or further investigation should
be considered.
Tan Delta
If the IFT and oil moisture content exceed their respective limits
then Tan Delta test is recommended. This is a good complement to
PI test and as remedial action drying is usually performed.
Field test results must be corrected to 20o C before comparison.
83
Basic Electrical Tests
Tan Delta (DLF) test
• In on site tan delta measurement there are two modes namely Grounded
Specimen Test (GST) and Ungrounded Specimen Test (UST). During GST
mode, the dielectric loss of insulation between one of the windings to
ground will be measured depending on the winding that is being excited.
Under UST mode, dielectric loss of insulation between the two windings
will be measured irrespective of the winding being excited.
• The ratio obtained from the field test should agree with nameplate
value within 0.2% for the insulation system between the high
voltage and low voltage winding at all taps. Otherwise, winding
repair is recommended.
• The ratio obtained from the field test should be within the limit of
0.5% for the insulation system between the high voltage winding
and ground. Otherwise, winding repair is recommended.
84
Power Factor Test
85
Power Factor Test
86
Power Factor Test
87
Power Factor Test
88
Power Factor Test Set up
89
Temperature correction factors for the power factor
of power transformer windings
where:
FP20 = power factor corrected to 20 degree C
FPT = power factor measured at T degree C
T = test temperature
K = correction factor from table
90
Power Factor of Some Common Materials
Bakelite 2 - 10%
Vulcanized Fibre 5%
Varnished Cambric 6 - 8%
Mica 2%
Polyethylene 0.03%
New Insulating Oil 0.01-0.2%
91
Insulation Current Test
High Voltage DC/AC Test
92
93
Insulation Current Test
94
HIGH-VOLTAGE, DC/AC TESTS
95
Test Procedure
The machine winding should be grounded for at least 1
hour before conducting the test
The phases should be separated and tested individually
Lightning arresters and capacitors must be disconnected
Cables and/or bus work should be disconnected if it is
convenient to do so
If the separation of phases is difficult then separation is
needed once for the benchmark tests, and thereafter the
phases may be tested together until deviation from normal
is detected
96
Test procedure
97
Test procedure
If the insulation microampere versus voltage plots are
straight lines, the test may be continued to the maximum
test voltages
The quality of the insulation may be judged by the
position of any curvature or knee in the plot of insulation
current versus test voltage
If curvature or knee appears, the test should be stopped
Upon completion of the dc, high- voltage test, the
winding should be discharged through the special
discharge resistor usually provided with the test set
The winding may be solidly grounded when the voltage
has dropped to zero or after a few minutes of discharge
have occurred
A winding should remain solidly grounded long enough
before restoring the machine to service
98