To understand the important concepts related to distance protection. To solve the related problems of step distance protection. Three Step Distance Protection We Like to set the reach of relay to 100% of the line section. However it is not possible to get the exact reach of 100% in practice. There is always certain amount of about the actual reach. Various contributing factors for this ambiguity in reach are: I. Inaccuracy in CT and PT ratios. II. Ambiguity about line parameters (line parameters are seldom measured, they are calculated from line data) Three Step Distance Protection I. Variation of line parameters with atmospheric conditions. II. DC offset in fault current. III. Transient response of capacitive voltage transformers (CVT) Out of these factors DC offset and CVT transient response cause over- reach. Other factors may cause error on either side. Thus, there is always a possibility of over-reach. If the reach of distance relay is adjusted to 100% then over-reach will cause loss of selectivity with the distance protection of the next section. This cannot be tolerated in the case of EHV lines. Thus, it is a usual practice to set the reach of distance protection about 80 to 90% of the line section. This leaves 20% to 10% of line without primary protection. Therefore, a comprehensive scheme of distance protection has evolved, providing primary protection to the line section under consideration as well as back-up to the next line section. Three Step Distance Protection First Step: it is not advisable to set the reach of distance protection to 100%. The first step of distance protection is, therefore, set to reach up to 80 to 90% of the length of the line section. This is an instantaneous protection, i.e. there is no intentional time delay. Three Step Distance Protection Second Step: The second step is required in order to provide primary protection to the remaining to 10% of the line, which is left out of the first step. In addition, it is set to cover up to 50% of the next line section. Third Step: The third step is provided with an intention to give full back-up to the adjoining line section. It covers the line section under consideration, 100% of the next line section and reaches further into the system. The motivation behind the extended reach of this step is to give full back-up to the next line section in spite of the maximum under-reach of the third step. Three Step Distance Protection Three Step Distance Protection Some Important Concept to be kept in mind
Fault Resistance (Arc Resistance):
Most of the faults involve an arc. The arc is resistive in nature. We have discussed that the distance relay measures the impedance of the line to be protected. As the impedance involved is proportional to the length, we can decide the reach of the according to the distance. Now when the fault takes place, the impedance is that of the line plus the fault impedance (resistance). In case of a line-to-ground fault, the fault impedance consists of the resistance of the arc (flashover at line insulator) plus tower footing-resistance. The result of the arc resistance is the under-reach of relay. Some Important Concept to be kept in mind DC Offset in fault current: Consider an electrical system running with a relatively symmetrical sine wave where the positive and negative peaks are equidistant from zero A fault is suddenly applied to the system and the sine wave suddenly becomes asymmetrical (the positive and negative peaks are not equidistant from zero), and then returns to normal (symmetrical) after a few cycles. The asymmetrical response to the fault is called DC Offset and it is a naturally occurring phenomenon of the electrical system. Some Important Concept to be kept in mind •Maximum Torque Angle (MTA): When a fault occurs the angle between V and I varies between 70o to 90o depending on the fault location. Hence a directional relay should be designed for MTA equal to this angle. The torque in this case will be, T VIcos(Ø-θ) where θ is the maximum torque angle (MTA). Some Important Concept to be kept in mind
A directional relay can be compared to a contact
making wattmeter. A wattmeter develops maximum positive torque when the current and voltage supplied to the current coil and the pressure coil are in phase. If we define the maximum torque angle (MTA) as the angle between the voltage and current at which the relay develops maximum torque, then a wattmeter can be called a directional relay with MTA of zero degree Related Problems
Book : Power System Protection and Switchgear Chapter 08 Example 8.1 Example 8.1 Example 8.1 Example 8.2 Example 8.2 Example 8.2 Example 8.3 Example 8.3 Example 8.3 Example 8.3 Example 8.3